|
---|
Category:LICENSEE EVENT REPORT (SEE ALSO AO
MONTHYEARML20024J3211994-10-0505 October 1994 LER 94-006-00:on 940909,failure to Perform Slave Relay Test Associated W/One Containment Isolation Valve Due to Improper Work Practices.Reviewed All Slave Relay Test Procedures & Trained All Qualified reviewers.W/941005 Ltr ML20046B5251993-08-0404 August 1993 LER 93-007-00:on 930705,TS Required Surveillance Was Not Performed Because of Inappropriate Action Because of Lack of Attention to Detail.Generated WO 93047633 to Perform Required Surveillance on Unit 1 IPE CA 9010.W/930729 Ltr ML20045H9821993-07-12012 July 1993 LER 93-005-00:on 930612,manual Rt in Unit 1 Occurred Due to Equipment Failure Due to Failure of L-13 Field Cable Between Data Cabinet B & Bulkhead for Undetermined Reasons.Replaced Field cable.W/930709 Ltr ML20045D9681993-06-25025 June 1993 LER 93-006-00:on 930526,discovered That Sample Blower for Radiation Monitor 1 EMF-43B Off & Monitor Declared Inoperable & Ventilation Sys Air Intakes Not Isolated.Caused by Deficient Procedures.Test Procedures Revised ML20045B2811993-06-11011 June 1993 LER 93-004-00:on 930513,both Trains of CR Ventilation Sys Declared Inoperable Due to Equipment Failure.Exact Cause of Failure Could Not Be Determined.Train B Nuclear Svc Water Sys Flow Balance completed.W/930611 Ltr ML20029C2091991-03-21021 March 1991 LER 91-003-00:on 910219,both Trains of Control Room Ventilation Sys Inoperable.Caused by Design Malfunction & Management Deficiency.Temporary Modifications,Removing Automatic Closure Function implemented.W/910321 Ltr ML20028G9561990-09-26026 September 1990 LER 90-025-00:on 900827,Unit 1 Shut Down Because of Unidentified RCS Leakage Exceeding Tech Spec Limits.Caused by Equipment Failure.Procedure AP/1/A/5500/10 Implemented. Valve 1NC-33 Will Be Repacked at Next outage.W/900926 Ltr ML20044A0091990-06-25025 June 1990 LER 90-015-00:on 900524,Tech Spec 3.0.3 Entered Because More than One Power Range Nuclear Instrumentation Channel Exceeded 5% Deviation.Caused by Mgt Deficiency.Boric Acid Added to Coolant sys.W/900625 Ltr ML20043H4991990-06-21021 June 1990 LER 90-012-00:on 900522,loose Matl,Consisting of Masslin Cloths & Stepoff Pad,Discovered in Upper Containment.Caused by Failure to Follow Procedures.Loose Items Removed & Cleanliness Procedures revised.W/900621 Ltr ML20043H2641990-06-20020 June 1990 LER 90-011-00:on 900521,noted That Valve 1RN-69A Auxiliary Feedwater Assured Supply from Train a Nuclear Svc Water Repositioned to Open Position After Start of Pump.Cause Unknown.Pump Shut Down & Valve closed.W/900620 Ltr ML20043F7471990-06-13013 June 1990 LER 90-010-00:on 900427,discovered That Annulus Ventilation & Control Room Ventilation Sys Headers Would Not Operate,As Designed,Under Postulated Operating Conditions. Caused by Design Deficiency.Change submitted.W/900613 Ltr ML20043F5071990-06-11011 June 1990 LER 90-009-00:on 900512,feedwater Isolation Occurred as Result of Steam Generator 1B Reaching hi-hi Level Setpoint of 82% Level.Caused by Inappropriate Action Because of Lack of Attention to Detail.Feedwater Logic reset.W/900611 Ltr ML20043D6541990-05-30030 May 1990 LER 90-007-00:on 881018,during Insp Ice Condenser Basket Found W/Bottom Screws Missing.Caused by Installation Deficiency Because of Improper Matl Selection.Work Request Initiated to Replace Improper screws.W/900530 Ltr ML20043D7121990-05-30030 May 1990 LER 90-006-00:on 900226,discovered Abnormal Degradation on Steel Containment Vessel.Corrosion Caused by Design Deficiency Caused by Unanticipated Environ Interaction. Detailed Insps conducted.W/900529 Ltr ML20043C8041990-05-30030 May 1990 LER 90-008-00:on 900430,radiation Monitor for Contaminated Parts Warehouse Ventilation & Sampler Min Flow Device Declared Inoperable.Caused by Personnel Error.Appropriate Procedures Enhanced to Prevent recurrence.W/900530 Ltr ML20012D1651990-03-19019 March 1990 LER 90-004-00:on 900208,determined That Holes Left in Auxiliary Shutdown Panel Could Allow Water Spray Into Cabinet.Cause Unknown.Holes Covered W/Duct Tape & Repaired. W/900319 Ltr ML20011F4261990-02-16016 February 1990 LER 90-002-00:on 900117,hold Down Screws on Sylvania Contactors in Motor Control Ctrs Found Loose.Caused by Mfg Deficiency.Contactor Screws Tightened.All Hold Down Screws Will Be Replaced W/Another type.W/900223 Ltr ML20006D5571990-02-0707 February 1990 LER 90-001-00:on 900108,reactor Trip Occurred Due to Clogged Strainer on Feedwater Pump a Speed Controller.Caused by Water in Oil Sys.Cause for Water Presence in Sys Unknown. Sludge Minimization Attempts pursued.W/900207 Ltr ML20006A8771990-01-21021 January 1990 LER 89-028-00:on 891204,self-initiated Technical Audit Team Personnel Identified Gap Around Control Room Ventilation Air Handling Unit Access Door.Caused by Possible Const/ Installation Deficiency.Door Sys modified.W/900122 Ltr ML19327C2581989-11-13013 November 1989 LER 89-031-00:on 891012,ac Power Supply Fuse Blew Resulting in Automatic Isolation of Four Outside Air Intakes on Ventilation Sys.Caused by Inappropriate Action.Intake Valves Returned to Svc & Tech Spec 3.3.3.1 exited.W/891113 Ltr ML19324C2031989-11-10010 November 1989 LER 89-024-00:on 890908,MSIV Stroke Timing Periodic Test Performed W/O Air Assistance & Three MSIVs Failed to Close within 5 S.Caused by Brass Guide Screws Excessively Tightened.Set Screws Properly set.W/891106 Ltr ML19324C2011989-10-31031 October 1989 LER 88-019-02:on 880719,damper Compartment Flows Did Not Meet Flow Requirements Due to Closure of Some Sys Dampers. Caused by Defective procedure.As-found Measurements Taken While Operating Fans for Damper positions.W/891030 Ltr ML19327B5611989-10-26026 October 1989 LER 89-030-00:on 