Letter Sequence Response to RAI |
---|
TAC:ME4640, Steam Generator Tube Integrity (Approved, Closed) |
Results
- Approval, Approval, Approval, Approval, Approval, Approval, Approval, Approval, Approval, Approval, Approval, Approval
Other: L-11-114, Drawing No. M-042B, Rev. 35, Sampling System Sh. 2 Local Grab Samples, L-11-131, Drawing No. LR-OS041A2, Revision 1, Operational Schematic Emergency Diesel Generator Systems., L-11-334, Reply to Request Additional Information for the Review of the License Renewal Application Amendment No. 21, L-12-337, Review of the Safety Evaluation Report with Open Items Related to the License Renewal, L-12-444, Submittal of Contractor Equivalent Margins Assessments for Reactor Vessel Welds (Nonproprietary Versions), L-12-456, Notification of Closure of Commitments Related to the Review of the License Renewal Application, L-13-257, Notification of Completion of a License Renewal Commitment Related to the Review of License Renewal Application TAC No. ME4640) and License Renewal Application Amendment No. 45), L-13-330, License Renewal Application Amendment No. 46 - Annual Update, L-13-341, Review of the Safety Evaluation Report Related to the License Renewal of Davis-Besse Nuclear Power Station, L-14-085, License Renewal Application (TAC No. ME4640) Amendment No. 48, L-14-206, License Renewal Application Amendment No. 50 - Annual Update, L-15-120, Notification of Completion of License Renewal Commitments Related to the Review of the Davis-Besse Nuclear Power Station, Unit No. 1, License Renewal Application and License Renewal Application Amendment No. 55, L-15-139, License Renewal Reactor Vessel Internals Inspection Plan, L-15-214, License Renewal Application Amendment No. 59 - Annual Update, L-15-309, License Renewal Application Amendment No. 60, L-15-310, C-CSS-099.20-069, Rev 0, Shield Building Laminar Cracking Limits., ML102450565, ML111050091, ML11110A089, ML11110A091, ML11110A092, ML11110A093, ML11110A094, ML11110A095, ML11110A105, ML11110A106, ML11110A107, ML11122A014, ML11126A017, ML11126A018, ML11126A019, ML11126A020, ML11126A021, ML11126A022, ML11126A023, ML11126A024, ML11126A025, ML11126A026, ML11126A032, ML11126A033, ML11126A034, ML11126A035, ML11126A036, ML11126A037, ML11126A038, ML11126A039, ML11126A040, ML11126A041, ML11126A042, ML11126A043... further results
|
MONTHYEARML11126A0882008-01-12012 January 2008 Drawing No. LR-M041B, Revision 1, Piping & Instrument Diagram Primary Service Water System. Job Code 12501 Project stage: Other ML11126A0902008-01-15015 January 2008 Drawing No. LR-OS41A1, Revision 1, Operational Schematic Emergency Diesel Generator Systems. Project stage: Other L-11-131, Drawing No. LR-OS041A2, Revision 1, Operational Schematic Emergency Diesel Generator Systems.2008-01-15015 January 2008 Drawing No. LR-OS041A2, Revision 1, Operational Schematic Emergency Diesel Generator Systems. Project stage: Other ML11126A0682008-05-0505 May 2008 Drawing No. LR-M-037E, Revision 28, Piping & Instrument Diagram Clean Liquid Radioactive Waste System. Project stage: Other ML11126A0652008-08-0606 August 2008 Drawing No. LR-M036B, Revision 1, Piping & Instrument Diagram Component Cooling Water System. Project stage: Other ML11126A0592008-10-0909 October 2008 Drawing No. LR-M033A, Revision 1, Piping & Instrument Diagram High Pressure Injection. Project stage: Other ML11126A0632008-10-10010 October 2008 Drawing No. LR-M033B, Revision 1, Piping & Instrument Diagram Decay Heat Train 1. Project stage: Other ML11126A0702008-10-10010 October 2008 Drawing No. LR-M033C, Revision 1, Piping & Instrument Diagram Decay Heat Train 2. Project stage: Other ML11126A0742008-11-0606 November 2008 Drawing No. LR-M043, Revision 1, Piping & Instrument Diagram Auxiliary Building Chilled Water System. Project stage: Other ML11126A0832008-12-18018 December 2008 Drawing No. LR-M038C, Revision 2, Piping & Instrument Diagram Gaseous Radioactive Waste System. Job Code 12501 Project stage: Other ML11126A0712009-04-0707 April 2009 Drawing No. LR-M034, Revision 1, Piping & Instrument Diagram Emerg. Core Cooling System Ctmt. Spray & Core Flooding Systems. Project stage: Other ML11126A0892009-04-0707 April 2009 Drawing No. LR-OS002, Revision 1, Operational Schematic Makeup and Purification System. Project