Other: 05000266/LER-1983-010-03, /03L-0:on 830929,acceptance Test of Fire Detection Sys Found Remote Alarm Function Disabled for Fire Detectors in Auxiliary Feedwater Pump,Vital Switchgear & Cable Spreading Rooms.Caused by Wiring Work, ML19208A635, ML19256F995, ML19262C226, ML19290E879, ML19294C012, ML19309A782, ML19309F407, ML19317H481, ML19318C032, ML19340B145, ML19350C020, ML20002B141, ML20002E093, ML20069Q173, ML20081E499, ML20100R666, ML20112E612, ML20210K148, ML20212F358
|
MONTHYEARML19207B4261979-08-0202 August 1979 Forwards Request for Addl Info on Steam Generator Water Hammer to Be Sent to Westinghouse & C-E Licensees,For Plants Not Equipped W/Top Discharge Devices on Steam Generator Feedwater Sys & for Which No Mods Are Planned Project stage: Request ML19208A6351979-08-17017 August 1979 Urges Firm Maint of Schedule for Implementation of All Mods Associated W/General Design Criterion 3 Re Fire Protection. Requests That Any Outstanding Info Re Open Items & Required Design Details Be Submitted on Expedited Basis Project stage: Other ML19209A6611979-10-0101 October 1979 Proposes Changes to Tech Specs of Licenses DPR-24 & DPR-27 Re Fire Brigade Size,In Reponse to NRC 790821 Request.Change Modifies Tech Spec Change Request 46 Project stage: Request ML19290E8791979-11-30030 November 1979 Forwards Recommendations for Fire Protection Design Review Items 3.1.2 & 3.1.23 Re Carbon Dioxide Hose Reel Nozzles & Smoke Exhaust Project stage: Other ML19256G3931979-12-17017 December 1979 Discusses Evaluation of Incomplete Items Identified in 790802 Fire Protection Safety Evaluation.Licensee Submitted Info Re Brigade Shift Size on 791001 & Basis for Staff Assignments on 790821.Proposed Fire Brigade Acceptable Project stage: Approval ML19256F9951979-12-20020 December 1979 Forwards Rept, Fire Detector Location Plan, Mod to Fire Protection Plan.Requests Comment Project stage: Other IR 05000301/19790201979-12-20020 December 1979 IE Insp Rept 50-301/79-20 on 791127-30.No Noncompliance Noted.Major Areas Inspected:Core Power Distribution Limits, Core Thermal Power Evaluation,Power Coefficient of Reactivity Measurement & Rod Drop Time Test Project stage: Request ML19262C2261980-02-0101 February 1980 Forwards Fire Protection Review of Safety Evaluation Items 3.1.12 & 3.2.5.Util Verification of Fire Detector Location Adequate.Util Personnel Qualified to Locate Detectors Project stage: Other ML19294C0121980-02-0505 February 1980 Forwards Info Re Open Fire Protection Issues Review.Encl 1 Summarizes Status of Open Issues.Encl 2 Is NRC Evaluation of Design Description for Proposed Detector Installations.Util 791220 Proposal for Detector Placement Is Acceptable Project stage: Other ML19322E4301980-03-0505 March 1980 Forwards Open Items & Resolution of Incomplete Items for 790802 Fire Protection Program Re Safety Evaluation Rept. Requests Response within 30 Days Project stage: Approval ML19309A7821980-03-26026 March 1980 Forwards Fire Protection Review Items 3.1.17,3.1.25,3.2.2 & 3.2.6.Licensee Proposed Mods to Hydrogen Sys & Reactor Coolant Pump Oil Collection Sys Are Only Partly Acceptable. NRC Should Request Drawings Re Mods Proposed in Item 3.2.2 Project stage: Other ML19309F4071980-04-21021 April 1980 Responds to Re Status of NRC Review of Plant Fire Protection Program.List Re Status of Resolution of Incomplete Items Encl Project stage: Other ML19317H4811980-05-19019 May 1980 Forwards Proposed Rule Entitled, Fire Protection Program for Nuclear Power Plants Operating Prior to 790101. Rule Adds New Section 50.48 & App R to 10CFR50 & Is Expected to Be Published in Fr by End of May Project