Letter Sequence Request |
|---|
|
Initiation
- Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request
- Acceptance
- Supplement, Supplement, Supplement
Results
Other: ML11349A005, ML12104A191, ML12139A058, ML12178A475, ML12180A023, ML13029A016, ML14035A575, ML14045A284, ML14052A230, ML14083A617, ML14084A319, ML14112A355, ML14125A199, ML14169A441, ML14169A604, ML14169A637, ML14223A602, ML14281A365, ML14302A238, ML14302A298, ML14302A302, ML14310A836, ML14328A006, ULNRC-05847, Calloway Plant, Unit 1 - License Renewal Application Online Lr Library, ULNRC-05886, Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses, ULNRC-05928, Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates, ULNRC-05950, Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates, ULNRC-05957, Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses, ULNRC-05979, Enclosure 2 to ULNRC-05979, Amendment 23, LRA Changes from RAI Responses and Commitment Updates Enclosure 2 Summary Table, ULNRC-06120, Update to License Renewal Application Environmental Permits, ULNRC-06122, Update to License Renewal Application Environmental Permits
|
MONTHYEARML11349A0052011-12-15015 December 2011 Biweekly Report - Applications and Amendments to Facility Operating Licenses Involving No Significant Hazards Considerations: Fr Publication Date December 27, 2011 Project stage: Other ULNRC-05847, Calloway Plant, Unit 1 - License Renewal Application Online Lr Library2012-03-28028 March 2012 Calloway Plant, Unit 1 - License Renewal Application Online Lr Library Project stage: Other ML12104A1912012-04-17017 April 2012 License Renewal Application Online Reference Portal (TAC No. ME7708) Callaway Portal Project stage: Other ML12139A0582012-05-31031 May 2012 Project Manager Change for the License Renewal Project (Safety) for Callaway Plant, Unit 1 Project stage: Other ML12144A0352012-06-11011 June 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML12157A0582012-06-22022 June 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application (TAC ME7708) 6 4 2012 Fmp Neutron Embrittlement and Rv Surveillance RAIs on Yee Chris Sydnor Project stage: RAI ML1218501682012-07-0202 July 2012 ULNRC-05877: Responses to RAI Set 1 and Amendment 4 to the Callaway LRA Project stage: Request ML12164A9052012-07-0505 July 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1, LRA Project stage: RAI ML12172A1112012-07-0909 July 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 4, Project stage: RAI ML12179A4002012-07-18018 July 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML12178A4752012-08-0606 August 2012 Scoping and Screening Methodology Audit Report Regarding the Callaway Plant, Unit 1, License Renewal Application Project stage: Other ML12206A2642012-08-0606 August 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 6 Project stage: RAI ML12220A1602012-08-0606 August 2012 Responses to RAI Set 3 and Amendment 5 to the Callaway License Renewal Application (LRA) Project stage: Response to RAI ULNRC-05886, Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses2012-08-0606 August 2012 Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses Project stage: Other ML12180A0232012-08-0909 August 2012 Aging Management Programs Audit Report Regarding the Callaway Plant Unit 1 License Renewal Application Project stage: Other ML12216A3382012-08-16016 August 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 7 Project stage: RAI ML12235A4672012-08-21021 August 2012 Responses to RAI Set 5 and Amendment 7 to the Callaway LRA (with Updates to Previous RAI Responses) Project stage: Request ML12233A6132012-08-23023 August 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 8, Electrical Project stage: RAI ML12233A5702012-09-0606 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 9 Project stage: RAI ML12284A4542012-09-12012 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 10, Public Version Project stage: RAI ML12240A1742012-09-18018 September 2012 Review of the 2011 Refueling Outage Steam Generator Tube Inservice Inspection Reports Project stage: Approval ML12250A7702012-09-20020 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 11 Project stage: RAI ML12256A8952012-09-25025 September 2012 RAI for the Review of the Callaway Plant, Unit 1, LRA, Set 12 Project stage: RAI ML12255A2872012-10-0101 October 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1, License Renewal Application, Set 13 Project stage: RAI ML12270A1472012-10-0303 October 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 14 Project stage: RAI ML12276A3732012-10-12012 October 2012 RAI for the Review of the Callaway Plant Unit 1, LRA Set 15 Project stage: RAI ML12299A2482012-10-24024 October 2012 Responses to RAI Set 11 & 12 and Amendment 13 to the Callaway LRA Project stage: Response to RAI ML12306A3312012-10-31031 October 2012 Responses to RAI Set 13 & 14 and Amendment 14 to the Callaway LRA, ULNRC-05923 (Cover Letter) Project stage: Request ULNRC-05928, Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates2012-11-0808 