ext mu ARY NOIIFICATION July.11,1977 SQ hCk@h PRELIMINARY NOTIFICATION OF EVENT OR UN This preliminary notification constitutes EARLY notice of an hven U
POSSIBLE safety or public interest significance. The information presented is as initially rechived without verification or evaluation and is basically all that is known by IE staf f on this dste.
~
Pacility:
Commonwealth Edison Company, Zion Unit 2 (Docket No. 50-304),
Zion, IL
_Subj ec t :
~
Commonwealth Edison Company reported that at 11:22 a.m. on July 10, 1977 a Unit 2 reactor scram occurred due to a 2C steam generator low-low level condition.
This condition was caused by the loss of a feedwater pump while performing maintenance on the feedwater pump lube oil filter system.
During recovery of the steam generator water level, a steam generator water hammer occurred.
The water hammer in turn, caused a disturbance of feedwa'ter flow transmitters on loop A resulting in a safety system injection.
Visual examination of the feedwater lines and steam flow by members of the plant review' committee showed no pipe support damages and no insula-tion disturbance.
in B loop and one in D loop were found to be cracked.However, one feedw The plant is still shut down for further evaluation of damage. A RIII (Chicago) inspector is at the site reviewing this matter.
Ne'ither the licensee or RIII have decided on the issuance of a Press Release at this time.
/
gg The State of Illinois has been notified.
RIII (Chicago) office received notification of this occurrenca by telephone from a member of the plant staff at 7:44 p.m. on July 10,
'1977.
This information is current as of 0830 on July 11, 1977.
Contact:
KWhitt, IE x27451 GLConstable, IE x27451 JHSniezek, IE x27451 Distribution: Transmitted H St /.*4 / W
/
C. C. IGtmmerer, CA G. F. Murphy, JCAE Commissioner Kennedy S. J. Chilk, SECY H. H. Whitesides SCNR Commissioner Gilinsky H. R. Myers, HCEE Transmitted: MNBBj.*d P Bldg /.* 8 SS Bids ///!
L. V. Gossick, EDO E. G. Case, NRR C. V. Sdith, NMSS S. H. Hanauer, EDO J. A. Harris, PA W. G. Mcdonald, MIPC Luge (MAIL)
E. Volgenau, IE R. G. Ryan, OSP T. J. McTiernr.n, OIA Region 8 _ff/ M H. K. Shapar, ELD w __
PRELIMINARY NOTIFICATION A-i 4X D)D j
9809170187 770711 PDR I&cE PNO-77-124 PDR O
e-me