Monthly Operating Repts for Jan 1998 for North Anna Power Station,Units 1 & 2
ML20202D581
Person / Time
Site: North Anna  
Issue date: 01/31/1998
From: Matthews W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
98-083, 98-83, NUDOCS 9802170119
Download: ML20202D581 (10)


Text

- _ _ _ _ _ _ _ - _

r VIHOINTA ELi:CTHIC AND POWP.H COMPANY Hacuxoxu,Viaorn:A 9a20:

Fe' ruary 5,1998 o

United States Nuclear Regulatory Commission Serial No.98-083 Attention: Document Control Desk NAPS /JHL Washington, D. C 20555 Docket Nos.

50-338 50-339 License Nos. NPF-4 NPF-7 Gentlemen:

l VIRGINIA IELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT NOS.1 AND 2 MONTHLY OPERATING REPORT Enclosed is the January 1998 Monthly Operating Report for North Anna Power Station Units 1 and 2.

r Very truly yours, D2W W. R. Matthews Station Manager Enclosure cc:

U. S. Nuclear Regulatory Commission E

Region ll Atlanta Federal Center 61 Forsytti St., SW, Suite 23T85 Atlanta, Georgia 30303 Mr. M. J. Morgan I

/'

NRC Senior Resident inspector North Anna Power Station

_ ac3 I.llll llll1llllllOli, i.l 9802170119 980131 PDR ADOCK 05000338 1 R

PM

{

j

VIRGINIA POWER COMPANY NORTH ANNA POWER STATION NONTHLY OPERATING REPORT MONTH: January Year: 1998 Approved:

(M

' Station Manager g

~

I OPERATING DATA REPORT DOCKET No.:

50-338 DATE: February v.1998 CL.NTACT N. R. Matthews PHONE:

(540) 894 2101 OPERAT!*3 STATUS 1,

Unit Naeos.,

North Anna 1 2.

Reporting Periods.

January 3.

Licensed Thermal Power (MWt).

2,093 4.

Nameplate Rati.ig (Gross MWeli..

979.74 5.

Design Electrical Rating (Not MWe):.

907 6.

.Naximum Dependable Capacity (Gross MWe).

940 7.

Maximum Dependable capacity (Net MWels..

893 8.

It changes occur to Capacity Ratings (Items 3 thru 7) since last report, g;ve reasons:

N/A 9.

Power twvel to which restricted, if any (Not MWe)i N/A l

10. Reasons for restrictions, if any N/A This Month Y-t-D Cumulative f

i 11.

Ects in Reporting Peried 744.0 744.0 171,924.0 I

13. Number of Houra Reactor was Critical.

144.0 144.0 133.999.0

13. Reactor Reserve Shutdown Hours.

0.0 0.0 7,095.0 14.

Hours Generator On Line.

744.0 744.0 130,911.4 l

15.

Unit Reserve Shutdown Hours..

0. 0 -

0.0 0.0

16. Gross Thermal Energy Generated (MWH).

2,151,440.0 2,151,440.0 352,685,912.5 a7. Gross Electrical Energy Generated (MWM).

702,902.0 702,902.0 152,873,555.0 18.

Net Bloctrical Energy Generated (MWH).

669,143.0 66e.163.0 109,0.3,346.0

19. Unit Service Factor.

100.0%

100.0%

76.1%

20. Unit Availability Factor.

100.0%

100.0%

76.1%

21. Unit Caaecity Factor (using MDC Net).

100.7n 100.7%

71.5%

22. Unit Capacity Factor (using DER Net).

99.2%

99.2%

70.4%

23. Forced Outage Rate.

0.0%

0.0%

8.3%

24.

Shutdowns Scheduled over Next 6 Months (Type, Date, Duration

_ N/A 25.

If Shutdown at end of Report Period, estimated time of Startu N/A

26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION l

t

5 AVERAGE DAILY UNIT POWER LEVEL Docket No.:

50-338 Units-NA-1 Date Febt5. 1998

Contact:

W.

R.

Matthews Phone (540) 894-2101 MONTH JANUARY 1998 DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

LEVEL (MWs-Net) 1 900 17 899 2

196 18 899 3

ER1

-19 899 4

900 20 899 5

900 21 899 6

900 22 899 7

900 23 899 8

900 24-900 9

900 25 899 10 900 26 899 11 900 27 899 12 900 28 899 13 901 29-899 14 900 30-898 15 900 31 898 16 900 Instructions:

On this format,-list the average daily unit power level in MWe-Net for each day in the reporting month.

Compute to the nearest whole megawatt.

A.

NORTH ANNA POWER STATION UNIT NO.: J MONTH January 1998 SLM4ARY OF OPERATING EXPERIENCE Page 1 of 1 Listed below in chronological scquence is a

summary of1 operating experiences for this month which required load reductions or resulted in significant non-load related incidents.

Date Time Data January 1, 1998 0000 Began month in Mode 1 at 100% Power, 945 Mwe.

g January 2,-1998 2200 Commenced ramp to 91% power for Turbine Valve Freedom Test (TVFT).

.Tanuary 2, 1998 2330 TVFT completed sat. Commenced ramp to 100%

power.

January 30,-1998 2310 Commenced-ramp to 91% power for TVFT.

-January 31, 1998 0010 TVFT completed sat. Commenced ramp to 100%

power.

. January 31, 1998.-

_2400 3ided the month at 100% power, 943Mwe.

p

l DOCKET NO.

50-338 UNIT NAMES NA-1 mTE: February 5, 1998 4

CONTACTS W. R. Matthews Unit Shutoowns and Power Reductions en NE: (540) e n-2101 Report Month:' January 1998 1

2 3

1 5

No.

