MONTHYEARML20217M8771999-10-25025 October 1999 Requests That Industry Studies on long-term Spent Fuel Pool Cooling Be Provided to R Dudley at Listed Mail Stop ML20217M4331999-10-19019 October 1999 Submits Rept 17, Requal Tracking Rept from Operator Tracking Sys. Rept Was Used by NRC to Schedule Requalification Exams for Operators & Record Requal Pass Dates ML20217F5841999-10-13013 October 1999 Requests Revocation of License OP-11038-1 for GE Kingsley. Individual Has Been Reassigned to Position within Naesco ML20217F5811999-10-13013 October 1999 Forwards Insp Data & Naesco Evaluation of a EDG Exhaust Insp Conducted on 990407.Insp Ensured That Unacceptable Wall Thinning Will Not Occur During 40-year Design Lifetime of Sys ML20217C7321999-10-0808 October 1999 Forwards Copy of Seabrook Station Videotape Entitled, Completion of Seal Barrier Installation. Videotape Documents Process of Selecting,Designing & Installing Seal Deterrent Barrier to Preclude Entrapment of Seals ML20217B8621999-10-0505 October 1999 Forwards Rev 28,change 1 to EPIP Er 1.1, Classification & Emergencies, Per 10CFR50.54(q).Rev to Procedure Does Not Decrease Effectiveness of Seabrook Station Radiological Emergency Plan ML20217B7471999-10-0101 October 1999 Provides Notification of Change in PCT of More than 50 F,Per Requirements of 10CFR50.46(a)(3)(i),(ii).Tabulation of Large Break LOCA PCT Margin Utilization Applicable to Seabrook Station,Encl ML20212J8271999-09-30030 September 1999 Informs of Completion of mid-cycle PPR of Seabrook Station. Staff Conducted Reviews for All Operating NPPs to Integrate Performance Info & to Plan for Insp Activities at Facility Over Next Six Months.Plant Issues Matrix & Insp Plan Encl ML20216J2381999-09-30030 September 1999 Responds to Re Enforcement Discretion for Nuclear Plants During Y2K Transition.Nrc Expects All Licensees to Operate Nuclear Facilities Safety IAW NRC Regulations & Requirements ML20216J2421999-09-30030 September 1999 Responds to Card Received in Aug 1999,providing Comments on NRC Interim Enforcement Policy Re Enforcement Discretion for Nuclear Plants During Y2K Transition.Informs That Naesc Reported Seabrook as Y2K Ready Prior to 990701 ML20216J2471999-09-30030 September 1999 Responds to Which Provided Comments on NRC Interim Enforcement Policy Re Enforcement Discretion for Nuclear Plants During Y2K Transition.Informs That Naesc Reported Seabrook as Y2K Ready Prior to 990701 ML20212K7921999-09-30030 September 1999 Confirms 990922 Telcon with J D'Antonio & T Grew Re Arrangements Made for NRC to Inspect Licensed Operator Requalification Program at Seabrook Facility ML20212J0301999-09-24024 September 1999 Forwards Insp Rept 50-443/99-10 on 990726-30 & 0809-13.No Violations Noted.Insp Discussed ML20212G5071999-09-21021 September 1999 Submits Complaint to NRC Re NRC Failure to Cite Seabrook Station NPP Operators for Failing to Periodically Calibrate & Establish Adequate Measures to Insure That Relay Equipment Met All Required Calibration Settings Prior to Installation ML20212C1881999-09-20020 September 1999 Ack Receipt of Which Raised Concerns Re NRC Enforcement Actions at Plant & Issuance of NCVs ML20212D1401999-09-17017 September 1999 Forwards SE Accepting Request to Use Proposed Alternative to Certain Weld Repair Requirements in ASME Boiling & Pressure Vessel Code ML20212B9511999-09-17017 September 1999 Forwards NRC Form 396 for MG Sketchley,License SOP-10685, Along with Supporting Medical Exam Info.Nrc Form 396 Has Been Superceded by Revised Version Dtd 971222,which Was Previously Submitted to NRC on 990812.Encl Withheld ML20212C3621999-09-15015 September 1999 Forwards Rev 34 to Seabrook Station Radiological Emergency Plan & Rev 85 to Seabrook Station Emergency Response Manual, Per 10CFR50,App E & 10CFR50.4 ML20212B5021999-09-14014 September 1999 Forwards Licensee Responses to EPA Questions Re Plant Seal Deterrent Barrier.Util Completed Installation of Subject Barriers on All Three Station Offshore Intake Structures on 990818.Barriers Will Preclude Entrapment of Seals ML20211Q8521999-09-0808 September 1999 Informs That Rl Couture,License SOP-11027,terminated Employment at Naesco on 990907.Revocation of License Requested ML20211N8781999-09-0303 September 1999 Forwards Response to 990820 RFI Re NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams ML20211J9291999-09-0303 September 1999 Forwards mark-ups & Retypes of Proposed Conforming License Changes Required in Connection with Transfers Being Sought in 990615 Application of Montaup Electric Co & New England Power Co for Transfer of Licenses & Ownership Interests ML20211M3221999-09-0202 September 1999 Responds to NRC Re Violations Noted in Insp of License NPF-86 & Proposed Imposition of Civil Penalty. Corrective Actions:Conducted Prompt Review of Layoff Decision to Determine Relevant Facts DD-99-10, Informs That Time Provided by NRC Regulation within Which Commission May Act to Review Director'S Decision (DD-99-10) Expired.Commission Declined Review & Decision Became Final on 990830.With Certificate of Svc.Served on 9909021999-09-0202 September 1999 Informs That Time Provided by NRC Regulation within Which Commission May Act to Review Director'S Decision (DD-99-10) Expired.Commission Declined Review & Decision Became Final on 990830.With Certificate of Svc.Served on 990902 ML20211J8811999-09-0101 September 1999 Forwards Comments on Seabrook Station Review of Reactor Vessel Integrity Database (Rvid)(Version 2).Minor Discrepancies Were Noted.Proposed Changes Are Encl in Order to Correct Discrepancies ML20211J8411999-09-0101 September 1999 Forwards Updated NRC Form 396 for E Decosta,Nrc License OP-10655-1.Without Encl ML20211G9191999-08-27027 August 1999 Informs NRC That Name of New Company, Ref in Order Approving Application Re Corporate Merger Is Nstar Which Is Massachusetts Business Trust ML20211J0401999-08-26026 August 1999 Responds to 990819 Request,On Behalf of Gr Pageau & Williams Power Corp,For Addl Time in Which to Reply to Nov,Issued on 990803.Response Due to NRC by 991008 ML20211H0651999-08-25025 August 1999 Forwards Insp Rept 50-443/99-05 on 990621-0801.One Violation Re Failure to Include Multiple Components within Scope of ISI Test Program Was Identified & Being Treated as NCV, Consistent with App C of Enforcement Policy ML20211G7761999-08-24024 August 1999 Expresses Great Concern Re Lack of Enforcement Actions Against Seabrook Station Despite Citations NRC Has Issued for Violations of Seabrook Operating License ML20211J2171999-08-23023 August 1999 Expresses Disappointment with Lack of Enforcement Action Against Seabrook Station Despite Repeated Safety Violations ML20211J4971999-08-21021 August 1999 Submits Comments Re Violations Cited in Early Mar & 990509 Insps ML20211H8361999-08-19019 August 1999 Submits Concerns Re Violations at Seabrook Station ML20211F2681999-08-19019 August 1999 Discusses Former Chairman Jackson & 990602 Predecisional Enforcement Conference Re Findings of Ofc of Investigations Involving Allegations Raised by Contract Electrician.Determined That Allegations Not Supported ML20211J3241999-08-15015 August 1999 Expresses Disappointment in Apparent Failure of NRC to Cite Seabrook Station NPP for Recent Violations of Safety Regulations Uncovered During Recent Insps in Mar & May ML20211J1831999-08-15015 August 1999 Submits Concerns Over Serious Deficiencies at Seabrook Station That NRC Has Declined to Take Enforcement Actions Against ML20210T1601999-08-13013 August 1999 Informs That as Result of Staff Review of Licensee Responses to GL 92-01,rev,supp1 1, Reactor Vessel Structural Integrity, NRC Revised Info in Reactor Vessel Integrity Database & Is Releasing It as Rvid Version 2 ML20211J2071999-08-13013 August 1999 Expresses Concerns Re Violations Occurring Recently at Seabrook Nuclear Power Station.Requests Effort to See That Measures Taken to Stop Flagrant,Continuing Violations That Hold Danger to Workers & Community ML20210S9611999-08-13013 August 1999 Informs That NRC Received Encl Ltr from Pb Johnston Expressing Concern About Certain Impacts on Shareholders of New England Electric Sys with Respect to Nees Proposed Merger with Natl Grid Group ML20210S9511999-08-13013 August 1999 Responds to to Collins Expressing Concerns with Certain Terms of Proposed Merger Between New England Electric Sys & National Grid Group.Nrc Has No Authority to Interject Itself in Nees Merger with National Grid Group ML20210S2001999-08-12012 August 1999 Forwards NRC Forms 398 & 396 in Support of Applications for Renewal of Operator Licenses for Individuals Listed Below. Without Encls ML20210R8401999-08-11011 August 1999 Forwards Response to NRC Second RAI Re GL 95-07, Pressure Locking & Thermal Binding of SR Power-Operated Gate Valves ML20210S7331999-08-11011 August 1999 Submits Third Suppl to 980423 Application to Renew NPDES Permit NH0020338 for Seabrook Station.Suppl Provides Addl Info on Input Streams & Requests Increased Permit Limit for Chemical Used in Makeup Water Treatment Sys ML20210R9581999-08-11011 August 1999 Forwards ISI Exam Rept of Seabrook Station, for RFO 6, Period 3,for Insps Conducted Prior to & During Sixth Refueling Outage Concluded on 990510 ML20210Q7441999-08-11011 August 1999 Forwards Order Approving Indirect Transfer of Control of Canal Interest in Seabrook Station Unit 1 as Requested in Application & SER ML20210R7931999-08-10010 August 1999 Forwards Cycle 7 Startup Rept for Seabrook Station, IAW Requirements of TS 6.8.1.1 ML20210N9421999-08-0505 August 1999 Informs That North Atlantic Suggests Listed Revisions to 990730 Draft Revisions to Committee Rept & Order.Further Revs Consistent with What North Atlantic Proposed at 990608 Hearing ML20210N5721999-08-0303 August 1999 Discusses Investigations Rept 1-98-005 Conducted by OI at Naesco,Seabrook Station & Forwards NOV & Proposed Imposition of Civil Penalty - $55,000.Violation Re Failure to Promptly Correct Incorrectly Terminated Cables of Control Bldg Air ML20210P3361999-08-0303 August 1999 Discusses Investigation Rept 1-98-005 Conducted by Region I OI at Naesco,Seabrook Station & Forwards Nov.Violations Re Electrical Wiring in Control Panel for Control Bldg Air Conditioning Sys ML20210P3161999-08-0303 August 1999 Discusses Investigation Rept 1-98-005,conducted Between 980129 & 0527 at Seabrook Station & Forwards Nov.Violation Re Discrimination of Williams Power Corp,Contractor of Naesco,Against Electrician for Raising Safety Issues 1999-09-08