November 2012 Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates Project stage: Other ML12314A1412012-11-0808 November 2012 Responses to RAI Set 15 and Amendment 15 to the Callaway LRA Project stage: Response to RAI ULNRC-05929, Responses to RAI Set 16 and Amendment 16 to the LRA2012-11-20020 November 2012 Responses to RAI Set 16 and Amendment 16 to the LRA Project stage: Response to RAI ML12321A1992012-11-29029 November 2012 9/27/12 - Summary of Telephone Conference Call Held Between the NRC and Union Electric Company (Ameren Missouri), Concerning RAIs Pertaining to the Callaway Plant, Unit 1, License Renewal Application Project stage: RAI ML12326A9152012-12-0707 December 2012 RAI for the Review of the Callaway Plant Unit 1, LRA, Set 18 Project stage: RAI ML12348A1362012-12-13013 December 2012 Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers Project stage: Request ML12356A0932012-12-19019 December 2012 Annual Update to the Callaway License Renewal Application Response to RAI Set 18 Project stage: Response to RAI ML12342A1722012-12-27027 December 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML13009A2112013-01-14014 January 2013 Request for Additional Information for the Review of the Callaway Plant 1 License Renewal Application Project stage: RAI ML13025A2282013-01-24024 January 2013 Annual Reporting Form for Drug and Alcohol Tests, for Period Ending 2012 Project stage: Request ULNRC-05950, Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates2013-01-24024 January 2013 Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates Project stage: Other ML13029A2432013-01-24024 January 2013 Responses to RAI Set 19 & Set 20 and Amendment 20 to the Callaway LRA Project stage: Response to RAI ML13025A0312013-01-30030 January 2013 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 21 Project stage: RAI ML13029A6592013-02-12012 February 2013 Summary of Telephone Conference Call Held on December 6, 2012, Between the NRC and Union Electric Company, Concerning Request for Additional Information Pertaining to the Callaway Plant Unit 1, LRA Project stage: RAI ML13029A0162013-02-12012 February 2013 Summary of Telephone Conference Call Held on January 22, 2013, Between the U.S. Nuclear Regulatory Commission Project stage: Other ULNRC-05957, Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses2013-02-14014 February 2013 Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses Project stage: Other ML13046A3072013-02-14014 February 2013 Enclosure 1 to ULNRC-05957, License Renewal Application, Request for Additional Information (RAI) Set 21 Responses Project stage: Request ML13046A3062013-02-14014 February 2013 Response to RAI Set 21 and Amendment 21 to the Callaway LRA Project stage: Response to RAI ML13038A3082013-02-21021 February 2013 RAI for the Review of the Callaway Plant Unit 1, LRA, Set 22 Project stage: RAI ML13063A4762013-02-28028 February 2013 Response to RAI Set 22 and Amendment 22 to the Callaway LRA Project stage: Response to RAI ML13042A0422013-03-26026 March 2013 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 23 Project stage: RAI ML13058A1242013-03-29029 March 2013 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 24 Project stage: RAI 2012-07-05
[Table View] |
Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers| ML12348A136 |
| Person / Time |
|---|
| Site: |
Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Quad Cities, Fort Calhoun, FitzPatrick, McGuire, LaSalle, Crane |
|---|
| Issue date: |
12/13/2012 |
|---|
| From: |
Porter D GE-Hitachi Nuclear Energy Americas |
|---|
| To: |
Office of Nuclear Reactor Regulation, Document Control Desk |
|---|
| References |
|---|
| MFN 12-128 R0 |
| Download: ML12348A136 (10) |
|
Similar Documents at Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Quad Cities, Fort Calhoun, FitzPatrick, McGuire, LaSalle, Crane |
|---|
Category:Letter
[Table view]The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Mcguire]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Quad Cities]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:Crane]] </code>. Category:Deficiency Report (per 10CFR50.55e and Part 21)
[Table view]The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Mcguire]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Quad Cities]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:Crane]] </code>. |
Text
GE Hitachi Nuclear Energy December 13, 2012 MFN 12-128 R0 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001
Subject:
Part 21 60-Day Interim Report Notification:
Adequacy of Design Change in AM Magne-Blast Circuit Breakers This letter provides information concerning an evaluation being performed by GE Hitachi Nuclear Energy (GEH) regarding the adequacy of a Design Change in AM 4.16-350-2C and AM 4.16-350-2H Magne-Blast Circuit Breakers. As stated herein, GEH has not concluded that there is a reportable condition in accordance with the requirements of 10CFR 21.21(d).