890714,visual Insp Revealed 3/4 Inch Open Conduit Connection Which Would Have Prevented Successful Leak Test.Cause Unknown.Connection Removed & Hole Sealed. W/891026 Ltr ML19327B4771989-10-23023 October 1989 LER 89-029-00:on 890922,ESF Actuation Occurred When Diesel Generator 1A Started Due to Momentary Undervoltage Condition on Train a 4,160-volt Essential Switchgear.Cause Unknown. Offsite Power Source Returned to Normal svc.W/891023 Ltr ML19327B1511989-10-19019 October 1989 LER 89-026-00:on 890720,both Trains of Control Area Ventilation Sys Inoperable.Caused by Design Deficiency Because of Unanticipated Interaction of Components.Original Check Damper Reinstalled in Fan on Train B.W/891019 Ltr ML19351A4301989-10-18018 October 1989 LER 89-025-00:on 890918,jumper Came Loose & Inadvertently Made Contact W/Sliding Link B-14 Directly Above Link B-15, Resulting in Turbine Driven Feedwater Pump Automatically Starting.Caused by Inappropriate action.W/891018 Ltr ML19325D4991989-10-16016 October 1989 LER 89-027-00:on 890915,preheaters Did Not Start Because Air Flow Permissive Was Not Made & Cross Connect Dampers Were Closed & Tagged & Ventilation Sys Train a Remained Logged Inoperable.Caused by Design deficiency.W/891016 Ltr ML19325C4871989-09-28028 September 1989 LER 89-018-00:on 890829,both Trains of Control Area Ventilation (VC) & Chilled Water (Yc) Sys Declared Inoperable.Caused by Equipment/Failure Malfunction. Refrigerant Added to Vc/Yc chiller.W/890928 Ltr ML20043D7041989-09-25025 September 1989 LER 89-022-01:on 890826,reactor Trip Occurred Due to Failed Universal Board in Solid State Protection Sys Cabinet A. Caused by Equipment/Malfunction.Universal Board Replaced. W/900530 Ltr ML19325C4731989-09-18018 September 1989 LER 89-015-00:on 890722,discovered That Neutral Pressure Was Best That Could Be Achieved in Some Required Sys Configurations.Caused by Design Deficiency Due to Design Oversight.Outside Air Ref Point installed.W/891004 Ltr ML20024F2791983-08-29029 August 1983 LER 83-066/03L-0:on 830817,invalid Alarm Received for Fire Detection Zone Efa 90 Which Would Not Clear.Caused by Unusual Svc Conditions.Detector Cleaned & replaced.W/830829 Ltr ML20024D8101983-07-29029 July 1983 LER 83-050/03L-0:on 830629,control Area Ventilation Sys Train B Declared Inoperable.Caused by Automatic Reset Preheater Overtemp Cutout Switch Failure.Replacement Switch Will Be installed.W/830729 Ltr ML20024D7531983-07-27027 July 1983 LER 83-048/03L-0:on 830624,control Area Ventilation Sys Train B Declared Inoperable Following Low Refrigerant Temp Alarm Trip of Control Room Chiller B.Caused by Cleaning of Condenser tubes.W/830727 Ltr ML20024D7701983-07-27027 July 1983 LER 83-049/03L-0:on 830624,surveillance Compliance Review Revealed Three Time Response Tests Not Performed.Cause Not Stated.Remaining Channels Will Be Tested During Next refueling.W/830727 Ltr ML20024D8951983-07-27027 July 1983 LER 83-047/03L-0:on 830627,discovered That 18-month Insp of Fire Hose Station 180 Not Performed During Nov 1981.Caused by Order Preventing Personnel from Entering Area Due to High Radiation Levels.Procedural Change instituted.W/830727 Ltr ML20024C4091983-06-28028 June 1983 Updated LER 83-002/03X-1:on 830110,pressurizer Heater Group 1B Failed to Energize in Manual & Declared Inoperable.Heat Damage Found at Heat Dissipating Resistor Connections.Caused by Design Defect in Contactor Coil circuit.W/830628 Ltr ML20024C3941983-06-28028 June 1983 LER 83-035/03L-0:on 830515,pressurizer Heater Group 1B Failed to Energize in Manual & Declared Inoperable Per Tech Spec 3.4.3.Caused by Blown Fuse in Heater Contactor Control Circuit.Fuse replaced.W/830628 Ltr ML20024C0001983-06-27027 June 1983 LER 83-030/01T-0:on 830526,discovered Monthly Test of Containment Pressure Control Sys Failed to Satisfy Surveillance Requirements to Check Permissive/Termination Setpoint Accuracy.Alarm Modules recalibr.W/830627 Ltr ML20023C4691983-05-0505 May 1983 LER 83-017/03L-0:on 830405,during Draining of Refueling Cavity RHR (Nd) Pumps Began to Cavitate & Eventually Both Nd Pumps Stopped.Caused by Level Gauge Isolation.Cavity Refilled.Nd Sys Vented.Procedures Revised ML20028E0131983-01-10010 January 1983 LER 82-081/03L-0:on 821211,lower Personnel Airlock Declared Inoperable After Reactor Door Found Partially Closed W/Small Seal Ruptured & Large Seal Inflated.Cause Not Known.Seal Not Designed to Withstand Unrestrained Inflationary Forces ML20028A5301982-11-10010 November 1982 LER 82-073/03L-0:on 820403,during QA Audit of Test Procedures,Incore & Nuclear Instrumentation Sys Correlation Monthly Check Found Not Performed.Caused by Incorrect Test Schedule ML20027D3351982-10-22022 October 1982 LER 82-071/03L-0:on 820922,motor Control Ctr Lemxd Lost Power Causing Temporary Inoperability of Several Essential Sys/Components.Caused by Automatic Trip of Feeder Breaker. Breaker Reset & Closed.Power Restored ML20027B5051982-09-10010 September 1982 LER 82-067/03L-0:on 820813,two Auxiliary Feedwater Pump Turbine Low Suction Pressure Switches Failed to Perform During Functional Test.Caused by Switches Being Out of Calibr,Possibly Due to Instrument Drift or Misadjustment ML20027B5521982-09-0808 September 1982 LER 82-064/03L-0:on 820809,vent Flow Monitor Indicated Zero W/Vent in Operation During Process of Returning to Mode 1. Caused by Out of Calibr Differential Pressure Transmitter Due to Instrument Drift.Transmitter Recalibr ML20052H5831982-05-10010 May 1982 LER 82-027/03L-0:on 820326,one Channel of Position Indication for RCS Power Operated Relief Valves NC-32 & NC-36 Declared Inoperable When Closed Indicator Lights Failed.Caused by Loose Fitting Bulb Due to Crack in Socket ML20052G6791982-05-0707 May 