Text

-- ._. . .. . . _ - - - - - - _ _ _ _ .

Appendix NOTICE OF VIOLATION Union Electric Company Docket No. 50-483 As a result of the inspection conducted during the period of February 23-24 to March 14-17, 1983, and in accordance with the NRC Enforcement Policy, 47 FR 9987 (March 9, 1982), the following violation was identified:

10 CFR 50, Appendix B, Criterion XI requires that testing be performed in accordance with written test procedures which incorporate the requirements and acceptance limits contained in applicable design documents.

The Westinghouse document " Standardized Nuclear Unit Power Plant Systems:

Precautions, Limitations and Setpoints for Nuclear Steam Supply Systems" delineates the temperature limits for pressurization of the safety injection accumulators.

Contrary to the above, preoperational test procedure CS-03EP01, Revision 0,

" Accumulator Testing," was approved and the test was conducted with no require-ments to verify or record safety injection accumulator temperature prior to and during pressurization.

This is a Severity Level V violation (Supplement II).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice a written statement or explanation in reply, including for each item of noncompliance: (1) cor-rective action taken and the results achieved; (2) corrective action to be taken to avoid further noncompliance; and (3) the date when full compliance

, will be achieved. Consideration may be given to extending your response time for good cause shown.

" Original Sign:d by n. L. Spenard"

, Dated R. L. Spessard, Director Division of Engineering i

8305020354 830418 PDR ADOCK 05000483 G PDR

--. - - - - - - . ..- ------.- -- --. . . - - - - , . . - . - . -. - --