VIRGINIA ELECTRIC AND PO'WEZR COMPANY RIChMOND, VIRGINIA 23261 February 14, 2005 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001 Serial No.
SPS Lic/JSA Docket Nos.05-055 RO 50-280 50-281 DPR-32 DPR-37 License Nos.
Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 MONTHLY OPERATING REPORT The Monthly Operating Report for Surry Power Station Units 1 January 2005 is provided in the attachment.
and 2 for the month of In October 2004, an issue was discovered with Surry Units 1 & 2 station service integrators that resulted in each unit's Net Generation being overstated by approximately 11 megawatts/hour since 1993. The metering issue has been corrected and the cumulative Net Generation data and Maximum Dependable Capacity for both units have been revised to reflect the correct data in this report.
If you hqyp any questions or require additional information, please contact us.
Vew/<
- yours, Donald E. Jernigan, Site Vice President Surry Power Station Attachment Commitments made by this letter: None
" -, ---, , H 11L
Serial No. 05-055: SPS Monthly Operating Report Page 2 of 2 cc:
United States Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23 T85 Atlanta, Georgia 30303-8931 Mr. N. P. Garrett NRC Senior Resident Inspector Surry Power Station
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION MONTHLY OPERATING REPORT REPORT No. 05-01 f -, 4 / , -Z -, " s-,
Approved:
Surry Monthly Operating Report No. 05-01 Page 2 of 15 TABLE OF CONTENTS Section Page Operating Data Report - Unit No. 1..........................................................
3 Operating Data Report - Unit No. 2..........................................................
4 Unit Shutdowns and Power Reductions - Unit No. 1.......................................................... 5 Unit Shutdowns and Power Reductions - Unit No. 2.......................................................... 6 Average Daily Unit Power Level - Unit No. 1...........................................................
7 Average Daily Unit Power Level - Unit No. 2..........................................................
8 Summary of Operating Experience - Unit Nos. 1 and 2...........................................................
9 Facility Changes That Did Not Require NRC Approval..........................................................
10 Procedure or Method of Operation Changes That Did Not Require NRC Approval............................................... 11 Tests and Experiments That Did Not Require NRC Approval..........................................................
12 Chemistry Report..........................................................
13 Fuel Handling - Unit Nos. 1 and 2..........................................................
14 Description of Periodic Test(s) Which Were Not Completed Within the Time Limits Specified in Technical Specifications..........................................................
15
Surry Monthly Operating Report No. 05-01 Page3 of 15 OPERATING DATA REPORT Docket No.:
Date:
Completed By:
Telephone:
50-280 02/01/05 R. Stief (757) 365-2486 1.
2.
3.
4.
5.
6.
7.
Unit Name:.........................................................
Reporting Period:................................................
Licensed Thermal Power (MWt):..........................
Nameplate Rating (Gross MWe):.........................
Design Electrical Rating (Net MWe):....................
Maximum Dependable Capacity (Gross MWe):....
Maximum Dependable Capacity (Net MWe):........
Surry Unit 1 January 2005 2546 847.5 788 840 799
- 8.
If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:
- 9.
Power Level To Which Restricted, If Any (Net MWe):
- 10.
Reasons For Restrictions, If Any:
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
Hours in Reporting Period Hours Reactor Was Critical Reactor Reserve Shutdown Hours Hours Generator On-Line Unit Reserve Shutdown Hours Gross Thermal Energy Generated (MWH)
Gross Electrical Energy Generated (MWH)
Net Electrical Energy Generated (MWH)
Unit Service Factor Unit Availability Factor Unit Capacity Factor (Using MDC Net)
Unit Capacity Factor (Using DER Net)
Unit Forced Outage Rate This Month 744.00 744.00 0.00 744.00 0.00 1893411.30 633797.00 603862.00 100.00%
100.00%
101.58%
103.00%
0.00%
Year-To-Date 744.00 744.00 0.00 744.00 0.00 1893411.30 633797.00 603862.00 100.00%
100.00%
101.58%
103.00%
0.00%
Cumulative 281496.00 210145.40 3774.50 207293.21 3736.20 496378089.10 163479072.00 155291261.00 73.64%
74.97%
70.34%
70.01%
11.61%
- 24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Type and duration of scheduled shutdowns are no longer provided.
[
Reference:
Letter S/N 00-069. dated February 7. 20001
- 25.
If Shut Down at End of Report Period, Estimated Date of Start-up:
Estimated start-up dates are no longer provided. [
Reference:
Letter SIN 00-069, dated February 7, 2000]
- 26.
