ML022040005
ML022040005 | |
Person / Time | |
---|---|
Site: | Surry |
Issue date: | 07/15/2002 |
From: | Blount R Virginia Electric & Power Co (VEPCO) |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
02-426, SPSLic/JSA R0 | |
Download: ML022040005 (16) | |
Text
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 July 15, 2002 U. S. Nuclear Regulatory Commission Serial No.02-426 Attention: Document Control Desk SPS Lic/JSA RO Washington, D.C. 20555-0001 Docket Nos. 50-280 50-281 License Nos. DPR-32 DPR-37 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 MONTHLY OPERATING REPORT The Monthly Operating Report for Surry Power Station Units 1 and 2 for the month o0 June 2002 is provided in the attachment.
Ifyou have any questions or require additional information, please contac.Lus.
Very truly yours, Richard H. Blount, Site Vice President Surry Power Station Attachment Commitments made by this letter: None cc: United States Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23 T85 Atlanta, Georgia 30303-8931 Mr. R A. Musser NRC Senior Resident Inspector Surry Power Station
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION MONTHLY OPERATING REPORT REPORT No. 02-06 Approved:
e Vicle resident Yate
Surry Monthly Operating Report No. 02-06 Page 2 of 15 TABLE OF CONTENTS Section Page Operating Data Report - Unit No. 1 ............................................................................................................................ 3 Operating Data Report - Unit No. 2 ............................................................................................................................ 4 Unit Shutdowns and Power Reductions - Unit No. 1 ............................................................................................. 5 Unit Shutdowns and Power Reductions - Unit No. 2 .............................................................................................. 6 Average Daily Unit Power Level - Unit No. 1 ....................................................................................................... 7 Average Daily Unit Power Level - Unit No. 2 ...................................................................................................... 8 Summary of Operating Experience - Unit Nos. 1 and 2 ......................................................................................... 9 Facility Changes That Did Not Require NRC Approval ......................................................................................... 10 Procedure or Method of Operation Changes That Did Not Require NRC Approval ............................................ 11 Tests and Experiments That Did Not Require NRC Approval .............................................................................. 12 Chemistry Report ..................................................................................................................................................... 13 Fuel Handling - Unit Nos. 1 and 2 ............................................................................................................................ 14 Description of Periodic Test(s) Which Were Not Completed Within the Time Limits Specified in Technical Specifications ....................................................................................................................... 15
Surry Monthly Operating Report No. 02-06 Page 3 of 15 OPERATING DATA REPORT Docket No.: 50-280 Date: 07/01/02 Completed By: R. Stief Telephone: (757) 365-2486
- 1. Unit Name: ........................................................... Surry Unit 1
- 2. Reporting Period: ................................................. June 2002
- 3. Licensed Thermal Power (MW t): .......................... 2546
- 4. Nameplate Rating (Gross MW e): ......................... 847.5
- 5. Design Electrical Rating (Net MW e): .................... 788
- 6. Maximum Dependable Capacity (Gross MWe): ... 842
- 7. Maximum Dependable Capacity (Net MWe): ....... 810
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:
- 9. Power Level To Which Restricted, If Any (Net MWe):
- 10. Reasons For Restrictions, If Any:
This Month Year-To-Date Cumulative
- 11. Hours in Reporting Period 720.0 4343.0 258791.0
- 12. Hours Reactor Was Critical 720.0 4343.0 190104.6
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 3774.5
- 14. Hours Generator On-Line 720.0 4343.0 187445.2
- 15. Unit Reserve Shutdown Hours 0.0 0.0 3736.2
- 16. Gross Thermal Energy Generated (MWH) 1833120.0 10999962.5 446307440.4
- 17. Gross Electrical Energy Generated (MWH) 620301.0 3691874.0 146771977.0
- 18. Net Electrical Energy Generated (MWH) 588362.0 3548111.0 140140972.0
- 19. Unit Service Factor 100.0% 100.0% 72.4%
- 20. Unit Availability Factor 100.0% 100.0% 73.9%
- 21. Unit Capacity Factor (Using MDC Net) 100.9% 100.9% 69.2%
- 22. Unit Capacity Factor (Using DER Net) 103.7% 103.7% 68.7%
- 23. Unit Forced Outage Rate 0.0% 0.0% 12.5%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Type and duration of scheduled shutdowns are no longer provided.
