Other: ML11349A005, ML12104A191, ML12139A058, ML12178A475, ML12180A023, ML13029A016, ML14035A575, ML14045A284, ML14052A230, ML14083A617, ML14084A319, ML14112A355, ML14125A199, ML14169A441, ML14169A604, ML14169A637, ML14223A602, ML14281A365, ML14302A238, ML14302A298, ML14302A302, ML14310A836, ML14328A006, ULNRC-05847, Calloway Plant, Unit 1 - License Renewal Application Online Lr Library, ULNRC-05886, Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses, ULNRC-05928, Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates, ULNRC-05950, Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates, ULNRC-05957, Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses, ULNRC-05979, Enclosure 2 to ULNRC-05979, Amendment 23, LRA Changes from RAI Responses and Commitment Updates Enclosure 2 Summary Table, ULNRC-06120, Update to License Renewal Application Environmental Permits, ULNRC-06122, Update to License Renewal Application Environmental Permits
|
MONTHYEARML11349A0052011-12-15015 December 2011 Biweekly Report - Applications and Amendments to Facility Operating Licenses Involving No Significant Hazards Considerations: Fr Publication Date December 27, 2011 Project stage: Other ULNRC-05847, Calloway Plant, Unit 1 - License Renewal Application Online Lr Library2012-03-28028 March 2012 Calloway Plant, Unit 1 - License Renewal Application Online Lr Library Project stage: Other ML12104A1912012-04-17017 April 2012 License Renewal Application Online Reference Portal (TAC No. ME7708) Callaway Portal Project stage: Other ML12139A0582012-05-31031 May 2012 Project Manager Change for the License Renewal Project (Safety) for Callaway Plant, Unit 1 Project stage: Other ML12144A0352012-06-11011 June 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML12157A0582012-06-22022 June 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application (TAC ME7708) 6 4 2012 Fmp Neutron Embrittlement and Rv Surveillance RAIs on Yee Chris Sydnor Project stage: RAI ML1218501682012-07-0202 July 2012 ULNRC-05877: Responses to RAI Set 1 and Amendment 4 to the Callaway LRA Project stage: Request ML12164A9052012-07-0505 July 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1, LRA Project stage: RAI ML12172A1112012-07-0909 July 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 4, Project stage: RAI ML12179A4002012-07-18018 July 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML12178A4752012-08-0606 August 2012 Scoping and Screening Methodology Audit Report Regarding the Callaway Plant, Unit 1, License Renewal Application Project stage: Other ML12206A2642012-08-0606 August 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 6 Project stage: RAI ML12220A1602012-08-0606 August 2012 Responses to RAI Set 3 and Amendment 5 to the Callaway License Renewal Application (LRA) Project stage: Response to RAI ULNRC-05886, Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses2012-08-0606 August 2012 Enclosure 1, Responses to the Individual Requests Contained in July 5, 2012 RAIs and Enclosure 2, Contains LRA Amendment 5 to Reflect Changes Made as a Result of the RAI Responses Project stage: Other ML12180A0232012-08-0909 August 2012 Aging Management Programs Audit Report Regarding the Callaway Plant Unit 1 License Renewal Application Project stage: Other ML12216A3382012-08-16016 August 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 7 Project stage: RAI ML12235A4672012-08-21021 August 2012 Responses to RAI Set 5 and Amendment 7 to the Callaway LRA (with Updates to Previous RAI Responses) Project stage: Request ML12233A6132012-08-23023 August 2012 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 8, Electrical Project stage: RAI ML12233A5702012-09-0606 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 9 Project stage: RAI ML12284A4542012-09-12012 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 10, Public Version Project stage: RAI ML12240A1742012-09-18018 September 2012 Review of the 2011 Refueling Outage Steam Generator Tube Inservice Inspection Reports Project stage: Approval ML12250A7702012-09-20020 September 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 11 Project stage: RAI ML12256A8952012-09-25025 September 2012 RAI for the Review of the Callaway Plant, Unit 1, LRA, Set 12 Project stage: RAI ML12255A2872012-10-0101 October 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1, License Renewal Application, Set 13 Project stage: RAI ML12270A1472012-10-0303 October 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 14 Project stage: RAI ML12276A3732012-10-12012 October 2012 RAI for the Review of the Callaway Plant Unit 1, LRA Set 15 Project stage: RAI ML12299A2482012-10-24024 October 2012 Responses to RAI Set 11 & 12 and Amendment 13 to the Callaway LRA Project