stage: Other ML19318C0321980-06-23023 June 1980 Forwards Addl Info Re Design of Fixed Water Suppression Sys, Fire Hydrant Insps & Control Room Light Fixtures for Fire Protection Safety Evaluation.Notification Requested by 800718,if Design Mods Are Required Project stage: Other ML19340B1451980-10-13013 October 1980 Forwards Status of Fire Protection Mods Per Amends 39 & 44 to Licenses DPR-24 & DPR-27.Justifications for Schedule Delays Encl Project stage: Other ML20002B1411980-11-18018 November 1980 Forwards Interim 10CFR50.48,suspending Completion Date for Previously Approved Effective Fire Protection Mods,Effective 801029.Rule Will Be Superseded by Pending Revision Project stage: Other ML20002E0931981-01-20020 January 1981 Requests That Completion Date for Fire Protection Mods Be Extended to 811117 to Provide Time Required for Installation of Remote Diesel Generator Panels W/Modified Carbon Dioxide Extinguishing Sys Nozzles & Light Fixture Diffusers Project stage: Other ML19351F8411981-01-22022 January 1981 Forwards Fire Protection Safety Evaluation Suppl,For Proposed Mods Re Revised 10CFR50.48 & New App R.Item 3.1.29 Acceptable.Item 3.1.15 Not Acceptable & Remains Open Item Project stage: Approval ML19351F8441981-01-22022 January 1981 Fire Protection Safety Evaluation Suppl Re Cable Tray Penetration Seal Qualification.Item 3.1.29 Acceptable.Item 3.1.15 Remains Open Project stage: Approval ML19350C0161981-02-13013 February 1981 Approves 810120 Request for Extension of Date to Install Emergency Diesel Generator Remote Panels for Fire Protection Sys.Fire Detector Installation Dates Meet Requirements of 801021 Fire Protection Safety Evaluation.Fr Notice Encl Project stage: Approval ML19350C0201981-02-13013 February 1981 Notice of Extension Until 811117 for Installation of Emergency Diesel Generator Remote Panels for Fire Protection Sys Project stage: Other ML20069Q1731982-12-0303 December 1982 Forwards Review of Util Fire Modeling & Analyses Used to Justify Exemption Requests from 10CFR50,App R Requirements Project stage: Other ML20069M4971983-04-28028 April 1983 Requests Revs to Proposed Mods to 10CFR50 App R Exemption Requests Re Separation Requirements,Per 830322 Meeting & 830325 & 31 Telcons.Detailed Discussion of Revs Encl Project stage: Meeting ML20077D0581983-07-20020 July 1983 Itemizes Clarification of Encl to Re Request for App R Fire Protection Exemptions,Including Revised Description of Proposed Plant Mods to Fire Zones 1-4 Project stage: Request ML20077J3941983-08-0909 August 1983 Suggests Periodic Progress Meetings Re Detailed Description of Alternate Shutdown Capability for Fire Areas & Zones. App R Exemption Requests to Be Submitted by 831027.First Progress Meeting Proposed for 830826 Project stage: Meeting ML20081E4991983-10-26026 October 1983 Forwards Final Rept,Response to 10CFR50 App R `Alternate Shutdown Capability, Supporting Requests for App R Exemptions.Rept Includes Responses to Generic Ltr 81-12 & Evaluation of Component Spurious Operation Project stage: Other 05000266/LER-1983-010-03, /03L-0:on 830929,acceptance Test of Fire Detection Sys Found Remote Alarm Function Disabled for Fire Detectors in Auxiliary Feedwater Pump,Vital Switchgear & Cable Spreading Rooms.Caused by Wiring Work1983-10-28028 October 1983 /03L-0:on 830929,acceptance Test of Fire Detection Sys Found Remote Alarm Function Disabled for Fire Detectors in Auxiliary Feedwater Pump,Vital Switchgear & Cable Spreading Rooms.Caused by Wiring Work Project stage: Other NRC Generic Letter 1984-051984-04-0202 April 1984 NRC Generic Letter 1984-005: Change to NUREG-1201 Operator Licensing