[
Reference:
Letter S/N 00-069, dated February 7, 2000]
- 25. If Shut Down at End of Report Period, Estimated Date of Start-up: Estimated start-up dates are no longer provided. [
Reference:
Letter S/N 00-069, dated February 7, 2000]
- 26. Unit In Test Status (Prior to Commercial Operation):
FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
Surry Monthly Operating Report No. 02-06 Page 4 of 15 OPERATING DATA REPORT Docket No.: 50-281 Date: 07/01/02 Completed By: R. Stief Telephone: (757) 365-2486
- 1. Unit Name: ........................................................... Surry Unit 2
- 2. Reporting Period: ................................................. June 2002
- 3. Licensed Thermal Power (MW t): .......................... 2546
- 4. Nameplate Rating (Gross MW e): ......................... 847.5
- 5. Design Electrical Rating (Net MW e): .................... 788
- 6. Maximum Dependable Capacity (Gross MWe): ... 847
- 7. Maximum Dependable Capacity (Net MWe): ....... 815
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:
- 9. Power Level To Which Restricted, If Any (Net MWe):
- 10. Reasons For Restrictions, If Any:
This Month Year-To-Date Cumulative
- 11. Hours in Reporting Period 720.0 4343.0 255672.0
- 12. Hours Reactor Was Critical 720.0 3684.8 187502.8
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 328.1
- 14. Hours Generator On-Line 720.0 3646.3 185262.7
- 15. Unit Reserve Shutdown Hours 0.0 0.0 0.0
- 16. Gross Thermal Energy Generated (MWH) 1833058.9 9203747.3 442228651.5
- 17. Gross Electrical Energy Generated (MWH) 611693.0 3087619.0 145464626.0
- 18. Net Electrical Energy Generated (MWH) 589501.0 2979759.0 138936809.0
- 19. Unit Service Factor 100.0% 84.0% 72.5%
- 20. Unit Availability Factor 100.0% 84.0% 72.5%
- 21. Unit Capacity Factor (Using MDC Net) 100.5% 84.2% 69.2%
- 22. Unit Capacity Factor (Using DER Net) 103.9% 87.1% 69.0%
- 23. Unit Forced Outage Rate 0.0% 0.0% 10.0%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Type and duration of scheduled shutdowns are no longer provided.
[
Reference:
Letter S/N 00-069, dated February 7, 20001
- 25. If Shut Down at End of Report Period, Estimated Date of Start-up: Estimated start-up dates are no longer provided. [
Reference:
Letter S/N 00-069, dated February 7, 2000]
- 26. Unit In Test Status (Prior to Commercial Operation):
FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
Surry Monthly Operating Report No. 02-06 Page 5 of 15 UNIT SHUTDOWN AND POWER REDUCTION (EQUAL To OR GREATER THAN 20%)
REPORT MONTH: June 2002 Docket No.: 50-280 Unit Name: Surry Unit 1 Date: 07/01/02 Completed by: R. Stief Telephone: (757) 365-2486 None during the Reporting Period (1) (2) (3)
F: Forced REASON: METHOD:
S: Scheduled A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Scram C - Refueling 3 - Automatic Scram D - Regulatory Restriction 4 - Other (Explain)
E - Operator Training & Licensing Examination F - Administrative G - Operational Error (Explain)
H Other (Explain)
(4) (5)
Exhibit G - Instructions for Preparation of Data Entry Sheets Exhibit 1 - Same Source for Licensee Event Report (LER) File (NUREG 0161)
Surry Monthly Operating Report No. 02-06 Page 6 of 15 UNIT SHUTDOWN AND POWER REDUCTION (EQUAL To OR GREATER THAN 20%)
REPORT MONTH: June 2002 Docket No.: 50-281 Unit Name: Surry Unit 2 Date: 07/01/02 Completed by: R. Stief Telephone: (757) 365-2486 None during the Reporting Period (1) (2) (3)
F: Forced REASON: METHOD:
SR Scheduled A - Equipment Failure (Explain) 1 Manual B - Maintenance or Test 2 - Manual Scram C - Refueling 3 - Automatic Scram D - Regulatory Restriction 4 - Other (Explain)
E - Operator Training & Licensing Examination F - Administrative G - Operational Error (Explain)
H Other (Explain)
(4) (5)
Exhibit G - Instructions for Preparation of Data Entry Sheets Exhibit 1 - Same Source for Licensee Event Report (LER) File (NUREG 0161)
Surry Monthly Operating Report No. 02-06 Page 7 of 15 AVERAGE DAILY UNIT POWER LEVEL Docket No.: 50-280 Unit Name: Surry Unit 1 Date: 07/03/02 Completed by: R. Stief Telephone: (757) 365-2486 MONTH: June 2002 Average Daily Power Level Average Daily Power Level Day (MWe - Net) Day (MWe - Net) 1 818 17 818 2 818 18 816 3 819 19 816 4 819 20 817 5 818 21 818 6 817 22 817 7 820 23 816 8 821 24 815 9 820 25 814 10 819 26 813 11 818 27 813 12 818 28 814 13 818 29 815 14 818 30 815 15 819 16 819 INSTRUCTIONS On this format, list the average daily unit power level in MWe - Net for each day in the reporting month. Compute to the nearest whole megawatt.