1982 LER 82-030/01T-0:on 820423,diesel Generator 1A Declared Inoperable After Failing to Start for Periodic Test.Caused by Failure of Station Design Change Implementation Program to Control Work on Station Mods ML20052H7421982-05-0707 May 1982 LER 82-031/03L-0:on 820408,boric Acid Transfer Pump a Failed to Perform at Capacity & Declared Inoperable.Caused by Reverse Rotation Due to Improperly Connected Windings. Personnel Counseled & Maint Routine Modified ML20052H7481982-05-0606 May 1982 LER 82-029/03L-0:on 820402,investigation of Power Operated Relief Valve (PORV) & Pressurizer Code Safety Discharge Line High Temp Alarms Revealed Indications of Leakage for PORV NC-34.Cause Undetermined.Valve Will Be Repaired ML20052H6091982-04-30030 April 1982 LER 82-028/03L-0:on 820401,during Mode 1 Operation,Radiation Monitors EMF-31 & EMF-33 Lost Power.Caused by Monitor EMF-46 Tripping Circuit Breaker Due to Direct Short Across Power bulb.EMF-46 Isolated & EMF-31 & 33 Returned to Svc ML20052G3611982-04-29029 April 1982 LER 82-025/03L-0:on 820318,vol Control Tank Makeup Frequency Increased & Containment Floor & Equipment Sump 1A Level Increased During RCS Leak Test.Caused by Failure to Verify Isolation Valves Closed Due to Procedural Deficiency 1994-10-05
[Table view] Category:RO)
MONTHYEARML20024J3211994-10-0505 October 1994 LER 94-006-00:on 940909,failure to Perform Slave Relay Test Associated W/One Containment Isolation Valve Due to Improper Work Practices.Reviewed All Slave Relay Test Procedures & Trained All Qualified reviewers.W/941005 Ltr ML20046B5251993-08-0404 August 1993 LER 93-007-00:on 930705,TS Required Surveillance Was Not Performed Because of Inappropriate Action Because of Lack of Attention to Detail.Generated WO 93047633 to Perform Required Surveillance on Unit 1 IPE CA 9010.W/930729 Ltr ML20045H9821993-07-12012 July 1993 LER 93-005-00:on 930612,manual Rt in Unit 1 Occurred Due to Equipment Failure Due to Failure of L-13 Field Cable Between Data Cabinet B & Bulkhead for Undetermined Reasons.Replaced Field cable.W/930709 Ltr ML20045D9681993-06-25025 June 1993 LER 93-006-00:on 930526,discovered That Sample Blower for Radiation Monitor 1 EMF-43B Off & Monitor Declared Inoperable & Ventilation Sys Air Intakes Not Isolated.Caused by Deficient Procedures.Test Procedures Revised ML20045B2811993-06-11011 June 1993 LER 93-004-00:on 930513,both Trains of CR Ventilation Sys Declared Inoperable Due to Equipment Failure.Exact Cause of Failure Could Not Be Determined.Train B Nuclear Svc Water Sys Flow Balance completed.W/930611 Ltr ML20029C2091991-03-21021 March 1991 LER 91-003-00:on 910219,both Trains of Control Room Ventilation Sys Inoperable.Caused by Design Malfunction & Management Deficiency.Temporary Modifications,Removing Automatic Closure Function implemented.W/910321 Ltr ML20028G9561990-09-26026 September 1990 LER 90-025-00:on 900827,Unit 1 Shut Down Because of Unidentified RCS Leakage Exceeding Tech Spec Limits.Caused by Equipment Failure.Procedure AP/1/A/5500/10 Implemented. Valve 1NC-33 Will Be Repacked at Next outage.W/900926 Ltr ML20044A0091990-06-25025 June 1990 LER 90-015-00:on 900524,Tech Spec 3.0.3 Entered Because More than One Power Range Nuclear Instrumentation Channel Exceeded 5% Deviation.Caused by Mgt Deficiency.Boric Acid Added to Coolant sys.W/900625 Ltr ML20043H4991990-06-21021 June 1990 LER 90-012-00:on 900522,loose Matl,Consisting of Masslin Cloths & Stepoff Pad,Discovered in Upper Containment.Caused by Failure to Follow Procedures.Loose Items Removed & Cleanliness Procedures revised.W/900621 Ltr ML20043H2641990-06-20020 June 1990 LER 90-011-00:on 900521,noted That Valve 1RN-69A Auxiliary Feedwater Assured Supply from Train a Nuclear Svc Water Repositioned to Open Position After Start of Pump.Cause Unknown.Pump Shut Down & Valve closed.W/900620 Ltr ML20043F7471990-06-13013 June 1990 LER 90-010-00:on 900427,discovered That Annulus Ventilation & Control Room Ventilation Sys Headers Would Not Operate,As Designed,Under Postulated Operating Conditions. Caused by Design Deficiency.Change submitted.W/900613 Ltr ML20043F5071990-06-11011 June 1990 LER 90-009-00:on 900512,feedwater Isolation Occurred as Result of Steam Generator 1B Reaching hi-hi Level Setpoint of 82% Level.Caused by Inappropriate Action Because of Lack of Attention to Detail.Feedwater Logic reset.W/900611 Ltr ML20043D6541990-05-30030 May 1990 LER 90-007-00:on 881018,during Insp Ice Condenser Basket Found W/Bottom Screws Missing.Caused by Installation Deficiency Because of Improper Matl Selection.Work Request Initiated to Replace Improper screws.W/900530 Ltr ML20043D7121990-05-30030 May 1990 LER 90-006-00:on 900226,discovered Abnormal Degradation on Steel Containment Vessel.Corrosion Caused by Design Deficiency Caused by Unanticipated Environ Interaction. Detailed Insps conducted.W/900529 Ltr ML20043C8041990-05-30030 May 1990 LER 90-008-00:on 900430,radiation Monitor for Contaminated Parts Warehouse Ventilation & Sampler Min Flow Device Declared Inoperable.Caused by Personnel Error.Appropriate Procedures Enhanced to Prevent recurrence.W/900530 Ltr ML20012D1651990-03-19019 March 1990 LER 90-004-00:on 900208,determined That Holes Left in Auxiliary Shutdown Panel Could Allow Water Spray Into Cabinet.Cause Unknown.Holes Covered W/Duct Tape & Repaired. W/900319 Ltr ML20011F4261990-02-16016 February 1990 LER 90-002-00:on 900117,hold Down Screws on Sylvania Contactors in Motor Control Ctrs Found Loose.Caused by Mfg Deficiency.Contactor Screws Tightened.All Hold Down Screws Will Be Replaced W/Another type.W/900223 Ltr ML20006D5571990-02-0707 February 1990 LER 90-001-00:on 900108,reactor Trip Occurred Due to Clogged Strainer on Feedwater Pump a Speed