Unit In Test Status (Prior to Commercial Operation):
FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
Surry Monthly Operating Report No. 05-01 Page 4 of 15 OPERATING DATA REPORT Docket No.:
Date:
Completed By:
Telephone:
50-281 02/01/05 R. Stief (757) 365-2486 1.
2.
3.
4.
5.
6.
7.
Unit Name:.........................................................
Reporting Period:................................................
Licensed Thermal Power (MWI):..........................
Nameplate Rating (Gross MWe):.........................
Design Electrical Rating (Net MWe):....................
Maximum Dependable Capacity (Gross MWe):....
Maximum Dependable Capacity (Net MWe):........
Surry Unit 2 January 2005 2546 847.5 788 840 799
- 8.
If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:
- 9.
Power Level To Which Restricted, If Any (Net MWe):
- 10.
Reasons For Restrictions, If Any:
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
Hours in Reporting Period Hours Reactor Was Critical Reactor Reserve Shutdown Hours Hours Generator On-Line Unit Reserve Shutdown Hours Gross Thermal Energy Generated (MWH)
Gross Electrical Energy Generated (MWH)
Net Electrical Energy Generated (MWH)
Unit Service Factor Unit Availability Factor Unit Capacity Factor (Using MDC Net)
Unit Capacity Factor (Using DER Net)
Unit Forced Outage Rate This Month 744.00 744.00 0.00 744.00 0.00 1893613.00 637408.00 606593.00 100.00%
100.00%
102.04%
103.47%
0.00%
Year-To-Date 744.00 744.00 0.00 744.00 0.00 1893613.00 637408.00 606593.00 100.00%
100.00%
102.04%
103.47%
0.00%
Cumulative 278377.00 208335.82 328.10 205797.17 0.00 494396004.80 162930253.00 154783038.00 73.93%
73.93%
70.57%
70.56%
9.23%
- 24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
April 2005 Type and duration of scheduled shutdowns are no longer provided.
[
Reference:
Letter S/N 00-069, dated February 7, 2000]
- 25.
If Shut Down at End of Report Period, Estimated Date of Start-up:
Estimated start-up dates are no longer provided. [
Reference:
Letter S/N 00-069, dated February 7,2000]
- 26.
Unit In Test Status (Prior to Commercial Operation):
FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
Surry Monthly Operating Report No. 05-01 Page 5 of 15 UNIT SHUTDOWN AND POWER REDUCTION (EQuAL To OR GREATER THAN 20%)
REPORT MONTH: January 2005 Docket No.:
Unit Name:
Date:
Completed by:
Telephone:
50-280 Surry Unit 1 02/02/05 R. Stief (757) 365-2486 None during the Reporting Period (1)
F:
Forced S: Scheduled (2)
REASON:
A -
Equipment Failure (Explain)
B -
Maintenance or Test C -
Refueling D -
Regulatory Restriction E -
Operator Training & Ucensing Examination F -
Administrative G -
Operational Error (Explain)
H Other (Explain)
(3)
METHOD:
1 -
Manual 2 -
Manual Scram 3 -
Automatic Scram 4 -
Other (Explain)
(4)
Exhibit G - Instructions for Preparation of Data Entry Sheets for Ucensee Event Report (LER) File (NUREG 0161)
(5)
Exhibit 1 - Same Source
Surry Monthly Operating Report No. 05-01 Page 6 of 15 UNIT SHUTDOWN AND POWER REDUCTION (EaUAL To OR GREATER THAN 20%)
REPORT MONTH: January 2005 Docket No.: 50-281 Unit Name:
Surry Unit 2 Date:
02/02105 Completed by: R. Stief Telephone:
(757) 365-2486 None during the Reporting Period (1)
F:
Forced S: Scheduled (2)
REASON:
A -
Equipment Failure (Explain)
B -
Maintenance or Test C -
Refueling D -
Regulatory Restriction E -
Operator Training & Ucensing Examination F -
Administrative G -
Operational Error (Explain)
H Other (Explain)
(3)
METHOD:
1 -
Manual 2 -
Manual Scram 3 -
Automatic Scram 4 -
Other (Explain)
(4)
Exhibit G - Instructions for Preparation of Data Entry Sheets for Licensee Event Report (LER) File (NUREG 0161)
(5)
Exhibit 1 - Same Source
Surry Monthly Operating Report No. 05-01 Page 7 of 15 AVERAGE DAILY UNIT POWER LEVEL Docket No.: 50-280 Unit Name:
Surry Unit 1 Date: 02/02/05 Completed by: R. Stief Telephone:
(757) 365-2486 MONTH:
January 2005 Day 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 Average Daily Power Level (MWe - Net) 813 813 813 813 813 813 813 812 812 811 811 810 810 811 813 812 Day 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Average Daily Power Level (MWe - Net) 812 811 811 810 811 812 812 811 811 811 811 811 811 811 811 INSTRUCTIONS On this format, list the average daily unit power level in MWe - Net for each day In the reporting month. Compute to the nearest whole megawatt.
