 Issue dateTitleTopic
ML20196D09123 November 1998Notice of Violation from Insp on 980920-1031.Violation Noted:On 981001,electricians Placed Single Degraded Cell Associated with Operable 1E Battery Bank on Single Cell Charge
ML20154J8619 October 1998Notice of Violation from Insp on 980809-0919.Violation Noted:On 980831,licensee Did Not Promptly Correct Condition Adverse to Quality in That 'C' Residual Heat Removal Pump Rendered InoperableCondition Adverse to Quality
ML20237E49825 August 1998Notice of Violation from Insp on 980628-0808.Violation Noted:As of 980810,util Had Not Corrected Known Deficiency in Verifying MSIV Full Closed During Springs Only Full Stroke Closing Tests
ML20236T16021 July 1998Notice of Violation from Insp on 980517-0627.Violation Noted:As of Oct 1997,chemistry Technicians Did Not Sample & Analyze Diesel Fuel Oil Deliveries for Particulates & Did Not Report Results by Written Notification within 14 Days
ML20249A20310 June 1998Notice of Violation from Insp on 980223-0319 & 0427-30. Violation Noted:Conditions Adverse to Quality Were Not Promptly Identified & CorrectedUnanalyzed Condition
Emergency Lighting
Condition Adverse to Quality
Fire Protection Program
ML20249A1074 June 1998Notice of Violation from Insp on 980405-0516.Violation Noted:During Refueling Outage RF03 in Dec 1990 Licensee Did Not Maintain RHR Sys in Operation
ML20217N62224 April 1998Notice of Violation from Investigation Conducted by Oi. Violation Noted:Safeguard Event Log,Required to Be Maintained by Licensee,Was Not Complete & Accurate in All Matl Aspects
ML20217H80523 April 1998Notice of Violation from Insp on 980222-0404.Violation Noted:Three Examples of Inadequate Accomplishment of Procedure Control Associated W/Temporary Equipment Installed in Plant Svc Water Intake StructureTemporary Modification
Scaffolding
ML20217C67120 March 1998Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $55,000.Violation Noted:On 971112,while Reactor Was in Cold Shutdown W/Rv Head Removed,Operators Did Not Verify That CR Position Did Not Change During WithdrawalSafe Shutdown
Shutdown Margin
ML20199L4793 February 1998Notice of Violation from Insp on 971126-980103.Violation Noted:On 971124,maint Technicians Failed to Follow HC.IC-DC.ZZ-0140(Q),Rev 3, Device/Equipment Calibration Masonleilan Pressure & Temperature Controllers
ML20199D31712 November 1997Notice of Violation from Insp on 970824-1004.Violation Noted:On 970914,electric motor-driven Fire Pump Supply Breaker Opened During Electrical Bus Swap Which Rendered Pump InoperableReactor Vessel Water Level
Condition Adverse to Quality
ML20196J65320 October 1997Notice of Violation from Insp on 970202 & 0317.Violation Noted:In Apr 1994,licensee Made Changes to Facility That Involved USQ Without Prior Commission Approval
ML20210N90611 August 1997Notice of Violation from Insp on 970601-0712.Violation Noted:Inoperable HPCI Sys Injection Valve Was Not Promptly Identified
ML20140J38112 June 1997Notice of Violation from Insp on 970429-0531.Violation Noted:Failing to Adhere to Established Procedural Guidance for safety-related Activities Were Identified,Significant Condition Adverse to QualityCondition Adverse to Quality
ML20148D20123 May 1997Notice of Violation from Insp on 970318-0428.Violation Noted:On 970423,operators Failed to Shut Six of Twelve Cylinder Indicator Test Cocks Following Completion of C Emergency Diesel Generator pre-start Checks
ML20137W77614 April 1997Notice of Violation,App B for Insp on 970202-0315.Violation Noted:On 970204-0315,RCICS Turbine Exhaust Check Valve Experienced Repeat Inservice Test Failure.Corrective Action Not Taken to Preclude Repetition of ConditionCondition Adverse to Quality
ML20137W77014 April 1997Notice of Violation,App a for Insp on 970202-0317.Violation Noted:On 970226,scaffolds Installed in safety-related Areas, Including a & B RHR Pump Rooms & Standby Liquid Control Pump Room in Rb,Lacked Appropriate Construction DocumentationScaffolding
ML20135A36521 February 1997Notice of Violation from Insp on 961222-970201.Violation Noted:Operators Performed Logic Sys Functional Test of TIP Primary Containment Isolation Sys Logic,Per TS SR 4.3.2.2 Surveillance Activity on 960717
ML20134B67427 January 1997Notice of Violation from Insp on 961110-1221.Violations Noted:Vital Area Access Control & Badge Sys Requirements of Util Security Plan Were Not Implemented for Listed Examples
ML20133A44911 December 1996Notice of Violation from Insp on 960815-0903.Violation Noted:On 960814,vital Area Access Not Physically Controlled in That Positive Access Control Over Photobadge Keycards Compromised,Creating Opportunity for Unauthorized Access