Controller.Caused by Water in Oil Sys.Cause for Water Presence in Sys Unknown. Sludge Minimization Attempts pursued.W/900207 Ltr ML20006A8771990-01-21021 January 1990 LER 89-028-00:on 891204,self-initiated Technical Audit Team Personnel Identified Gap Around Control Room Ventilation Air Handling Unit Access Door.Caused by Possible Const/ Installation Deficiency.Door Sys modified.W/900122 Ltr ML19327C2581989-11-13013 November 1989 LER 89-031-00:on 891012,ac Power Supply Fuse Blew Resulting in Automatic Isolation of Four Outside Air Intakes on Ventilation Sys.Caused by Inappropriate Action.Intake Valves Returned to Svc & Tech Spec 3.3.3.1 exited.W/891113 Ltr ML19324C2031989-11-10010 November 1989 LER 89-024-00:on 890908,MSIV Stroke Timing Periodic Test Performed W/O Air Assistance & Three MSIVs Failed to Close within 5 S.Caused by Brass Guide Screws Excessively Tightened.Set Screws Properly set.W/891106 Ltr ML19324C2011989-10-31031 October 1989 LER 88-019-02:on 880719,damper Compartment Flows Did Not Meet Flow Requirements Due to Closure of Some Sys Dampers. Caused by Defective procedure.As-found Measurements Taken While Operating Fans for Damper positions.W/891030 Ltr ML19327B5611989-10-26026 October 1989 LER 89-030-00:on 890714,visual Insp Revealed 3/4 Inch Open Conduit Connection Which Would Have Prevented Successful Leak Test.Cause Unknown.Connection Removed & Hole Sealed. W/891026 Ltr ML19327B4771989-10-23023 October 1989 LER 89-029-00:on 890922,ESF Actuation Occurred When Diesel Generator 1A Started Due to Momentary Undervoltage Condition on Train a 4,160-volt Essential Switchgear.Cause Unknown. Offsite Power Source Returned to Normal svc.W/891023 Ltr ML19327B1511989-10-19019 October 1989 LER 89-026-00:on 890720,both Trains of Control Area Ventilation Sys Inoperable.Caused by Design Deficiency Because of Unanticipated Interaction of Components.Original Check Damper Reinstalled in Fan on Train B.W/891019 Ltr ML19351A4301989-10-18018 October 1989 LER 89-025-00:on 890918,jumper Came Loose & Inadvertently Made Contact W/Sliding Link B-14 Directly Above Link B-15, Resulting in Turbine Driven Feedwater Pump Automatically Starting.Caused by Inappropriate action.W/891018 Ltr ML19325D4991989-10-16016 October 1989 LER 89-027-00:on 890915,preheaters Did Not Start Because Air Flow Permissive Was Not Made & Cross Connect Dampers Were Closed & Tagged & Ventilation Sys Train a Remained Logged Inoperable.Caused by Design deficiency.W/891016 Ltr ML19325C4871989-09-28028 September 1989 LER 89-018-00:on 890829,both Trains of Control Area Ventilation (VC) & Chilled Water (Yc) Sys Declared Inoperable.Caused by Equipment/Failure Malfunction. Refrigerant Added to Vc/Yc chiller.W/890928 Ltr ML20043D7041989-09-25025 September 1989 LER 89-022-01:on 890826,reactor Trip Occurred Due to Failed Universal Board in Solid State Protection Sys Cabinet A. Caused by Equipment/Malfunction.Universal Board Replaced. W/900530 Ltr ML19325C4731989-09-18018 September 1989 LER 89-015-00:on 890722,discovered That Neutral Pressure Was Best That Could Be Achieved in Some Required Sys Configurations.Caused by Design Deficiency Due to Design Oversight.Outside Air Ref Point installed.W/891004 Ltr ML20024F2791983-08-29029 August 1983 LER 83-066/03L-0:on 830817,invalid Alarm Received for Fire Detection Zone Efa 90 Which Would Not Clear.Caused by Unusual Svc Conditions.Detector Cleaned & replaced.W/830829 Ltr ML20024D8101983-07-29029 July 1983 LER 83-050/03L-0:on 830629,control Area Ventilation Sys Train B Declared Inoperable.Caused by Automatic Reset Preheater Overtemp Cutout Switch Failure.Replacement Switch Will Be installed.W/830729 Ltr ML20024D7531983-07-27027 July 1983 LER 83-048/03L-0:on 830624,control Area Ventilation Sys Train B Declared Inoperable Following Low Refrigerant Temp Alarm Trip of Control Room Chiller B.Caused by Cleaning of Condenser tubes.W/830727 Ltr ML20024D7701983-07-27027 July 1983 LER 83-049/03L-0:on 830624,surveillance Compliance Review Revealed Three Time Response Tests Not Performed.Cause Not Stated.Remaining Channels Will Be Tested During Next refueling.W/830727 Ltr ML20024D8951983-07-27027 July 1983 LER 83-047/03L-0:on 830627,discovered That 18-month Insp of Fire Hose Station 180 Not Performed During Nov 1981.Caused by Order Preventing Personnel from Entering Area Due to High Radiation Levels.Procedural Change instituted.W/830727 Ltr ML20024C4091983-06-28028 June 1983 Updated LER 83-002/03X-1:on 830110,pressurizer Heater Group 1B Failed to Energize in Manual & Declared Inoperable.Heat Damage Found at Heat Dissipating Resistor Connections.Caused by Design Defect in Contactor Coil circuit.W/830628 Ltr ML20024C3941983-06-28028 June 1983 LER 83-035/03L-0:on 830515,pressurizer Heater Group 1B Failed to Energize in Manual & Declared Inoperable Per Tech Spec 3.4.3.Caused by Blown Fuse in Heater Contactor Control Circuit.Fuse replaced.W/830628 Ltr ML20024C0001983-06-27027 June 1983 LER 83-030/01T-0:on 830526,discovered Monthly Test of Containment Pressure Control Sys Failed to Satisfy Surveillance Requirements to Check Permissive/Termination Setpoint Accuracy.Alarm Modules recalibr.W/830627 Ltr ML20023C4691983-05-0505 May 1983 LER 83-017/03L-0:on 830405,during Draining of Refueling Cavity RHR (Nd) Pumps Began to Cavitate & Eventually Both Nd Pumps Stopped.Caused by Level Gauge Isolation.Cavity Refilled.Nd Sys Vented.Procedures Revised ML20028E0131983-01-10010 January 1983 LER 82-081/03L-0:on 821211,lower Personnel Airlock Declared Inoperable After Reactor Door Found Partially Closed W/Small Seal Ruptured & Large Seal Inflated.Cause Not Known.Seal Not Designed to Withstand Unrestrained Inflationary Forces ML20028A5301982-11-10010 November 