Testing and continued evaluation is required to determine whether this condition is a reportable condition and what impact and extent of this condition may exist.
The information required for a 60-Day Interim Report Notification per §21.21(a)(2) is provided in Attachment 3. The commitment for follow-on actions is provided in Attachment 3, item (vii).
If you have any questions, please call me at (910) 819-4491.
Sincerely, Dale E. Porter Safety Evaluation Program Manager GE-Hitachi Nuclear Energy Americas LLC Attachments:
- 1. Description of Evaluation
- 2. US Plants Potentially Affected
- 3. 60-Day Interim Report Notification Information per §21.21(a)(2)
Dale E. Porter GE-Hitachi Nuclear Energy Americas LLC Safety Evaluation Program Manager 3901 Castle Hayne Rd.
Wilmington, NC 28401 USA T 910 819-4491 Dale.Porter@GE.Com
MFN 12-128 R0 Page 2 of 2 cc:
S. S. Philpott, USNRC S. J. Pannier, USNRC O. Tabatabai-Yazdi, USNRC D. C. Crawford, GEH J. F. Harrison, GEH J. G. Head, GEH G. A. Watford, GEH P. L. Campbell, GEH Washington PRC File DRF Section No. 0000-0155-6212
MFN 12-128 R0 Attachment 1 - Description of Evaluation Page 1 of 3 Summary GE Hitachi Nuclear Energy (GEH) is investigating the adequacy of a Design Change in AM 4.16-350-2C and AM 4.16-350-2H Magne-Blast Circuit Breakers as a result of a breaker failure at a BWR Licensee.
GEH has not completed the evaluation of this condition to determine reportability under 10 CFR Part 21 and is therefore issuing this 60-day Interim Notification. GEH will close or issue an update on this matter on or before June 14, 2013. Given the early status of the evaluation, GEH has no recommended actions at this time. This 60-day Interim Notification is issued in accordance with 10CFR Part 21.21(a)(2), and will be sent to all GE BWR/2-6 plants and all PWRs.
Discussion On October 30, 2012 GEH determined that a part of a Safety Related Breaker (Model AM 4.16-350-2H/2C 1200A, 2000A, 3000A) may be installed in such a manner that could cause the breaker to fail.
A customer reported a breaker failure which involved the booster piston impacting the bottom of the booster cylinder. GEH performed a causal evaluation for the licensee and the root cause was indeterminate. It was noted that there were multiple contributing maintenance factors associated with the breaker failure. The report concluded that no single issue could have caused the impact and subsequent failure.
GEH developed the design of this model breaker in the late 1960s and were sold to Licensees as Safety Related, prior to the development of IEEE-323. However, that did not relinquish GEH from developing test reports according to existing industry standards. One industry standard established at that time was ANSI C37.06, which required successful demonstration of 10,000 cycles under no load. This standard is used today as part of the IEEE-323 Qualification.
GEH constructed, tested and supplied a specialized breaker for a licensee in 1971 to improve response time. Heavier springs were installed on a base model AM 4.16-350-2H.
Modification testing revealed that the heavier springs provided extra momentum to the mechanism, causing the puffer piston and booster cylinder bottom to contact. Two additional design changes were performed to eliminate the contact. First, the opening and closing spring rates were decreased. Second, another design change lowered the booster cylinder in relation to the booster piston, providing additional impact margin (gap). Follow-up testing revealed no impact; however, the contribution of either design change is unknown. The heavier springs were utilized for the special breaker and the product line
MFN 12-128 R0 Attachment 1 - Description of Evaluation Page 2 of 3 returned to the standard springs for subsequent breaker manufacture. The modification to lower the booster cylinder was incorporated into the base product design on October 6, 1971 (with standard springs) and has carried forth until the present. This modification increased the clearance between the piston end stroke and booster cylinder bottom.
