ST-HL-AE-3563, 1RE02 Inservice Insp Summary Rept for Sys Pressure Tests at South Texas Project Electric Generating Station,Unit 1

From kanterella
Jump to navigation Jump to search
1RE02 Inservice Insp Summary Rept for Sys Pressure Tests at South Texas Project Electric Generating Station,Unit 1
ML20064A882
Person / Time
Site: South Texas STP Nuclear Operating Company icon.png
Issue date: 09/08/1990
From: Mcintyre A, Pathak A, Timmaraju S
HOUSTON LIGHTING & POWER CO.
To:
Shared Package
ML20064A880 List:
References
ST-HL-AE-3563, NUDOCS 9010010168
Download: ML20064A882 (14)


Text

e-ATTACHMENT ST-HL AE-S56 3

,[ PAGE A 0F S COVER SHEET 1RE02 INSERVICE INSPECTION

SUMMARY

REPORT FOR SYSTEM PRESSURE TESTS AT THE SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION, UNIT 1 P. O. Box 289 Wadsworth, Texas 77483 USNRC DOCKET NO: 50 498

, OPERATING LICENSE NO: NPF 76 COMMERCIAL OPERATION DATE: August 25, 1988 Prepared by: S 9" 8"90 A. P Pathak, Consulting Engineer - Codes & Standards Reviewed by: ^= = ~- w

  • 9'9o S. Timmaraju, Sr. C' onsulting Engineer - Codes & Standards Approved by: 4 M MA > 9 - 8 C)o A. C. McIntyre, Maniger Design Engineering Department AP/WS100/034  :

901001016e 900914

{DR A00CKOSoOg8

~s

!-IJ 5 3 EEE5

" ST-HL AE ss + 3 0F 9 PAGE _3 a SCOPE 1RE02 SYSTEM PRESSURE TESTS The examinations summarized in this report were performed la accordance with the 1983 Edition through Summer 1983 Addenda of the ASME Code,Section XI which is applicable to the South Texas Project Electric Generating Station Unit 1.

This report covers selected ASME Code Class 1,2, and 3 Systems / Components.

Examinations and tests required by the Code are scheduled in accordance with

" Inspection Program B" as oefined in IWB-2412 and IWC 2412 for ASME Code Class 1 and 2 Systems / Components. All ASME Code Class 1 components were examined as prescribed by Table IWB-2500-1, Examination Category B P which established the examination frequency at each refueling outage. The ASME Code Class 2 and 3 Systems / Components were selected on a random basis. This random selection process will continue until all ASME Code Class 2 and 3 Systems / Components are examined in accordance with Table IWC 2500-1, Examination Category C-H and Table IWD 25001, Examination Category D A, D B, and D C for ASME Code Class 2 and 3 Systems / Components, respectively. These examination categories for ASME Code Class 2 and 3 Systems / Components established the examination frequency at each inspection period. The remaining first period examinations are anticipated to be completed by the end of the third refueling outage which should occur within the first period time frame.

The System Leakage Test [IWA 5211(a)) conducted on Class 1 Systems / Components in accordance with Examination Category B P also satisfied the system pressure test required by IWA-5214 (c) subsequent to the disassembly and reassembly of mechanical joints in ASME Code Class 1 components.

AP/WS100/034 1

ynV3H M I

'~ SI Hl-V3 as$r dfida Y 03

" 6 4Voz ? oJ E

_#' douM MIS-t ORMIMeS MIdoM3 4081 INSIMAI3W INSAROZIOMS ys sebnysep qA ggo imoaisious og )qe YENI 3 ope gntes t- omue2 Hviste irstyira 9 dome 2 o:evuA 3oo2210 MneJ' d' O* tom 1100' Hmssa' n 44001

)N mo eup yppsees og orue2(

t' diwug Sonay ,wxes gapeog moogats oeueae21:m 6M1im d' o goz gge' nepsna21y' n 4479E

