ig I YlltOINIA MLI CTit1C ANT) 'POWI:1[ COMi%NY f H ICilMOND,YllfulNIA 203 61

September 2,1992 United StatesLNuclear Regulatory Commission Serial No.92-548

- Attention:- Document Control Desk NL&P/EJW .-

Washingic D.C. 20555 Docket No. 50 339 l License No. NPF-7  ;

Gentlemen:-

VIRGINIA ELECTRIC AND- POWER COMPANY-NORTH ANNA ~ POWER = STATION- UNIT 2 -  ;

FIRE BARRIER NOT INSTALLED +

- VOLUNTARY SPECIAL- HEPORT

-i

-During an engineering walkdown of North Anna Power Station on July 21,1992, it - .

was. discovered that a fire damper was not installed as specified in a station drawing,.

Theidrawing . depicted -the damper in a vertical- Heating Ventilation and Air.

Conditioning (HVAC) duct between the Unit . Normal Switchgear Room and Cable - ,

Spreading Room.1For compliance with: Appendix A to-Branch Technical Position APCSB 9.5-1, this' duct is required to have a three hour rated fire damper. Deviation Repo" 92-1579 was submitted when the missing. damper was discovered, and an i hourly fire watch was implemented. Subsequently, the duct was wrapped with a fire

" rated material tolensure fires in the Normal Switchgear Room will not affect the Cable.

-Spreading Room; iThis material is-a mineral: wool batting which rneets UL design

?X301(for a three hour fire barrier and is not within the scope. of NRC Bulletin 92 01

' dated Ju'ne 24,1992, involving fire barrier systems. - An engineering walkdown of the remaining Appendix A and Appendix _R dampers determined that they are installed in -

_ ~

> accOrdance wit _h_ station drawings. L Apparently, the missing ~ damper-was not installed

,during initial plant construction.

- No signif.icant safety consequences resulted from this condition because these areas are controlled with either operable fire detection and. suppression equipment or- ,

Lappropriate administrative measures such as a firewatch. Furthermore,- Appendix R'

. safe _ shutdown equipment is not located in either room. The subject duct is_ a HVAC

" throughway"'with no: openings:in' the Normal-Switchgear Room or the Cable LSpreadi_ng Room. The ductwork has an inherent fire rating of one _ hour due to its steel, construction fan existing. damper in the_same duct located near the floor of the Unit 2 LCable Spreading-Room would have-provided the required separation from the areas -

below.- Therefore, the health and safety of the public were not affected as a result of

this condition.

t 92o910o059 92o902 9 DR ADOCK 0500

f. I g

4 . g.

4 l

. l This Special Report has been reviewed by the Station Nuclear Safety and Operating Committee and will be provided to the Management Safety Review Committee. The condition is bcing reported on a voluntary basis to provide operating experience information to the NRC and nuclear industry.

Should you have any questions regarding this report, please contact us.

Very truly yours, fr M. L. Bowling, Manager Nuclear Licensing and Programs cc: -United States Nuclear Regulatory Commission Region 11 101 Marietta Street, N.W.

Suite 2900 Atlanta, GA 30323 Mr. M. S. Lesser NRC Senior Resident inspector North Anna Power Station