Other: ML19338E122, ML19338E126, ML19339B208, ML19340B681, ML19347D323, ML19347E204, ML20008F589, ML20009F108, ML20033D218, ML20040H345, ML20050C823, ML20054E801, ML20062J441, ML20065H986, ML20070L991, ML20071N774, ML20074A858, ML20076F399, ML20080Q925, ML20080Q937, ML20087P125, ML20090B920, ML20090H443, ML20091M568, ML20093E084, ML20093E100, ML20093E443, ML20093F665, ML20093J657, ML20094B628, ML20097D991, ML20098E985, ML20099C148, ML20099C474, ML20137T507
|
MONTHYEARML19338E1261980-08-29029 August 1980 Order for Mod of Licenses DPR-57 & NPF-5 to Add Info Which Fully Responds to NRC Request for Info Re Environ Qualification of safety-related Electrical Equipment.Info Should Be Submitted by 801101 Project stage: Other ML19338E1221980-08-29029 August 1980 Forwards Order Requiring Info Supporting Environ Qualification of safety-related Electrical Equipment. Requests Submittal of Info by 801101 Project stage: Other ML20062J4411980-09-19019 September 1980 Revised Order for Mod of License Requiring Timely Submission of Info Previously Requested Re Environ Qualification of safety-related Electrical Equipment Project stage: Other ML19340B6811980-10-24024 October 1980 Revised Tech Spec Pages Per 801024 Order for Mod of Licenses Re Environ Qualification of safety-related Electrical Equipment Project stage: Other ML19339B2081980-10-31031 October 1980 Provides Info Re Environ Qualification of safety-related Equipment in Response to DG Eisenhut .Util Is Willing to Participate in Establishment of Standardized Equipment Environ Qualification Acceptance Criteria Project stage: Other ML19347D3231981-02-17017 February 1981 Confirms Commitment to Install Qualified Limit Switches & Solenoids by 820630.Commitment Will Be Reflected in Package Updating Util Response to IE Bulletin 79-01B, Environ Qualification of Class IE Equipment Project stage: Other ML19350C6801981-04-0101 April 1981 EN-81-11:on 810407 Notice of Violation & Proposed Imposition of Civil Penalties Will Be Issued to Util Based on Alleged Violations Re Inadequate Sampling Procedures Which Allowed Contaminants to Reach Unrestricted Area Project stage: Request ML20003E6901981-04-0101 April 1981 Forwards Partial Review of Environ Qualification of safety- Related Electrical Equipment.Written Response Required within 10 Days Project stage: Approval ML20008F5891981-04-13013 April 1981 Responds to NRC 810401 Evaluation of Util Response to IE Bulletin 79-01B Re Environ Qualification of safety-related Electrical Equipment.Potential Deficiencies Will Not Impact Facility Safe Operation.Detailed re-evaluation to Follow Project stage: Other ML19347E2041981-04-20020 April 1981 Advises of Error in NRC Re Environ Qualification of safety-related Electrical Equipment.No Caustic Sprays Are Used in Either Containment.Phrase in Section 3.2 Should Be Deleted Project stage: Other ML20009F1081981-07-14014 July 1981 Forwards TER-C5417-9, Equipment Environ Qualification,Hatch Nuclear Plant Unit 1, Final Technical Evaluation Rept.Rept Replaced 810131 Rept Project stage: Other ML20033D2181981-11-16016 November 1981 Forwards Info on Issues Discussed During 810806 Telcon in Support of Extension of 820630 Deadline for Compliance W/ Environ Qualifications Guidelines,Per IE Bulletin 79-01B Project stage: Other ML20040D1291981-12-11011 December 1981 Equipment Environ Qualification Review of Licensee Resolution of Outstanding Issues from NRC Equipment Environ Qualification Safety Evaluation Repts & TMI Action Plan Installed Equipment, Request for Addl Info Project stage: Request ML20040D1281981-12-11011 December 1981 Equipment Environ Qualification Review of Licensee Resolution of Outstanding Issues from NRC Equipment Environ Qualification Safety Evaluation Repts & TMI Action Plan Installed Equipment, Request for Addl Info Project stage: Request ML20040H3451982-02-10010 February 1982 Forwards Info Requested in Re Environ Qualification of safety-related Electrical Equipment.Encl Withheld (Ref 10CFR2.790) Project stage: Other ML20040H1791982-02-10010 February 1982 Discusses Corrective Actions Re Implementation of Operating Procedures to