Surry Monthly Operating Report No. 02-06 Page 8 of 15 AVERAGE DAILY UNIT POWER LEVEL Docket No.: 50-281 Unit Name: Surry Unit 2 Date: 07/03/02 Completed by: R. Stief Telephone: (757) 365-2486 MONTH: June 2002 Average Daily Power Level Average Daily Power Level Day (MWe - Net) Day (MWe - Net) 1 821 17 818 2 822 18 819 3 821 19 819 4 821 20 819 5 821 21 819 6 820 22 817 7 820 23 817 8 822 24 816 9 821 25 816 10 820 26 816 11 820 27 817 12 819 28 817 13 818 29 816 14 819 30 816 15 818 16 819 INSTRUCTIONS On this format, list the average daily unit power level in MWe - Net for each day in the reporting month. Compute to the nearest whole megawatt.
Surry Monthly Operating Report No. 02-06 Page 9 of 15
SUMMARY
OF OPERATING EXPERIENCE MONTH/YEAR; June 2002 The following chronological sequence by unit is a summary of operating experiences for this month that required load reductions or resulted in significant non-load related incidents.
UNIT ONE:
06/01/02 0000 Unit started the month at 100% / 848 MWe.
06/30/02 2400 Unit finished the month at 100% / 846 MWe.
UNIT Two:
06/01/02 0000 Unit started the month at 100% / 851 MWe.
06/30/02 2400 Unit finished the month at 100% / 848 MWe.
Surry Monthly Operating Report No. 02-06 Page 10 of 15 FACILITY CHANGES THAT DID NOT REQUIRE NRC APPROVAL MONTH/YEAR: June 2002 None during the Reporting Period
Surry Monthly Operating Report No. 02-06 Page 11 of 15 PROCEDURE OR METHOD OF OPERATION CHANGES THAT DID NOT REQUIRE NRC APPROVAL MONTH/YEAR: June 2002 None during the Reporting Period
Surry Monthly Operating Report No. 02-06 Page 12 of 15 TESTS AND EXPERIMENTS THAT DID NOT REQUIRE NRC APPROVAL MONTHNEAR: June 2002 None during the Reporting Period
Surry Monthly Operating Report No. 02-06 Page 13 of 15 CHEMISTRY REPORT MONTHIYEAR: June 2002 Unit No. 1 Unit No. 2 Primary Cooiant Analysis Max. Min. Avg. Max. Min. Avg.
Gross Radioactivity, liCi/ml 3.41 E-1 2.38E-1 2.91E-1 3.29E-1 2.21 E-1 2.65E-1 Suspended Solids, ppm 0.01 0.01 0.01 0.01 0.01 0.01 Gross Tritium, ýtCi/ml 1.23E+0 1.14E+0 1.19E+0 7.54E-1 5.07E-1 6.25E-1 1131, gCtI/ml 2.08E-4 1.06E-4 1.51 E-4 1.27E-4 7.23E-5 1.02E-4 1131/1133 0.13 0.06 0.08 0.17 0.08 0.12 Hydrogen, cc/k_ __ -35.6 34.3 35 39.1 36.2 37 Lithium, p~m 2.33 2.08 2.22 2.61 2.33 2.46 Boron-iC, pp-
- 206 190 198 276 264 272 Oxygen, (DO), ppm < 0.005 _ 0.005 *0.005 < 0.005 < 0.005 *0.005 Chloride, porn 0.006 0.004 0.005 0.008 0.003 0.003 pH @ 25 degree Celsius I 6.67 6.56 6.61 6.46 6.31 6.4 Boron - 1C = Total Boron x 0196 Comments:
None
Surry Monthly Operating Report No. 02-06 Page 14 of 15 FUEL HANDLING UNITS 1 & 2 MONTHIYEAR: June 2002 New Fuel Number of New or Spent Shipment or Date Stored or Assemblies Assembly ANSI Initial Fuel Shipping Cask No. Received Der Shipment Number Number Enrichment Cask Activity None duing the Reporting Period
Surry Monthly Operating Report No. 02-06 Page 15 of 15 DESCRIPTION OF PERIODIC TEST(S) WHICH WERE NOT COMPLETED WITHIN THE TIME LIMITS SPECIFIED IN TECHNICAL SPECIFICATIONS MONTH/YEAR: June 2002 None during the Reporting Period