[Table view] Category:INCOMING CORRESPONDENCE
MONTHYEARML20217F5841999-10-13013 October 1999 Requests Revocation of License OP-11038-1 for GE Kingsley. Individual Has Been Reassigned to Position within Naesco ML20217F5811999-10-13013 October 1999 Forwards Insp Data & Naesco Evaluation of a EDG Exhaust Insp Conducted on 990407.Insp Ensured That Unacceptable Wall Thinning Will Not Occur During 40-year Design Lifetime of Sys ML20217B8621999-10-0505 October 1999 Forwards Rev 28,change 1 to EPIP Er 1.1, Classification & Emergencies, Per 10CFR50.54(q).Rev to Procedure Does Not Decrease Effectiveness of Seabrook Station Radiological Emergency Plan ML20217B7471999-10-0101 October 1999 Provides Notification of Change in PCT of More than 50 F,Per Requirements of 10CFR50.46(a)(3)(i),(ii).Tabulation of Large Break LOCA PCT Margin Utilization Applicable to Seabrook Station,Encl ML20212G5071999-09-21021 September 1999 Submits Complaint to NRC Re NRC Failure to Cite Seabrook Station NPP Operators for Failing to Periodically Calibrate & Establish Adequate Measures to Insure That Relay Equipment Met All Required Calibration Settings Prior to Installation ML20212B9511999-09-17017 September 1999 Forwards NRC Form 396 for MG Sketchley,License SOP-10685, Along with Supporting Medical Exam Info.Nrc Form 396 Has Been Superceded by Revised Version Dtd 971222,which Was Previously Submitted to NRC on 990812.Encl Withheld ML20212C3621999-09-15015 September 1999 Forwards Rev 34 to Seabrook Station Radiological Emergency Plan & Rev 85 to Seabrook Station Emergency Response Manual, Per 10CFR50,App E & 10CFR50.4 ML20211Q8521999-09-0808 September 1999 Informs That Rl Couture,License SOP-11027,terminated Employment at Naesco on 990907.Revocation of License Requested ML20211N8781999-09-0303 September 1999 Forwards Response to 990820 RFI Re NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams ML20211J9291999-09-0303 September 1999 Forwards mark-ups & Retypes of Proposed Conforming License Changes Required in Connection with Transfers Being Sought in 990615 Application of Montaup Electric Co & New England Power Co for Transfer of Licenses & Ownership Interests ML20211M3221999-09-0202 September 1999 Responds to NRC Re Violations Noted in Insp of License NPF-86 & Proposed Imposition of Civil Penalty. Corrective Actions:Conducted Prompt Review of Layoff Decision to Determine Relevant Facts ML20211J8411999-09-0101 September 1999 Forwards Updated NRC Form 396 for E Decosta,Nrc License OP-10655-1.Without Encl ML20211J8811999-09-0101 September 1999 Forwards Comments on Seabrook Station Review of Reactor Vessel Integrity Database (Rvid)(Version 2).Minor Discrepancies Were Noted.Proposed Changes Are Encl in Order to Correct Discrepancies ML20211G9191999-08-27027 August 1999 Informs NRC That Name of New Company, Ref in Order Approving Application Re Corporate Merger Is Nstar Which Is Massachusetts Business Trust ML20211G7761999-08-24024 August 1999 Expresses Great Concern Re Lack of Enforcement Actions Against Seabrook Station Despite Citations NRC Has Issued for Violations of Seabrook Operating License ML20211J2171999-08-23023 August 1999 Expresses Disappointment with Lack of Enforcement Action Against Seabrook Station Despite Repeated Safety Violations ML20211J4971999-08-21021 August 1999 Submits Comments Re Violations Cited in Early Mar & 990509 Insps ML20211H8361999-08-19019 August 1999 Submits Concerns Re Violations at Seabrook Station ML20211J3241999-08-15015 August 1999 Expresses Disappointment in Apparent Failure of NRC to Cite Seabrook Station NPP for Recent Violations of Safety Regulations Uncovered During Recent Insps in Mar & May ML20211J1831999-08-15015 August 1999 Submits Concerns Over Serious Deficiencies at Seabrook Station That NRC Has Declined to Take Enforcement Actions Against ML20211J2071999-08-13013 August 1999 Expresses Concerns Re Violations Occurring Recently at Seabrook Nuclear Power Station.Requests Effort to See That Measures Taken to Stop Flagrant,Continuing Violations That Hold Danger to Workers & Community ML20210S2001999-08-12012 August 1999 Forwards NRC Forms 398 & 396 in Support of Applications for Renewal of Operator Licenses for Individuals Listed Below. Without Encls ML20210R8401999-08-11011 August 1999 Forwards Response to NRC Second RAI Re GL 95-07, Pressure Locking & Thermal Binding of SR Power-Operated Gate Valves ML20210R9581999-08-11011 August 1999 Forwards ISI Exam Rept of Seabrook Station, for RFO 6, Period 3,for Insps Conducted Prior to & During Sixth Refueling Outage Concluded on 990510 ML20210R7931999-08-10010 August 1999 Forwards Cycle 7 Startup Rept for Seabrook Station, IAW Requirements of TS 6.8.1.1 ML20210K3281999-07-30030 July 1999 Forwards Response to NRC RAI Re License Amend Request 98-17. North Atlantic Concurs with Staff That Bases Should State That Maintaining ECCS Piping Full of Water from RWST to Reactor Coolant Sys Ensures Sys Will Perform Properly ML20210H8991999-07-27027 July 1999 Forwards Tabulation of Current LBLOCA & SBLOCA Peak Clad Temp Margin Utilization Tables Applicable to Seabrook Station ML20210H0921999-07-27027 July 1999 Forwards Naesc Semi-Annual Fitness-for-Duty Rept,Jan-June 