ML20009G208
| ML20009G208 | |
| Person / Time | |
|---|---|
| Site: | McGuire |
| Issue date: | 05/29/1981 |
| From: | Parker W DUKE POWER CO. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| Shared Package | |
| ML20009G209 | List: |
| References | |
| NUDOCS 8108030429 | |
| Download: ML20009G208 (2) | |
Text
y r ,
- m. OFFICIAL COPY DUKE POWER COMPNRW o r p"q'2 , sCj Powra Butt.ntwo$7'-
'-a. +n *<'O,,, .
422 Souta Launcu SrazzT, CnAnt. orts, N. C. 2824a 31 JUN I A8
Vocr PmEsscE*.* TELE *MONE: AREA 704 svEu. Paooveno- May 29, 1981 37s-4o83 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II ?
f h]~ f {f, h. hf?If(
s ge i L LJ Y f 101 Marietta Street, Suite 3100 9y U'gg y.D Atlanta, Georgia 30303 jul Ps , Q Re: McGuire Nuclear Station Unit 1 b':\ u.5.d' ds Docket No. 50-369 /
Y,4 ._ \
Dear Mr. O'Reilly:
Please find attached Reportable Occurrence Report R0-369/81-75. This report ._
concerns the Control Room Outside Air Filter Makeup Fan 1A being declared in-operable. This incident was considered to be of.no significance with respect to the health and safety of the public. - -
Very truly yours, William O. Parker, Jr.
RWO:pw Attachment :
cc: Director Mr. Bill Lavallee Office of Management & Program Analysis Nuclear Safety Analysis Center U.S. Nuclear Regulatory Commission P. O. Box 10412 Washington, D. C. 20555 Palo Alto, CA 94303 M2 M. J. Graham Resident Inspector - NRC McGuire Nuclear Station SrIf i e108030429 810529 PDR ADOCK 05000369 S PDR A
=
.4 McGUIRE NUCLEAR STATION INCIDENT REPORT Report Number: 81-75 Report Date: May 31, 1981 Occurrence Date: May 1, 1981 Facility: McGuire Unit 1, Cornelius, N. C.
Identification of Occurrence: The Control Room Outside Air Filter Makeup Fan 1A was declared inoperable.
Condition Prior to Occurrence: Mode 5 Description of Occurrence: On May 1, 1981-at 0125 hours0.00145 days <br />0.0347 hours <br />2.066799e-4 weeks <br />4.75625e-5 months <br /> the Control Room Out-side Air Filter Makeup Fan 1A was declared inoperable. Broken motor mounts were discovered in the course of routine surveillance. This incident was reportable -
pursuant to Technical Specification 3.7.6. A work request was written, the _
motor mounts were repaired and the fans were returned to service on May 7, 1981 at 1509 hours0.0175 days <br />0.419 hours <br />0.0025 weeks <br />5.741745e-4 months <br />.
Appyrent Cause of Occurrence: The fan motor mounts failed'due to metal fatigue.
Thi. is believed to be ar isolated occurrence, since no other similar failures have been reported.
Analysis of Occurrence: There are two,100% capacity fans which provide outside air for the Control Room. TrainBreyainedoperableduringtheentiretimethat r
the Train A was out of service.
~
- r Corrective Action: A work request was written to repair the motor mounts. The .-'
system was returned to an oparable status at 1509 hours0.0175 days <br />0.419 hours <br />0.0025 weeks <br />5.741745e-4 months <br /> on May 7, 1981.
Safety Analysis: The health and safety of the public were not affected by this incident. The redundant Train B air fan was operable while Train A was out of service.