Georgia Power Company l 40 invemess Center Parkway  ;

. Post Office Box 1295 l

  • Birmingham. Alabama 35201 l Telephono 205 877 7279 J. T. Beckham, Jr. Georgia Power Vice President Nuclear Hatch Project tne scuthem ewiec system October 31, 1994

> Docket No. 50-366 HL-4727 U.S. Nuclear Regulatory Commission -

ATTN: Document Control Desk Washington, D.C. 20555 Edwin I. Hatch Nuclear Plant - Unit 2 Special Report 2-94-002 Inappropriately Terminated Fire Watch Results in Special Report as Required by the Fire Hazards Analysis Gentlemen:

In accordance with the requirements of the Unit 2 Technical Specifications and Fire Hazards Analysis, Georgia Power Ccmpany is su' omitting the enclosed Special Report concerning an event wherein a fire watch was inappropriately terminated. This event occurred at Plant Hatch - Unit 2.

Sincerely, P l T. Beckham, Jr.

JKB/et

Enclosure:

Special Report 2-94-002 080013 ffYm wunar S

I l

4 i

Georgia Power d l .

U.S. Nuclear Regulatory Commission Page Two October 31, 1994 cc: Georgia Power Company Mr. H. L. Sumner, General Manager - Nuclear Plant NORMS U.S. Nuclear Regulatory Commission. Washineton. D.C.

Mr. K. Jabbour, Licensing Project Manager - Hatch U.S. Nuclear Resmlatory Commission. Region 11 Mr. S. D. Ebneter, Regional Administrator Mr. B. L. Holbrook, Senior Resident Inspector - Hatch I

l l

l l

I i

HL-4727

l

. l i

Enclosure Edwin I. Hatch Nuclear Plant - Unit 2 Special Report 2-94-002 Inappropriately Terminated Fire Watch Results In Special Report as Required by the Fire Hazards Analysis A. _R_tquirement For Report This report is requt . ., we riant Hatch Unit 2 Technical Specifications, Section 6.9.2, and the Plant Hatch Fire Hazards Analysis, Appendix B, Section 1.1.1.

Specifically, Technical Specifications, Section 6.9.2 states:

Special Reports for fire protection equipment operating and surveillance requirements shall be submitted, as required, by the Fire Hazards Analysis (FHA) and its Appendix B requirements.

FHA Appendix B, Section 1.1.1, states:

Fire-rated assemblies and sealing devices in fire-rated assembly penetrations separating portions of safety-related fire areas or separating redundant systems important to safe shutdown within a fire area shall be OPERABLE.

Furthermore, Action Statement (a) of Appendix B, Section 1.1.1, allows the fire rated assembly and/or sealing device to be inoperable for up to 14 days provided, within I hour, a continuous fire watch on at least one side of the affected assembly (ies) and/or sealing device (s) is established, or fire detectors are verified operable on at least one side of the inoperable barrier and an hourly fire watch patrol is established. In the event described in this report, a required hourly fire watch patrol was inappropriately tenninated.

B. Unit Status At Time Of Event On 10/7/94, at 0200 EDT, Unit I was shutdown for a refueling outage with all fuel removed from the reactor vessel. Unit 2 was in the Run mode at a power level of 2358 CMWT (96.8% rated thennal power).

HL-4727 E-1

Enclosure

patrol for the fire area mentioned above was terminated on 10/2/94 due to removal of all fuel from the Unit I reactor vessel. The operating and surveillance requirements for fire-rated assemblies contained in the FHA are applicable when fuel is in the reactor vessel. l On 10/7/94, at 0200 EDT, a licensed shift supervisor was performing a review of FHA related Limiting Conditions for Operations (LCO) and discovered that the required hourly fire watch patrol had been inappropriately terminated for fire area 0040. The fire area is common to both units and '5e fire watch should have been maintained to satisfy the FHA requirements for Unit 2. Deficiency Card 1-94-2650 was written to document the failure to maintain the required fire watch. The hourly fire watch patrol for the affected area was re-established on 10/7/94 at 0230 EDT as required by LCO 1-92-420.

D. Cause OfThe Evgg The cause of the inappropriate termiaation of the fire watch in fire area 0040 was personnel error. Specifically, licensed personnel did not recognize that fire area 0040 is common to both units.

E. Analysis Of Event In this event, a required hourly fire watch patrol for fire area 0040 was not performed from 10/2/94 to 10/7/94. Upon discovery of the condition, an hourly fire watch patrol was re-established for the affected fire area in accordance with FHA Appendix B, Section 1.1.1.

The fire area affected by this event is equipped with a full coverage linear thermal detection system which, in the event of a fire, would provide an alarm both locally and in the Main Control Room to ensure prompt response by the plant fire brigade. The area is also protected by a wet pipe sprinkler system which would rapidly extinguish a fire. Additionally, a hose station and portable carbon dioxide fire extinguishers are ,

available in nearby fire area 0014.

HL-4727 E-2

JL 1

i Enclosure -

Special Report 2-94-002 Based on the above information, it is concluded that this event had no adverse effect on nuclear safety.  :

L F. Corrective Actions i

1. On 10/7/94, an hourly fire watch patrol was re-established for the affected fire area.
2. Involved personnel have been counseled.

i i

L HL-4727 E-3 5