1999, Per 10CFR26.71(d).Rept Includes Data from 990101- 0610 ML20210S9911999-07-18018 July 1999 Requests NRC Intervene for All Shareholders of New England Electric System & to Help with Merger with National Grid Group & That NRC Petition Security & Exchange Commission to Investigate Matter Relative to No Shareholder Options ML20210A2521999-07-15015 July 1999 Forwards Rev 33 to Seabrook Station Radiological Emergency Plan & Rev 84 to Seabrook Station Emergency Response Manual ML20209J0601999-07-14014 July 1999 Forwards Rev 11 to Vols 1-10 of State of Nh Radiological Emergency Response Plan & Vols 11-50 to Town Radiological Emergency Response Plans,In Support of Vermont Yankee & Seabrook Station.Vols 17-19 of Were Not Included ML20209G1351999-07-0909 July 1999 Forwards Relief Request Re Repair Welding on SA-351 Matl to Be Installed in Seabrook Station SW Pumps & SW Cooling Tower Pumps ML20209D2871999-07-0606 July 1999 Submits Response to NRC AL 99-02,re Numerical Estimate of Licensing Actions Expected to Be Submitted in Fy 2000 & 2001.Schedule Does Not Include Activities Which Meet AL Definition of Complex Review ML20209C9021999-06-30030 June 1999 Provides Revised Distribution List for Seabrook Station Correspondence to Reflect Current Organization ML20196G2391999-06-23023 June 1999 Responds to GL 98-01,Suppl 1, Y2K Readiness of Computer Sys at Nuclear Power Plants. Y2K Readiness Disclosure for Plant Encl ML20196G3381999-06-23023 June 1999 Forwards LAR 99-19 for License NPF-86,increasing AOT for Cracs from 30 Days to 60 Days on One Time Basis for Each Train to Facilitate on-line Implementation of Design Enhancements During Current Operating Cycle ML20195J0981999-06-17017 June 1999 Forwards Responses to Questions Posed in Re Application of New England Power Co for Transfer of Control of Licenses NPF-49 & NPF-86.Copy of 1998 Schedule 13G, Included,As Requested ML20196D0561999-06-16016 June 1999 Forwards Certified Copy of Endorsements 77 & 78 to Nelia to Policy NF-0296 ML20195H1741999-06-15015 June 1999 Forwards Original & Copy of Request for Approval of Certain Indirect & Direct Transfer of License & Ownership Interests of Montaup Electric Co (Montaup) with Respect to Nuclear Facilities Described as Listed ML20195J1221999-06-15015 June 1999 Forwards Addl Clarifying Info to Suppl Info Provided at 990602 Predecisional Enforcement Conference at Region I. Proprietary Declarations by Util Employees to Correct Inaccuracies Encl.Proprietary Info Withheld,Per 10CFR2.790 ML20210K4971999-06-15015 June 1999 Forwards Copy of Ltr from Concerned Constitutent AC Menninger from Franconia,Nh to Senator Smith Re Seabrook Nuclear Power Station Y2K Readiness ML20195E9731999-06-0707 June 1999 Forwards Rev 32 to Seabrook Station Radiological Emergency Plan & Rev 83 to Emergency Response Manual ML20206T4201999-05-20020 May 1999 Forwards Certified Copies of Resolution Adopted by Shareholders of National Grid Group Approving Acquisition of New England Electric Sys & Vote of New England Electric Sys Shareholders Approving Merger with National Grid Group ML20196L2001999-05-0707 May 1999 Forwards Rev 01-07-00 to RE-21, Cycle 7 COLR, Per TS 6.8.1.6.c ML20206K4301999-05-0707 May 1999 Forwards Copy of Corrective Order of Notice by State of Nh Nuclear Decommissioning Financing Committee ML20206J3321999-05-0505 May 1999 Forwards Tabulation of Number of Tubes Plugged in Each of Two SGs Inspected During Sixth Isi,Per Plant TS SR 4.4.5.5a. Sixth ISI Was Completed on 990420 ML20206J3341999-05-0505 May 1999 Informs That on 990501,ISO New England & New England Power Pool Implemented Restructured Wholesale Electricity Market. Summary of Util Action as Result of Implementation of Subject Market,Encl ML20206J2801999-04-30030 April 1999 Forwards 1998 Annual Financial Repts for CT Light & Power Co,Western Ma Electric Co,Public Svc Co of Nh,North Atlantic Energy Corp,Northeast Nuclear Energy Co & North Atlantic Energy Svc Corp,License Holders ML20206G4371999-04-30030 April 1999 Forwards 1998 Annual Environ Operating Rept for Seabrook Station.Encl Rept Is Summary of Implementation of EPP for Period of Jan-Dec 1998 ML20206H4801999-04-30030 April 1999 Forwards 1998 Annual Radioactive Effluent Release Rept for Seabrook Station. Listed Info Provided in Encls 1999-09-08
[Table view] Category:UTILITY TO NRC
MONTHYEARML20059K5221990-09-14014 September 1990 Responds to NRC Re Violations Noted in Insp Rept 50-443/90-15.Corrective Actions:Procedure ON1090.04 Revised to Require That Whenever Containment Entry Made,Entry Logged in Action Statement Status Log ML20059K5951990-09-14014 September 1990 Forwards Endorsement 29 to Nelia Policy NF-296,Endorsement 22 to Maelu Policy MF-127,Endorsement 9 to Nelia Policy N-109 & Maelu Policy M-109 ML20059K1051990-09-13013 September 1990 Advises of 1990 Biennial Exercise Meeting Scheduled for 900928 at Facility to Discuss Comments Re objectives/extent- of-play Submittal & Present Operational & Radiological Details of Scenario.Suggested Agenda Encl ML20059D6971990-08-30030 August 1990 Forwards 10CFR50.59 Quarterly Rept for Apr-June 1990 ML20064A4001990-08-21021 August 1990 Forwards, New Hampshire Yankee Fitness-For-Duty Semiannual Rept,900103-0630 