stage: Other ML1024505652010-08-27027 August 2010 License Renewal Application and Ohio Coastal Management Program Consistency Certification Project stage: Other ML1104500462011-02-17017 February 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station - Fire Protection Project stage: RAI ML11126A0792011-02-25025 February 2011 Drawing No. LR-M900A, Revision 0, Instrument Air System Piping Schematic. Project stage: Other ML1104205972011-02-28028 February 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station - Section 2.4 Project stage: RAI ML1106801722011-03-17017 March 2011 Request for Additional Information on the Reactor Vessel Surveillance Aging Management Program, Time-Limited Aging Analyses for Neutron Embrittlement of the Rv and Internals, and Other TLAAs for the Review of the Davis-Besse Nuclear Power S Project stage: RAI ML1107007322011-03-18018 March 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station-Section 2.2 & 2.3 Project stage: RAI L-11-078, Reply to Request for Additional Information for the Review of License Renewal Application (TAC ME4640) Amendment No. 12011-03-18018 March 2011 Reply to Request for Additional Information for the Review of License Renewal Application (TAC ME4640) Amendment No. 1 Project stage: Response to RAI ML11068A0002011-03-21021 March 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station - Section 4.7 (TAC Number ME4640) Project stage: RAI L-11-079, Reply to Request for Additional Information for the Review of the License Renewal Application2011-03-23023 March 2011 Reply to Request for Additional Information for the Review of the License Renewal Application Project stage: Response to RAI L-11-089, Reply to Request for Additional Information for the Review License Renewal Application2011-03-23023 March 2011 Reply to Request for Additional Information for the Review License Renewal Application Project stage: Response to RAI ML1108206242011-03-30030 March 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station-Section 2.1 (Tac No. ME4640) Project stage: RAI ML1109002952011-03-31031 March 2011 Safety Evaluation Report Related to the License Renewal of Salem Nuclear Generating Station Project stage: Approval ML1108204902011-04-0505 April 2011 Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station - Batch 1 Project stage: RAI ML11110A0932011-04-15015 April 2011 Drawing No. M-037D, Rev. 21, Clean Liquid Radioactive Waste System Project stage: Other ML11110A1072011-04-15015 April 2011 Drawing No. M-045, Rev. 56, Chemical Addition Systems Project stage: Other ML11110A1062011-04-15015 April 2011 Drawing No. M-042C, Rev. 33, Sampling System Sh. 3 Project stage: Other ML11110A1052011-04-15015 April 2011 Drawing No. M-040A, Rev. 76, Reactor Coolant System Details Project stage: Other ML11110A0952011-04-15015 April 2011 Drawing No. M-039B, Rev. 18, Miscellaneous Liquid Radioactive Waste Project stage: Other ML11110A0942011-04-15015 April 2011 Drawing No. M-039A, Rev. 33, Miscellaneous Liquid Radioactive Waste Project stage: Other ML11110A0922011-04-15015 April 2011 Drawing No. M-037C, Rev. 30, Clean Liquid Radioactive Waste System Project stage: Other L-11-114, Drawing No. M-042B, Rev. 35, Sampling System Sh. 2 Local Grab Samples2011-04-15015 April 2011 Drawing No. M-042B, Rev. 35, Sampling System Sh. 2 Local Grab Samples Project stage: Other L-11-107, Reply to Request for Additional Information on Reactor Vessel Surveillance Aging Management Program & Time-Limited Aging Analyses for Neutron Embrittlement for Review of License Renewal Application & License Renewal Application...2011-04-15015 April 2011 Reply to Request for Additional Information on Reactor Vessel Surveillance Aging Management Program & Time-Limited Aging Analyses for Neutron Embrittlement for Review of License Renewal Application & License Renewal Application... Project stage: Response to RAI ML11110A0882011-04-15015 April 2011 Reply to Request for Additional Information for the Review of the License Renewal Application, Sections 2.2 & 2.3, License Renewal Application Amendment No. 3, and Revised License Renewal Project stage: Response to RAI ML11110A0912011-04-15015 April 2011 Drawing No. M-011, Rev. 61, Domestic Water System Project stage: Other ML11110A0892011-04-15015 April 2011 