, O>mnw>nwcalth lilimn Comp.my

e. Quad Citics Generating Station j 22710 200th Awnue N>rth Cordova. II. 612 42-9740 rci wou22u SVP 99-004 i

January 21,1999 l l

i I

U. S. Nuclear Regulatory Commission ATTN: Document Control Desk i Washington, D C 20555 l

Quad Cities Nuclear Power Station Unit 1 and Unit '

Facility Operating License Nos. DPR-29 and DPR-30 j NRC Docket Nos. 50-254 and 50-265 l

Subject:

Notification of Changes of Bases 3/4.10.K and 3/4.10.L.

Residual Heat Removal and Coolant Circulation

/

Pursuant to 10CFR50.59, Commonwealth Edison (Comed) Company has changed the Bases of Facility Operating Licenses DPR-29 and DPR-30, Appendix A, Technical Specifications Bases

/

for Sections 3/4.10.K and 3/4.10.L.

The following information will be included in the Bases for sections 3/4.10.K and 3/4.10.L. g[

3.4.10.K/3.4.10.L Add Statenient: The RllR Shutdown Cooling subsystem configuration was not designed to be throttled to sufficiently maintain constant reactor coolant temperature. Continuous or intermittent operation of one subsystem can maintain and reduce the reactor coolant temperature as required. Each RHR shutdown cooling subsystem is considered OPERABLE ifit can be manually aligned either remotely or locally in the shutdown cooling mode.

This change in the Technical Specification Bases provides a description of the design and operation of the Residual Heat Removal (RHR) Shutdown Cooling subsystem. This change also provides consistency with Technical Specification footnote (e) of Section 3/4.5.A.2 and footnote (a) of Section 3/4.5.B, related to manual alignment and an OPERABLE subsystem.

9901280137 990121 PDR ADOCK 05000254 P PDR L A Unicom company J

L USNRC 2 January 21,1999 t . SVP-99-004

- If there are any questions 'or comments concerning this letter, please refer them to

- Mr. Charles Peterson, Regulatory Assurance Manager, at (309) 654-2241, extension 3609.

Sincerely, Cp yw N ~

Jccl P. Dimmette, Jr; Site Vice President ~

._ Quad Cities Station -

Attachment:

Technical Specification Bases cc:  : Regional Administrator-NRC Region III NRC Senior Resident inspector - Quad Cities Nuclear Power Station ef

u. ,2

l ATTACIIMENT i .

TECIINICAL SPECIFICATION HASES l

, SVP-99-004 1

Page 1 of 3 I

i Marked-up Page B.3.4.10-3