ML20059B0231990-08-21021 August 1990 Forwards Addl Info Re Topics Discussed on 900816 Concerning Licensees Response to Intervenors Emergency Motion to Reopen Record on Adequacy of Staffing of New Hampshire Radiological Emergency Response Plan & Immediate Shutdown ML17348B4921990-08-15015 August 1990 Forwards Revised Evacuation Time Estimates Incorporating Vehicles Hidden from Aerial Observation,Per ALAB-932 & ASLB Memorandum & Order LBP-90-20.Revised Estimates Will Be Incorporated Into Radiological Emergency Response Plan ML20059A3051990-08-14014 August 1990 Informs of Closing on United Illuminating Co Sale & Leaseback Transaction on 900809,per Amend 1 to License. Transaction Conforms to Description in Amend Application, ,as Supplemented by 900426 & 0606 Ltrs ML20058L9571990-08-0303 August 1990 Forwards Rev 1 to Inservice Testing Program for Pumps & Valves,Adding Cold Shutdown Justification ML20058M2211990-08-0303 August 1990 Notifies of Change in Listed Licensed Operator Position. MR Breault Will Continue to Maintain Senior Operator License in New Position Until 900917 ML20055J4751990-07-26026 July 1990 Confirms That Util Completed Installation & Testing of Facility ATWS Mitigation Sys,Per 890706 Commitment ML20055J0271990-07-24024 July 1990 Forwards Rev 5 to Facility Security Training & Qualification Plan.Rev Withheld (Ref 10CFR73.21) ML20055H5831990-07-20020 July 1990 Forwards Rev 11 to Physical Security Plan.Rev Withheld (Ref 10CFR73.21) ML20044B1861990-07-10010 July 1990 Forwards Rev 1.B to Spmc,App H,New Hampshire Yankee Offsite Response Communications Directory & Spmc,App M,New Hampshire Yankee Offsite Response Emergency Resource Manual. ML20044A6631990-06-25025 June 1990 Responds to NRC 900524 Ltr Re Violations Noted in Insp Rept 50-443/90-10.Corrective Actions:Maint Group Instruction Issued Describing Valve Verification When Valves Not Covered by Procedure & Procedures Written Re Monitoring Skids ML20044A3741990-06-22022 June 1990 Notifies That United Illuminating Co Received Approval of State of CT Dept of Public Util Control of Sale & Leaseback of Facility ML20043H1321990-06-18018 June 1990 Forwards New Hampshire Yankee Power Ascension Assessment Self-Assessment Team Phase 2 50% Power Plateau. ML20043G4761990-06-11011 June 1990 Lists Changes in Status of Licensed Operator Positions at Facility,Per 10CFR50.74 ML20043F5791990-06-0808 June 1990 Requests That Meeting W/Nrc & Westinghouse Be Held During Wk of 900624 to Further Discuss Intended Cycle 2 Fuel Design Features & Fuel Mgt Strategies ML20043E9811990-06-0606 June 1990 Forwards Info on Owner Participation & Owner Trustee in United Illuminating Co Sale/Leaseback Transaction, Consisting of Sec Form 10K & Citicorp 1989 Annual Rept. ML20043E5371990-06-0606 June 1990 Responds to NRC 900508 Ltr Re Violations Noted in Insp Rept 50-443/90-08.Corrective Actions:Signs Will Be Placed on Containment Hatches to Remind Personnel That Retest Required After Containment Hatch Use & to Notify Control Room ML20043C5251990-05-31031 May 1990 Responds to NRC Bulletin 88-010,Suppl 1, Nonconforming Molded Case Circuit Breakers. Util Verified That Certificates of Conformance Issued by Telemecanique for All 305 Telemecanique-supplied Molded Case Circuit Breakers ML20043B7291990-05-24024 May 1990 Forwards Employee Allegation Resolution Program Radio Communication Transcript Review. Transmissions Did Not Contain Issues of Detrimental Safety Significance to Public or Plant Personnel ML20043C1031990-05-23023 May 1990 Forwards Revs 53 & 54 to Production Emergency Response Manual. ML20043F7071990-05-18018 May 1990 Forwards Addl Info Re Status of Licensee Actions in Response to INPO Evaluation Repts of Facility for 1983-1989,including Update of Response to INPO Rept of 1983 Const Project Evaluation & Evaluation of Seabrook Station Const Project. ML20042G2511990-05-0808 May 1990 Forwards Estimates of Time Impact on Facility Personnel Re Topics Identified in Generic Ltr 90-01.Info Presented in Format of Completed Questionnaire Sheets ML20042G6501990-05-0808 May 1990 Forwards Rev 10 to Physical Security Plan.Rev Withheld (Ref 10CFR73.21) ML20042F7471990-05-0404 May 1990 Informs of 900430 Election of Le Maglathlin to Replace Jc Duffett as President & Chief Executive Officer ML20042E8371990-04-30030 April 1990 Forwards Annual Environ Operating Rept 1989, Seabrook Environ Studies 1988,Characterization of Baseline Conditions in Hampton-Seabrook Area,1975-1988,Preoperational Study for Seabrook Station & Seabrook Environ Studies... Rept. ML20012E9991990-03-30030 March 1990 Suppls Info to 890417 Submittal on Station Blackout Rule (10CFR50.63).Instrumentation Required to Cope W/Station Blackout Is safety-related & Evaluated for Operability at Elevated Temps ML20012E9881990-03-30030 March 1990 Forwards marked-up FSAR Section 13.2 (Training) Descriptive Enhancements,Per 891113 Commitment.Rev Will Be Included in 900415 FSAR ML20042D8251990-03-30030 March 1990 Requests NRC Participation at 900405 Working Session to Discuss Objectives & Extent of Play for 1990 Biennial Emergency Preparedness Exercise on 901213.Encl Withheld ML20012F0341990-03-30030 March 1990 Forwards Suppl to, Semiannual Radioactive Release Rept Initial Plant