)H me eup yppsess o; dieuq(

E' attug m it I  ?? omueJ ge221;iooge o; yniyosT eti m )13 rebnT2SP( N/V S' W 23T*t 5e2Atse qsgo og/gg/gg 9' Negimut gov 2p yuqaJ ;oJ MT4 N/V ta o:udoueuts rusdeoep ygJ 0E3 3WSS i dIdGG VNO )F5ODiNIS gsun3eetnaeJ JO T oJ Nsur;eognaeJ o2 tustett02 ggege oJ getiouvt yddnzteuouco oa lustvII'J S8P 81 No' duuluco No' Soap Nc' iD!VDIOM AliSSIT DNEDSLI@ EGINllEMIlG/ e iMi01 M i01V nilslCDDOS3 )H( li0LE N/V 3ET60 sIH' emyn IWTETNSCIOTV niiSlGDG053 )H( 3iET N/V Mt9961 ,,

sIH' oa n y n THICINS01018 RSJUODISE )H( tiEC N/V Mt996C sId" )ENliHVIE TWIETNSDI0IO M3SJGD00S3 )H( 3 TEE N/V Mt996E stN' e e v n I iHICINE' lot 3 niiSJC D niSS )H( ~

ETE7 N/V Mf9967 diD!SSOBI E iHITINd2101V nliSJCD00S3 )H( C171 N/V Mt8560 13 M IHiETNJdi0TY MliSlGOG052 )H( I-iiS3SG000( M/V CS

!3 M iHTETNddl0IH niiSJGD0053 )H( E-iiS3590001 N/V ;6 13 M THiETNddl0ID niiSJGDDISS )H( E-iiS3590001 N/V EC NM THIETNddl0IG RliSlGD00S3 )H( 1-iiS35900CI M/V EI DYSS i dIdINC REY 6E )I( N/V M/V N/V 3 WSS 1-AVINiiS AVHIVIS N/V N/V N/V 1

NOI3i snddt suautut syeets tu ;enu o; tists' saetoyas' o2 p2mTuas rueX qe nsop' d2cppep )t(

siza is 9 T/E iu' X 11 Tu );;( iu;onusttou iu 12ws i 1y2on94 9 ou gnis 2edo21 is Tuoinpop ou seoy syset' sup )E( seoy s4881 Te urtge2ep eup gge snuqaJ o; sysats is t.eco2 pop et gys god o; gyts ;ouua NI SI

  • 31'l
  • 14303

. I PAGE 2 of 3 4

FORM NIS-1 (Back)

  • 8.1kanination Dates 11/02/89 to 06/21/9C 9. Inspection Interval fatra 08/25/88 to 08/25/9B I

.10. Abstract of Busninatims. Include a list of esamirviens and a statenant concomirs status of work requirw4 for current interval. Refer to supplanantal L4et Page 3 of 3. t

11. Atatract of Conditions Noted No relevant condities affectire pressure retainirs boundaries were noted.
12. Abstract of Corrective Measures Reconnended and Taken Refer to Sgplenantal ihmet Page 3 of 3. I We certify that the statanents made in this report are correct and the ensninations and corrective reasures taken ceform to the rules of the AM Code,Section XI.  ;

Certificate of Authorization No. (if applicable) N/A Ehpiration Data N/A f Date NwY DC 19% Signed Hauston 1.lahtira ir Power Co. KN1 Omer X 9. Hgy, Jr.

GRTIFICAIE & DEERVJG DSM CTICN I, the undersigned, holdire a valid cairnission issued by the Nationa. Board 1 Boiler and Pressure Vessel  !

2nspectors and the State or Province of Tnxas and enployed ty Arkw .aht IOtual Insurance Co. of '

Norwood. NASS. have inspected the s. w -nts described in this  ;

CWner's Report durits the period 6 -//- To to 74& - To , and state L that to the best of rqr knowledge and belief, the Osner has perforned examinations and taken corrective neasures described in this Owner's Report in accordance with the inspection plar. and as required by the ASME j

Code,Section XI.

By signirs thM certificate reither the Inspector nor his anployer makes any warranty, expressed  !

l or inplied, concerning the examinations and corrective measures described in this Owner's Report. Furthernere, reither the Inspector nor his enployer shall be liable in any manner for any persmal injury or property danage or a loss of any kind arisirg frtzo or connected with this inspection.