Drawing No. M-0060, Rev. 52, Auxiliary Feedwater System Project stage: Other ML1110500912011-04-19019 April 2011 Scoping and Screening Audit Report Regarding the Davis-Besse Nuclear Power Station License Renewal Application Project stage: Other L-11-115, Reply to Request for Additional Information for the Review of the License Renewal Application and License Renewal Application Amendment No. 42011-04-20020 April 2011 Reply to Request for Additional Information for the Review of the License Renewal Application and License Renewal Application Amendment No. 4 Project stage: Response to RAI ML1109807182011-04-20020 April 2011 Request for Additional Information for the Review of the Davis-Bessie Nuclear Power Station - Batch 2 Project stage: RAI ML11126A0362011-04-29029 April 2011 Drawing No. LR-M017D, Revision 1 Piping & Instrument Diagram, Steam Blackout Diesel Generator. Project stage: Other ML11126A0352011-04-29029 April 2011 Drawing No. LR-M017C, Revision 2, Piping & Instrument Diagram, Fuel Oil. Project stage: Other ML11126A0342011-04-29029 April 2011 Drawing No. LR-M017B, Revision 1, Piping & Instrument Diagram, Diesel Generators Air Start. Project stage: Other ML11126A0332011-04-29029 April 2011 Drawing No. LR-M016B, Revision 1, Piping & Instrument Diagram Station Fire Protection System Project stage: Other ML11126A0322011-04-29029 April 2011 Drawing No. LR-M016A, Revision 1, Piping & Instrument Diagram Station Fire Protection System Project stage: Other ML11126A0262011-04-29029 April 2011 Drawing No. LR-M010C, Revision 1, Piping & Instrument Diagram Make-up Water Treatment System Project stage: Other ML11126A0252011-04-29029 April 2011 Drawing No. LR-M010A, Revision 1, Piping & Instrument Diagram Make-Up Water Treatment System Project stage: Other ML11126A0242011-04-29029 April 2011 Drawing No. LR-M009B, Revision 1, Piping & Instrument Diagram Cooling Water System Project stage: Other ML11126A0192011-04-29029 April 2011 Drawing No. LR-M003A, Revision 1, Piping & Instrument Diagram Main Steam and Reheat System. Sheet 1 Project stage: Other ML11126A0452011-04-29029 April 2011 Drawing No. LR-M024H, Revision 1, Piping & Instrument Diagram, No. 2 Main and Auxiliary Turbine Driven Feed Pumps. Project stage: Other 2011-02-25
[Table View] |
|
---|
Category:Letter type:L
MONTHYEARL-23-260, Corrections to the 2022 Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report for the Davis-Besse Nuclear Power Station2023-12-0707 December 2023 Corrections to the 2022 Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report for the Davis-Besse Nuclear Power Station L-23-243, Independent Spent Fuel Storage Installation - Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation2023-12-0606 December 2023 Independent Spent Fuel Storage Installation - Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation L-23-215, Changes to Emergency Plan2023-10-19019 October 2023 Changes to Emergency Plan L-23-205, Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-09-12012 September 2023 Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments L-23-172, Quality Assurance Program Manual2023-08-31031 August 2023 Quality Assurance Program Manual L-23-188, Energy Harbor Nuclear Corp., Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-08-0707 August 2023 Energy Harbor Nuclear Corp., Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments L-23-175, Submittal of Fifth Ten Year Inservice Testing Program2023-08-0101 August 2023 Submittal of Fifth Ten Year Inservice Testing Program L-23-034, 2022 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models2023-06-13013 June 2023 2022 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models L-23-135, Response to Regulatory Issue Summary 2023-01, Preparation and Scheduling of Operator Licensing Examinations2023-05-31031 May 2023 Response to Regulatory Issue Summary 2023-01, Preparation and Scheduling of Operator Licensing Examinations L-23-065, Annual Financial Report2023-05-22022 May 2023 Annual Financial Report L-23-131, Readiness for Resumption of NRC Supplemental Inspection2023-05-12012 May 2023 Readiness for Resumption of NRC Supplemental Inspection L-23-101, Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report for the Davis-Besse Nuclear Power Station - 20222023-05-12012 May 2023 Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report for the Davis-Besse Nuclear Power Station - 2022 L-23-092, Occupational Radiation Exposure Report for Year 20222023-04-27027 April 2023 Occupational Radiation Exposure Report for Year 2022 L-23-061, Submittal of the Decommissioning Funding Status Reports2023-03-31031 March 2023 Submittal of the Decommissioning Funding Status Reports L-23-037, and Perry Nuclear Power Plant - Independent Spent Fuel Storage Installation Changes, Tests, and Experiments2023-03-29029 March 2023 and Perry Nuclear Power Plant - Independent Spent Fuel Storage Installation Changes, Tests, and Experiments L-23-066, Annual Notification of Property Insurance Coverage2023-03-21021 March 2023 Annual Notification of Property Insurance Coverage L-23-059, Response to Apparent Violation in NRC Inspection Report 05000346/2022091; EA 23-0022023-03-0909 March 2023 Response to Apparent Violation in NRC Inspection Report 05000346/2022091; EA 23-002 L-22-212, CFR 50.55a Request RP-5 Regarding Inservice Pump Testing2023-03-0606 March 2023 CFR 50.55a Request RP-5 Regarding Inservice Pump Testing L-23-048, Response to Request for Additional Information Regarding Technical Specification 5.6.6 Steam Generator Tube Inspection 180-Day Report2023-03-0101 March 2023 Response to Request for Additional Information Regarding Technical Specification 5.6.6 Steam Generator Tube Inspection 180-Day Report L-23-057, Energy Harbor Nuclear Corp Retrospective Premium Guarantee2023-02-20020 February 2023 Energy Harbor Nuclear Corp Retrospective Premium Guarantee L-22-253, Submittal of Pressure and Temperature Limits Report, Revision 52023-01-10010 January 2023 Submittal of Pressure and Temperature Limits Report, Revision 5 L-22-284, Request for Notice of Enforcement Discretion for Technical Specification 3.7.9, Ultimate Heat Sink (UHS)2022-12-28028 December 2022 Request for Notice of Enforcement Discretion for Technical Specification 3.7.9, Ultimate Heat Sink (UHS) L-22-211, Technical Specification 5.6.6 Steam Generator Tube Inspection 180-Day Report2022-09-29029 September 2022 Technical Specification 5.6.6 Steam Generator Tube Inspection 180-Day Report L-22-216, Submittal of Pressure and Temperature Limits Report. Revision 42022-09-27027 September 2022 Submittal of Pressure and Temperature Limits Report. Revision 4 L-22-213, Occupational Radiation Exposure Report for Year 2021 - Correction2022-09-23023 September 2022 Occupational Radiation Exposure Report for Year 2021 - Correction L-22-129, Submittal of the Updated Final Safety Analysis Report, Revision 342022-09-20020 September 2022 Submittal of the Updated Final Safety Analysis Report, Revision 34 L-22-194, Submittal of Supplemental Information for the Reanalysis for Protection Against Low Temperature Reactor Coolant System Overpressure Events2022-09-19019 September 2022 Submittal of Supplemental Information for the Reanalysis for Protection Against Low Temperature Reactor Coolant System Overpressure Events L-22-203, Submittal of Evacuation Time Estimates2022-09-12012 September 2022 Submittal of Evacuation Time Estimates L-22-050, Summary of Changes to the Energy Harbor Nuclear Corp. Quality Assurance Program Manual2022-08-0909 August 2022 Summary of Changes to the Energy Harbor Nuclear Corp. Quality Assurance Program Manual L-22-152, Response to Request for Additional Information Regarding a License Amendment Request That Revises the Davis-Besse Nuclear Power Station Emergency Plan2022-07-0505 July 2022 Response to Request for Additional Information Regarding a License Amendment Request That Revises the Davis-Besse Nuclear Power Station Emergency Plan L-22-068, Cycle 22 and Refueling Outage 22 Inservice Inspection Summary Report2022-06-30030 June 2022 Cycle 22 and Refueling Outage 22 Inservice Inspection Summary Report L-22-037, 2021 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models2022-06-30030 June 2022 2021 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models L-22-149, Post Accident Monitoring Report2022-06-23023 June 2022 Post Accident Monitoring Report L-22-153, Readiness for NRC Supplemental Inspection Required for a White Finding2022-06-22022 June 2022 Readiness for NRC Supplemental Inspection Required for a White Finding L-22-098, Withdrawal