June 13, 2003 Applicant:
Omaha Public Power District FACILITY:
Fort Calhoun Station, Unit 1
SUBJECT:
SUMMARY
OF TELECOMMUNICATION WITH OMAHA PUBLIC POWER DISTRICT (OPPD) TO DISCUSS OPEN ITEM 3.6.2.4.3.2-1 ON ELECTRICAL BUS BARS - RENEWAL OF THE OPERATING LICENSE FOR FORT CALHOUN STATION, UNIT 1 (FCS)
On June 6, 2003, the NRC staff (the staff) and representative from OPPD held a telecommunication (telecon) to discuss the Open Item 3.6.2.4.3.2-1 in the draft safety evaluation report for renewal of the operating license for FCS. A list of telecon participants are enclosed (see Enclosure 1). The following is a summary of the discussion.
Staff Question (1) :
The staff had a point of clarification concerning the applicants previous response to a staff dialogue on May 8, 2003 on the subject. The response to the open item were as follows :
When scoping and screening was performed for bus bars at FCS, as a conservative measure, all bus bars were included in the scope of license renewal with the exception of those associated with SBO. SBO beyond the plant boundary was added later in response to a staff RAI and the NRC Interim Staff Guidance on SBO. All of the in-plant bus bars are inside the enclosure of an active component, such as switchgear, power supplies, etc., and are considered to be piece parts of the larger assembly. Per 10 CFR 54.21, OPPD considers them outside the scope for license renewal. However, in the final response, the last three lines concerning the SBO beyond the plant boundary were omitted. The staff wanted to know why the applicant dropped the discussion.
Resolution:
The applicant did not have any objection to restoring the discussion concerning the SBO path beyond the plant boundary in the discussion as above.
Staff Question (2) :
The staff also had a question regarding the bolted iso-phase bus connection (not welded) if it will be managed as part of the periodic surveillance and preventive maintenance program.
Resolution:
The applicant stated that the bus bars credited in the SBO restoration path are all connected to the primary side of the auxiliary transformers by bolted connections. The aging of the bolted connections is managed through implementation of the OPPD Periodic Surveillance and Preventive Maintenance Program.
The applicant agreed to incorporate these two clarifications in its final response to OI 3.6.2.4.3.2-1.
OPPD has reviewed and provided no comments on this telecon summary.
/RA/
Ram Subbaratnam, Project Manager License Renewal Section License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket No.: 50-285
Enclosures:
As stated cc w/encl: See next page The applicant agreed to incorporate these two clarifications in its final response to OI 3.6.2.4.3.2-1.
OPPD has reviewed and provided no comments on this telecon summary.
/RA/
Ram Subbaratnam, Project Manager License Renewal Section License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket No.: 50-285
Enclosures:
As stated cc w/encl: See next page DISTRIBUTION: See next page Accession no.: ML031640609
- See previous concurrence C:\\ORPCheckout\\FileNET\\ML031640609.wpd OFFICE PM:RLEP:DRIP PM:RLEP:DRIP LA:RLEP:DRIP SC:RLEP:DRIP NAME RSubbaratnam*
WBurton*
YEdmonds*
SLee*
Date 06/12/2003 06/13/2003 06/12/2003 06/13/2003 OFFICIAL RECORD COPY
DISTRIBUTION: Summary of Telecon with OPPD Re: FCS RAIs, Dated: June 13, 2003 ML031640609 HARD COPY RLEP RF WBurton E-MAIL:
PUBLIC J. Johnson W. Borchardt D. Matthews F. Gillespie RidsNrrDe R. Barrett E. Imbro G. Bagchi K. Manoly W. Bateman J. Calvo C. Holden P. Shemanski H. Nieh G. Holahan H. Walker S. Black B. Boger D. Thatcher G. Galletti C. Li J. Moore R. Weisman M. Mayfield A. Murphy W. McDowell S. Smith (srs3)
T. Kobetz R. Assa S. Duraiswamy C. Munson RLEP Staff O. Chopra, EEIB, DE LIST OF ATTENDEES OMAHA PUBLIC POWER DISTRICT(OPPD)
FORT CALHOUN STATION, UNIT 1 JUNE 6, 2003 Telecon Participants Attendees Affiliation Tom Matthews OPPD Ram Subbaratnam U.S. Nuclear Regulatory Commission (NRC)
Om Chopra NRC
Ft. Calhoun Station, Unit 1 cc:
Winston & Strawn ATTN: James R. Curtiss, Esq.
1400 L Street, N.W.
Washington, DC 20005-3502 Mr. Kent Wilcox, Chairman Washington County Board of Supervisors P.O. Box 466 Blair, NE 68008 Mr. Wayne Walker, Resident Inspector U.S. Nuclear Regulatory Commission Post Office Box 309 Fort Calhoun, NE 68023 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011 Mr. John Fassell, LLRW Program Manager Health and Human Services Regulation and Licensure Consumer Health Services 301 Cententiall Mall, South P. O. Box 95007 Lincoln, Nebraska 68509-5007 Mr. Richard P. Clemens Manager - Fort Calhoun Station Omaha Public Power District Fort Calhoun Station FC-1-1 Plant Post Office Box 399 Hwy. 75 - North of Fort Calhoun Fort Calhoun, NE 68023 Mr. Joseph Gasper Manager - Nuclear Licensing Omaha Public Power District Fort Calhoun Station FC-2-4 Adm.
Post Office Box 399 Hwy. 75 - North of Fort Calhoun Fort Calhoun, NE 68023-0399 Mr. S. K. Gambhir Division Manager - Nuclear Operations Omaha Public Power District Fort Calhoun Station FC-2-4 Adm.
Post Office Box 399 Hwy. 75 - North of Fort Calhoun Fort Calhoun, NE 68023-0399 Mr. Mark T. Frans Manager - Nuclear Licensing Omaha Public Power District Fort Calhoun Station FC-2-4 Adm.
Post Office Box 399 Hwy. 75 - North of Fort Calhoun Fort Calhoun, NE 68023-0399 Mr. Alan P. Nelson Nuclear Energy Institute 1776 I Street, N.W., Suite 400 Washington, DC 20006-3708 W. Dale Clark Library Attn: Margaret Blackstone 215 South 15th Street Omaha, NE 68102 Blair Public Library Attn: Ruth Peterson 210 South 17th Street Blair, NE 68008-2055