Date Type Duration Reason Method of Licensee System Component Cause & Corrective (hrs)

Shutting Event Code Code Action to Down Reactor Report i Prevent Recurrence

  • No entries this month.

1 3: Method 4:

Y Type 2: Reason F= Forced I.= Equipment Failure (explain) 1=Hanual Exhibit F - Instructious S= Scheduled B=Hain;enance or Test 2=Hanual Scram for preparation of Data 3= Automatic Scram Entry Sheets for Licensee C= Refueling D= Regulatory Red?tiction 4= Continuations Event Report (LER) File E= Operator Training & License Examination 5= Load Reduction (NUREG-o161)

F= Administrative 9-Other 5:

G= Operational Error Exhibit H - Same Source H=Other (explain) e m

OPERATING DATA REPORF e

DOCERT NO.t 50-339 DATE: February 5, 1998 COWTACT:

W. R. Matthews PHONE:

(540) 894 2101 OPERATING STATUS 1.

Unit Names.

North Anna 2 2.

Reporting pericis..

January 3.

Licensed Thermal Power (MWtle.

2,893 4.

Nameplete Rating (Gross MWe)s.

979 5.

Design Electrical Rating (Not MWel:...

907 4.

Maximum Dependable Capacity (Gioss awe).

944 1.

Maximum Dependable Capacity (Net MWa)...

897 8.

It changes occur to capacity Ratings (Items 3 thru 7) since last report, give reasonst N/

9.

Power level to which restricted,12 any (Net MWe):

N/A

10. Reasons for restrictions, if any:

N/A l

l This Month Y-t-D Cumulative i

f.

11.

Hours in Reporting Period.

744,0 744.0 150,192.0

_12.

Number of Hours peactor was Critical.

-4.0 744.0 126,459.2 13.

Reacto? Reserve Shutdown Hours.

0.0 0.0 7,184.2 2

14.

Hours Generator on-Line.

744.0 744.0 125,266.2

15. Unit Reserve Shutdown Hours..

0.0 0.0 0.0 16.

Cross Thermal Energy Generated (MWH).

2,151,798.7 2,151.798.7 342,944,978.7

17. Gross Electrical Energy Generated (MWH).

bl.102. 0 701.102.0 112,203,616.0 18.

Net Electrical Energy Generated (MWH)...

647,510.0 667,510.0 107,195,478.0

19. Unit Service Factor.

100.0%

100.0%

83.4%

20. Unit Aval16bility Factor.

100.0%

100.0%

83.4%

21.

Unit Capacity Factor (using MDC Net).....

100.0%

100.0%

79.4%

22. Unit Capacity Factor (using DER Net).

98.9%

98.9%

78.7%

23. torced Outage Rate.,

0.0%

0.0%

5.0%

24.

Shutdowna scheduled over Next 6 Months (Type, Date, Dut, tion of Each):

Aefueling, April 5 1998 for 35 days 25.

If Shutdown at end of Report Period, estimated time of Startu N/A

26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL E1.ECTRICITY COMMERCIAL OPERATION t

1

.g AVERAGE DAILY UNIT POWER LEVEL Docket No.:

50-339 Unit:

NA-2 Date:

Feb.5. 1998

Contact:

W.

R. Matthews Phones (540) 894-2101

! i

' MONTH JANUARY 1998 l

l-DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER

~

LEVEL (MWe-Net)

LEVEL (MWe-Ne t) 1 898 17 896 2

898-18 896 3

899 19 997 4

899 20

.897 5

899 21 897 6

898 22 896

-7 898 23 896 8

898 24 895 9

898 25 897 10 898 26 896 11 898 27 S2E 12 898 28 897 13 898 29 897 14 897 30 897 15 896 31~

897 M

895-Instructions:

On this format, list the average daily unit power level in MWe-Net for each day in'the reporting month.

Compute to the nearest whole megawatt.

-NORTH ANNA POWER STATION

.\\

UNIT NO : 2-

.~

MONTH: January 1998 T

SUbHARY OF OPERATING EXPERIENCE Page 1 of 1 Listed below -in chronological -sequenco_ is a

summary of' operating

experiences for this month which required load reductions or resulted in lsignificant non-load related incidents.

i Dato Time

' Data Jan'1ary 1, 1998 0000 Began the month in Mode 1 100% Power 940 Mwe, January _23, 1998 2331 Commenced ramp to 93% power for Turbine Valve Freedom Test (TVFT).

-Janbary-24, 1998 0100 TVFT completed sat. Commenced ramp to 100%

power.

January 31, 1998-2400 Ended the month at 100% power, 945 Mwe.

u

~ - - ~ ' -

._.s-w

. +-

DOCKET MO.

50-339 UNIT NME:- m-2

. Unit Shutdowns and Power Reductions' mTE Febnsry 5,1998 ~

"*tth'"*

Report Month:.Tanuary 1998 PHONE: (540) 894-2101 a

1 2

3 4

5 No.

Date Type-Duration Reason Method of Licensee System Component dause & Corrective--

(hrs)

Shutting Event Code Code-Action to Down Reactor Report 8 Prevent Recurrence i

'I

  • No entries this month.

1: Type 2: Reason 31 Method 4s F= Forced A= Equipment rallure (explain) 1= Manual Exhibit F - lastructions S-Scheduled B-Maintenance or Test 2= Manual Scram for preparStion of Data 3= Automatic Scram Entry SheY.s for Licensee C=lefueling i

D=Pegulato' Restriction 4= Continuations Event Report (LERI File E=0perator Training & License Examination 5= Load Reduction (NUREG-0161) l F= Administrative 9-Other 5:

G= Operational Error Exhibit H - Some Source H=Other (explain)

L- _. _ _ _ _ _ _ _ _ _ _. _

.