Health Physics Sample Records_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~

Sample ID: 142492 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

140605BD03 SOUTH LAY DOWN# 4

]Commonl Resp Org: P4000 - PROJECT MANAGEMEr Cross Ref Sample ID: Priority: N

Contact:

COOPER, TERRY L Survey No:

Reference ID: Accounting Subcode: Unknown Mat: NO Hazardous Mat: NO Comments: COUNT TO MDA Reviewed: DYNES, WILLIAM J Date: 06/06/14 07:29 Comments:

Origin I Mat. SizeNolume: 1913 GRAMS Docmnt/MO/Act #: Proposed Ship Date: 00/00/00 00:00

Description:

SOUTH LAY DOWN# 4 IColle~tioriJ Sample Tech: DYNES, WILLIAM J Sample Date: 06/05/14 12:15 Count Time: 900 (secs.)

Tritium Req: No Sample SizeNolume: 1913 GRAMS Instructions: COUNT TO MDA Comments: COUNT TO MDA I RLS§S Exempt: No Evaluated: No Chem Notification: No State Permit: No Offsite Analysis: No Effluent Permit: No Container Surveyed: No Cleared For Release: Yes Container Evaluated: Yes Form 212 Ready: W' LL_<?~.!~

Unit: NON-UNIT RE Area: MS Elev: 100 Room: Depth: (in.) Equip ID:

Stored By:, Date: 00/00/00 00:00 Sample Loe:

Other: COUNT TO MDA Material Loe:

06/19/2014 09:53 Page 1 of 3

Health Physics Sample Records Sample ID: 142492 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

1406058003 SOUTH LAY DOWN# 4 I Analysis I Geometry MCA ID Quant. Units Method FP/AP Lab Analys~~r Date Mod ID Mod Date

--~------

B_1L_marinelli_sand_ 30386 1913 GR .000 NEESE, DAVID J 06/06/14 20:48 lsoto.~ l'!_ode_ Activity Activity Uncert. LLD/MDA %Abund. Atom. No. Comments Mod Id Mod Date 0 K-40 NT 0.00001204 1.55E-6 86.476% 40 0 TL-208 NT 4.093E-7 8.88E-8 2.940% 208 0 PB-212 NT 3.769E-7 1.226E-7 r 2.707% 212 0 81-214 NT 5.365E-7 1.206E-7 r 3.853% 214 0 PB-214 NT 5.602E-7 1.525E-7 r 4.024% 214 0 BE-7 AP 1.0421E-6 r;7 0.000% 7 0 MN-54 AP 3.2428E-8 r;7 0.000% 54 0 MN-56 AP 9.1097E-8 ~ 0.000% 56 0 C0-57 AP 9.3582E-8 ~ 0.000% 57 0 C0-58 AP 1.0581E-7 ~ 0.000% 58 0 C0-60 AP 1.7561 E-7 ~ 0.000% 60 0 SB-124 AP 1.1698E-7 Ji1' 0.000% 124 0 SB-125 FP 2.9104E-7 r;7 0.000% 125 0 CS-134 FP 1.1428E-7 Ji1' 0.000% 134 0 CS-137 FP 3.0386E-8 ~ 0.000% 137

[_Analysis Review Re-Analize: No Lie Rad Mat Present: No Reviewed: COOPER, TERRY L Date: 06/11/14 06:39 Hp Eng Rvw Reqd: Yes Rad Mat Present: Yes HP Notified Name:

Comments:

06/19/2014 09:53 Page 2 of 3

Health Physics Sample Records Sample ID: 142492 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

140605BD03 SOUTH LAY DOWN# 4

[ Review/Approve I HP Review Reviewed: COOPER, TERRY L Date: 06/11/14 06:39 Comments:

Disposition Disposition: OTHER Result: Sample contains only natural isotopes Remarks:

Final Approval Approved: COOPER, TERRY L Date: 06/11/14 06:40 Comments:

