PNO-III-86-121, on 861110,preliminary Evaluation by Licensee & Region III Determined Diesel Generator 1B Failure Caused by Improperly Torqued Bolt in Articulated Connecting Rod. Licensee Plans to Examine Remaining Generators

From kanterella
Jump to navigation Jump to search
PNO-III-86-121:on 861110,preliminary Evaluation by Licensee & Region III Determined Diesel Generator 1B Failure Caused by Improperly Torqued Bolt in Articulated Connecting Rod. Licensee Plans to Examine Remaining Generators
ML20213G431
Person / Time
Site: Zion File:ZionSolutions icon.png
Issue date: 11/10/1986
From: Burgess B, Guldemond W, Muffett J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
References
PNO-III-86-121A, NUDOCS 8611180110
Download: ML20213G431 (1)


PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-III-86-121A Date November 10, This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The information is as initially received without verification or evaluation, and is basically all that is known by the Region III staff on this date.

Facility: Commonwealth Edison Company Licensee Emergency Classification:

Zion Unit 1 Notification of an Unusual Event Zion, IL 60099 Alert Site Area Emergency Docket No. 50-294' / General Emergency Q X Not Applicable f

Subject:

FAILURE OF DIESEL GENERATOR (UPDATE)

A preliminary evaluation by the licensee and Region III (Chicago) had determined that the IB diesel generator failure was caused by an improperly torqued bolt in the articulated connecting rod. A review of quality assurance records, interviews with licensee personnel, and physical examination of the components indicate that the failure resulted from the improper torquing of the bolt during a piston replacement which occurred during the current outage. The failure occurred during post-maintenance testing. Metallurgical examination of the failed bolt showed the failure mechanism to be fatigue.

The licensee has examined two of the four other diesel generators on site. Several bolts were found that had suspect torque valves; these bolts have been replaced and torqued to the proper value. Based on the current review, it does not appear that the failure has generic implications. The licensee plans to examine the remL:ining diesel generators.

Repair activities on the diesel generator are continuing. Region III (Chicago) is monitoring the repair work.

The State of Illinois will be informed.

This information is current as of 11 a.m. (CST), November 10, 1986.