1982 LER 82-073/03L-0:on 820403,during QA Audit of Test Procedures,Incore & Nuclear Instrumentation Sys Correlation Monthly Check Found Not Performed.Caused by Incorrect Test Schedule ML20027D3351982-10-22022 October 1982 LER 82-071/03L-0:on 820922,motor Control Ctr Lemxd Lost Power Causing Temporary Inoperability of Several Essential Sys/Components.Caused by Automatic Trip of Feeder Breaker. Breaker Reset & Closed.Power Restored ML20027B5051982-09-10010 September 1982 LER 82-067/03L-0:on 820813,two Auxiliary Feedwater Pump Turbine Low Suction Pressure Switches Failed to Perform During Functional Test.Caused by Switches Being Out of Calibr,Possibly Due to Instrument Drift or Misadjustment ML20027B5521982-09-0808 September 1982 LER 82-064/03L-0:on 820809,vent Flow Monitor Indicated Zero W/Vent in Operation During Process of Returning to Mode 1. Caused by Out of Calibr Differential Pressure Transmitter Due to Instrument Drift.Transmitter Recalibr ML20052H5831982-05-10010 May 1982 LER 82-027/03L-0:on 820326,one Channel of Position Indication for RCS Power Operated Relief Valves NC-32 & NC-36 Declared Inoperable When Closed Indicator Lights Failed.Caused by Loose Fitting Bulb Due to Crack in Socket ML20052G6791982-05-0707 May 1982 LER 82-030/01T-0:on 820423,diesel Generator 1A Declared Inoperable After Failing to Start for Periodic Test.Caused by Failure of Station Design Change Implementation Program to Control Work on Station Mods ML20052H7421982-05-0707 May 1982 LER 82-031/03L-0:on 820408,boric Acid Transfer Pump a Failed to Perform at Capacity & Declared Inoperable.Caused by Reverse Rotation Due to Improperly Connected Windings. Personnel Counseled & Maint Routine Modified ML20052H7481982-05-0606 May 1982 LER 82-029/03L-0:on 820402,investigation of Power Operated Relief Valve (PORV) & Pressurizer Code Safety Discharge Line High Temp Alarms Revealed Indications of Leakage for PORV NC-34.Cause Undetermined.Valve Will Be Repaired ML20052H6091982-04-30030 April 1982 LER 82-028/03L-0:on 820401,during Mode 1 Operation,Radiation Monitors EMF-31 & EMF-33 Lost Power.Caused by Monitor EMF-46 Tripping Circuit Breaker Due to Direct Short Across Power bulb.EMF-46 Isolated & EMF-31 & 33 Returned to Svc ML20052G3611982-04-29029 April 1982 LER 82-025/03L-0:on 820318,vol Control Tank Makeup Frequency Increased & Containment Floor & Equipment Sump 1A Level Increased During RCS Leak Test.Caused by Failure to Verify Isolation Valves Closed Due to Procedural Deficiency 1994-10-05
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217G7951999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for McGuire Nuclear Station,Units 1 & 2 ML20217F3661999-09-22022 September 1999 Rev 18 to McGuire Unit 1 Cycle 14 Colr ML20212D1911999-09-20020 September 1999 SER Accepting Exemption from Certain Requirements of 10CFR50,App A,General Design Criterion 57 Closed System Isolation Valves for McGuire Nuclear Station,Units 1 & 2 ML20216E8851999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for McGuire Nuclear Station,Units 1 & 2 ML20211B1281999-08-31031 August 1999 Dynamic Rod Worth Measurement Using Casmo/Simulate ML20217G8101999-08-31031 August 1999 Revised Monthly Operating Repts for Aug 1999 for McGuire Nuclear Station,Unit 1 & 2 ML20211G5261999-08-24024 August 1999 SER Accepting Approval of Second 10-year Interval Inservice Insp Program Plan Request for Relief 98-004 for Plant,Unit 1 ML20211F3441999-08-17017 August 1999 Updated non-proprietary Page 2-4 of TR DPC-NE-2009 ML20210S2371999-07-31031 July 1999 Monthly Operating Repts for July 1999 for McGuire Nuclear Station,Units 1 & 2 ML20216E8951999-07-31031 July 1999 Revised Monthly Operating Repts for July 1999 for McGuire Nuclear Station,Units 1 & 2 ML20209E4361999-07-0909 July 1999 SER Agreeing with Licensee General Interpretation of TS LCO 3.0.6,but Finds No Technical Basis or Guidance That Snubbers Could Be Treated as Exception to General Interpretation ML20196K6631999-07-0707 July 1999 Safety Evaluation Supporting Licensee 990520 Position Re Inoperable Snubbers ML20209H1631999-06-30030 June 1999 Monthly Operating Repts for June 1999 for McGuire Nuclear Station,Units 1 & 2 ML20210S2491999-06-30030 June 1999 Revised Monthly Operating Rept for June 1999 for McGuire Nuclear Station,Units 1 & 2 ML20209H1731999-05-31031 May 1999 Revised Monthly Operating Rept for May 1999 for McGuire Nuclear Station,Units 1 & 2 ML20206T4771999-05-31031 May 1999 Rev 3 to UFSAR Chapter 15 Sys Transient Analysis Methodology ML20196L1881999-05-31031 May 1999 Non-proprietary Rev 1 to DPC-NE-3004, Mass & Energy Release & Containment Response Methodology ML20195K3691999-05-31031 May 1999 Monthly Operating Repts for May 1999 for McGuire Nuclear Station,Units 1 & 2 ML20206N3511999-05-11011 May 1999 Safety Evaluation Accepting Licensee Response to GL 96-05, Periodic Verification of Design-Basis Capability of Safety- Related Movs ML20195K3761999-04-30030 April 1999 Revised MORs for Apr 1999 for McGuire Nuclear Station,Units 1 & 2 ML20206R0891999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for McGuire Nuclear Station,Units 1 & 2 ML20205L2341999-04-0505 April 1999 SFP Criticality Analysis ML20206R0931999-03-31031 March 1999 Revised Monthly Repts for Mar 1999 for McGuire Nuclear Station,Units 1 & 2 ML20205P8991999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for McGuire Nuclear Station,Units 1 & 2 ML20205C4171999-03-25025 March 1999 Special Rept 99-02:on 801027,Commission Approved for publication,10CFR50.48 & 10CFR50 App R Delineating Certain Fire Protection Provisions for Nuclear Power Plants Licensed to Operate Prior to 790101.Team Draft Findings Reviewed ML20207K2051999-03-0505 March 1999 Special Rept 99-01:on 