06/19/2014 09:53 Page 3 of 3

  • SONGS HEALTH PHYSICS REPORT 6-JUN-2014 20:42 *
  • >>>>> SAMPLE PARAMETERS<<<<< *
  • Title 140605BD03 SOUTH LAY DOWN# 4 *
  • ID 30386 Acquisition date: 6-JUN-2014 20:39:10. *
  • Start Time: 6-JUN-2014 20:39:00. *
  • Stop Time: 6-JUN-2014 20:39:00. Counting System U2GSP *
  • Quantity 1.91300E+03 GR IHPS Sample Number: 142492 *
  • Geometry B lL marinelli_sand_l Analysis Library HP NATURAL *
  • Operator: DAVID NEEBE *
  • >>>>> B #42-TP11663A PARAMETERS<<<<< *
  • Elapsed Live Time 0 00:03:00.41 Calibration 6-JUN-2014 20:09: *
  • Elapsed Real Time 0 00:03:00.45 Energy Offset -4.40560E-01 *
  • Deadtime 0.0% Energy Slope 5.00074E-01 *
  • Activity Mult Factor: l.OOOOOE+OO Energy Tolerance: 1.00000 *
  • Half Life Ratio 8.00000 Sensitivity 5.00000
  • Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left Pw %Err Fit Nuclides 1 238.61 38 30 1. 43 478.04 471 11 32.5 2.56E+OO PB-212 1 295.16 21 2 1.17 591.12 586 8 27.2 1.53E+OO PB-214 1 351.81 29 7 1. 87 704.40 699 10 25.7 6.llE-01 PB-214 1 583 .11 29 5 2.28 1166. 93 1162 9 21. 7 5.22E-01 TL-208 1 609.44 26 2 1. 43 1219.60 1216 8 22.5 2.42E+OO BI-214 1 1460.86 69 4 1. 99 2922.23 2915 12 12.9 1.15E-01 K-40

Summary of Nuclide Activity Page : 2 Sample ID : 30386 Acquisition date 6-JUN-2014 20:39:10 Total number of lines in spectrum 6 Number of unidentified lines 0 Number of lines tentatively identified by NID 6 100.00%

Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error %Error Flags K-40 1.28E+09Y 1. 00 1.204E-05 1. 204E-05 0.155E-05 12.86 A TL-208 3.05M 1. 43 2.854E-07 4.093E-07 0.888E-07 21. 70 A PB-212 10.64H 1. 00 3.762E-07 3.769E-07 l.226E-07 32.53 A BI-214 19.90M 1. 06 5.064E-07 5.365E-07 1.206E-07 22.47 A PB-214 26.80M 1. 04 5.366E-07 5.602E-07 1.525E-07 27.23 A Total Activity 1.375E-05 1. 393E-05 Grand Total Activity : 1.375E-05 1.393E-05 Flags: "K" Keyline not found "M" Manually accepted "E" Manually edited "A" Nuclide specific abn. limit

Unidentified Energy Lines Page : 3 Sample ID : 30386 Acquisition date 6-JUN-2014 20:39:10 None Flags: "T" Tentatively associated

Interference Report Page : 4 Sample ID : 30386 Acquisition date 6-JUN-2014 20:39:10 No interference correction performed

Nuclide Line Activity Report Page : 5 Sample ID : 30386 Acquisition date 6-JUN-2014 20:39:10 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area %Abn %Eff uCi/GR uCi/GR %Error K-40 1460.83 69 10.67* 4. 211E-01 l.204E-05 1. 204E-05 12.86 TL-208 72.80 ------ 2.14 1.070E+OO ------ Line Not Found ------

74.97 ------ 3.60 1.156E+OO ------ Line Not Found ------

84.79 ------ 1. 27 1.506E+OO ------ Line Not Found ------

252.45 ------ 0.80 1.745E+OO ------ Line Not Found ------

277.28 ------ 6.80 l.645E+OO ------ Line Not Found ------

510.61 ------ 21. 60 1.035E+OO ------ Line Not Found ------

583.02 29 86.00* 9.198E-01 2.854E-07 4.093E-07 21.70 763.06 ------ 1. 64 7.126E-01 ------ Line Not Found ------

