ML19289D722
| ML19289D722 | |
| Person / Time | |
|---|---|
| Site: | Hatch |
| Issue date: | 03/05/1979 |
| From: | Scott Wilson GEORGIA POWER CO. |
| To: | |
| Shared Package | |
| ML19289D718 | List: |
| References | |
| NUDOCS 7903140284 | |
| Download: ML19289D722 (11) | |
Text
..
OPERATING DATA REPORT 50-321 DOCKET NO.
DATE 3-5-/9 CO.\\1PLETED llY S. Wilson TELEPilONE 912-167-7781 OPER ATING STATUS
- 1. Unit Name:
HATCH I Notes
- 2. Reporting Period:
February
- 3. Licensed Thermal Power (%!Wr):
2436
- 4. Nameplate Rating (Gross alWe):
809 3
- 5. Design Electrical Rating (Net 51We):
786.3
- 6. Sladam Dependable Capacity (Gross alWe): 764.3
- 7. 51a. naum Dependable Capachy (Net 51We):
731.3
- 8. If Changes Occur in Capacity Rstings (Ite ns Number 3 Through 7) Since Last Report. Give Reasons:
- 9. Power Level To Which Restricted. If Any (Net 5f We)
- 10. Reasons For Restrictions,if Any:
This Afonth Yr.-t o.Da t e Cumulatis e 11 Ilours In Reporting Period
_ 672.
1416 39122
- 12. Number Of Hours Reactor Was Critical 659.6 1196.8 29644
- 13. Reactor Resene Shutdown Ifours 0
0 o
- 14. Ilours Generator On-Line 642.
I162.9 27163.3
- 15. Unit Resene Shutdown flours 0
0 0
- 16. Gross Thermal Energy Generated (51WH) 1492986 2638472 522342'7 a
- 17. Gross Electrical Energy Generated (.\\lWH) 493100 873970 16924301
- 18. Net Electrical Energy Generated (.\\f WH) 472641 835505 161n7799
- 19. Unit Senice Factor 95.5 R2.1 71.6
- 20. Unit Asailability Factor 95.5 82.1 71.6
- 21. Unit Capacity Factor (Using 51DC Net) 96.2 80.7 58.0
- 22. Unit Capacity Factor (Using DER Net) 89.4 75.0 54.0
- 23. Unit Forced Outage Rate 4.5 17.9 18.1
- 24. Shutdowns Scheduled Oser Next 6.\\lonths (Type. Date,and Duration of Each):
Refuel / Maintenance, 5-1-79, 9 weeks
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup: _-
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achiesed INIIIA L CRillCA LITY INIIIAL ELECT RICITY CO\\l\\lERCI \\L OPER \\ TION 79031402 6 cm7)
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-321 trNi r Hatch 1 3-5-79 DATE S. Wilson CON 1PLETED In' 912-367-7781 TELEPilONE
%!ONTil February DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POWER LEVEL (51We-Net) g33we yeg, 1
-13 739 i7 2
254 18 763 3
516 19 761 761 4
714 r
2g 5
698 758 21 6
763 755 22 7
764 751 23 s
766 741 24 9
766 25 751 10 767 26 756 11 765 27 761 12 762 756 2s 13 760 79 14 758 3g 15 754 3,
16 747 INSTRUCTIONS On this format.hst the average daily umt power leselin.\\1We-Net for each day in the reporting month. Compute to the nearest whole megawatt.
(o /77 )
UNIT SIIUTDOWNS AND POWER REDUCTIONS DOCKET NO.
50-321 UNIT NAME Hatch 1 DATE J-5-/9 REPORT MONTil February COMPLETED BY S. Wilson TELEPIIONE 912 167-7781 "E
- s
.! E h
) E)
Licensee
,E -t, h*o Cause & Corrective E.?
Action to No.
Da te g
3g
(
jg5 Event
- ?
$E j@g Report a
<E C U
H Prevent Recurrence 6
79-04 2-1-79 F
30.0 G
3 CF VALVEX High D/W Pressure Due to Venting Into Torus When Ell-F015A Leaked i
1 2
3 4
F: Forced Reason :
Method:
Exhibit G - Instructions S: Scheduled A-Equipment Failure (Explain) 1 -Manual for Preparation of Data ll-Maintenance of Test 2-Manual Scram.