990128,DG Tripped After 2 H of Operation During Loaded Operation for Monthly Test.Caused by Several Components That Were Degraded or Had Intermittent Problems.Parts Were Replaced & Initial Run Was Performed ML20204C8911999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for McGuire Nuclear Station,Units 1 & 2 ML20205P9021999-02-28028 February 1999 Revised Monthly Operating Repts for Feb 1999 for McGuire Nuclear Station,Units 1 & 2 ML20204C8961999-01-31031 January 1999 Revised Monthly Operating Repts for Jan 1999 for McGuire Nuclear Station,Units 1 & 2 ML20199E0301998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for McGuire Nuclear Station,Units 1 & 2 ML20216F9931998-12-31031 December 1998 Piedmont Municipal Power Agency 1998 Annual Rept ML20198A4481998-12-11011 December 1998 Safety Evaluation Concluding That for Relief Request 97-004, Parts 1 & 2,ASME Code Exam Requirements Are Impractical. Request for Relief & Alternative Imposed,Granted ML20198D7561998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for McGuire Nuclear Station,Units 1 & 2 ML20199E0491998-11-30030 November 1998 Revised Monthly Operating Rept for Nov 1998 for McGuire Nuclear Station,Units 1 & 2 Re Personnel Exposure ML20199E9651998-11-24024 November 1998 Rev 1 to ATI-98-012-T005, DPC Evaluation of McGuire Unit 1 Surveillance Weld Data Credibility ML20196D4171998-11-24024 November 1998 Special Rept 98-02:on 981112,failure to Implement Fire Watches in Rooms Containing Inoperable Fire Barrier Penetrations,Was Determined.Repair of Affected Fire Barriers in Progress ML20196G0581998-11-0606 November 1998 Rev 17 to COLR Cycle 13 for McGuire Unit 1 ML20196G0761998-11-0606 November 1998 Rev 15 to COLR Cycle 12 for McGuire Unit 2 ML20198D7771998-10-31031 October 1998 Revised Monthly Operating Rept for Oct 1998 for McGuire Nuclear Station,Units 1 & 2 ML20195E5961998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for McGuire Nuclear Station,Units 1 & 2 ML20154L6251998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for McGuire Nuclear Station,Units 1 & 2 ML20195E6021998-09-30030 September 1998 Revised Monthly Operating Rept for Sept 1998 for McGuire Nuclear Station,Units 1 & 2 ML20154B4131998-09-22022 September 1998 Rev 0 to ISI Rept for McGuire Nuclear Unit 1 Twelfth Refueling Outage ML20151W3521998-09-0808 September 1998 Special Rept 98-01:on 980819,maint Could Not Be Performed on FPS Due to Isolation Boundary Leakage.Caused by Inadequate Info Provided in Fire Impairment Plan.Isolated Portion of FPS Was Returned to Svc ML20154L6321998-08-31031 August 1998 Rev 1 to MOR for Aug 1998 for McGuire Nuclear Station,Unit 1 ML20153B3741998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for McGuire Nuclear Station,Units 1 & 2 ML20236U1601998-07-31031 July 1998 Non-proprietary DPC-NE-2009, DPC W Fuel Transition Rept ML20237B2381998-07-31031 July 1998 Monthly Operating Repts for July 1998 for McGuire Nuclear Station,Units 1 & 2 ML20153B3931998-07-31031 July 1998 Revised Monthly Operating Repts for Jul 1998 for McGuire Nuclear Station,Units 1 & 2 ML20236P0451998-07-0808 July 1998 Part 21 Rept Re non-conformance & Potential Defect in Component of Nordberg Model FS1316HSC Standby Dg.Caused by Outer Spring Valves Mfg from Matl That Did Not Meet Specifications.Will Furnish Written Rept within 60 Days 1999-09-30
[Table view] |
Text
, .
i i
. buke nne:r Compa:.y (704)375-4C00
. .*~ . McGuire NuclearStatiw
!!!00 Hagen Ferry kbad Huntentille, NC28018 8985 DUKE POWER June 11, 1990 U.S. Nuclear Regulatory Commission Document Control Desk t Washington, D.C. 20555
Subject:
McGuire Nuclear Station Unit 1 Docket No. 50-369 !
Licensee Event Report 369/90-09 Gentlemen:
Pursuant to'10 CFR 50.73 Sections (a)(1) and (d), attached is Licensee Event Report 369/90-09 concerning a feedwater isolation as a result of Steam Generator 1B reaching its Hi-Hi-level setpoint while in Mode 5. This report is being submitted in accordance with 10 CFR 50.73(a)(2)(iv). This event is considered to be of no significance with respect to the health and safety of the public.
Very ruly you,s,
/ # ,
, p T.L. McConnell DVE/ADJ/cb1 l Attachment xct- 'Mr. S.D. Ebneter American Nuclear Insurers l
Administrator, Region II c/o Dottie Sherman, ANI Library U.S. Nuclear Regulatory Commission The Exchange, Suit 245 101 Marietta St., NW, Suite 2900 270 Farmington Avenue l
-Atlanta, GA 30323 Farmington, CT 06032
- l. .INPO Records Center Mr. Darl Hood l Suite 1500 U.S. Nuclear Regulatory Commission l 1100 Circle 75 Parkway Office of Nuclear Reactor Regulation Atlanta, GA 30339 Washington, D.C. 20555 L
i M&M Nuclear Consultants Mr. P.K. Van Doorn L 1221 Avenue of the Americas NRC Resident Inspector l New York, NY 10020 McGuire Nuclear Station l'
1 90061SOOy3 900513
{DR. ADOCK 05000369 PDC 76 D
!)i
9/=
.' LER 369/90-00 c Paga 2
'* June-11 '1990-bxc B.W. Bline
.L.G. Bost l J.S. Warren l R.L. Gill C.L. Hartzell (CNS) i R.S.-Matheson (ONS) ,
P.R. Herran l S.S. Kilborn (W) l R.E. Lopez-Ibanez l M.A'. Mullen 1 R.O. Sharpe (MNS)
G.B. Swindlehurst K.D. "homas M.S. '.'uckman L.E. Feaver R.L. Leber J.D.-Uylie (PSD)
J.W. 'dillis QA Tech. Services NRC Coordinator (EC 12/55)
MC-815-04 (20)
-i l
l 1
i l-4 I
-)
i l i t-1
, c. 1 L i l
l i
l !
L l l 1 j
3,,' . s effic pere agg . U.S. NUCLEAct 6 EIULATORv C0amele860er M3'
- APPR0Vf D OMS 8e0 21089104
'" * '8 8'n
LICENSEE EVENT REPORT (LER)
DOCKET NUGABER 129 F*UE G E8u'iYNu' clear Station, Unit 1 olslolol413l6 l9 1 l0FI O 15 TITLE tea .
.A Feedwater Isolation occurred Because of Lack of' Attention To Detail event oAftis, tiR NuMetii., REPORT oATE m ofaER F ACiutiu iNvolvto esi uoNTu oAv vtAR vtAR :
= ; ',*- :y,=,y,: voNT- oAv vEAR **ciuvv ~ Avis ooc =ET NUv u m i.
