Person / Time
Site: Maine Yankee
Issue date: 11/14/1985
From: Whittier G
Maine Yankee
To: Butcher E
Office of Nuclear Reactor Regulation
References
6622L-SDE, GDN-85-285, GDW-85-285, MN-85-194, NUDOCS 8511250224
Download: ML20136H898 (1)


Text

EDISON DRIVE MAIRE HARHEE ATOMICPOWERCOMPARUe ruausra. uninE o<sas (20D 623G21 (kf November 14, 1985 g MN-85-194 GDW-85-285 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission Washington, D. C. 20555 Attention: Mr. Edward J. Butcher, Jr.

Acting Branch Chief Operating Reactors Branch No. 3 Division of Licensing

References:

(a) License No. DPR-36 (Docket No. 50-309)

(b) USNRC Letter to MYAPCo dated August 24, 1984 (c) MYAPCo Letter to UStRC dated January 8,1985 (MN-85-04)

(d) MYAPCo Letter to USNRC dated March 5, 1985 (MN-85-50)

Subject:

Containment Leak Testing Program Gentlemen:

This letter constitutes our completed response to the issues raised in the f Staff's Safety Evaluation of Maine Yankee's Type C leak testing program and i containment liner weld test channel integrity, Reference (b).

In Reference (c), we responded to all areas of concern raised in Reference (b) with the exception of Type C testing of steam generator blowdown valves.

After a detailed re-evaluation of these valves during the recently completed 1985 refueling outage, Maine Yankee agrees with the Staff's position.

1. By July 1,1986 Maine Yankee's Containment Leak Teeting Program will be revised to require local (Type C) leak rate testing of the steam generator blowdown valves for containment penetrations 47A, 478 and 47C in accordance with 10 CFR 50 Appendix J, III.C. The valves will be tested by the end of the next refueling outage.

We trust this information is satisfactory, however, if you have any questions, please do not hesitate to contact us.

Very truly yours, MAINE YANKEE ATOMIC POWER C0bf)ANY hgjl2g24851114 p

J[%

0500h G. D. Whittier, Manager Nuclear Engineering & Licensing GOW/bjp , plh a

cc: Dr. Thomas E. Murley I g

Mr. Cornelius F. Holden 6622L-SDE