Notice of Violation from Insp on 970727-0906.Violation Noted:On 970817,licensee Identified That Procedures STP-345.001,STP-345.002 & STP-345.003 Had Not Been Maintained to Ensure Correct Setting of OT Delta T
ML20211K527
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 10/02/1997
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20211K524 List:
References
50-395-97-11, NUDOCS 9710090264
Download: ML20211K527 (2)


Text

.. - . _ - ..

NOTICE OF VIOLATION South Carolina Electric & Gas Company Docket No. 50-395 V. C Summer Nuclear Station License No. NPF-12 During an NRC inspection conducted on July 27 through September 6. 1997.

violations of NRC requirements were identified. In accordance with the

" General Statement of Policy atj Procedures for NRC Enforcement Actions."

NUREG-1600, the violations are listed below:

A. Technical Specification (TS) 6.8.1.a requires that written 3rocedures shall be established, implemented and maintained covering t1e a)plicable procedures recommended in A)pendix A of Regulatory Guide 1.33. Revision

2. February 1978. Paragrap1 8.b.(1) of Appendix A states that the licensee should have instructions for reactor protection system calibrations.

Surveillance Test Procedures (STP). STP-345.001, " Delta T-TAVG Protection Loop 1 Calibration." Revision 8: STP-345.002. " Delta T-TAVG Protection Loop 2 Calibration." Revision 8; and STP-345.003. " Delta T-TAVG Protection Loop 3 Calibration." Revision 9, verify calibration of the three reactor coolant loop delta T-Tavg protection sensors and their associated signal processing equipment. Calibration of these sensors ensures proper setting of Overtemperature delta Temperature (OT delta T) and Overpower delta, Temperature (OP delta T) reactor trip setpoints.

Contrary to the above, on August 17. 1997, the licensee identified that procedures STP-345.001, STP-345.002 and STP-345.003 had not been maintained to ensure correct setting of the OT delta T and OP delta T reactor trip setpoints. The procedures listed an incorrect error tolerance for the OT delta T and OP delta T reactor trip setpoint time constants. This resulted in OT delta T and OP delta T time constants beingsetnonQonservativelyduringprotectionloopcalibrationsin Aprii 1996 and a small reduction in the Departure from Nucleate Boiling design margin.

This is a Severity Level IV violation (Supplement I).

B. 10 CFR Part 50, Appendix B. Criteria V. Instructions. Procedures, and Dre,t ngs, as implemented by the licensee's accepted quality assurance i

program, South Carolina Electric & Gas Company Operational Quality Assurance Han, Section 4 " Procedures." requires that activities affecting qualli.y shall be prescribed by documented instructions, procedures. or drawings of a type approariate to the circumstances and shall be accomplished in accordance wit 1 these instructions, procedures, or drawings.

Contrary to the above, on July 25. 1997 activities affecting quality were not accomplished in accordance with prescribed drawings. A guard pipe surrounding a portion of Reactor Makeup W ter System piping was not installed in accordance with safety-related drawing: E-304-794 and E-304-795. This resulted in the guard pipe not meeting it: design 9710090264 971002 PDR ADOCK 05000395 G PDR

l l NOV 2 l

function of providing spray protection for essential safety-related k electrical components after a postulated pipe break. I i

This is-a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201. South Carolina Eitctric & Gas Company is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission. ATTN: Document Control Desk. Washington, D.C. 20555 with a copy to the Regional Administrator, Region 11. and a copy to j the NRC Resident Inspector at the V. C. Summer Nuclear Station, within 30 days of the date of the letter transmitting this Notice of Violation (Notice).

This reply should be. clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, or, if coni.csted, the basis for disputing the violation. (2) the corrective steps-

} that have been taken and the results achieved. (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Your response may reference or include previously docketed correspondence, if the correspondence adequately addresses the required response. If an adequate reply is not received within the time specified in this Notice,'an order or a Demand for Information may be issued as to why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response time.

Because your res)onse will be placed in the NRC Public Document Room (PDR), to the extent possi ale, it should not include any personal privacy, )roprietary..

or safeguards information so that it can be placed in the PDR witlout redaction. If personal privacy or proprietary information is necessary to provide an-acceptable response, then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your response that deletes such information. If you request withholding of such material. you !!nsi s)ecifically identify the portions of your response that you seek to have withield and provide in detail the bases for your claim of withholding (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR-2.790(b) to support a request for withholding confidential commercial or financial information). If safeguards information is necessary to provide an acceptable response.-please provide the level of.-

protection described in 10 CFR 73.21.

Dated at Atlanta Georgia this 2 day of October 1997 r _