Examiner Standards Project stage: Request ML20088A2931984-04-0404 April 1984 Responds to 840326 Request for Clarification of 831026 Submittal Describing Alternate Shutdown Capability (10CFR50,App R).Fire Repairs Not Proposed for Sys Required for Hot Shutdown Project stage: Request ML20084G3171984-04-27027 April 1984 Responds,W/Addl Clarification,To 840423 Request for Addl Info on 10CFR50,App R Re Alternate Shutdown Capability. Proposed Double Break Circuit Mod Will Prevent Spurious Operation of Excess Letdown Isolation Valves Project stage: Request ML20100R6661984-11-27027 November 1984 Forwards Notice of Environ Assessment & Finding of No Significant Impact Re 830517 Application,Supplemented by ,For Exemptions from 10CFR50 App R Requirements Project stage: Other ML20101Q5051985-01-0303 January 1985 Requests Final Resolution of 820630 Request for Exemption from Requirements of App R Through Approval of Proposed Mods.Requests Meeting W/Nrc to Discuss Schedule for Completion of Proposed Mods So Mutual Objectives Can Be Met Project stage: Meeting ML20112E6121985-01-0909 January 1985 Corrects Re Routing of Normal & Alternate Control Power to Safeguards Buses 1-A05 & 1-A06.Errors Discovered in Cable Schedule Used to Perform Evaluation When Compared W/Electrical Elementary Diagrams Project stage: Other ML20129J0531985-07-0303 July 1985 Exemption from 10CFR50,App R,Subsection Iii.G Re Requirements for Fire Protection of Safe Shutdown Capability Project stage: Approval ML20129J0711985-07-0303 July 1985 Notice of Granting of Exemption from 10CFR50,App R, Subsection Iii.G Re Fire Protection Requirements Project stage: Approval IR 05000301/20040301985-08-21021 August 1985 Notice of Violation from Insp on 850301-0430 Project stage: Request ML20134K6751985-08-21021 August 1985 Safety Evaluation Denying Util 820630 Request for Exemption from 10CFR50,App R Re Requirements of Separation of Redundant Trains of Safe Shutdown Capability Equipment in Switchgear Room Project stage: Approval ML20138J1951985-12-11011 December 1985 Forwards Response to Telecopied Request for Info Re 830428 & 1026 App R Exemption Requests Concerning Svc Water Pump Room,Rhr Pump Zones & Auxiliary Bldg Fire Area & Summarizes 851126 Meeting W/Nrc at Facility Project stage: Meeting ML20210K1481986-04-11011 April 1986 Evaluation of Fire Protection Exemption Requests from 10CFR50.48 & App R to 10CFR50,Point Beach Units 1 & 2, Technical Evaluation Rept Project stage: Other ML20215G3211986-10-10010 October 1986 Forwards Addl Info for 860509 Request for Exemption from Certain Requirements of 10CFR50,App R Re Fire Suppression Sys & 3 H Fire Barrier Requirement,Per 860918 Request Project stage: Request ML20212A8251986-12-19019 December 1986 Environ Assessment & Finding of No Significant Impact Re Issuance of Exemption from Technical Requirements of 10CFR50,App.R Project stage: Approval ML20212F3581986-12-31031 December 1986 Exemption to 10CFR50,App R,Section Iii.G Fire Protection Requirements,Per Licensee 830428 Request,As Supplemented by 831026,851211,860509 & 1010 Ltrs & Encl Franklin Research Ctr Technical Evaluation Rept Project stage: Other ML20212F3791986-12-31031 December 1986 Safety Evaluation Supporting Exemption to 10CFR50,App R, Section Iii.G Re Svc Water Pump Room Fire Zone,Rhr Pump Fire Zone & Auxiliary Bldg Fire Area Project stage: Approval 1982-12-03
[Table View] |
Text
[
x Q
Wisconsin Elecinc eom coww 231 W. MICHIGAN, P.O. BOX 2046, MILWAUKEE, WI $3201 October 1, 1979 Mr. liarold R. Denton, Dimetor Office of fluclear Reactor Regulation O. S. IlUCLEAR REGULATORY C0tf tISS10ii t
licshington, D. C.