ML20135D2075 December 1996Notice of Violation from Insp on 960922-1109.Violation Noted:Offsite Safety Review Staffing & Review Requirements Were Not Met for Listed Examples
ML20129F64423 October 1996Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $150,000 Based on Licensee Failure to Plan Appropriate Surveillance Testing on Certain safety-related Equipment Following MaintenanceCondition Adverse to Quality
ML20129D08418 October 1996Notice of Violation from Insp on 960804-0921.Violation Noted:Changes Implemented by Licensee Identified That Involved Failures to Appropriately Evaluate Proposed Changes Involved Change in TS or Unreviewed Safety QuestionsTemporary Modification
ML20058P93615 October 1993Notice of Violation from Insp on 920614-0725.Violation Noted:Licensee Determined Several Instances in Which Personnel Assigned to Fire Watch Patrols Failed to Perform or Complete Function as Required by TS & Falsified RecordsFire Barrier
Fire Protection Program
Fire Watch
Hourly Fire Watch
ML20248J18731 March 1989Notice of Violation from Insp on 890124-0313.Violation Noted:Two Electrical Jumpers Installed in Controls of Drywell Equipment Drain Pumps W/O Meeting Administrative Controls for Temp Mods & Not Removed Until DiscoveredTemporary Modification
ML20154M37416 September 1988Notice of Violation from Insp on 880712-0829.Violation Noted:Measures Established for Tagging Valves Not Adequate & Relay for Valve GS-HV-4958 Erroneously Removed on 880527
ML20151L21327 July 1988Corrected Notice of Violation Re Dept of Labor 880401 Final Decision & Order Holding That Former Contractor Employee Working at Plant Discriminated Against by Contractor for Raising Safety Concerns & Holding Up Test Packages
ML20151J26114 July 1988Notice of Violation & Proposed Imposition of Civil Penalty. Noncompliance Noted:A Francis Demoted from Supervisory Position to Technician Position for Engaging in Protected Activities
ML20151W16627 April 1988Notice of Violation from Insp on 880126-29.Violation Noted: Equipment Qualification Files J-601,J-313 & E-171 Contained Deletions,Whiteout Changes of Original Text Not Initiated or Dtd
ML20151C4584 April 1988Notice of Violation from Insp on 880209-0321.Violation Noted:On 880226,recirculation & Ventilation Sys Fan Flow Pressure Switch Not Correctly Restored to Svc During Implementation of Procedure IC-DC.ZZ-057
ML20150A8197 March 1988Notice of Violation from Insp on 880105-0208.Violation Noted:Liquid Radwaste Discharge Line to Cooling Tower Blowdown Line Does Not Isolate on Circuit or Instrument Downscale Failure & Function Not Tested Quarterly
ML20237E22218 December 1987Notice of Violation from Insp on 870714-0817.Violation Noted:Two Discharge Pressure Instruments for RHR Pump C Inoperable Due to Closure of Isolation Valve for Pressure Transmitters.W/Enforcement Conference Meeting Summary
ML20236N2675 August 1987Notice of Violation from Insp on 870609-0713.Violation Noted:Valve IEP-HV-2225 A/B/C/D & IEG-HV-2496 A/B/C/D/ Did Not Have Thermal Overload Protection Bypass Circuit Installed,Per Tech Spec 3.8.4.2
ML20212M1455 March 1987Notice of Violation from Insp on 870101-0209Grab sample
ML20211M06412 February 1987Notice of Violation from Insp on 870112-16
ML20213A12727 January 1987Notice of Violation from Insp on 860813-0902.Violations Noted:Failure to Place Reactor Into Startup,Hot Shutdown or Cold Shutdown While Vacuum Breaker Assemblies & Acoustic Monitors Inoperable
ML20213A06922 January 1987Notice of Violation from Insp on 861203-05
ML20207N0769 January 1987Notice of Violation from Insp on 861201-04
ML20207N1345 January 1987Notice of Violation from Insp on 861020-31
ML20214W9048 December 1986Notice of Violation from Insp on 861014-1117
ML20214V3493 December 1986Notice of Violation from Insp on 861027-31
ML20214K81412 November 1986Notice of Violation from Insp on 860924-1003
ML20206U60224 September 1986Notice of Violation from Insp on 860812-0908
ML20212Q16026 August 1986Notice of Violation from Insp on 860707-24
ML20204H75631 July 1986Notice of Violation from Insp on 860610-0714
ML20204F52028 July 1986Notice of Violation from Insp on 860623-0703Shutdown Margin
ML20202D8979 July 1986Notice of Violation from Insp on 860519-30
ML20198E21120 May 1986Notice of Violation from Insp on 860317-0430
ML20140H18927 March 1986Notice of Violation from Insp on 860127-0207
ML20149M12414 March 1986Notice of Violation from Insp on 860107-17.Violation Noted: Startup Test Procedure TE-SU.ZZ-041, Full Core Shutdown Margin Demostration, Rev 0,reviewed,approved & Issued W/ Listed DeficienciesShutdown Margin