GEH has attempted to locate documentation of the No Load Cycle Test required per ANSI C37.06 for both the pre-modification and post modification designs relating to the booster cylinder change. GEH has documentation that demonstrates the post modification models successfully passed the ANSI C37.06/C37.09 testing in 1977, as part of the IEEE-323 Qualification. GEH has been unable to locate ANSI C37.06 No Load Cycle Testing for the design prior to the 1971 modification (with standard springs). Additionally, GEH is not aware of any further design changes which would invalidate the Qualification of the breakers prior to the IEEE-323 Qualification in 1977.
The GEH position, regarding the pre-1971 modified breakers, is that the breakers will perform all safety related functions involving the booster cylinder and piston. This is based on:
The GEH Service center has performed maintenance on this style breaker for over 40 years. There have been no documented piston impacts on the booster cylinder bottom, except for the single licensee failure noted above.
GEH has also performed an EPIX search for all functional failures regarding this product line. The only instance where this occurred was the above mentioned licensee failure.
GEH has taken a conservative approach to this issue and has committed to testing an AM 4.16-350 breaker per ANSI C37.06, for purposes of validating the pre-modification design.
GEH advises Licensees to take no action at this point. However, if licensees wish to determine the extent, they may identify breaker models AM 4.16-350-2H/2C with a date of manufacture prior to October 6, 1971. Other AM breaker styles do not use the booster cylinder as designed in breaker model AM 4.16-350-2H/2C.
Extent of Condition GEH has documentation that the licensee who reported the failure, was shipped additional breakers that fall within the date of manufacture prior to October 6, 1971. GEH is unable at this time to identify other licensees who may have been shipped this series of breakers.
This is not of concern because the current GEH position is that no defect exists. If testing identifies any anomaly with the pre-October 6, 1971 design, GEH will immediately begin determining the extent of condition, and initiate notification to the industry and regulatory authority.
MFN 12-128 R0 Attachment 1 - Description of Evaluation Page 3 of 3 ABWR and ESBWR Design Certification Documentation Applicability The issue described above has been reviewed for applicability to documentation associated with 10 CFR 52, and determined to have no effect on the technical information contained in either the ABWR certified design or the ESBWR design in certification. This is true because the Technical Specifications submitted with the Design Certification Documentation do not include specific details associated with these components.
Recommendation GEH advises licensees to take no action at this time. However, if licensees wish to determine if the extent of this issue is present at their respective plants, they may identify breaker models AM 4.16-350-2H/2C with a date of manufacture prior to October 6, 1971.
Other AM breaker styles do not use the booster cylinder as designed in breaker model AM 4.16-350-2H/2C and are not included in this concern. Therefore the extent is limited to the AM 4.16-350-2H/2C models manufactured prior to October 6, 1971.
Corrective/Preventive Actions GEH will complete the testing and post-test evaluation and issue either a closure of this 10CFR Part 21 concern or issue an update, based on the results of these tests, by June 14, 2013.
Refer to Attachment 3, Item (vii) for corrective actions.
MFN 12-128 R0 Page 1 of 3 US Plants Potentially Affected US BWR Plants and Associated Facilities Utility Plant X
Constellation Energy Nine Mile Point 1-2 X
Detroit Edison Co.
Fermi 2 X
Energy Northwest Columbia X
Entergy Grand Gulf X
Entergy River Bend X
Entergy FitzPatrick X
Entergy Pilgrim X
Entergy Vermont Yankee X
Exelon Clinton X
Exelon Dresden 2-3 X
Exelon LaSalle 1-2 X
Exelon Limerick 1-2 X
Exelon Oyster Creek X
Exelon Peach Bottom 2-3 X
Exelon Quad Cities 1-2 X
FirstEnergy Nuclear Operating Co.
Perry 1 X
Florida Power & Light Duane Arnold X
Nebraska Public Power District Cooper X
PPL Susquehanna LLC Susquehanna 1-2 X
Progress Energy Brunswick 1-2 X
PSEG Nuclear, LLC Hope Creek X
Southern Nuclear Operating Co.