N/A ogo,o,n;n, ,,
90 9l0 0 ] O j9 O jo 0l6 1l1 9l0 o,n,n,n,,, , ,
0 }-5 1l2 THlO RtPORT 18 SUOMitit0 PURSUANT TO TME Rh0UIREMENTS OF 10 CPR S (Ch.c4 ea. or mere et ra. renew avs 1110 OPERAT M te004 m $ 20 402tti 20 408ts) E 80.73teH2Hevi 73.71tti to 36WH1) 90.73teH2Het 73.716el R 20 4054a10101 _
60.381eH2) to.73(all2Hvai 0 Mt a de er (101 l ] 20.4054eH1Hal _ _ _
to.73telt2Hil 90.73teH2HumHAl J64dl 20.405(eH1 Hell _
20.4064eH1Hivl 60.734eH2 Hun 30.73delf2HvmHel 20 405leH1Het to 73tell2Hel C*. 72tsH2Hal LICENSEE CONT ACT FOR THl$ LER {121 gayg TELtPMONE NUM9ER ARE A CQQt Alan Sipe, Chairman, McGuire Safety Review Group 7,0 g4 8,7 ,S i i4 i 1,8 i3 COAGPLETE ONS LINE FOR E ACH C040PONENT F AILURE DESCRIGED IN THIS REPORT (131 MA AC. R MA AC- REpORTA E l CAU$t Sv 8T E U COMPONENT g O pR CAU$6 SYSTEM COMPONENT g l dl l 'l l l l l ! ! ! ! !
r I l -l i I I l' I I l _t l I I MONTH DAY YEAR
$UPPL8 MENT AL REPORT EXPtCTED (14)
'o*AU'E"
-pus or w ao om. uvucreo sUnwssioN oa rti No l l l AuT R ACT a -,, r. r av .
. . . .,,,e.-. , ,,,, o,,,,,. .u. ,,,..n.,,,, , - n e i On May 12, 1990, at 0229, a Feedwater Isolation occurred on Unit I as a result of Steam Generator IB reaching its Hi-Hi level setpoint of 82% level.
Operationu personnel were in the process of feeding and bleeding the Steam Generators for chemistry control in anticipation of changing from Mode 5 (Cold Shutdown), to Mode 4 (Hot Shutdown) on the following shift. Valve ICF-105, 1B Steam Generator Feed Reg Bypass, was leaking past its seat requiring Operator A to control the level in Steam Generator 1B by opening and closing ICF-127, IB Steam Generator Preheater Bypass Valve. Operator A was assisting in other testing in progress and failed to secure feedwater to the Steam Generator prior to reaching its Hi-Hi level setpoint. Corrective actions included resetting the Feedwater Isolation logic and restoring level to normal.
Operations shift personnel met to discuss the importance of limiting the number of activities requiring control operators attention at any one time.
The computer alarm setpoint for high Steam Generator level will be reduced to provide the Operators an early warning. This event has been assigned a cause of Inappropriate Action resulting from lack of attention to detail.
't q ; NRC perm 300 ma* .. . _ _ _ _ _ _ - - - - -
~
f g.
w .*'
esRC term sesA U S NUCLE A2 CtIUL& TORY COMMiest0N e tt <
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Amoveo ove No mo-om a ,
EXPtRES: $!3115 TAC 4LITY haast Itp DocatET Nunesen al. ggn gynagga (gl PAGE (3)
TE'" WuNm -
vue a McGuire Nuclear Station,-Unit 1 o sjojo;o;3; 6g9 9;O Og 0 g9 Og0 0 {2 OF 0l5 ftXT (# nesse spese a seguset ses aduleureW NAC Form WU (17)
EVALUATION:
Background
The Engineered Safety Features Actuation System [EIIS:JF]- (ESFAS) is designed to' actuate ESF equipment in the event predetermined safety limits are exceeded. The analog portion of the ESFAS consists of three to four redundant.
channels of process instrumentation for each parameter or variable that is monitored. The digital. portion of the ESFAS consists of two redundant logic trains which receive inputs from the analog. channels and is a part of the Solid State Protection System (SSPS). . The SSPS performs the logic necessary to determine when and which ESF equipment needs to be actuated, and through systems of relays [EIIS:RLY], actuates the ESF equipment. Technical Specifications do not require t.he ESFAS to be operable in Mode 5.
Each Steam Generator (EIIS:SG] utilizes three level instruments to monitor for
, a high Steam Generator level of M.%,. If two of three of these level instruments see a high level, the SSPS will actuate appropriate. relays to cause the turbine [EIIS:TRB] to trip, 'the feedwater pumps (EIIS:P] to trip, and feedwater to isolate to the Steam Generators.
K Description of Event
,On May 12, 1990 at 0225, Operations personnel were in the process of " feeding and bleeding" the Unit 1 Steam Generators. This involved draining some water from the-Steam Generators by way of the Blowdown System [EIIS:WIl. Drain valves were opened on the Blowdown System which drained water from the Steam Generators to the Turbine Building [EIIS:NM]' Sump. The water was replaced by
~
. feeding from the Condensate system [EIIS:KA]. This drain and makeup was being performed in an effort to improve the chemistry of the water in the Steam Generators.
At 0229, the Operator' Aid Computer [EIIS: CPU] alarmed indicating "Hi Steam Generator B Narrow Range Level Channel I". Channels III and IV also alarmed.
At the same time, a Feedwater Isolation signal was received. This signal, caused by the.high Steam Generator level, closed the Steam Generator Preheater Bypass Valves, ICF-126-127-128 and 129, which were being used to feed the Steam Generators. Annunciator [EIIS: ANN] alarm [EIIS: ALM] 1AD-4 D2, Steam
-Generator B Hi-Hi Level _ Alert, alarmed at the same time the isolation signal occurred.
Operator A had been assigned the task of monitoring the Steam Generator levels and adjut, ting Feedwater flow to maintain the levels. This task was complicated by the fact that valve ICF-105, 1B Steam Generator Feed Reg Bypass, was leaking past its seat. This required the operator to periodically open and close valve ICF-127, Steam Generator B Feedwater Preheater Bypass, to maintain the level. Valves ICF-105 and ICF-107 are controlled from the Steam Generator control panel [EIIS:PL).
. ... .. . ,,..., . s. -
- .go.. .
- a. ,., .
00HC Pero mea . U S. DeuCLlan CSIULAfomV COMMISS4088
~
LICENSEE EVENT REPORT (LER) TEXT CCNTINUATION u,xono ove no mo.om q
I EXPIRES: $/3113 PACILITY teAME (11 DOCKEY 80VRSER (21 gga psUh8844101 PAGE (3
"*a -
" tO. "'To*st op 6' McGuire Nuclear Station, Unit 1 o ls j o j o l o l 3 l 6l 9 9l0 --
0l 0 l9 --
0l0 0l3 0 l5 itXT (# sense ansse 4 meusesf, asse essmanaf ##C 7snn MbeW ltM Operator A was also assisting other Operations personnel in the performance of PT/1/A/4350/26, Auxiliary Shutdown Panel Controls Verification.- This procedure requires operations personnel to take control of various pumps and valves at the local Auxiliary Shutdown Panel to ensure these components operate properly from-this location. Operator A was realigning the pumps and valves in the Component Cooling System [EIIS:CC) after the Operators-at the local panel had completed this portion of the procedure when the isolation signal occurred.