Startup Through Fourth Quarter 1989, Consisting of Dose Calculations ML20012E8751990-03-29029 March 1990 Advises That Replacement of Rosemount Transmitter from High Failure Fraction Mfg Lot Completed on 900314,per 900312 Commitment ML20012D9181990-03-21021 March 1990 Forwards Executed Amend 4 to Indemnity Agreement B-106 & Opinion Ltr from Ropes & Gray Re Signature Authority of Util as Agent for Joint Owners of Plant ML20012D9681990-03-20020 March 1990 Discusses Steam Generator Overfill Protection,Per Generic Ltr 89-19 & USI A-47, Safety Implications of Control Sys in LWR Nuclear Power Plants. Steam Generator Overfill Protection at Plant Meets Recommendations of Generic Ltr ML19324G6791990-03-15015 March 1990 Provides Info in Response to late-filed Allegations,Per 900314 Telcon ML20012B8601990-03-14014 March 1990 Clarifies 900312 Supplemental Response to Proposed Draft NRC Bulletin on Loss of Fill Oil in Rosemount Transmitters. If More Frequent Calibr Required,Transmitter Will Be Time Response Tested to Operability Acceptance Criteria ML20012B8351990-03-13013 March 1990 Notifies That Senior Operator License No Longer Required for PD Mccabe & License Considered Expired ML20012B8371990-03-13013 March 1990 Clarifies Supplemental Response to Proposed Draft NRC Bulletin on Loss of Fill Oil in Rosemount Transmitters,Per 900313 Telcon.Operability Acceptance Test Will Be Performed ML20012B6191990-03-12012 March 1990 Advises That Licensee Intends to Submit FSAR Amend 63 by 900415 Instead of 900315 ML20012B4901990-03-0808 March 1990 Forwards Corrected Response Re Allegation by Employees Legal Project Concerning Reactor Coolant Pump Support Leg Anchor Bolts ML20012B1191990-03-0707 March 1990 Responds to NRC 900205 Ltr Re Violations Noted in Insp Rept 50-443/89-17.Corrective Actions:Conduit Seals Installed on Required Solenoids & Operability Completed on 900204 ML20012C2521990-03-0606 March 1990 Documents Info Provided in Telcon Re Relief & Safety Valve Testing ML20012B3631990-03-0202 March 1990 Forwards Secondary Chemistry Annual Rept, for 1989.Rept Summarizes & Evaluates 1989 Condensate,Feedwater & Steam Generator Water Chemistry Operating Experience & Repts Total Time Secondary Water Chemistry Parameters Out of Spec ML20012A1581990-03-0101 March 1990 Submits Annual Rept of Challenges to Pressurizer PORVs & Safety Valves for Initial Criticality Period Through 891231 ML20012A1861990-03-0101 March 1990 Forwards Seabrook Station 10CFR50.59 Safety Evaluation Quarterly Rept,Oct-Dec 1989. Power Supply Breakers for Containment Lighting Panel XL4 Replaced & Smoke Detector Insp Frequency Changed to at Least Semiannually ML20012A1011990-02-26026 February 1990 Responds to Info Notice 89-045, Metalclad Low-Voltage Power Circuit Breakers Refurbished W/Substandard Parts. One molded-case Circuit Breaker Purchased from Satin American in Nov 1989 for Use in Plant Simulator ML20006F5401990-02-23023 February 1990 Submits Addl Info Re Util Maint Program,Per NRC 900221 Telcon Request.Util Maint Program Includes Preventive, Predictive & Corrective Maint as Well as Implementation of Design Enhancements ML20006G1571990-02-21021 February 1990 Forwards Renewal Application for NPDES Permit NH0020338,per App B to License NPF-67.State of Nh EPA Determined That Requested Changes to Discharges 001,022,023 & 024 Will Not Jeopardize Environ When Full Power Operation Begins 1990-09-14
[Table view] |
Text
'
. o.
SEABROM STATION
PUBLIC SEAVICE Engineering Office:
Companyc' Wew Hampshre 1671 Worcester Road Framingham, Mossochusetts 01701 (617) - 872- 8100 June 23, 1982 SBN- 284 T. F. B7.1.2 United States Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, PA 19406 Attention: Richard W. Starostecki, Director Division of Resident and Project Inspection
References:
(a) Construction Permit CPPR-135 and CPPR-136, Docket Numbers 50-443 and 50-444.
(b) L'SNRC Letter, dated May 26, 1982, " Combined Inspection Numbers 50-443/82-03 and 50-444/82-03" R. W. Starostecki to W. C. Tallman.
Subject:
RESPONSE TO INSPECTION NUMBERS 50-443/82-03 and 50-444/82-03
Dear Sir:
In response to the violations which you reported in Reference (b), PSNH offers the following:
Violation 1:
10 CFR 50, Appendix B, Criterion X and the Seabrook Station PSAR require that a program for inspection of activities affecting quality be established. The Seabrook Station FSAR endorses USNRC Regulatory Guide 1.30 (Revision 0) and requires that safety-related systems comply with IEEE-3 36-19 71, which itself includes raceways as part of Class 1E systems requiring an inspection program to verify physical integrity.
Contrary to the above, as of March 28, 1982, no program of inspection to verify the physical integrity of installed Class IE cable tray (a raceway) had been established. Defects were located in installed tray without evidence that they would have been identified by the licensee program, since no site inspection criteria exist for the documentation and resolution of such deficiencies.
A. Response:
We do not concur that the aforementioned item of violation is correct as stated; however, we recognize that at the time of the inspection, we were remiss in not fully outlining the scope of our cable tray inspection program.