stage: Response to RAI ML12306A3312012-10-31031 October 2012 Responses to RAI Set 13 & 14 and Amendment 14 to the Callaway LRA, ULNRC-05923 (Cover Letter) Project stage: Request ULNRC-05928, Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates2012-11-0808 November 2012 Enclosure 2 to ULNRC-05928, Amendment 15, LRA Updates Project stage: Other ML12314A1412012-11-0808 November 2012 Responses to RAI Set 15 and Amendment 15 to the Callaway LRA Project stage: Response to RAI ULNRC-05929, Responses to RAI Set 16 and Amendment 16 to the LRA2012-11-20020 November 2012 Responses to RAI Set 16 and Amendment 16 to the LRA Project stage: Response to RAI ML12321A1992012-11-29029 November 2012 9/27/12 - Summary of Telephone Conference Call Held Between the NRC and Union Electric Company (Ameren Missouri), Concerning RAIs Pertaining to the Callaway Plant, Unit 1, License Renewal Application Project stage: RAI ML12326A9152012-12-0707 December 2012 RAI for the Review of the Callaway Plant Unit 1, LRA, Set 18 Project stage: RAI ML12348A1362012-12-13013 December 2012 Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers Project stage: Request ML12356A0932012-12-19019 December 2012 Annual Update to the Callaway License Renewal Application Response to RAI Set 18 Project stage: Response to RAI ML12342A1722012-12-27027 December 2012 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application Project stage: RAI ML13009A2112013-01-14014 January 2013 Request for Additional Information for the Review of the Callaway Plant 1 License Renewal Application Project stage: RAI ML13025A2282013-01-24024 January 2013 Annual Reporting Form for Drug and Alcohol Tests, for Period Ending 2012 Project stage: Request ULNRC-05950, Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates2013-01-24024 January 2013 Enclosure 1, License Renewal Application, RAI Set 19 & Set 20 Responses, Enclosure 2, Amendment 20, LRA Changes from RAI Responses and Commitment Updates Project stage: Other ML13029A2432013-01-24024 January 2013 Responses to RAI Set 19 & Set 20 and Amendment 20 to the Callaway LRA Project stage: Response to RAI ML13025A0312013-01-30030 January 2013 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 21 Project stage: RAI ML13029A6592013-02-12012 February 2013 Summary of Telephone Conference Call Held on December 6, 2012, Between the NRC and Union Electric Company, Concerning Request for Additional Information Pertaining to the Callaway Plant Unit 1, LRA Project stage: RAI ML13029A0162013-02-12012 February 2013 Summary of Telephone Conference Call Held on January 22, 2013, Between the U.S. Nuclear Regulatory Commission Project stage: Other ULNRC-05957, Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses2013-02-14014 February 2013 Enclosure 2 to ULNRC-05957, Amendment 21, LRA Changes from RAI Responses Project stage: Other ML13046A3072013-02-14014 February 2013 Enclosure 1 to ULNRC-05957, License Renewal Application, Request for Additional Information (RAI) Set 21 Responses Project stage: Request ML13046A3062013-02-14014 February 2013 Response to RAI Set 21 and Amendment 21 to the Callaway LRA Project stage: Response to RAI ML13038A3082013-02-21021 February 2013 RAI for the Review of the Callaway Plant Unit 1, LRA, Set 22 Project stage: RAI ML13063A4762013-02-28028 February 2013 Response to RAI Set 22 and Amendment 22 to the Callaway LRA Project stage: Response to RAI ML13042A0422013-03-26026 March 2013 Request for Additional Information for the Review of the Callaway Plant Unit 1 License Renewal Application, Set 23 Project stage: RAI ML13058A1242013-03-29029 March 2013 Request for Additional Information for the Review of the Callaway Plant, Unit 1, License Renewal Application, Set 24 Project stage: RAI 2012-07-05
[Table View] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Fadi Diya Senior Vice President and Chief Nuclear Officer Union Electric Company P.O. Box 620 Fulton, MO 65251 February 12, 2014
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE CALLAWAY PLANT, UNIT 1, LICENSE RENEWAL APPLICATION, SET 30 (TAC NO. ME7708)
Dear Mr. Diya:
By letter dated December 15, 2011, Union Electric Company (Ameren Missouri) (the applicant) submitted an application pursuant to Title 10 of the Code of Federal Regulations Part 54 (10 CFR Part 54) for renewal of operating license No. NPF-30 for the Callaway Plant, Unit 1 (Callaway). The staff of the U.S. Nuclear Regulatory Commission (NRC or the staff) is reviewing this application in accordance with the guidance in NUREG-1800, "Standard Review Plan for Review of License Renewal Applications for Nuclear Power Plants." During its review, the staff has identified areas where additional information is needed to complete the review.