Entry Sheets for Licensee C Refueling 3-Automatic Scram.
Event Report (LER) File (NURI:G-D-Regulatory Restriction 4-Ot her ( E xplain )
0161)
E-Operator Training & License Examination F-Administ rative 5
G-Operational Er ror (Explain)
Exhibit ! - Same Source P)/77) 11-01he r (E xplain )
NARPATIVE REPOHT HATCH 1 Feb. 1 Rx. trttical 1235 CST Feb. 2 On line 0602 CST Feb. 4 Rod pottern thange 2133 CST Feb. 5 Normal operatiori at ra ted p owei-There was no sitigle release of radioactivtiy or single radia tion e x p osu r e-uliich act uun ts for ino r e than 10 percent of the a110wable atitiual values during the too n t h of February 1979.
MR -f t Dale Description 77-102S 2-19-79 R eino v e d ross solenoid operated air valve in order to repair 77-1627 2-19-79 Replaced inotor and fili.ers on underwa ter vacuuin cleaner 78-2644 2-1-79 Replaced GM Lube on sensor converLor.
Per f ortne J calibralions 78-3136 2-1-79 Repaired carbon bed vault area radia ti on inon t ior 78-3171 2-1-79 Repaired carbon bed vault area radiation inan i tor 78-39E.7 2-16-79 Replaced transf ormer on Chromatux Healer 78-4276 2-5-79 Removed and cleaned air lock inner door seals 78-4303 2-7-79 Investigated position indication liglits in control room 78-43/15 1-31-79 Replaced SRM detecter and cable g r ouiid connectors 78-4361 2-5-79 Checked valvc7 N21-FOO58, packing and lighLened 78-436/1 2-7-79 Replaced 9achets and cleaned RCIC inlet drain pot steamtrap bypass valve
~78-/4 396 2-5-79 Repaired leaking pathing on E41-FC'Go 9a le valve 78-4.'405 1-26-79 Cleaned crystals from standby liquid con trol pump 78-4406 1-26-79 Cleaned crystals from standby liquid control puur 78-4414 2-5-79 Replaced SRV l eal< i n g pressure switch 78-4458 1-30-79 Cleaned valve T/18-AGF-323A and adjusted operating speed 79-29 2-1-79 Installed caulk around A Tx 8 cen trifuge plaies 79-81 2-11-79 Cleaned all input cables to SHM (51-K600C) 79-82 2-4-79 Investigated and repaired main sicch flot recorder 79-94 1-2S-79 Modified service platform suppor tc 79-163 2-1-79 Repaired hand and foot moni tor
79-191 2-9-79 Ground out cracl< in 1/2 SS line and welded b a t i:
79-191 1-31-79 Relocated Fisfier Con troller and support
, rl i n t a i< e structure 79-193 1-31-79 Replaced and calibrated RWCU leait alarm tim" delay relay 79-194 2-8-79 Inspected Unit I and Unit 2 fire dampers79-195 1-28-79 Performed operability test HNP-1-3960 sa tisf ac tor ly 79-196 2-9-79 Performed operability Leut HN=-1-6950 satisfactorly
~/9-197 1-28-79 Performed operability tes t HNP 399 satisfactorly
/9-202 2-9-79 Perfurmed operability test HNP-1-$+ O satisfactorly (9-203 2-9-79 Performed operability test HNP-1-6960 satisfactorly
/9-216 2-9-79 Performed
'bperabili ty test HNP 3'9'-l '
satisfactorly
'/9-219 2-14-79 Performed operability tecL HNP 3'960 satisfactorly (9-220 2-9-79 Performed operabilily tesL HtF-L-3960 satisfactorly
/9-221 2-9-79 Performed operab111ty i.e s t HNR-1-$960 satisfatturly 79-222 2-9-79 Performed operabili ty test HNP 5S9 )
satisfactorly 79-225 2-14-79 Performed operabiltly test HNC-1-3960 satisfattorly
/9-226 1-30-79 Repaired bad amplifier ou drywell vent e x haus t flow recorder (9-233 2-9-79 Performed operability Les t hip 3 99 '-
satisfatlorly 79-246 2-14-79 Checked AC line on POO1 con trol panel
'79-298 2-15-79 Repaired and calibrated core pressure drop i' e C o r d e r 79-262 2-6-79 Removed and repaired burned HPC1 injettion vi : l v t:
inotor 79-263 2-3-79 Set limit swittlieu on RCIC inin flow valve 79-266 2-3-79 Replaced bad i 15 volt regulator card 79-268 1-29-79 Calibra ted SBCT inside air to ou ts idr.