8209090145 820027 PDR ADOCK 05000443 G PDR J
. e United Nuclear Regulatory Commisalon - June 23, 1982 At'tention: Richard W. Starostecki, Director Page2 The following chronology of actions taken and requirements imposed from the initiation of design to the point of installation inspection is offered in support of our contention that an adequate quality assurance program exists and has been in existence prior to acceptance and af ter installation.
- 1. On October 4, 1974, at the then AEC offices in Bethesda, Maryland, UE&C met with your Messrs. T. A. Ippolito and C. Miller to discuss certain generic problems with respect to regulatory requirements.
The AEC stated that the regulatory requirement is that the cables should remain functional after a design basis seismic event, irrespective of what may eventually happen to the tray. If only the tray supports are seismically qualified, then an analysis should be presented to verify that the cables will remain functional after a seismic event. Such an analysis should include actual test data to show that the cable supported at the supports will remain functional, for the worst possible conditions, after a seismic event and a LOCA. Aspects such as the cable loadings due to maximum expected sag, etc. should be considered. Also, the analysis should include considerations of non-seismic trays falling on Class IE circuits, and equipment. No two events occurring at the same time need be considered in such an analysis. Such analysis may be presented in the form of topical reports covering a range of plants whereby the need to repeat the analysis on each job may be eliminated.
The AEC statement, which was made at the meeting, "there is no regulatory requirement that the cables be supported in a tray
- 2. The UE6C cable tray Specification (Spec. No. 9763-006-109-1) was written for commercial grade cable tray with the exception that the tray must meet a static biaxial load test (Appendix E of the Specification). The cable tray seller (Metal Products Corporation) submitted a proposal including an offer to UE6C to witness the static load test. The static tests were perf ormed on or about September 1977 on ladder type cable tray, similar to the proposed Seabrook cable tray. These tests were witnessed by UE6C. The results of these tests (Proposal Data) proved that the vertical and the transverse design loads were less than sixty percent (60%) of the test vertical and transverse allowable load ifmits. Metal Products Corporation (M-P) was therefore awarded the contract to furnish Seabrook cable trays.
l The specification imposed UE&C's Quality Assurance Administrative and System Fequirements Document No. 9763-QAS-2. This document l
provides requirements for the Quality Assurance / Control program to be maintained by the vendors supplying Non-Nuclear Safety / Class
! (NNS) items and services.
l l
United Nuclear Regulatory Commission ,
- June 23, 1982 Attention: Richard W. Starostecki, Director Page3
- 3. On or about May 1978, Metal Products Corporation conducted static biaxial tests on the. ladder type and the corrugated bottom (solid) type cable trays, similar to the proposed Seabrook cable tray. This series of tests was witnessed by UE6C. The results of these tests proved that the vertical and the transverse design loads for the ladder type cable tray were equal to or less than the allowable load limits. Metal Products Corporation was then released for procurement of material in June 1978, and for fabrication of cable trays in August 1978.
On or about December 1978, Metal Products Corporation of fered a trailer load of the ladder type cable tray, destined for Seabrook Station, Seabrook, New Hampshire. UE6C visited the M-P factory site and selected one (1) twelve-foot (12 ft.) straight section from the trailer for production run cable tray tests. The results of these tests were considered acceptable by UE6C's Mechanical Analysis Group.
- 4. On or about February 1979, material was received in damaged condition at the construction site, and was responded to indirectly by memorandum from M-P Corporation local sales office to M-P Corporation home office (Copy on file - UE6C). Approximately 181 pieces of cable tray items were set aside for ultimate return to Metal Products Corporation.
On or about June 1979, Fischbach-Boulos-Manzi, NH (FEM) (Seabrook Electrical Installation Contractor) refused to accept cable tray materials that UE6C Material Departrent had received and accepted.
FBM cited a list of discrepancies (NCR-FBM-004, 6/11/79) and recommended replacement by M-P Corporation. The seller, M-P Corporation, came to Seabrook and inspected all cable tray material.
Material accepted by this inspection was reinspected by UE6C Materials Receiving and ultimately used. From this group of accepted material, M-P Corporation offered to retest sections of cable tray that were randomly selected by UE6C. On or about September 1980, UE6C visited M-P Corporation factory for the purpose of witnessing cable tray test on the job-site returned material (10 foot supports). UE6C representatives selected a corrugated bottom (solid bottom) cable tray from six (6) sections returned (3 ea. -
ladder 6 3 ea. - solid) for the ten (10) foot support test. The results of this test was considered acceptable by UE6C Mechanical Analysis Group. UE6C witnessed an additional optional test (12-foot supports) on new material. The results are recorded and calculated on calculation set number 9763-C-EE-IE-04-F, Revision 1.
The conclusions, Sheet #15, are that the twelve (12) foot support span, fully loaded cable tray, meets the requirements of Spec.
No. 9763-006-109-1, Rev. 2, Appendix C.
- 5. M-P Corporation recognized the workranship and galvanizing problems.
Due to the workmanship and galvanizing problems, UE6C/YAEC reviewed Metal Products' Quality Control Program for manufacturing and for
United Nuclear Pegulatory Commission ,
June 23,1982
. Attention: Richard W. Starostecki, D'irector Page4 hot dip galvanizing at the vendors facilities. This includes procedure review and implementation at the vendor work stations.
Recommendations to M-P were made and implemented (UE6C Notes of Conference E-91).
As a result of this review / inspection at the vendor facilities the UE&C Vendor Surveillance Check Plan was revised, and vendor surveillances at M-P were scheduled.
- 6. Please note that all of the above actions occurred prior to the installation of the cable tray.
We submit that all identified workmanship deficiencies were addressed, and adequate and reasonable actions were taken to correct and control the deficiencies.