Hatch 1 - 2 X
Tennessee Valley Authority Browns Ferry 1-3 X
Xcel Energy Monticello
MFN 12-128 R0 Page 2 of 3 US Plants Potentially Affected US PWR Plants and Associated Facilities Utility Plant X
AmerenUE Callaway X
Arizona Public Service Palo Verde 1-3 X
Constellation Energy Calvert Cliffs 1-2 X
Constellation Energy Ginna X
Entergy Arkansas Nuclear One 1-2 X
Entergy Indian Point 2-3 X
Dominion Kewaunee X
Dominion Millstone 2 X
Dominion Millstone 3 X
Dominion North Anna 1-2 X
Dominion Palisades X
Dominion Surry 1-2 X
Dominion Waterford 3 X
Duke Energy Corporation Catawba 1-2 X
Duke Energy Corporation Oconee 1-3 X
Duke Energy Corporation McGuire 1-2 X
Exelon Braidwood 1-2 X
Exelon Byron 1-2 X
Exelon Three Mile Island 1 X
FirstEnergy Nuclear Operations Co.
Beaver Valley 1-2 X
FirstEnergy Nuclear Operating Co.
Davis-Besse X
Florida Power & Light Seabrook X
Florida Power & Light St. Lucie 1-2 X
Florida Power & Light Turkey Point 3-4 X
Florida Power & Light Point Beach 1-2 X
Indiana Michigan Power Corp D C Cook 1-2 X
Northern States Power Prairie Island 1-2 X
Omaha Public Power District Fort Calhoun X
Pacific Gas & Electric Co.
Diablo Canyon 1-2 X
Progress Energy Crystal River 3 X
Progress Energy Robinson X
Progress Energy Shearon Harris X
PSEG Nuclear LLC Salem 1 X
PSEG Nuclear LLC Salem 2 X
South Carolina Electric & Gas Co.
Summer X
South Texas Project Nuclear Operating Co.
South Texas Project 1-2 X
Southern California Edison Co.
San Onofre 2-3 X
Southern Nuclear Operating Co.
Farley 1-2 X
Southern Nuclear Operating Co.
Vogtle 1-2 X
Tennessee Valley Authority Sequoyah 1-2
MFN 12-128 R0 Page 3 of 3 X
Tennessee Valley Authority Watts Bar 1 X
TXU Electric Generation Co.
Comanche Peak 1-2 X
Wolf Creek Nuclear Operating Corp.
Wolf Creek
MFN 12-128 R0 Page 1 of 2 60-Day Interim Report Notification Information per §21.21(a)(2)
(i) Name and address of the individual or individuals informing the Commission.
Dale E. Porter GE Hitachi Nuclear Energy Safety Evaluation Program Manager 3901 Castle Hayne Road, Wilmington, NC 28401 (ii) Identification of the facility, the activity, or the basic component supplied for such facility which fails to comply or contains a defect.
AM 4.16-350-2C and AM 4.16-350-2H Magne-Blast Circuit Breakers (iii) Identification of the firm constructing the facility or supplying the basic component which fails to comply or contains a defect.
GE Hitachi Nuclear Energy (iv) Nature of the defect or failure to comply and the safety hazard which is created or could be created by such defect or failure to comply.
Failure of a Safety Related AM 4.16-350-2H/2C breaker to close or open. Failure to prevent arching between phases during opening.
(v) The date on which the information of such defect or failure to comply was obtained.
A Potential Reportable Condition Evaluation in accordance with 10 CFR Part 21 was initiated on October 30, 2012.
(vi) In the case of a basic component which contains a defect or fails to comply, the number and location of these components in use at, supplied for, being supplied for, or may be supplied for, manufactured, or being manufactured for one or more facilities or activities subject to the regulations in this part.
As a conservative measure this Transfer of Information is being supplied to all BWR and PWR plants as the AM 4.16-350-2H/2C breaker is widely used.
(vii) The corrective action, which has been, is being, or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action.
GEH will complete the testing and post-test evaluation and issue either a closure of this 10CFR Part 21 concern or issue an update, based on the results of these tests, by June 14, 2013.
MFN 12-128 R0 Page 2 of 2 60-Day Interim Report Notification Information per §21.21(a)(2)
(viii) Any advice related to the defect or failure to comply about the facility, activity, or basic component that has been, is being, or will be given to purchasers or licensees.
GEH advises Licensees to take no action at this time.
(ix) In the case of an early site permit, the entities to whom an early site permit was transferred.
This is not an early site permit concern.