SUBJECT:

SURRY POWER STATION - BIENNIAL PROBLEM IDENTIFICATION AND RESOLUTION INSPECTION REPORT 05000280/2024010 AND 05000281/2024010

Dear Eric S. Carr:

On August 29, 2024, the U.S. Nuclear Regulatory Commission (NRC) completed a problem identification and resolution inspection at your Surry Power Station and discussed the results of this inspection with David Wilson, Site Vice President, and other members of your staff. The results of this inspection are documented in the enclosed report.

The NRC inspection team reviewed the stations problem identification and resolution program to confirm that the station was complying with NRC regulations and licensee standards. Based on the samples reviewed, the team determined that your program complies with NRC regulations and applicable industry standards such that the Reactor Oversight Process can continue to be implemented.

The team also evaluated the stations effectiveness in identifying, prioritizing, evaluating, and correcting problems, reviewed licensee audits and self-assessments, and its use of industry and NRC operating experience information. The results of these evaluations are in the enclosure.

Finally, the team reviewed the stations programs to establish and maintain a safety-conscious work environment and interviewed station personnel to evaluate the effectiveness of these programs. Based on the teams observations and the results of these interviews, the team found no evidence of challenges to your organizations safety-conscious work environment. Your employees appeared willing to raise nuclear safety concerns through at least one of the several means available.

October 2, 2024 No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Matthew S. Fannon, Chief Reactor Projects Branch 4 Division of Reactor Projects Docket Nos. 05000280 and 05000281 License Nos. DPR-32 and DPR-37

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000280 and 05000281

License Numbers:

DPR-32 and DPR-37

Report Numbers:

05000280/2024010 and 05000281/2024010

Enterprise Identifier:

I-2024-010-0039

Licensee:

Virginia Electric and Power Company

Facility:

Surry Power Station

Location:

Surry, VA

Inspection Dates:

August 12, 2024 to August 29, 2024

Inspectors:

M. Donithan, Senior Operations Engineer

D. Jung, Resident Inspector

G. Khouri, Construction Project Manager

J. Seat, Senior Project Engineer

Approved By:

Matthew S. Fannon, Chief

Reactor Projects Branch 4

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees

performance by conducting a biennial problem identification and resolution inspection at Surry

Power Station, in accordance with the Reactor Oversight Process. The Reactor Oversight

Process is the NRCs program for overseeing the safe operation of commercial nuclear power

reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in

effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with

their attached revision histories are located on the public website at http://www.nrc.gov/reading-

rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared

complete when the IP requirements most appropriate to the inspection activity were met

consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection

Program - Operations Phase. The inspectors reviewed selected procedures and records,

observed activities, and interviewed personnel to assess licensee performance and compliance

with Commission rules and regulations, license conditions, site procedures, and standards.

OTHER ACTIVITIES - BASELINE

71152B - Problem Identification and Resolution

Biennial Team Inspection (IP Section 03.04) (1 Sample)

(1)

The inspectors performed a biennial assessment of the effectiveness of the licensees

Problem Identification and Resolution program, use of operating experience, self-

assessments and audits, and safety conscious work environment.

Problem Identification and Resolution Effectiveness: The inspectors assessed

the effectiveness of the licensees Problem Identification and Resolution

program in identifying, prioritizing, evaluating, and correcting problems. The

inspectors also conducted a five-year review of the alternate alternating

current power, emergency diesel generator, and safety injection systems. The

corrective actions for the following non-cited violations (NCVs) were evaluated

as part of the assessment: 2022003-01, 2022003-02, 2022004-01, 2022004-

02, 2022004-03, 2023001-01, 2023001-02, 2023002-01, 2023002-02,

2023004-01, 2023004-02, 2024001-01, and 2024002-01.

Operating Experience: The inspectors assessed the effectiveness of the

licensees processes for use of operating experience.

Self-Assessments and Audits: The inspectors assessed the effectiveness of

the licensees identification and correction of problems identified through

audits and self-assessments.

Safety Conscious Work Environment: The inspectors assessed the

effectiveness of the stations programs to establish and maintain a safety-

conscious work environment.

INSPECTION RESULTS

Assessment

71152B

PI&R Assessment

1. Corrective Action Program Effectiveness

Problem Identification: The inspectors determined that the licensee was effective in

identifying problems and entering them into the corrective action program and there was a

low threshold for entering issues into the corrective action program. This conclusion was

based on a review of the requirements for initiating condition reports as described in licensee

procedure PI-AA-200, "Corrective Action," and managements expectation that employees

were encouraged to initiate condition reports. Additionally, site management was actively

involved in the corrective action program and focused appropriate attention on significant

plant issues.

Problem Prioritization and Evaluation: Based on the review of condition reports, the

inspectors concluded that problems were prioritized and evaluated in accordance with the

condition report significance determination guidance in procedure PI-AA-200. The inspectors

determined that adequate consideration was given to system or component operability and

associated plant risk. The inspectors determined that plant personnel had conducted cause

evaluations in compliance with the licensees corrective action program procedures and

cause determinations were appropriate, and considered the significance of the issues being

evaluated.

Corrective Actions: Based on a review of corrective action documents, interviews with

licensee staff, and verification of completed corrective actions, the inspectors determined that

corrective actions were timely, commensurate with the safety significance of the issues, and

effective, in that conditions adverse to quality were corrected. For significant conditions

adverse to quality, the corrective actions directly addressed the cause and effectively

prevented recurrence. The inspectors reviewed condition reports and effectiveness reviews to

verify that the significant conditions adverse to quality had not recurred. Effectiveness reviews

for corrective actions to preclude repetition were sufficient to ensure corrective actions were

properly implemented and were effective.

Based on the samples reviewed, the team determined that the licensees corrective action

program complied with regulatory requirements and self-imposed standards. The licensees

implementation of the corrective action program adequately supported nuclear safety.

2. Operating Experience

The inspectors determined that the station's processes for the use of industry and NRC

operating experience information were effective and complied with all regulatory requirements

and licensee standards. The implementation of these programs adequately supported nuclear

safety. The inspectors concluded that operating experience was adequately evaluated for

applicability and that appropriate actions were implemented to address lessons learned as

needed.

3. Self-Assessments and Audits

The inspectors determined that the licensee was effective at performing self-assessments

and audits to identify issues at a low level, properly evaluated those issues, and resolved

them commensurate with their safety significance. Self-assessments were generally detailed

and critical. The inspectors verified that condition reports were created to document areas for

improvement and findings resulting from self-assessments, as well as verified that

actions had been completed consistent with those recommendations. Audits of the quality

assurance program appropriately assessed performance and identified areas for

improvement. Generally, the licensee performed evaluations that were technically accurate.

4. Safety Conscious Work Environment

Based on interviews with plant staff and reviews of the latest safety culture survey results to

assess the safety conscious work environment on site, the inspectors found no evidence of

challenges to the safety conscious work environment. Employees appeared willing to raise

nuclear safety concerns through at least one of the several means available.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On August 29, 2024, the inspectors presented the biennial problem identification and

resolution inspection results to David Wilson, Site Vice President, and other members of

the licensee staff.