W3F1-2005-0016, February 2005 Monthly Operating Report for Waterford Unit 3

From kanterella
Jump to navigation Jump to search
February 2005 Monthly Operating Report for Waterford Unit 3
ML050730261
Person / Time
Site: Waterford Entergy icon.png
Issue date: 03/09/2005
From: Murillo R
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
W3F1-2005-0016
Download: ML050730261 (7)


Text

VEt - y

,-- Entergy Entergy Operations, Inc.

17265 River Road Killona, LA 70057 Tel 504-739-6650 W3Fl -2005-0016 March 9, 2005 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001

Subject:

Monthly Operating Report Waterford Steam Electric Station, Unit 3 (Waterford 3)

Docket No. 50-382 License No. NPF-38

Dear Sir or Madam:

Attached is the subject report which covers the operating statistics for the month of February 2005. This report is submitted per Section 6.9.1.6 of the Waterford 3 Technical Specifications for Facility Operating License No; NPF-38. Please note that beginning this month, Gross Electrical Energy Generated values on line 10 of the report are estimated values. Estimated values are being reported due to watt-meter failures on the Main Generator and the in-house load buses. Net generation was able to be determined by measuring current flows in the off-site switchyard.

Should you have any questions regarding the above, please contact R. J. Pollock at (504) 739-6561.

There are no new commitments contained in this submittal.

Sirely, R.J. Murillo Acting Licensing Manager RJM/RJP1 Attachment(s)

W3Fl -2005-0016 Page 2 cc: Dr. Bruce S. Mallett Regional Administrator U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064 NRC Senior Resident Inspector Waterford Steam Electric Station Unit 3 P.O. Box 822 Killona, LA 70066-0751 U. S. Nuclear Regulatory Commission Attn: Mr. N. Kalyanam Mail Stop 0-07 D1 Washington, DC 20555-0001 Wise, Carter, Child & Caraway ATTN: J. Smith P.O. Box 651 Jackson, MS 39205 Winston & Strawn ATTN: N.S. Reynolds 1400 L Street, NW Washington, DC 20005-3502 Platts Energy ATTN: B. Lewis 1200 G. St., N.W. Suite 1000 Washington, DC 20005 lerevents@inpo.org - INPO Records Center (MOR Only)

NRC MONTHLY OPERATING REPORT WATERFORD 3 for February, 2005

SUMMARY

OF OPERATIONS The unit operated at an average reactor power level of 99.9% and experienced no shutdowns or significant power reductions during the period.

PRESSURIZER SAFETY VALVE FAILURES AND CHALLENGES There were no pressurizer safety valve failures or challenges experienced during the month.

3,1100 Page: I of 5

OPERATING DATA REPORT DOCKET NUMBER: 50-382 UNIT NAME: WATERFORD 3 DATE OF REPORT: March 2, 2005 COMPLETED BY: Jim Pollock TELEPHONE: (504) 739-6561 OPERATING STATUS

1. Reporting Period  : February, 2005 Gross Hours in Reporting Period  : 672
2. Currently Authorized Power Level (MWt)  : 3,441 Maximum Dependable Capacity (Net MWe) : 1,075 Design Electrical Rating (Net MWe)  : 1,104
3. Power Level to which Restricted (if any) (Net MWe) N/A
4. Reason for Restriction (if any) . N/A THIS YEAR TO MONTH DATE CUMULATIVE
5. Number of Hours Reactor was Critical 672.0 1,416.0 148,412.3
6. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
7. Hours Generator was On-line 672.0 1,416.0 147,017.0
8. Unit Reserve Shutdown Hours 0.0 0.0 0.0
9. Gross Thermal Energy Generated (MWH) 2,309,099 4,867,561 491,389,386
10. Gross Electrical Energy Generated (MWH) 769,604 1,627,687 164,600,091
11. Net Electrical Energy Generated (MWH) 738,692 1,562,608 157,300,386
12. Reactor Service Factor 100.0 100.0 87.1
13. Reactor Availability Factor 100.0 100.0 87.1
14. Unit Service Factor 100.0 100.0 86.3
15. Unit Availability Factor 100.0 100.0 86.3
16. Unit Capacity Factor (using MDC) 102.3 102.7 85.9
17. Unit Capacity Factor (using DER) 99.6 100.0 83.6
18. Unit Forced Outage Rate 0.0 0.0 3.3 1=2X5 Page: 2 of 5

OPERATING DATA REPORT DOCKET NUMBER: 50-382 UNIT NAME: WATERFORD 3 DATE OF REPORT: March 2, 2005 COMPLETED BY: Jim Pollock TELEPHONE: (504) 739-6561 OPERATING STATUS (Cont.)

19. Shutdowns Scheduled over next 6 months (type, date and duration of each):

REFUEL OUTAGE #13 - commencing on April 17, 2005 - 45 day outage

20. If Shutdown at end of report period, estimated date of startup: N/A
21. Unit is in Commercial Operation.

THIS YEAR TO MONTH DATE CUMULATIVE

22. Hours in Reporting Period 672 1,416 170,353
23. Unit Forced Outage Hours 0.0 0.0 5,008.1
24. Nameplate Rating (Gross MWe) 1,200 Max. Dependable Capacity (Gross MWe) 1,120
25. If changes occur in capacity ratings (Items 2 and 24) since the last report, give the reasons:

N/A 3.21"S0 Page: 3 of 5

AVERAGE DAILY UNIT POWER LEVEL DOCKET NUMBER: 50-382 UNIT NAME: WATERFORD 3 DATE OF REPORT: March 2, 2005 COMPLETED BY: Jim Pollock TELEPHONE: (504) 739-6561 Reporting Period : February, 2005 (NET MWe)

DAY Avg. Power Level DAY Avg. Power Level 1 1,101 16 1,103 2 1,101 17 1,102 3 1,101 18 1,102 4 1,099 19 1,103 5 1,103 20 1,098 6 1,100 21 1,099 _,

7 1,105 22 1,098 8 1,096 23 1,088 9 1,100 24 1,079 10 1,102 25 1,098 11 1,106 26 1,102 12 1,105 27 1,096 13 1,104 28 1,092 14 1,098 15 1,098 INSTRUCTIONS:

On this form, list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.

Reflects On-Line Net Generation.

3=ZX5 Page: 4 of 5

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NUMBER: 50-382 UNIT NAME: WATERFORD 3 DATE OF REPORT: March 2, 2005 COMPLETED BY: Jim Pollock TELEPHONE: (504) 739-6561 REPORTING PERIOD: February, 2005 Outage Date

  • Duration ** Shutdown Cause, Comments and Number (yymmdd) Type (Hours) Reason Method Corrective Actions NIA TYPE REASON F - Forced A - Equipment Failure (explain)

S - Scheduled B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training and METHOD License Examination 1 - Manual F - Administrative 2 - Manual Scram G - Operational Error (explain) 3 - Automatic Scram H - Other (explain) 4 - Continuation from Previous Period 5 - Power Reduction 6 - Other (explain) 3,2205 Page: 5 of 5