W3F1-2022-0037, Submittal of Owner'S Activity Report Form for Inservice Inspection Performed During Operating Cycle 24 / Refuel 24

From kanterella
Jump to navigation Jump to search
Submittal of Owner'S Activity Report Form for Inservice Inspection Performed During Operating Cycle 24 / Refuel 24
ML22220A306
Person / Time
Site: Waterford Entergy icon.png
Issue date: 08/08/2022
From: Milster L
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
W3F1-2022-0037
Download: ML22220A306 (7)


Text

E) entergy Leia Milster Manager Regulatory Assurance 504-739-6250 W3F1-2022-0037 August8,2022 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

Subject:

Submittal of Owner's Activity Report Form for lnservice Inspection Performed During Operating Cycle 24 / Refuel 24 Waterford Steam Electric Station, Unit 3 Docket No. 50-382 Renewed Facility Operating License No. NPF-38 Attached is the subject report which covers the Owner's Activity Report Form, OAR-1, for Waterford 3 Operating Cycle 24 / Refuel 24, enclosed as Attachment 1. This report is being submitted in accordance with ASME Code Case N-532-5, "Repair/Replacement Activity Documentation Requirements and lnservice Summary Report Preparation and Submission,"

which was adopted for use at Waterford 3 commencing its incorporation into Regulatory Guide 1.147 and subsequent revision to CEP-RR-001 "ASME Section XI Repair/Replacement Program" on October 13, 2021.

The OAR-1 form is prepared and certified upon completion of each refueling outage and submitted within 90 calendar days of the completion of the refueling outage. This OAR-1 form provides: (1) a listing of items with flaws or relevant conditions that exceeded the acceptance criteria of Division 1 and that required evaluation to determine acceptability for continued service and (2) an abstract for repair/replacement activities that were required due to an item containing a flaw or relevant condition that exceeded Division 1 acceptance criteria. A copy of this letter and the attached report is also being submitted to the office of the Louisiana State Fire Marshall.

There are no new commitments contained in this submittal.

Please contact Leia Milster, Regulatory Assurance Manager, at (504) 739-6250 should you have any questions regarding this submittal.

Entergy Operations, Inc., 17265 River Road Killona, LA 70057-3093

W3F1 -2022-0037 Page 2 of 2 Leia Milster LM/llb

Enclosure:

1. Owner's Activity Report for lnservice Inspection Performed During Operating Cycle 24/ Refuel 24 cc: NRC Region IV Regional Administrator NRC Senior Resident Inspector - Waterford 3 NRC Project Manager - Waterford 3 Mr. Daniel H. Wallis Office of the State Fire Marshall 8181 Independence Blvd.

Baton Rouge, LA 70806

Enclosure to W3F1-2022-0037 Owner's Activity Report for lnservice Inspection Performed During Operating Cycle 24/Refuel 24

ATTACHMENT 7.2 Program Section No: CEP-RR-001 Page No.: l of 3 Revision No.: 318 FORM OAR-I OWNERS ACTIVITY REPORT Report Numher: _ _ _ _ _ _ _ _ _ _ _ __ Page _1_ of_4_

Pl ant: __W-'-'--'a=t-=-e,'--'*f. : .o. :. . rd:: . . :.:S-=-tc='a=n.:. :.1-=E=*l=e-=-ct=r-=-=ic:. . *':..:..S=ta=t1:...:.*o=n:..:. .-=-1-'-7~6=5-=Rc..: . :. .c"-=

i

  • c-=-r-=-R=lc. .: J;,=u.1:. :. .-=-K.::.:i:..:. .;h:.:. .:>n='=l*-=I=-'=t._,7. . ;;0:.. .:.:0=5-'-7_

Unit No: _ ___,.;;.3_ _ Commercial Service Date: 09/24/1985 Refueling Outage No.: ---=2=-4'----_

(if applicabk)

Current Inspection Interval: __4_;_1_11 . . : .I=S=-I=In:. :. :t=e-=-n,,;.,.:*,=1!_ _ _ _ _ __

(1st.2nd. 3rd. -ith. Otha)

Current Inspection Period: 2m..1 Period (Isl.2nd. 3rd)

Edition and Addenda of Section XI applicahlc to the Inspection Plans: 2007 Edition Throu!!h 2008 Addenda Date and Revision of Inspection Plans: 10/13/2021 Revision 11 of SEP-ISl-104 Edition and Addenda of Section XI applicahlc to repair/replacement activities, if different than the Inspection Plans:

Code Cases used for inspection and evaluation: _ _;N: . . :. . .;-5:;:.;.3:. . :2=---=5_ _ _ _ _ _ _ _ __

(if applicable. including cases modified by Cas1: N-532 und later revision s)

CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report arc correct: (h) the examinations and tests meet the Inspection Plan as required hy the ASME Code, Section XI: and (c) the repair/replacement activities and evaluations supporting the completion of Refuel 24 conform to the requirements of Section XI.