Surry Monthly Operating Report No. 05-01 Page 8 of 15 AVERAGE DAILY UNIT POWER LEVEL Docket No.: 50-281 Unit Name:
Surry Unit 2 Date: 02/02/05 Completed by: R. Stief Telephone:
(757) 365-2486 MONTH:
January 2005 Day 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 Average Daily Power Level (MWe-Net) 816 815 815 815 815 815 816 816 816 816 816 816 816 816 816 816 Day 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Average Daily Power Level (MWe-Net) 815 815 815 815 815 815 815 815 815 815 815 815 815 816 815 INSTRUCTIONS On this format, list the average daily unit power level In MWe - Net for each day in the reporting month. Compute to the nearest whole megawatt.
Surry Monthly Operating Report No. 05-01 Page 9 of 15
SUMMARY
OF OPERATING EXPERIENCE MONTHNEAR: January 2005 The following chronological sequence by unit is a summary of operating experiences for this month that required load reductions or resulted in significant non-load related Incidents.
UNrT ONE:
01/01/05 01/31/05 UNrr Two:
01/01/05 01/31/05 0000 2400 0000 2400 Unit started the month at 100% /852 MWe.
Unit finished the month at 100% / 853 MWe.
Unit started the month at 1 00% / 857 MWe.
Unit finished the month at 100% / 856 MWe.
Surry Monthly Operating Report No. 05-01 Page 10 of 15 FACILITY CHANGES THAT DID NOT REQUIRE NRC APPROVAL MONTHIYEAR: January 2005 None during the Reporting Period.
r Surry Monthly Operating Report No. 05-01 Page 11 of 15 PROCEDURE OR METHOD OF OPERATION CHANGES THAT DID NOT REQUIRE NRC APPROVAL MONTHYEAR: January 2005 None during the Reporting Period.
Surry Monthly Operating Report No. 05-01 Page 12 of 15 TESTS AND EXPERIMENTS THAT DID NOT REQUIRE NRC APPROVAL MoNTHIYER: January 2005 None during the Reporting Period
Surry Monthly Operating Report No. 05-01 Page 13 of 15 CHEMISTRY REPORT MoNTWhYEAR: January 2005 Unit No. 1 l
Unit No. 2 Primary Coolant Analysis Max.
Min.
Avg.
Max.
Min.
Avg.
Gross Radioactivity, gCVml 4.65E-1 2.55E-1 3.75E-1 2.90E-1 1.51 E-1 2.21 E-1 Suspended Solids, ppm l
Gross Tritium, ltCiml 7.30E-1 3.23E-1 5.73E-1 1.03E+0 7.37E-1 9.62E-1 1131, PCVml 2.21 E-4 1.05E-5 1.06E-4 1.08E-4 2.89E5 6.28E-5 1131/1133 0.12 0.04 0.07 0.26 0.15 0.20 Hydrogen, ccfkg 42.8 38.4 40.4 44.5 40.6 42.2 Lithium, ppm 3.68 3.38 3.51 2.27 2.12 2.19 Boron-10, ppm' 270 261 267 91 71 81 Oxygen, (DO), ppm
- 0.005
- 0.005
- 0.005
- 0.005
- 0.005
- 0.005 Chloride, pprn 0.016 0.005 0.011 0.007 0.002 0.003 pH @ 25 degree Celsius 6.67 6.43 6.53 7.19 6.98 7.09 Boron - 10 = Total Boron x 0.196 Comments:
Unit 1: Unit at 100% power. Quarterly Suspended Solids not required.
Unit 2: Unit at 100% power. Quarterly Suspended Solids not required.
Surry Monthly Operating Report No. 05-01 Page 14 of 15 FUEL HANDLING UNITS 1 & 2 MoTrH/YEAR: January 2005 New Fuel Shipment or Cask No.
Date Stored or Received Number of Assemblies per Shipment New or Spent Assembly ANSI Initial Fuel Shipping Number Number Enrichment Cask Activity None during the Reporting Period
Surry Monthly Operating Report No. 05-01 Page 15 of 15 DESCRIPTION OF PERIODIC TEST(S) WHICH WERE NOT COMPLETED WITHIN THE TIME LIMITS SPECIFIED IN TECHNICAL SPECIFICATIONS MoNrHTYEAR: January 2005 None during the Reporting Period