The staff's request for additional information is included in the enclosure. Further requests for additional information may be issued in the future.
Items in the enclosure were discussed with David E. Shafer, of your staff, and a mutually agreeable date for the response is within 30 days from the date of this letter. If you have any questions, please contact me by telephone at 301-415-2946 or by e-mail at Samuel. CuadradoDeJesus@nrc.gov.
Docket No. 50-483
Enclosure:
Request for Additional Information cc: Listserv Sincerely,. U/(!7 amuel Cuadrado de Jesus, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation
ML14029A192 Sincerely, IRA/
Samuel Cuadrado de Jesus, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation OFFICE LA:DLR/RPB2 PM:DLR/RPB1 BC:DLR/RPB1 PM:DLR/RPB1 NAME YEdmonds SCuadrado YDiaz-Sanabria SCuadrado DATE 2/7/2014 2/12/2014 2/12/2014 2/12/2014
Letter to F. Diya from S. Cuadrado de Jesus dated February 12, 2014
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE CALLAWAY PLANT, UNIT 1, LICENSE RENEWAL APPLICATION, SET 30 (TAC NO. ME7708)
DISTRIBUTION:
HARD COPY:
DLR R/F E-MAIL:
PUBLIC RidsNrrDirResource RidsNrrDraAfpb Resource RidsNrrDraApla Resource RidsNrrDeEmcb Resource RidsNrrDeEeeb Resource RidsNrrDssSrxb Resource RidsNrrDssSbpb Resource RidsNrrDssScvb Resource RidsOgcMaiiCenter Resource RidsNrrPMCallaway Resource SCuadrado THartman CFells DMorey BMizuno (OGC)
DCylkowski (OGC)
LSubin (OGC)
GPick (RIV)
RAI3.1.2.1-6
Background:
CALLAWAY PLANT, UNIT 1 LICENSE RENEWAL APPLICATION REQUEST FOR ADDITIONAL INFORMATION, SET 30 By letter dated October 24, 2012, Union Electric Company (Ameren Missouri) provided License Renewal Application (LRA) Amendment No. 13 which revised LRA Table 3.1.2-1, "Reactor Vessel, Internals, and Reactor Coolant System -Summary of Aging Management Evaluation -
Reactor Vessel and Internals," to provide an amended aging management review (AMR) for the reactor vessel internals clevis insert bolts. In this amended AMR, the applicant confirmed that the clevis insert bolts are fabricated from nickel alloy materials and that potential cracking and loss of material due to wear will be managed by the applicant's American Society of Mechanical Engineers (ASME)Section XI lnservice Inspection (lSI), Subsections IWB, IWC, and IWD Program.
Issue:
Appendix A to Electric Power Research Institute (EPRI) Technical Report No. 1022863, "Materials Reliability Program: Pressured Water Reactor (PWR) Internals Inspection and Evaluation Guidelines (MRP-227-A)," indicates that failures of nickel alloy (Alloy X-750) clevis insert bolts were reported by the licensee for one domestic Westinghouse-designed pressurized water reactor in 2010. The ASME Section XI visual VT-3 inspections of the clevis insert assemblies on a 1 0-year frequency may not be adequate to ensure the integrity of clevis insert assemblies during design basis events if multiple bolt failures occur prior to detection and a design basis event occurs.
Request:
(a)
Describe the configuration of clevis insert assemblies at Callaway Plant, Unit 1 (Callaway) including number of bolts in the assemblies. Specify the material of fabrication, including any applicable heat treatment, that were used for the design of the clevis insert bolts at Callaway.
(b)
Discuss and justify whether the operating experience associated with cracking of the clevis insert bolts is applicable to clevis insert assembly designs at Callaway.
(c)
Describe the inspections that have been performed of the clevis insert bolts, including the type of inspection (e.g., VT-3). Clarify the visual inspection coverage that was achieved during these inspections. Clarify the ASME examination category that applies to inspections of the clevis insert bolts (and identify the applicable inspection method and frequency) and whether the past examinations have resulted in the detection of any ENCLOSURE
indications of cracking or failures of the clevis insert bolts that are included in the clevis insert assembly designs. If so, provide the details of the inspection results and clarify the corrective actions that were taken at the facility to justify the structural integrity of the clevis insert assemblies and the intended safety function of the plant's core support structure and its components during plant operations.
(d)
Based on your responses to Parts (a) through (c) of this request, clarify whether the 1 0-year lSI basis for the clevis insert bolts is sufficient to manage cracking and wear of the bolts during the period of extended operation. Justify your response to this request.
ENCLOSURE