of Proposed Inservice Inspection Alternative RR-A22022-06-22022 June 2022 Withdrawal of Proposed Inservice Inspection Alternative RR-A2 L-22-136, Steam Generator Tube Circumferential Crack Report - Spring 2022 Refueling Outage2022-06-0707 June 2022 Steam Generator Tube Circumferential Crack Report - Spring 2022 Refueling Outage L-22-102, Report of Facility Changes, Tests, and Experiments2022-05-16016 May 2022 Report of Facility Changes, Tests, and Experiments L-22-092, Combined Annual Radiological Environmental Operating Report and Radiological Effluent Release Report for the Davis-Besse Nuclear Power Station - 20212022-05-16016 May 2022 Combined Annual Radiological Environmental Operating Report and Radiological Effluent Release Report for the Davis-Besse Nuclear Power Station - 2021 L-22-124, Response to Request for Additional Information Regarding License Amendment Request to Revise the Design Basis for the Shield Building2022-05-12012 May 2022 Response to Request for Additional Information Regarding License Amendment Request to Revise the Design Basis for the Shield Building L-22-047, Unit No.1 - Core Operating Limits Report, Cycle 23, Revision O and Revision 12022-05-10010 May 2022 Unit No.1 - Core Operating Limits Report, Cycle 23, Revision O and Revision 1 L-22-127, Readiness for NRC Supplemental Inspection Required for a Greater than Green Finding2022-05-0606 May 2022 Readiness for NRC Supplemental Inspection Required for a Greater than Green Finding L-22-089, Occupational Radiation Exposure Report for Year 20212022-04-12012 April 2022 Occupational Radiation Exposure Report for Year 2021 L-22-056, Energy Harbor Nuclear Corp., Annual Notification of Property Insurance Coverage2022-03-22022 March 2022 Energy Harbor Nuclear Corp., Annual Notification of Property Insurance Coverage L-22-059, Response to Request for Additional Information on Proposed Inservice Test Alternative RP-32022-03-21021 March 2022 Response to Request for Additional Information on Proposed Inservice Test Alternative RP-3 L-22-074, Response to Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations2022-03-15015 March 2022 Response to Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations L-22-061, Ile Post Exam Letter L-22-0612022-02-24024 February 2022 Ile Post Exam Letter L-22-061 L-22-023, Retrospective Premium Guarantee2022-02-17017 February 2022 Retrospective Premium Guarantee L-21-266, Response to Request for Additional Information on Proposed Inservice Inspection Alternative RR-A22022-01-27027 January 2022 Response to Request for Additional Information on Proposed Inservice Inspection Alternative RR-A2 L-20-289, Emergency Plan Amendment Request2022-01-19019 January 2022 Emergency Plan Amendment Request L-21-290, Response to NRC Inspection Report 05000346/2021091, EA-21-1762021-12-21021 December 2021 Response to NRC Inspection Report 05000346/2021091, EA-21-176 2023-09-12
[Table view] |
Text
FENOCTM F 5501 North State Route 2 FirstEnergy Nuclear Operating Company Oak Harbor,Ohio 43449 Raymond A. Lieb 419-321-7676 Vice President,Nuclear Fax: 419-321-7582 May 17, 2013 L-13-181 10 CFR 54 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Davis-Besse Nuclear Power Station, Unit No. 1 Docket No. 50-346, License Number NPF-3 Supplemental Reply to Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station, Unit No. 1, License Renewal Application (TAC No. ME4640) and License Renewal Application Amendment No. 41 By letter dated August 27, 2010 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML102450565), FirstEnergy Nuclear Operating Company (FENOC) submitted an application pursuant to Title 10 of the Code of FederalRegulations, Part 54 for renewal of Operating License NPF-3 for the Davis-Besse Nuclear Power Station, Unit No. 1 (Davis-Besse). By letter dated March 14, 2013 (ML13077A391), FENOC responded to a Nuclear Regulatory Commission (NRC) request for additional information (RAI) B.2.4-1 b regarding structural high strength bolting.
During telephone conference calls with the NRC held on April 11, April 24, and May 2, 2013, FENOC agreed to submit a supplemental response to RAI B.2.4-1b to address volumetric examinations of high strength structural bolts managed by the Davis-Besse Inservice Inspection (ISI) - IWF Program.
