Notice of Violation from Insp on 970624.Violation Noted: Until 970227,TS Intrepretation 18 & Procedure OTN-NE-0002 Permitted Manual,Vice Automatic,Operation of Supply Fans, Placed in pull-to-lock, Condition Inconsistent W/Fsar
ML20212B711
Person / Time
Site: Callaway 
Issue date: 10/22/1997
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20212B693 List:
References
50-483-97-05-01, 50-483-97-5-1, EA-97-168, NUDOCS 9710280178
Download: ML20212B711 (5)


Text

.

- - ~

t J.

NOTICE OF VIOLATION Union Electric Co.

Docket No. 50-483.-

LCallawdy Plant -

License No. NPF 30

' EA 97168 -

-During an NRC inspection completed June 24,;1997/victations of NRC requirements were.

identified. In act.ordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG 1600, the violations are listed below:

10 CFR 50.59(a)(1) states, in part, that a licensee may make changes in the facility as described m the safety analysis report and changes in procedures as described in the safety analysis without prior Commission approval unless the proposed change involves a change in the technical specifications incorporated in the license or an unreviewed safety -

question.

-10 CFR 50.59(b)(1) states, in part, that the licensee shall maintain records.of changes in -

the facility _ and of changes in procedures made pursuant to this section to the extent that

-these. changes constitute changes in the facility as described in the safety analysis report or changes in procedures as described in the safety analysis report. These records must

-include a written safety evaluation which provides the bases for tl.a determination that the change does not involve an unreviewed safety question.

A.

The Final Safety Analysis Report (FSAR) for the Callaway Plant states in Section 9.4.7.2.3 that the diesel generator building supply f ans automatically start when the room temperature exceeds 90aF and automatically shut down when room temperature falls below 86'F.

Contrary to the above, until February 27,1997, Technical Specification Interpretation (TSI) No.-18 and Procedure OTN-NE-0002 (and superceded Procedures OTN-NE-0001 A and OTN-NE-0001B) permitted manual, vice automatic, operation of the supply fans by placing them in " pull-to-lock," a condition inconsistent with the description in the FSAR, and the licensee did not have a record of a written safety evaluation which provided the bases for the determination that this change to the f acility and procedures as described in the FSAR did not involve an unreviewed safety question. Specifically, TSI No.18 and the procedure -

permitted placing a supply far;in pull-to lock "... provided it is still under the total control of the Reactor Operator" and stated that this was based on administrative controls that allow the operator to maintain the room temperature below the FSAR-

--described limit of 119'F. (01014)

This is a Severity Level IV violation iSupplenient I).

L S.

The FSAR for the Callaway Plant states in Section 16.9.2.1a that the refueling l

machine trip set points' for the load overload trips (wet conditions) and load reduction trips (wet 7r dry conditions) be set at 250 pounds above and below the t suspended 'oads, respectively.

l-Contrary to the above, as of October 20,' 1995, TSI No. 25 permitted the trip cet' points to be based on the heaviest fuel assembly for the overload trip and the 9710290178 971022 PDR ADOCK 05000403 l

0 PM l

.x-

N V i

i lightest fuel assembiy for the load reduction trip, as opposed to the " suspended loads" as descobed in the FSAR, and the licensee did not have a record of a written safety evaluation which provided the bases for the determination that this change to the facility as described in the FSAR did not involve an unreviewed safety question.

TSI No. 25 allowed these trips to be set in excess of 250 pounds by approximately 150 pounds, (01024)

This is a Severity LevelIV violation (Supplement I),

C.

Final Safety Analysis Report, Section 18,2,3, specifies that details regarding the design of the post accident sampling system (PASS) were described in a letter to the NRC, dated February 4,1983. This letter describes the post-accident sampling system as a computer controlled automated system.

Contrary to the above, on November 1,1995, the licensee changed the PASS (RMP 94 2005A) by changing the computer controlled operation of the sample panel equipment to a manually controlled operation, a change that was inconsistent with the description in the FSAR, and the licensee did not have a record of a written safety evaluation which provided the bases for the determination that this change to the f acility as described in the FSAR did not involve an unreviewed safety question.

(01034)

This is a Severity Level IV violation (Supplement I),

Pursuant to the provisions of 10 CFR 2.201, Union Electric is hereby required to submit a wntten statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region IV,611 Ryan Plaza Drive, Suite 400, Arlington, Texas 76011, and a copy to the NRC Resident inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a " Reply to a Notice of Violation" and should include fcr each violation: (1) the reason for the violations, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Your response may reference or include previous docketed correspondence, if the correspondence adequately addresses the required response, if an adequate reply is not received within the time specified in this Notice, an order or a Demand for Information may be issued as to why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to

- extending the response time.

Because your response will be placed in the NRC Public Document Room (PDR), to the

. extent possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be placed in the PDR without redaction. If personal privacy or proprietary information is necessary to provide an acceptable response, then ple.ase provide a bracketed copy of your response that identifies the information that should be protected

[

l l

l

3-and a redacted copy of your response that' deletes such information. 'If you request withholding of such material, you must specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of withholding (e.g.,

explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2.790(b) to support a request for with-holding confidential commercial or financial information). If safeguards information is -

necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

Dated at Arlington, Texas this 22th day of Octobar i997