Resolve Concerns Referenced in GE SIL 299 & SIL 299 Suppl 1 Concerning Leg Flashing of Yarway Level Instruments & Cold Leg Flashing of Ge/Mac Level Instruments Project stage: Request ML20049J3361982-02-25025 February 1982 Forwards Request for Addl Info Needed to Continue Review of Environ Qualification Program for safety-related Electrical Equipment.Response Due in 30 Days Project stage: RAI ML20050C8231982-04-0505 April 1982 Forwards Addl Info in Response to 820225 Request Re Peak Containment Temps for Equipment Qualification.Small Steam Line Break Analysis Peak Drywell Temps Lower than FSAR DBA Temps Project stage: Other ML20054E8011982-06-0707 June 1982 Forwards Franklin Research Ctr Requests for Addl Info Re Equipment Environ Qualification Program.Response Requested within 30 Days Project stage: Other ML20055A0811982-07-0909 July 1982 Responds to NRC 820607 Request for Addl Info on Correlation Between TMI Action Plan Equipment & Specific Sections in NUREG-0737.Procurement of Equipment Per Scope of IE Bulletin 79-01B Will Meet NUREG-0588 Requirements Project stage: Request ML20065H9861982-09-28028 September 1982 Forwards Schedule for Qualification Testing of Analog Transmitter Trip Sys,In Response to 801001 Request Project stage: Other ML20070L9911983-01-0303 January 1983 Updates 801101 Response to IE Bulletin 79-01B Re Electrical Equipment Qualification.Completion of Mild Environ Qualification Programs Deferred Until Publication of Final Rule (SECY-82-207).Summary of Outstanding Items Encl Project stage: Other ML20074A8581983-05-0606 May 1983 Submits 30-day Response to SER & Technical Evaluation Rept Re Environ Qualification of Class IE Equipment (IE Bulletin 79-01B).Final Plans for Resolving Qualification of Items in Categories I.B,Ii.A & Ii.B Will Be Transmitted by 830520 Project stage: Other ML20071N7741983-05-20020 May 1983 Forwards Rev 0 to Ei Hatch Nuclear Plant Units 1 & 2 Environ Qualification of Class IE Equipment, in Response to IE Bulletin 79-01B & 10CFR50.49 Requirements Project stage: Other ML20076F3991983-06-0808 June 1983 Advises That SER & Technical Evaluation Repts Re Environ Qualification of safety-related Electrical Equipment Do Not Contain Proprietary Info.Repts May Be Placed in PDR Project stage: Other ML20093E1001983-12-0909 December 1983 Design Stress Rept Project stage: Other ML20083H8061984-01-0606 January 1984 Notifies of Equipment Qualification Problems Which Could Result in Request for Extension of 10CFR50.49 Rulemaking Deadline Project stage: Request ML20080Q9251984-02-24024 February 1984 Forwards Containment post-accident Profiles Utilized in 10CFR50.49 Qualification Program & Extended Drywell Temp Analysis.Drywell Temp Analysis Withheld (Ref 10CFR2.790) Project stage: Other ML20080Q9371984-02-24024 February 1984 Post-Accident Temp & Pressure Profiles Project stage: Other ML20087P1721984-03-30030 March 1984 Discusses 840214 Meeting W/Nrc Re Ongoing Program Developed for Qualification of Electrical Equipment.Central Qualification Documentation File & Master List of All Equipment Established.Rept on Methodology Used Encl Project stage: Meeting ML20087P1251984-04-0303 April 1984 Notifies of Potential Problem Re 10CFR50.49 Equipment Qualification Deadline.Qualification Testing Program for Pyco Resistance Temp Detectors & Qualification of Valve Motor Operators Could Require Extensions Project stage: Other ML20091M5681984-06-0404 June 1984 Forwards Addl Info Requested Per Re Electrical Equipment Qualification,Covering Balance of Plant Components,Nsss Components & Methodology to Identify Equipment Per 10CFR50.49(b) Project stage: Other ML20090B9201984-07-0606 July 1984 Requests Extension of Environ Equipment Qualification Deadline for Analog Transmitter Trip Sys Until 851130 So Necessary Equipment Installation Can Be Completed During 1985 Scheduled Refueling Outage Project stage: Other ML20093E0841984-07-12012 July 1984 Forwards Design Stress Rept, in Attempt to Resolve Seismic Problem.Requests Exemption from Outage Based Deadline Specified in 10CFR50.49(g) for Motorized Operators on Valves 2E11-F016A&B Project stage: Other ML20093F6651984-07-17017 July 1984 Requests Extension Be Granted for Existing Unit 1 Hydrogen & Oxygen Analyzers.Replacement of Existing Analyzers Scheduled for Fall 1985 Refueling Outage.Qualification Deadline Extension to 850331 Requested for Unit 2 Analyzers Project stage: Other ML20090F8741984-07-19019 July 1984 Forwards Rev to Equipment Qualification Program,Per 840706 Request for Deadline Extension for Analog Transmitter Trip Sys Project stage: Request ML20094B6281984-07-19019 July 1984 Notifies of Potential Equipment Qualification Problems Re 10CFR50.49 Equipment Qualification Deadline.Problems Result from Inability of Pyco,Inc to Provide Qualification for Resistance Temp Detectors in Use Project stage: Other ML20090H4431984-07-24024 July 1984 Forwards Response to IE Bulletin 79-01B,consisting of Justifications for Continued Operation of balance-of-plant Components,Nsss Components & Unit 2 balance-of-plant,per 840716 Telcon Project stage: Other ML20093J6571984-07-24024 July 1984 Requests Further Extension of 10CFR50.49(g) Environ Qualification Deadline for Motorized Actuators on RHR Isolation Valves 2E11-F016A & B,Until Startup Date Following Next Refueling Outage in May 1985 Project stage: Other ML20097D9911984-09-11011 September 1984 Requests Extension Until 851130 of Equipment Qualification Program Deadline,Per 10CFR50.49(g),due to Delays in Extensive Equipment Replacement Effort.Response Requested So Final Planning for Upcoming Outage Can Proceed Project stage: Other ML20098F0701984-09-26026 September 1984 Responds to 840917 Request for Addl Info Re 1984 Refueling Outage Insp Program for Stainless Steel Piping.Topics Addressed Include Sampling Plan,Qualification of Exam Personnel,Leak Detection & Leakage Limits Project stage: Request ML20098E9851984-09-26026 September 1984 Forwards New &/Or Revised Pages to 840724 Equipment Qualification Program Justifications for Continued Operation Transmittal.Revs Due to Changes in Qualification Status of Certain Equipment Project stage: Other ML20093E4431984-10-0404 October 1984 Resubmits List Updating & Combining Items in Equipment Qualification Program.Extension of Qualification Program Deadline to 851130 Requested Project stage: Other ML20106D1111984-10-19019 October 1984 Responds to 841012 Request for Addl Info Re Extension of Deadline for Equipment Qualification Until 851130 Project stage: Request ML20106E2851984-10-23023 October 1984 Forwards Corrections to 841019 Response to NRC Request for Addl Info Re Util Request for Schedular Relief from Certain Environ Qualification Requirements Project stage: Request ML20204G9481984-11-0202 November 1984 Forwards Response to NRC 841031 Request for Addl Info Re 840706 Request for Extension to Schedular Requirements of 10CFR50.49(g) for Certain Electrical Equipment Due to Test Complications & Procurement Lead Times Project stage: Request ML20099C4741984-11-12012 November 1984 Forwards Revised Reponse to Item 3 in 841102 Submittal of Addl Info Re Percentage of Contract Workers Accumulating Significant Overtime Hours During Unit 2 Equipment Qualification Program Project stage: Other ML20099C1481985-03-0404 March 1985 Forwards Response to Generic Ltr 84-24 Re Certification of Requirements of 10CFR50.49.Environ Qualification Plan Implemented.Equipment Either Fully Qualified or Justification for Continued Safe Operation Submitted Project stage: Other ML20100N1401985-04-0404 April 1985 Confirms That Surface Exam of Two Feedwater Nozzles Scheduled During Upcoming Maint/Refueling Outage,Per NUREG-0619.Justification for Reducing Number of Feedwater Nozzles Based on Sparger Configuration Project stage: Request ML20127P6851985-05-10010 May 1985 Responds to NRC 850404 Request for Addl Info Re Small Break LOCA Drywell Temp Profiles Used for Environ Qualification of Electrical Equipment.Curves & Rept Describing Methodology Used in Generating Curves,Transmitted w/ Project stage: Request 1983-05-06
[Table View] |
Similar Documents at Hatch |
|---|
|
Text
p Georgia Power Company 333 Pedrr.or t Avenue A'tanta, Ce>rg+a 30308 Telectone 404 526-6526 Ma+ng Address.