The Attachment provides the FENOC supplemental response to the NRC request for additional information. The NRC request is shown in bold text followed by the FENOC response. The Enclosure provides Amendment No. 41 to the Davis-Besse License Renewal Application.
Davis-Besse Nuclear Power Station, Unit No. 1 L-1 3-181 Page 2 There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Clifford I. Custer, Fleet License Renewal Project Manager, at 724-682-7139.
I declare under penalty of perjury that the foregoing is true and correct. Executed on May _.J__, 2013.
Sincerely,
Attachment:
Supplemental Reply to Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station, Unit No. 1 (Davis-Besse), License Renewal Application (LRA), Section B.2.4
Enclosure:
Amendment No. 41 to the Davis-Besse License Renewal Application cc: NRC DLR Project Manager NRC Region III Administrator cc: w/o Attachment or Enclosure NRC DLR Director NRR DORL Project Manager NRC Resident Inspector Utility Radiological Safety Board
Attachment L-1 3-181 Supplemental Reply to Request for Additional Information for the Review of the Davis-Besse Nuclear Power Station, Unit No. 1 (Davis-Besse),
License Renewal Application (LRA),
Section B.2.4 Page 1 of 2 Supplemental Question RAI B.2.4-1b By letter dated March 14, 2013 (ML13077A391), FENOC provided a response to RAI B.2.4-1 b addressing visual inspections and volumetric examinations of high strength structural bolts managed by the Structures Monitoring Program. In a conference call with FENOC on April 11, 2013, the NRC staff stated they had identified a gap between the FENOC response and NUREG-1801, "Generic Aging Lessons Learned (GALL) Report." Specifically, the NRC staff stated that NUREG-1801 requires monitoring of A325 and A490 high strength bolting (i.e., actual measured yield strength greater than or equal to 150 ksi [thousand pounds per square inch]) in ASME Section XI, Subsection IWF applications for stress corrosion cracking using volumetric examination. The staff stated that the IWF Program requirement for A325 and A490 bolting is different from the requirement for A325 and A490 high strength structural bolting addressed in the Structures Monitoring Program, because there is an exemption for high strength A325 and A490 bolting in the Structures Monitoring Program that does not exist in the IWF Program. After some discussion, FENOC proposed a follow-up conference call on this topic once the issues were better understood.
Additional conference calls were conducted on April 24 and May 2, 2013. In summary, FENOC agreed to provide a supplemental response to RAI B.2.4-1b to address volumetric examinations of IWF high strength structural bolts (i.e., actual measured yield strength greater than or equal to 150 ksi) in sizes greater than 1 inch nominal diameter.
SUPPLEMENTAL RESPONSE RAI B.2.4-1b NUREG-1801, "Generic Aging Lessons Learned (GALL) Report," Revision 2,Section XI.S3, "ASME Section Xl, Subsection IWF," requires monitoring of high strength structural bolting (i.e., actual measured yield strength greater than or equal to 150 ksi or 1,034 MPa) in sizes greater than 1 inch nominal diameter for cracking using volumetric examination.
FENOC has identified that Davis-Besse has high strength structural bolts (i.e., actual measured yield strength greater than or equal to 150 ksi) in sizes greater than 1 inch nominal diameter in the IWF bolting population consisting of material types ASTM A490 and ASTM A540.
Attachment L-1 3-181 Page 2 of 2 ASTM A325 bolts in the IWF bolting population were determined not to be high strength.
The specified minimum yield strength for the subject ASTM A325 Type 1 bolting is 81 ksi, which is substantially below the high strength threshold of 150 ksi. The certified material test reports (CMTRs) for 214 ASTM A325 bolts confirm that the yield strengths are less than 150 ksi. Therefore, it is reasonable to conclude that the IWF ASTM A325 bolts are not high strength.
The ASTM A540 bolts used in IWF applications have a specified minimum yield strength of 130 ksi. With only a margin of 20 ksi between the minimum yield specification and the high strength threshold of 150 ksi, it is reasonable to conclude that the subject bolting is high strength. In accordance with NUREG-1 801,Section XI.S3, volumetric examinations of high strength bolting may be waived with adequate plant-specific justification. Based on similar material specifications and environmental conditions, the volumetric examination results of the Davis-Besse reactor head closure studs are used to provide the plant-specific justification. The 60 reactor head closure studs are constructed of ASTM A540 Grade 823 material with an actual measured yield strength of greater than 150 ksi. Volumetric examinations of these studs are performed once per each 10-year inservice inspection (ISI) interval. Davis-Besse has completed three ISI intervals, for a total of 180 reactor head closure stud volumetric examinations to date with no unacceptable indications noted. Therefore, volumetric examination of IWF ASTM A540 bolts is not required based on plant-specific justification.