B. Action Taken To Evaluate NRC Notice of Violation
- 1. A team consisting of three YAEC and one UE6C QA personnel chose three separate areas in Category I buildings to conduct an inspection on installed cable trays. The inspection points are the ones listed in the Vendor Surveillance Check Plan. The results of the inspection are summarized as follows:
- a. Electrical "B" Train Tunnel - elevation - 15' . 18 trays inspected - 7 deficiencies.
- b. Cable Spreading Room - elevation 50' . 9 trays inspected - 5 deficiencies.
- c. PAB - elevation 30' 8". 16 trays inspected - 7 deficiencies.
Total of 43 trays inspected, total of 19 deficiencies noted.
NOTE: The standard length of ladder type cable tray is 12 feet long containing 16 rungs. Each rung has four weld areas that requires 4 inspection points at each area for a total of 16 inspection points per rung. As there are 16 rungs per 12 foot standard tray length, this totals 256 inspection points for the rungs. In addition, there are 3 general inspection criteria for the overall cable tray, 259 inspection points per 12-foot standard section of ladder type cable tray.
i Translated to the 43 trays that were inspected there were 11,137 l possible areas for deficiencies to occur with only 19 deficiencies 4
found by the inspection team.
- 2. The YAEC Electrical and Mechanical Engineering Group were requested to evaluate the results of the team inspection.
l Engineering elected to reinspect the same areas that the team had i inspected plus one additional area that they randomly selected.
Based upon the reinspection, Engineering determined that the trays, as installed, will fulfill the requirements expected of the trays.
l t
l l
l l
L
United Nuclear Regulatory Commission June 23, 1982 Attention: Richard W. Starostecki, Director Page5 The structural integrity of the trays is also considered to be adequate; however , additional evaluation of UE&C's analysis will be performed by YAEC Engineering to substantiate this position. The re-evaluation will be completed by July 30, 1982.
C. Inspection Program
- 1. UE&C's Seabrook Site QA Department does receiving inspection to their Vendor Surveillance Check Plan Section C.
- 2. FBM (the installing contractor) performs installation inspection per their procedure QCP-503. Two attributes of the inspection check list entitled Final Inspection do address some of the same inspection points as found on UE&C's Vendor Surveillance Check Plan; namely:
- a. Tray is free of burrs and sharp edges.
- b. Field cuts , holes , and damaged areas of tray have been coated with galvanized dressing.
In addition, FBM stated that while performing (a) and (b) above ,
they do report broken, cracked or loose welds.
D. Conclusion
- 1. We feel that the history of the action taken prior to the installation of cable tray must be considered when evaluating quality of the cable tray installed at the Seabrook Station. It demonstrates the recognition given to the initial tray deliverers, workmanship problems, and the action taken to adequately correct these problems.
- 2. The evaluation of YAEC Engineering demonstrates that the type and number of the deficiencies in the installed tray does not compromise the integrity of the cable tray system, nor do they endanger the cable during or af ter cable installation.
- 3. We submit that the UE&C receiving inspection and the contractor's (FBM) installation inspection program (QCP-503) is in fact an adequate inspection program for installed cable tray verification in line with IEEE-336 commitments.
Violation 2:
10CFR50, Appendix B, Criterion X and the Seabrook Station PSAR require that conformance to drawing details of activities affecting quality be verified by inspection of those activities. Details for the proper erection of a pipe support (833-SG-6) and conduit supports (e.g.: 4214) are provided in the following documents, respectively:
4
w
, United Nuclear Regulatory Commission June 23, 1982 At t,entio n : Richard W. Starostecki, Director' Page6
- 1. Pullman Hanger Drawing 833-SC-06 (Revision 3A)
- 2. UE&C Engineering Change Authorization 03/1067F, sketch of surface mounted strut details Contrary to the above, as of April 28, 1982, QC inspection of pipe support 833-SG-6 had failed to identify several items (e.g.: weld length, member location and configuration, modification details) in nonconformance with the hanger drawing. QC inspection of several conduit supports (e.g.: 4244) typified by ECA 03-1067F had failed to identify the installation of nonconforming washers causing a visible deformation in part of the detailed strut connections.
This is a Severity Level IV Violation (Supplement II) applicable to Docket No. 50-443.
A. Response:
Corrective Action Taken and Results Achieved As a result of the reinspection of support 833-SG-6, the installation contractor (Pullman-Higgins) initiated NCR No. 2209 which has been submitted to UE6C Engineering for disposition. The NCR also includes the actions proposed by Pullman-Higgins to prevent recurrence of situations of this type. UE6C expects to render disposition on the hardware errors and the proposed corrective action by June 30, 1982. YAEC will keep the NRC Site Inspector informed of the results of the UE&C review.
Fischbach-Boulos-Manzi, NH (FBM) has reinspected for installation of incorrect washers, resulting in the initiation of six (6) nonconformance re por t s . To prevent recurrence of this situation, FBM has retrained construction and QC personnel regarding washer requirements. In addition, ECA 03-1168A has been issued, revising the Bill of Material, specifying that 33 CL washers are to be used. It is expected that the required repairs will be completed by September 15, 1982.
Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY
'l'/
W. P ohnson $ ()1 Vice President COMMONWEALTH OF MASSACHUSETTS)
)ss MIDDLESEX COUNTY )
Then personally appeared before me, W. P. Johnson, who, being duly sworn, "did state that he is a Vice President of Yankee Atomic Electric Company, that he is duly authorized to execute and file the foregoing request in the no,m,e.o ..,,,
and on the behalf of Public Service Company of New Hampshire and that t4ie statements therein are true to the best of his knowledge and belief. N..***L E c yk.
A *a J. mY h A. L." legffdre, JrV NoQ'y-r 3 !$
My Commission Expires Augwg, /{