Post Ctfice Box 4545 Atlanta. Georg:a 30302 L
Georgia Power L T. Gucwa IN wuN " "1rc grem Manager Nuclear Engineering and Chief Nuclear Engfee' NED-84-334 ally 12, 1984 Director of Riclear Reactor Reg 21ation Attention: Mr. John F. Stolz, Chief Operatirg Reactors Branch No. 4 Division of Licensirg U. S. Riclear Reg 21atory Omnission Washirgton, D. C.
20555 NRC DOCKEP 50-366 OPERATING LICENSE NDF-5 EDNIN I. HA'ICH NUCLEAR PIANP LNIT 2 EQUIINENP QUALIFICATION PROGRAM DEADLINE EXTDEION REQUEST FOR RHR ISOLATION VALS ACIUATORS Gentlenen:
On March 50, 1984, Georgia Power Conpany (GPC) albnitted a report to the NRC (NED-84-161) - which cutlined the program for meeting the reg 2irements of 10 CFR 50.49 at Plant Hatch.
'Ihis report included a listirg of eglipment items at Hatch-2 (Encloaire 2, Table 2, Footnote A) which GPC believed might not be fully g2alifiable by the reg 21atory deadline (second refueling cutage after March 31, 1982.
Included in this list were the new Limitorgie SB-3-150 motorized operators purchased as envirorsnentally gjalified replacements for the motors on valves 2 Ell-F016A&B.
'Ibese new valve operators meet the gialification req 2irements of 10 CFR 50.49; however, they can not be installed at present since they would cause severe overstressing of the body flanges on the albject values diring a Design Basis Earthglake. All attenpts to resolve this seismic problem using refined analysis techniq2es have been unasccessful (see Attachment 2 for the analysis report).
GPC has also determined that there is no other conimercially available motorized operator which cculd meet the applicable performance specifications and the req 2irements of 10 CFR 50.49.
Therefore, the only remainirg course of action is replacement of the two affected valves.
A
\\
[)k 8407170373 840712 PDR ADOCK 05000366 P
PDR
m-GeorgiaPower A NED-84-334 ally 12,1984 Page Two GPC is expediting procurement of two new valves to replace the current 2 Ell-F016A&B valves which serve as cutboard containment isolation on the two Resicinal Heat Removal System Containment Spray Lines.
The items reg 2 ired are 16 inch, 300 lb., Class 2 globe valves.
GPC has attenpted to procure existing spare valves from other utilities and alpplyers (includiry those listed in Attachnent 1) without alccess.
01rrently, GPC estimates that the new valves could not be received at Plant Hatch before the end of 1984.
This is well beyond the gialification deadline date (end of the current Hatch-2 refueling / pipe-replacenent outage) which is currently projected to be near the end of ally 1984.
Conseglently, GPC hereby recpests an exemption from the autage based deadline specified in 10 CFR 50.49(g) for the motorized operators on valves 2 Ell-F016A&B at Plant Hatch Unit 2.
- However, GPC will make every practicable attenpt to meet the March 31, 1985, deadline date specified in that same regulation.
Sircerely yours, M
L. T. G1 cwa GS Encloaires xc:
J. T. Ihckham, Jr.
H. C. Nix, Jr.
J. P. O'Reilly (NRC-Region II)
Senior Resilent In@ector e
y-ATTACIDENT 1 NRC D00Tr 50-366 OPERATING LICENSE NPF-5 EDWIN I. HA'101 NUCLEAR PIANT UNIT 2 EQUIP!GNP QUALIFICATICN PROGRAM DEADLINE EXTHEION REQUEST FOR RIM ISOLATION VALVE AC'IUA"DRS Following unalccessful attenpts to obtain appropriate replacements for the 2 Ell-F016A&B valves from internal conpany sources, including the construction project for the Vogtle N.1 clear Plant, GPC contacted the following utilities and valve alppliers:
Tennessee Valley Authority Union Electric Conpany Mississippi Power & Light Company Washington RIDlic Power S2pply System Philadelphia Electric Canpany Houston Lighting & Power Conpany Dake Power Company Southern California Edison Arizona Riblic Service Company cincinnati Gas & Electric Conpany BJ:X Corporation valve Systems & Controls comapny Borg-Warner Fluid Controls Aloyco Division - Walworth Conpany i
Anchor /Darlirg Valve Company Atwood & Morrill Conpany, Inc.
Only the last two companies on this list are able to alpply valves which meet GPC's specifications.
Neither of these firms is able to deliver the valves prior to the end of 1984.