IR 07100026/2012006

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 971026-1206.Violation Noted:Licensee Personnel Failed to Follow Documented Instructions During Preventive Maint Task to Record Differential Pressure Across Essential Svc Water Supply
ML20203H159
Person / Time
Site: 07100026, Callaway 
Issue date: 12/16/1997
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20203H148 List:
References
50-483-97-20, NUDOCS 9712180327
Download: ML20203H159 (2)


Text

.

.,

e ENCLOSURE 1 NOTICE OF VIOLATION Union Electric Company Docket No.:

50-483 Callaway Plant License No.:

NPF-30 Curing an NRC inspection conducted on October 26 through December 6,1997, one violation of NRC requirements was identified. In accordance witn the " General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violation is listed below:

Technical Specification 6.8.1.a requires, in part, that written procedures shall be established, implemented, and maintained covering the applicable procedures recommended in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978.

Regulatory Guide 1.33, Revision 2, Appendix A, Section 9.a., requires, in part, that maintenance which can affect the performance of safety-related equipment be properly performed in accordance with documented instructions.

Contrary to the above, on October 29, i997, licenseo pe:sonnel failed to follow documented instructions during a preventive maintenance task to record differential pressure across the essential service water supply and return lines to the Fmergency Diesel Generator A engine.

Specifically, a temporary differential pressure gauge was left installed for approximately 14.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> after completion of the preventive maintenance task.

This is a Severity Level IV violation (Supplement 1) (50-48^/9720-01).

Pursuant to the provisions of 10 CFR 2.201, Union Electric Company is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administsator, Region IV,611 Ryan Plaza Dnve, Suite 400, Arlington, Texas 76011, and a copy to the NRC Resident inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly

'

marked as a " Reply to a Notice of Molation" and should include for each violation: (1) the reason for the violation, or, if contested, the basis for disputing the vio!ation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Your response may reference or include previaus docke'ed correspondence, if the correspondence adequately addresses the required response. If an adequate reply is not received within the time specified in this Notice, an order or a Demand for Information may be issued as to why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response time.

Because your response will be placed in the NRC Public Document Room, to the extent possible, it should not include any personal p:Nacy, proprietary, or safeguards information so that it can be placed in the Public C7cument F com without redaction. However, if you find it 9712180327 971216

-

PDR ADOCK 05000483 G

PDR

,

_.

_. - _ -._

_._ _ _.. _ - _. _ _ _..___

.. _ _. _ _ _.. _ _..... _ _ _.......

-. _ _

_

-

....

..

,

L2

..-

- necessary to include such information, you should clearly indicate the specific information that -

you desire not to be placed in the Public Document Room, and provide the legal basic to support

_

- your request for withholding the information from the public.

-

Dated at Arlington, Texas

- this 16 day of December,1997

.

i

-

.

1

%

~

-

,,

- -,

.,, -, -