air O.P.
monitoru 79-2/O 1-2S-79 Repaired lube oil pump starter 79-271 2-6-79 Repaired main stack rad monitor sample pump "A"
79-2'74 2-3-79 Made adjustments to APHM F retorder 79-280 2-4-79 Repair 12SV battery char 9er 79-2E2 2-6-79 Cleaned and ti9htened strew connet Lions on rela >
G11-POO1-3 Rebuilt RWCU ".g B"
pump to inanuf ac tureu spet 79-293 2-3-79 e
79-299 2-3-79 Cleaned and replaced motor bearing 79-300 1-30-79 Replaced lower upeed char t dr ive mo tor 79-301 2-10-79 Chetl<ed all cables connected to IRM "A"
for loose connetLionu 79-304 1-30-79 Calibrated G.E.D.P.
transmitter G11-NO49 79-305 1-26-79 Repaired jacket coolant prouture low annunciator 79-347 2-9-79 Repaired hand and foot monttor 79-348 2-9-79 Repaired hand and f oo t mon t tor 79-349 2-9-79 Repaired leatr on hand and foo' mois t lor 79-352 1-31-79 Cheticed reactor b1d9 put contaminated high rad.
annunciaior 79-354 1-31-79 Replaced bulbs in MS1V tlosure le ip L> y p a s -
annunciator 79-355 2-10-79 Repaired lealc un RHR injetLion valve
~79-3'58 2-4-79 Replaced control rod 38-47 79-364 2-19-79 Repaticed sanitary booster pump "A"79-367 1-31-79 Re-installed Locus man-way cover 79-376 2-10-79 Repaired containmen t radia tion munilor "A"79-377 2-6-79 Repaired limit swiLch for radwaste empty druw C O Tiv e y o r 79-378 2-5-79 Changed out bad Lunde11 annuutiator terd 79-396 2-10-79 A6ded packing to HPCI closure valve to contoinment 79-398 2-3-79 Repaired annunciator H11-P603 79-399 2-6-79 Adjusted limit switch for empty drum conveyor 79-401 2-14-79 Repaired power supply to ven t rad monitor 79-408 2-3-79 Repaired "B"
GE Mac Rx.
wa ter level ind i ca t i on 0-60 inthes79-424 2-3-79 Replaced wateTJ analysis recorder's speed motor 79-42b 2-10-79 Replaced union at lap for pressure gauge sensing line 79-434 2-1-79 Removed torus access hatch 79-436 2-6-79 Repaired Rx. water level indicator 79-437 2-6-79 Investigated IRM "B"
channel "B" RPR 79-438 2-15-79 Changed setpo_ats of Rx. 81d9 vent rad, monitor 79-443 2-3-79 Replaced tore matrix full in lights79-445 2-3-79 Replaced light bubls in panel H11-P65a 79-448 2-11-79 Added 4 9 ts. of deminerallzed water
- 1. 0 the 29/4E volt RPS batteries
=
79-449 2-3-79 Repaired red pen on 241-H618 recurder 79-451 2-3-79 Adjusted setpoint
- f. o correct valve for "B" SRM 79-452 2-3-79 Replaced torque switch on CRD cooling wa le-press. tontainmenL valve
f 79-453 2-5-79 Changed out theee blown atinunt ia tor lights79-474 2-8-79 Cleaned and replaced 1/4" recirt s arnp l e line 79-476 2-3-79 Repaired ead ueleti raa t r i x 79-477 2-3-79 Baticfilled R x. Water level instruments79-479 2-6-79 Drained water from pretreatment saine le line and inon i tor 79-453 2-6-79 Replaced bad annunciator tard H11-P650 79-489 2-3-79 Replaced blown fuses in ERM drive con trol panet 79-490 2-6-79 Adjusted packing on "R"