(Rcfuding outage numher)

Signed: R. Luter ~- ~ __W_1.:~'l~d_in"'""g__/_R_e,._p_a_ir_R~e.....'p~l~a_ce_'n_1_e_n~t~E_n.._!!~in~e~'e~r___ Date: --~7/~1~3~/2~<~>.2= *2 ~ - - - - -

Owner or Owner's Dcsig:nce. Title CERTIFICATE OF INSERVICE INSPECTION I. tht: undt:rsigned. holding a valid commission issued hy the National Board of Boiler and Pressure Y1.:sscl Inspectors an<l employed hy The Hartford Steam Boiler Inspection and Insurance Companv of Connecticut have inspcctc<l the items dcscrihed in this Owner's Activity Report. and state that. to the hest of my knm,vlcdge and helief. the Chvncr has performed all activities represented hy this report in accor<lance with the requirements of Section XI.

By signing thi s certificate neither the Inspector nor his employer makes any warranty. expressed or implied. concerning the repair/replacement activities and evaluation descrihed in thi s report. Furthermore. neither the Inspector nor his employer shall he liahle in any manner for any personal injury or property dam age ur loss of any kind arising from or connected with this inspection.

Commissions: /5 C/7 t: 11/L

( National Board Numba and Enc!or~emenl)

ATTACHMENT 7.2 Program Section No: CEP-RR-001 Page No.: 2 of 3 Revision No.: 318 FORM OAR-I OWNERS ACTIVITY REPORT Report Nurnhcr: _ _ _ _ _ _ _ _ _ _ __ Pagc_Lof_:L_

Plant: Waterford Steam Electric Station. 1765 River Road. Kilona. La. 70057 Unit No: _ _ 3___ Commercial St.:rvicc Date: 09/?4/1985 Refueling Outage No.: _2+/-._

(if applicabk)

TABLE l:

ITE:\IS Wrrn FLAWS OR RELEVANT CONDITIONS TII.-\T REQUIRED EVALl'..\TION FOR CONTINUEO SER\'ICE Examination Item Description Evaluation Description Category and Item Number NONE N()NE NONE 2

TABLE 2:

ABSTRACT OF REPAIR/REPLACEMENT ACTIVITIES REQUIRED FOR CONTINUED SERVICE Code Item Description Description of Work Date Repair/Replacement Class Completed Plan Number 3 3CC1 1/2-46 Bl; Reactor Remove Temporary Modification 6/14/22 22-RR-02 Coolant Pump lB Seal Cooler EC-91068, replace piping.

Component Cooling Water Reference CR-WF3-2021-05004 Outlet and CR-WF3-2021-04997 3 3CC1 1/2-41 Al; Reactor Replace degraded piping. 6/14/22 22-RR-04 Coolant Pump lA Seal Cooler Reference CR-WF3-2021-04998 Outlet and CR-WF3-2022-2008, CR-WF3-2021-05004 3 3CC1 1/2-53 A2; Reactor Replace degraded piping. 6/14/22 22-RR-05 Coolant Pump 2A Seal Cooler Reference CR-WF3-2022-02086 Outlet Fail-Safe Tubing 3 3CC11/2-59 B2; Reactor Replace degraded piping. 7 /12/22 22-RR-06 Coolant Pump 2B Seal Cooler Reference CR-WF3-2022-02103 Outlet Fail-Safe Tubing and CR-WF3-2021-05004 3 3CC11/2-47 Bl; Reactor Replace degraded piping. 6/14/22 22-RR-09 Coolant Pump lB Seal Cooler Reference CR-WF3-2022-02102 Outlet Fail-Safe Tubing and CR-WF3-2021-05004 3 3CC1 1/2-41 Al; Reactor Replace degraded piping. 6/14/22 22-RR-10 Coolant Pump lA Seal Cooler Reference CR-WF3-2022-02191 Outlet and CR-WF3-2021-05004 2 2FW18-41B; Steam Replace pipe in accordance with 5/11/22 19-RR-47 Generator 2 Inlet EC-73451 and EC-73453 2 2FW18-40A; Steam Replace pipe in accordance with 5/11/22 19-RR-48 Generator 1 Inlet EC-73451 and EC-73453 2 SI MVAAA1401 B; Low Replace 2SIO 3/4-352 leaking 7 /12/22 22-RR-36 Pressure Safety Injection pipe. 11/4" reducing insert will Header to Reactor Coolant be replaced. Reference Loop lB Check Valve Test CR-WF3-2022-04273 Connection 1 RC MPZR000l; Reactor Replace degraded heaters. 6/14/22 22-RR-03 Coolant System Pressurizer EC-83474 Vessel 1 SI MVAAA512 A; Reactor Replace valve, leaks by seat. 6/14/22 19-RR-41 Coolant Loop 1 Hot Leg Reference EC-83354 Injection Check 1 RC ITE0112 CDl; Reactor Install temporary plug in 7 /12/22 22-RR-28 Coolant Loop lB Cold Leg thermowell in accordance with Temperature EC-92952 3

3 NF Support ACR-444 Install Missing Lug On Line 7/12/22 22-RR-35 3AC10-15, For ACR-444 CR-WF3-2022-2595 CR-WF3-2022-4007 4