Forwards Alden Research Lab 800205 Ltr Re Containment Sump Model Jet Impingement Tests,In Response to NRC 820317 Request.Tests Indicate That No Mods Are Required for Containment Recirculation Sumps
ML17334A382
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 04/28/1982
From: HERING R F
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: DENTON H R
Office of Nuclear Reactor Regulation
References
AEP:NRC:0355A, AEP:NRC:355A, NUDOCS 8205040601
Download: ML17334A382 (5)


Text

REGULATURYIRUATIONDISTRI8UTIONSYST(RIDS)ACCESSIONNt>R:8205040b01DOC~DATE:82/04/20NOTARIZED;NQDOCKETFACIL:50315Dona1dC~CookNuc1earPowerPlantiUn)t1iIndianaL0505021550-316DonaldC~Coom.induc1earPowerP1antiUnit2iIndianalt~M90&~AUTH.fAI4'EAUTHURAFFILIAt'ONHERINGiR~FeIndianaltf~ichiganElectricCo~RECIP~NAMERECIPIENTAFFILIATION,DEtiTONHEREOfficeofNuclearReactorRegulationiDirectorSUt3JE.CT:ForwardsAldenresearchLab8002ti5ltrrecontainmentsumpmodelJetimpingementtestsiinresponsetoNRC820317reauest.Testsindicatethatnomodsarereauiredforcontainmentrecirculationsump'ISTRIBUTIONCODE:A001SCOPIESRECEIVED:LTRENCLSTZE:TITLE:GeneralDistributionforafterIssuanceofOperatingLicenseNOTES:RECIPIENTIDCODE/NAh'EORU01BC01COPIESLTTRENCL77RECIPIENTIDCODE/NAtiECOPIESLTTREh'CLINTERhAL:EL'RR/DLDIRNRH/DSI/f7A9RGN310NRR/DHFSDEPY0811NHR/DL/DRAB11Q~D'LE041'1111011EXTERNAL:ACRSt4RCPDRNTIS09101002I111t.PDRNSIC03052211TOTALNUBBEROFCOPIESREQUIRED;LTTR29ENCL27 glINDiANAIIMICHiGANELECTRICCOMPANYP.O.BOX18BOWLINGGREENSTATIONNEWYORK'.Y10004April28,1982AEP:NRC:0355ADonaldC.CookNuclearPlantUnitNos.1and2DocketNos.50-315and50-316LicenseNos.DPR-58andDPR-74CONTAINMENTRECIRCULATIONSUMPTEST.i.'~~',+lIl~Mr.HaroldR.Denton,DirectorOfficeofNuclearReactorRegulationU.S.NuclearRegulatoryCommissionVashington,D.C.205551

DearMr.Denton:

ThisletteranditsattachmentrespondtoMr.StevenVarga'sletterofMarch17,1982andsupplementsourlettertoyouofJanuary28,1980(AEP:NRC:0355)whichrespondedtotherequestforadditionalinformation'enclosedinMr.A.Schwencer'sletterofAugust1,1979.PleasefindattachedacopyoftheAldenResearchLaboratory(ARL)letter,fromMr.'Padmanabhan(ARL)toMr.Marrocco(AEPSC)datedFebruary5,1980.Theletterindicatesthattheresultsofthetestperformedwithwaterinthesumpcorrespondingtoanelevationof607.0feetweresatisfactoryinthattherewasnonoticeablewithdrawalofairbubblesthroughthesuctionpipeinoperation.BasedontheresultsofthetestweconcludethatnomodificationsarerequiredtotheDonaldC.CookPlantcontainmentrecirculationsumps.ThisdocumenthasbeenpreparedfollowingCorporateProcedureswhichincorporateareasonablesetofcontrolstoinsureitsaccuracyandcompletenesspriortosignaturebytheundersigned.Verytrulyyours,R.F.HeringVicePresident/mdcc:(attached)820504060l820428PDRADOCK05000315PPDR Mr.HaroldR.DentonAEPNRC:0355Acc:JohnE.Dolan-ColumbusR.W.JurgensenW.G.Smith,Jr.-BridgmanR.C.CallenG.CharnoffJoeWilliams,Jr.NRCResidentInspectoratCookPlant-Bridgman h=ALDENRESEAICHLABORATORYWORCESTERPOLYTECHNlC!NSTlTUTEATTACHMENTTOAEP:NRC:0355AMr.M.MarroccoMechanicalEngineeringDivisionAmericanElectricPowerServiceCorporation2BroadwayNewYork,NY10004~February5,1980D.C.COOKNUCLEARPOWERSTATIONCONTAINMENTSUMPMODELJETIMPINGEMENTTESTSDCC/JET-ARL-178P

DearMr.Marrocco:

Asperyourrecenttelephonerequest,wehaveconductedadditionaltestssimul'atingthe'condenserdrainflowjetimpingement,withwaterelevationinthesumpcorrespondingtoEl.607'0".ThisconditionpresumablydescribestheswitchoveroffirstECCStraintorecircula-tionmodetakingintoaccountthevolumeofwaterduetoicecondensermeltandassumingabreakinsidethebiologicalboundary(notin'eludedinmodel).Testswereconductedwithandwithoutscreenblockages(upto504)andwithbothdrainflowjetandsuctionpipevelocitiesincreasedto,prototypevelocities.Testsindicatednonoticeablewithdrawalofairbubblesthroughthesuctionpipeinoperation.Eventhoughlargesurfaceair-entrainmentduetodrainflowjetimpingementwasobserved,mostofthebubblesdidnotpenetrate'thewatersurfacedeepenoughtoenterintothesumparea.Thefewbubblesthatenteredthesumpaeawerelargeenoughtoriseupandwerenotdawncownunderthecranewallextensiontothedownstreamportionof:thesumo.Also,nosicnificantvorticeswereobservedduringthetesting.Hence,wefeelthatbasedonthemodeltestresults,th'esumpperformedsatisfactorilyattheaboveflowconditiontested.Ifyouhaveanyquestions,pleasefeelfreetocallme.Sincerely,M.PadmanabhanLeadResearchEngineerFluidMachineryHOLOLN.MASSACHUSFTTSor520~VELEPHOhre6178294323