ML20199F216

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 860512-29
ML20199F216
Person / Time
Site: Callaway 
Issue date: 06/17/1986
From: Shafer W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20199F208 List:
References
50-483-86-14, NUDOCS 8606240228
Download: ML20199F216 (1)


Text

NOTICE OF VIOLATION Union Electric Company Docket No. 50-483 As a result of the inspection conducted during the period May 12-29, 1986, and in accordance with the " General Policy and Procedures for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1985), the following violation was identified:

Technical Specification 3.3.3.10 and Table 3.3-13 require that with less than one channel of the Radwaste Building Vent System iodine and particulate sampler operable, auxiliary sampling equipment must be utilized to continuously collect l

the samples specified in Table 4.11-2 or the effluent release must be terminated.

Contrary to the above, the Radwaste Building Vent System iodine and particulate sampler was inoperable on April 16, 1986, between about 0545 and 1545, but auxiliary sampling equipment was not utilized, and the particulate and charcoal (iodine) samples specified in Table 4.11-2 were not collected, nor was the effluent releases terminated.

l This is a Severity Level IV violation (Supplement I).

The inspection showed that action had been taken to correct the identified violation and to prevent recurrence.

Consequently, no reply to the violation is required and we have no further questions regarding this matter.

h Tdo h)D%Yeo Dated W.'D. Shafer Chief l

Emergency Pr aredness and l

Radiation rotection Branch 1

0606240228 860617 1

PDR ADOCK 05000483 O

PDR

-