20555 Attention: Mr. A. Schwencer, Chief Operating Reactors Branch 1 Gentlemen:
DOCKET liOS. 50-266 Arid 50-301 MODIFICATI0ii 0F TEQttilCAL SPECIflL&floa CNMGE REQUEST ti0. 46 POIHT ulAOI fluCLLAR PLMIT, UNITS 1 ANO 2 Your letter dated August 21, 1979, and received August 28, 1979, requested that we increase the minimum size of the fire brigade contained in the Technical Specifications for Point Beach Nuclear Plant Unit Hos.1 and 2 to five neobers within 30 days of our receipt of the letter.
In accordance with this request, Wisconsin Electric Power Company hereby proposes the enclosed change to the Point Beach Technical Specifications. This change represents a modification to facility Operating License llos. DPR-24 and DPR-27 amendment application dated i
July 28,1977, as subsequently modified by our letters dated October 5,1977 and Decerber 12, 1977. of your August 21 letter at Page 3. Item 1, states the NRC opinion that designation of the Shift Supervisor as the fire brigade leader is unacceptable.
tio do not agroo with this opinion.
The Shift Supervisor is respon-sible for the overall operation and safety of the plant.
It is his responsibility to investigate all plant emergencies, nake decisions, and direct operating and recovery actions.
Regulatory Guide 1.120 Section C.l.d.(1) states that fires need not be postulated to be concurrent with non-fire related failures in safety systet.s, Other plant accidents or the most severe natural phenomena, tle see no reason why the Shift Supervisor would be required to leave the scene of the emergency.
,, Table 1, lists the following required actions for the l
fire brigade leader.
1.
Evaluate the fire (cuergency) situation.
2.
Determine the effective actions to be taken.
110 088 3.
liaintain conraunication with the control room.
7910050 % p I
m
M
/
,c Itr. liarold R. Denton, Director October 1,1979 4.
Direct fire fighting activities.
5.
Judge effectiveness and safety.
6.
Consider alternative actions, such as need for offsite assistance.
7.
Consider irpact on plant safe shutdown capability, such as equipment which may be disabled.
The above decisions directly affect plant operation and safety.
Such decisions and actions are the responsibility of the Shift Supervisor, who is the shift person most knowledgeable and qualified to make these decisions and inplermint proper actions.
Delegation of this responsibility to other personnel would compromise the authority and responsibility of the Shift Supervisor and would increase the potential for erroneous decisions and/or actions.
For these reasons, we consider the Shift Supervisor to be the proper designec as fire brigade leader and will continua to have hin so designated.
You should further note that the Point Beach iluclear Plant organization structure, which has an operating supervisor (normally SRD licensed) assigned in charge in the control room in the absence of the Shift Supervisor from the control room, provides a sound organization for allowing the Shift Supervisor to be the fire brigade leader.
We have enclosed herewith three signed originals of this Technical Specification change request. We will forward under separate cover forty copies of this application.
lie trust this change is compatible with your request and will be approved on a timely basis.
Very truly yours, n D-
,f Sol Burstein Exe utive Vice President Subscribed and sworn to before tu This 1st day of October,1979.
c h ?1 h W
-chwa Hotary PubMc, State of Wisconsin Itr Connission expires %3. 4/f 30.
1 o
1i10 089
~
e 15.6.2.2.f A Fire Brigade of at least 5 members shall be maintained onsite at all times. This excludes 3 rnorrbers of the minimum shift crew necessary for safe shutdown of the plant and any personnel required for other essential functions during a fire emergency.
1110 090 15.6.2-2 l
!