The Davis-Besse Inservice Inspection (ISI) - IWF Program is revised to include monitoring of ASTM A490 high strength bolting (i.e., actual measured yield strength greater than or equal to 150 ksi or 1,034 MPa) in sizes greater than 1 inch nominal diameter for cracking using volumetric examination. The volumetric examinations will be performed in accordance with the requirements of the ASME Boiler and Pressure Vessel Code,Section V, Article 5, Appendix IV, 2007 Edition through 2008 Addenda.
The representative sample size will be equal to 20 percent (rounded up to the nearest whole number) of the entire IWF population of ASTM A490 high strength bolts in sizes greater than 1 inch nominal diameter, with a maximum sample size of 25 bolts. The selection of the representative sample will consider susceptibility to stress corrosion cracking (e.g., actual measured yield strength) and as low as reasonably achievable (ALARA) radiation dose reduction principles. The frequency of examination will be once each 10-year ISI interval beginning with the fourth interval that started September 21, 2012.
LRA Section A.1.23 "Inservice Inspection (ISI) Program - IWF," Table A-i, "Davis-Besse License Renewal Commitments," and Section B.2.23, "Inservice Inspection (ISI) Program - IWF," are revised to address volumetric examination of high strength bolting.
See the Enclosure to this letter for the revision to the Davis-Besse LRA.
Enclosure Davis-Besse Nuclear Power Station, Unit No. 1 (Davis-Besse)
Letter L-1 3-181 Amendment No. 41 to the Davis-Besse License Renewal Application Page 1 of 6 License Renewal Application Sections Affected Section A. 1.23 Table A-1 Section B.2.23 The Enclosure identifies the change to the License Renewal Application (LRA) by Affected LRA Section, LRA Page No., and Affected Paragraph and Sentence. The count for the affected paragraph, sentence, bullet, etc. starts at the beginning of the affected Section or at the top of the affected page, as appropriate. Below each section the reason for the change is identified, and the sentence affected is printed in italics with deleted text Aped u and added text underlined.
Enclosure L-13-181 Page 2 of 6 Affected LRA Section LRA Page No. Affected Paragraph and Sentence A.1.23 Page A-17 2 New Paragraphs Based on the supplemental response to request for additional information (RAI)
B.2.4-1 b regarding aging management of high strength bolting and related Inservice Inspection (ISI) Program - IWF enhancements, LRA Section A.1.23, "Inservice Inspection (ISI) Program - IWF," is revised to include two new paragraphs, to read as follows:
A.1.23 INSERVICE INSPECTION (ISl) PROGRAM - IWF The Inservice Inspection (ISI) Program - IWF establishes responsibilities and requirements for conducting ASME Code,Section XI, Subsection IWF (IWF) inspections as required by 10 CFR 50.55a. The Inservice Inspection (ISI)
Program - IWF includes visual examination of supports based on sampling of the total support population. The sample size varies depending on the ASME Class.
The largest sample size is specified for the most critical supports (ASME Class 1). The sample size decreases for the less critical supports (ASME Classes 2 and 3). The primary inspection method is visual examination.
Degradation that potentially compromises support function or load capacity is identified for evaluation. Supports determined to be unacceptable for continued service requiring corrective actions are re-examined during the next inspection period in accordance with the requirements of IWF.
The Inservice Inspection (ISI) Program- IWF includes monitoring of ASTM A490 hiOh strength boltinq (i.e., actual measured yield strength greaterthan or equal to 150 ksi or 1,034 MPa) in sizes greaterthan 1 inch nominal diameter for cracking using volumetric examination. The volumetric examinations are performed in accordance with the requirements of the ASME Boiler and Pressure Vessel Code,Section V, Article 5, Appendix IV, 2007 Edition through 2008 Addenda.
The representativesample size is equal to 20 percent (rounded up to the nearest whole number) of the entire IWF population of ASTM A490 high strength bolts in sizes greater than 1 inch nominal diameter, with a maximum sample size of 25 bolts. The selection of the representative sample considers susceptibility to stress corrosion cracking (e.g., actual measured yield strength) and as low as reasonably achievable (ALARA) radiation dose reduction principles. The frequency of examination is once each 10-year ISI interval beginning with the fourth interval that started September 21, 2012.