tetirt putop diuthar9" valve 79-503 2-6-79 Replaced faulty annuntiator card for H11-P601 79-504 2-6-79 Replaced faulty annunciator card for H11-F602 79-5C6 2-6-79 Investigated RCIC exhaust line vacuum biecker MOV 79-513 2-6-79 Repaired leaking Na charging valve C11-F111 79-530 2-4-79 Repaired frozen CRD teinp returder 79-534 2-6-79 Replaced faulty annunciator card for H11-PE50 79-535 2-6-79 Replaced faulty annunc2ator card for H11-P653 79-542 2-15-79 Adjuuted 1A off9as H2 Analyzer Flow 79-54S 2-10-79 Calibrated D/W torus Na purge flow recorder 79-549 2-10-79 Repaired and calibrated D/W Na pas LOCA makeup flow recorder 79-550 2-7-79 Repaired, cleaned, and replaced g a sle e lt, on valve E51-F026 79-551 2-11-79 Repaired leaking packing on valve 551-F059 79-553 2-8-79 Replaced reset bulb on torus vatuutn relief r310 open annuntiator 79-563 2-7-79 Replaced hand wheel on steam trap isolation valve 79-571 2-20-79 Repaired leaky packing on valve E41-F028
79-5'74 2-8-79 Replaced bulb in lube oil storage lat il annunciator 79-614 2-12-79 Load tested gas powered forl: liei 79-615 2-12-79 Load tested 15 ton hydraulic lif(79-619 2-23-79 Replaced oil seal and added oil to gearbox of filter aid agilator
'79-620 2-10-79 Repaired logic in RWCU Powder panel 79-621 2-14-79 Replaced bad annunciator card for H11-P653 annunciator 79-627 2-18-79 Repaired linhage for service outiet i s o l a f.i o n valve 79-631 2-14-79 Purged the tube to the lab hood low flow clarin 79-638 2-19-79 Changed the setpoints for pretrealment a ud.
monilor 79-6/12 2-14-79 Repaired drive motor and generator temp. recorde 79-643 2-19-79 Removed B mithine gamma tip and
>erlaced zu series two dummy cables79-647 2-14-79 Replaced bulbs in H11-P652 annuncialor 79-648 2-14-79 Replaced bulbs
.n H11-P650 annunciator 79-661 2-15-79 Checked 1A Rx. recirt M-G set speed controller 79-676 2-18-79 Replaced RPS Yarway indicator 79-677 2-18-79 Replaced two bulbs in D/W pneumalit bathup systeTTI oft allnultC ia tor 79-684 2-18-79 Repaired H11-P651 annunciator card 79-703 2-20-79 Replaced blown fuse for valve posttion indica tion on control panel 79-704 2-23-79 Adjusted air flow for intake "i>u bb l e" levei iTtdica lor 79-705 2-23-79 Changed point card for 4-u e l oil level hi-len or tank wa ter detection alartu 79-710 2-2C'-79 Repaired dr ive Inotor fx generator temp recordue
79-7'12 2-23-79 Repaired recirc drive temp recorder 79-725 2-20-79 Replaced annunciator card for Hll-PM3 79-726 2-23-79 Repaired 1C diesel generator annunciator panel 79-730 2-20-79 Repaired door liandle and luiob to Rx.
- Ulds, to turbine b1dg. airlock door 79-731 2-23-79 Filled oil reservoir for circulating water pump 1A 79-732 2-23-79 Filled oil reservoir for circulating water pump 18 79-739 2-20-79 Tiglitened set screw for circula ting water pump 1B 79-754 2-23-79 Repaired standby licuid tank !.crne. iii/ low alarui 79-763 2-20-79 Secured nameplate on NSSS relay in patie l Hl l-P 6e 79-767 2-23-79 Clianged out Lundell annuntlator card vor H i l -F6.O i 79-768 2-23-79 Clianged blown li9 lit bulbs in annunciator H11-P650 79-782 2-23-79 Rep lac ed car <T Yor air lot h aniiunc ia tor
'/9-786 2-23-79 Replaced card for annunciator HL1-P650 79-787 2-23-79 Fixed con tacts for ~18 Re-vent alarm 79-768 2-26-79 Fixed contacts for A1. Rx. Bidu. 203' a larni