Other activities in progress at the time of this event were PT/1/A/4200/28B, Train'B Slave Relay Test. Also, Instrumentation and Electrical (IAE)
Maintenance personnel were working on the Volume Control Tank (EIIS:TKl (VCT)
-level control system under work request 07166A. Another Licensed Control Operator was manually controlling the level in the VCT while this work was in progress.
Unit I was in Mode 5 when the Feedwater Isolation occurred. Station personnel intended to place the Utit in Mode 4 at approximately 0900 on this same morning.
Operations personnel closed the Reactor Trip Breakers at 0305 on May 12, 1990,
,- -after investigating to ensure this would not cause any further problems. The breakers were closed to allow resetting the Feedwater Isolation Signal. The Reactor Trip Breakers were then reopened and the Steam Generator Levels were returned to normal.
The NRC was notified of this event at 0316 as directed by RP/0/A/5700/10, NRC Immediate Notification Requirements.
Conclusion This event is assigned a cause of Inappropriate Action because of lack of-attention to detail. Operator A was assigned the task of monitoring Steam
, fGenerator levels while feeding and bleeding the Steam Generatvc For chemistry control. Operator A was-periodically opening and closing valve ICF-12? to maintain the level in Steam Generator 1B because the control valve, ICF 195, L was leaking past the seat. Operator A was also assisting in the performanc' of the Auxiliary Shutdown Panel Control Verification PT. While assisting on this procedure, he failed to secure feed to Steam Generator 1B prior to teaching the 82% level setpoint for a Feedwater Isolation Signal. -]a, A-mitigating circumstance in this event is the amount of work on going in preparation for changing modes. The Auxiliary Shutdown Panel procedure requires the operator to monitor the response of the various systems being
- tested and their ef fects on the Reactor Coolant System (EIIS: ABl temperature
- u. and pressure. This procedure also required the operator to realign portions of the systems being tested. .
Also at the_ time of the event, procedure PT/1/A/4200/28B, Train B Slave Relay Test, was being performed by Performance personnel. This procedure required l
..c. ,0 u 3
.u.s. cm um um e l i .19 81,
~
- . t 3 %
NMC form 3304 . U S. huCLE12 041UL ATORY COMM10 BIO 8e
'" ~
"a . . LICENSEE EVENT REPORT (LER) TEXT CONTINUATION arenovs0 oue no mo-oio4 I '
EXPIRES: 0/31/3 P ACitaTY NAmt (Il DOCKET Nueseth (2) .LER NUMG4R 16) PA04 13)
"e"
- wYa'm EMaYa McGuire Nuclear Station, Unit 1 o ls j o lo j o l3 l 6l9 9 l 0 _
Og9 0l0 0l4 oF 0l5 J TEXT W more mese a seg.asser, use asumener MC Asrm m'si d173 s
the control operator to verify equipment conditions before and after segments s of the procedure are. performed. Both control operators had been assisting.
with.this procedure. 4 At the same time, IAE personnel were working on the level control system for (
the VCT. This required one control operator to maintain the VCT level ,
-enually. The second control operator on Unit.1 was performing this task, R is work was being performed as directed by work request 07166A.
mather mitigating circumstance is the avail'able alarms for Steam Generator level. The Steam Generator level deviation alarm is set for +/- 5 percent of program level. In this case, the level deviation alarm came in at 43 percent 7 on the Steam Generator. No other alarms are available to alert the, operators until.the Steam Generator level reaches 82 percent where a Hi-Hi Level Alert annunciator alarms and Feedwater Isolation occurs. A computer alarm for high q Icvel also occurs at this 82 percent level. All four Steam Generators were -[
operating above the + 5 percent deviation alarm because of the feed and bleed ;
I of the Steam Generators.
This event occurred on the first night of this crew's schedule. All normal ~
-Control Room crew members were present. Operator A han performed feed'and q bleed of the Steam Generators many times in the past. At the time of l, occurrance, Operator A was realigning the component cooling system which is l located approximately fifteen feet from the Steam Generator controls. ,
l t i A. review of the Operating Experience Program database for the past twenty-four l mont.hs prior to this event revealed no events' involving Steam Generator L overfill as a result of Inappropriate Action. Therefore, this event is not l considered recurring.
ESF actuations resulting from Inappropriate Actions is considered a recurring problem.
g This event is not Nuclear Plant Reliability Data System (NPRDS) reportable.
l l
There were no personnel injuries, radiation overexposures, or uncontrolled releases of radioactive material as a result of this event.
CORRECTIVE ACTIONS:
Immediate: 1) The Feedwater Isolatior. Logic was reset by Operations personnel.
- 2) Operations personnel restored Steam Generator level to the normal operating range.
Subsequent: 1) Operations personnel performed an NRC notification per RP/0/A/5700/10.
g ,on. .. .v.s. cro, usemoos+ co
.k
..'-l M tiflC Pere 888. . U.S. IeuCLtt.2 REZULAT0nY C0heastgese.
,[ ** ' ' ' . ...- '
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION mmovio ove no. aino-oio4 ex*ines: erwe
. utv a ma ni Occaev=u en m t. . .u .. i., . ....i.
'Ege e% nsyeN (k vsam .: p .
u a McGuire Nuclear Station, Unit-1 o ls j o j o j o l3 l 6l 9 9l0 -
0l 0 l9 0l0 0l5 oF 0l5 TENT If ausse apose e assused see salatumsf NAC sieme was(1M
- 2) Operations Shift personnel met to discuss this event and to emphasize the importance of limiting the activities in 9 progress to minimize the chance of mistakes.
This event was reviewed with the personnel involved.
3)
Planned: 1)' The computer alarm setpoint for Hi Steam Generator Narrow Range Level will be reduced-to provide the Operators an early warning.
SAFFTY ANALYSIS:
The purpose of the Feedwater Isolation signal from a Steam Generator Hi-Hi Level is to prevent water from entering the main steam lines. The added weight of the water could potentially challenge the steamline stress limits.
Water in the steam lines could carry over'and damage the Main Turbine or damage,the Auxiliary Feedwater Pump Turbine.
These potential problems were prevented by the closure of the valves supplying 4 water t'o the Steam Generators. Had the valves failsd to close, annunciator
, alarms and computer alarms would have alerted the operators of the situation..
i The operators would have had sufficient time to restore the levels to normal.
Technical Specifications do not require the ESFAS to be operable until Mode 2.
(Startup). The unit was in Mode 5 at the time of occurrance.
The health and safety of the public were not affected by this event.
I
'V.S. CFoi '988 2 -196 UN f NRO F0mM 336A 3 19 Sh
.