NOTICE OF VIOLATION

Union Electric Company

Docket No. 50-483

As a result of the inspection conducted on March 10 through June 24, 1985,

and in accordance with the General Policy and Procedures for NRC Enforcement

Actions (10 CFR Part 2, Appendix C), the following violation was identified:

Technical Specification 3.7.10.3 states, in part, "The following Halon Systems

shall be operable (the systems specified includes the following:)

Building

Elevation

Area Protected

Auxiliary

2026

Load center and M.G. SETS

Room *(1403)

  • Areas containing redundant systems or components which could be damaged."

Action: "a." states, in part, "With one or more of the above required Halon

Systems inoperable, within one hour establish a continuous fire watch with

backup fire suppression equipment for those areas in which redundant systems

or components could be damaged."

Contrary to the above, a continuous fire watch was not established when Door

No. 14031 for Room 1403 was open from February 8 to February 10, 1985, which

rendered the Halon system for the room inoperable.

This is a Severity Level IV violation (Supplement 1).

The inspection showed that licensee action had been taken to correct the

violation and to prevent recurrence. Consequently, no reply to this violation

is required and we have no further questions regarding this item.

.

rJUL 2 41985'

7N[d/'

b

Dated

/N. J. Chrisd6tilnos, Chief