Enclosure L-1 3-181 Page 3 of 6 There are no other hiqh strength bolts in IWF applications except ASTM A540 bolts. The volumetric examinations for these IWF bolts were waived based on plant-specific operating experience associatedwith the volumetric examination of the Davis-Besse reactor head closure studs constructed of ASTM A540 material.
The 60 reactorhead closure studs are examined once each ISI interval,and after three intervals, no unacceptableindications were noted.
The inservice examinations conducted throughout the service life of Davis-Besse will comply with the requirements of the ASME Code Section Xl edition and addenda incorporated by reference in 10 CFR 50.55a(b) twelve months prior to the start of the inspection interval, subject to prior approval of the edition and addenda by the NRC.
Enclosure L-1 3-181 Page 4 of 6 Affected LRA Section LRA Page No. Affected Paragraph and Sentence Table A-1 Page A-69 New Commitment No. 50 Based on the supplemental response to request for additional information (RAI) B.2.4-1 b regarding aging management of high strength bolting, new license renewal future Commitment 50 in LRA Table A-I, "Davis Besse License Renewal Commitments," is added to address Inservice Inspection (ISI) Program - IWF enhancements, as follows:
Table A-1 Davis-Besse License Renewal Commitments Item Iter Commitment Implementation Sheme Schedule Source TRelated LRA Section No./
Number -Cmet Comments 50 Enhance the Inservice Inspection (ISI) Program- IWF to: Priorto LRA A. 1.23 Include monitoring of ASTM A490 high strength bolting (i.e., October 22, 201 B.2.23 actualmeasured yield strength greaterthan or equal to 150 ksi and and or 1,034 MPa) in sizes greaterthan 1 inch nominal diameter for FENOC Supplemental cracking using volumetric examination. The volumetric Letter Response to examinations will be performed in accordancewith the L-13-181 NRC RAI requirementsof ASME Boiler and Pressure Vessel Code, B. 2.4-lb Section V, Article 5, Appendix IV, 2007 Edition through 2008 from telecons Addenda. The representativesample size will be equal to 20 held with the percent (rounded up to the nearest whole number) of the entire NRC on IWF population of ASTM A490 high strength bolts in sizes April 11, greaterthan 1 inch nominal diameter, with a maximum sample April 24 and size of 25 bolts. The selection of the representativesample will May 2. 2013 consider susceptibility to stress corrosioncracking (e.g., actual measured yield strength)and as low as reasonablyachievable
Enclosure L-13-181 Page 5 of 6 Table A-1 Davis-Besse License Renewal Commitments Item Commitment Ii Implementation m Source Section LRA Related No./
Number Schedule I Comments (ALARA) radiation dose principles. The frequency of examination will be once each 10-year inservice inspection interval beginning with the fourth interval that started September 21, 2012.
Enclosure L-13-181 Page 6 of 6 Affected LRA Section LRA Page No. Affected Paragraph and Sentence B.2.23 Page B-100 Enhancements Based on the supplemental response to request for additional information (RAI)
B.2.4-1 b regarding aging management of high strength bolting, LRA Section B.2.23, "Inservice Inspection (ISI) Program - IWF," subsection titled "Enhancements," is revised to add an enhancement, to read as follows:
Enhancements None.
The followinq enhancement will be implemented in the identified program element prior to the period of extended operation.
, Detection of A-gincg Effects Include monitorinq of ASTM A490 high strength boltinq (i.e., actual measured yield strength greaterthan or equal to 150 ksi or 1,034 MPa) in sizes greater than 1 inch nominal diameter for cracking using volumetric examination. The volumetric examinations will be performed in accordance with the requirements of ASME Boiler and Pressure Vessel Code,Section V, Article 5, Appendix IV, 2007 Edition through 2008 Addenda. The representative sample size will be equal to 20 percent (roundedup to the nearest whole number) of the entire IWF population of ASTM A490 high strength bolts in sizes greater than 1 inch nominal diameter, with a maximum sample size of 25 bolts. The selection of the representative sample will consider susceptibility to stress corrosion cracking (e.g., actual measured yield strength) and as low as reasonably achievable (ALARA) radiation dose principles. The frequency of examination will be once each 10-year inservice inspection interval beginning with the fourth interval that started September 21, 2012.