860.30 ------ 12.00 6.341E-01 ------ Line Not Found ------

PB-212 74.81 ------ 10.50 1.150E+OO ------ Line Not Found ------

77 .11 ------ 17.70 1. 239E+OO ------ Line Not Found ------

87.19 ------ 6.27 l.579E+OO ------ Line Not Found ------

90.13 ------ 1. 86 1.662E+OO ------ Line Not Found ------

115. 12 ------ 0.59 2.085E+OO ------ Line Not Found ------

238.58 38 43.60* 1.805E+OO 3.762E-07 3.769E-07 32.53 300.03 ------ 3.34 1.562E+OO ------ Line Not Found ------

BI-214 76.86 ------ 0.58 1.229E+OO ------ Line Not Found ------

79.29 ------ 0.97 1.320E+OO ------ Line Not Found ------

609.31 26 46.10* 8.831E-01 5.064E-07 5.365E-07 22.47 665.44 ------ 1. 56 8.131E-01 ------ Line Not Found ------

768.35 ------ 4.88 7.078E-01 ------ Line Not Found ------

806.16 ------ 1. 23 6.754E-01 ------ Line Not Found ------

934.04 ------ 3.16 5.861E-01 ------ Line Not Found ------

1120. 27 ------ 15.00 4.982E-01 ------ Line Not Found ------

1155.18 ------ 1. 69 4.860E-01 ------ Line Not Found ------

1238. 11 ------ 5.92 4.615E-01 ------ Line Not Found ------

1280.95 ------ 1. 47 4.510E-01 ------ Line Not Found ------

1377.66 ------ 4.02 4.323E-01 ------ Line Not Found ------

1385.30 ------ 0.78 4.311E-01 ------ Line Not Found ------

1401. 48 ------ 1. 39 4.287E-01 ------ Line Not Found ------

1407.97 ------ 2.48 4.277E-01 ------ Line Not Found ------

1509.22 ------ 2.19 4.165E-01 ------ Line Not Found ------

1583.22 ------ 0. 72 4.120E-01 ------ Line Not Found ------

1661. 26 ------ 1.15 4.103E-01 ------ Line Not Found ------

1729.58 ------ 3.05 4 .114E-01 ------ Line Not Found ------

1764.49 ------ 15.90 4.128E-01 ------ Line Not Found ------

1847.41 ------ 2.12 4.187E-01 ------ Line Not Found ------

PB-214 53.17 ------ 1.10 2.929E-01 ------ Line Not Found ------

74.81 ------ 6.52 1.150E+OO ------ Line Not Found ------

77 .11 ------ 11. 00 1.239E+OO ------ Line Not Found ------

87.19 ------ 3.88 1.579E+OO ------ Line Not Found ------

90.13 ------ 1.15 1.662E+OO ------ Line Not Found ------

241. 92 ------ 7.46 1. 7 90E+OO ------ Line Not Found ------

258.94 ------ 0.55 1.718E+OO ------ Line Not Found ------

295.09 21 19.20* 1.579E+OO 5.366E-07 5.602E-07 27.23 351.87 29 37.10 1.395E+OO 4.318E-07 4.507E-07 25.69 785.83 ------ 1. 09 6.925E-01 ------ Line Not Found ------

839.00 ------ 0.59 6.497E-01 ------ Line Not Found ------

Nuclide Line Activity Report (continued) Page : 6 Sample ID : 30386 Acquisition date 6-JUN-2014 20:39:10 Flag: "*" Keyline

Minimum Detectable Activity Report Page : 7 Sample ID 30386 Acquisition date 6-JUN-2014 20:39:10 Bckgnd Energy MDA Nuclide Sum (keV) (uCi/GR)

BE-7 7. 477.61 l.0421E-06 MN-54 0. 834.83 3.2428E-08 MN-56 1. 846.81 9.1097E-08 C0-57 17. 122.06 9.3582E-08 C0-58 2. 810.79 l.0581E-07 C0-60 3. 1173.24 1.7561E-07 SB-124 5. 602.73 1.1698E-07 SB-125 5. 427.88 2.9104E-07 CS-134 5. 604. 71 l.1428E-07 CS-137 o. 661.66 3.0386E-08