FACICRY M7IthL SYSIIH v

- - v- -

Cannissions 'DC-826 B. R. Russell, inspector's Signature National Board, State, Province, and lihdormanents acte %76- 19 90 l

l NIS).CLI.1RE02

ATTACHMENT ST HL AJ.rs53 PAGE__ 1 0F_ Q PAGE 1 of 3

, FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the trovisions of the ABME Code Rules

1. Owner Mcuston Liahtira & Power Casany Electric 'Ibwer. P. O. Box 1700, Haustem, 'DC 77001 l .

(Nme and Address of Owner)

! 2. Plant South Texas Project Electric Gereratira Statice P. O. Bax 289, Wadsworth, 'DC 77483 (Nane and Address of Plant)

3. Plant thit 1 4. Owner Certificate of Autts>rization (if required) r/A
5. M mercial Service Date 08/25/88 6. National Board 14mber for thit N/A
7. Cu yanents Inspected A9E OCIE C1 ASS 1 FIPDG AND CDf0ENIS Manutacturer Caponent or Manufact.urer or Installer State or National Appartenance or Installer Serial No. Prwince No. Board No.

REACIIR VISSEL COSUSIICH BGINEERDC/

1R10DRv101A WEETDOCUSE (M) 11073 N// 22190 SIM. GNERAER 1R121N9G101A WESTDOCUSE (M) 2131 N/A W18691 SIM. GNERATOR 1R121NsG101B ul5rD G tDSE (M) 2132 N/A W18692 SIM. GNERAER 1R121N9G101C WESIDGOUSE (M) 2133 N/A W18693 SIM. GENERAIUt IF121NSG101D WESIDOCUSE (M) 2134 N/A W18694 PIGSSURIZER 1R111NPZ101A WESIDGOUSE (M) 2141 N/A W18590 IC IWP 1R131hPP101A WESTDOCUSE (M) 1-115E580001 N/A 28

)C PWe AR131NPP101B WESTDGOUSE (M) 2-115E580001 N/A 29 IC Pee IR131NPP131C WESTDGOUSE (M) 3-115E580CD1 N/A 30 IC Pue IR131NPP101D WESTDGEUSE (M) 4-115E580001 N/A 31 CUWSS 1 FIPDC I!BA!KL (I) N/A N/A N/A CLASS 1

, VALVES VARIOUS N/A N/A N/A IGIE: Supplanental sheets in form of lists, sketches, or drawings may be used, prwided (1)

ire is 81/2 in. X 11 in., (2) information in itens 1 through 6 on this report is irv.1.ded on each sheet, a:x! (3) each sheet is runtered ard the runber of sheets is recorded at the top of this form.

HISI.CLI.1RE02

i'

  • PAGE 2 cf 3' ,

TORM NIS-1 (Back) '~

8. Busnination Dates 11/02/89- to _ 06/21/90 9. Inspection Interval fran _08/25/88 to 08/25/98
10. Atn. tract of Eneminations. Include a list of waninations and a statenant concerning status of work regairm! for current interval. Refer to %pplemstal 9 met Page 3 of 3.
11. Abstract of Consilles Noted No relevant conditicas affecting pressure retainirig boundaries were noted.
12. Abstract of Corrective Measures Reconnended and Taken Refer to Supplanantal Smet Page 3 of 3.

We certify that tim statsients made in this report are correct and the examinations and corrective reasurws taken ocatorm to the rules of the AM Code,Section XI.

' Certificate of Authorisati<n No. (if applicable) N/A EMpiration Date N/A Date M w %C - 19D Signed Houston Liahtira & Power Co. By%d V

Owner X 9. Hgy, Jr.

QRTIFICA3E T INSEPVIG INSPICTICN I, the undersigned, holdirig a valid conmissica issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Prwince of Texas and enployed by Arkwright itstual Insurance Co. of Norwd, WS. have inspected tie empenents described in this Owner's Report during the period G -//- To 7-d -To to . and state that to the best of ny knowledge and telief, the Osner has performed examinations and taken corrective neasures described in this Chmer's Report in accordance with the inspection plan and as required by the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his enployer makes any warranty, expressed or inplied c: cerning the exantnations and corrective naasures described in this Owner's Report. Furthernere, neither %e Inspector nor his enployer shall be liable -in any menner for any personal injury or property danwy or a loss of any kind arisirs fran or connected with this inspection.

FACIIRY MJIUAL SYSIEM

-g - Ccranissions *Dl-826 B. R. Russell, Inspector's Signature National Board, State, Prwince, and Ehdorsements hte ~7 76- 19 90 i

w-i NIS1.CL1,1RE02 l

PAGE 2 of 3 FORM NIS-1 (Back)

8. Eunination Dates 11/02/89 to 06/21/90 9. Inspection Interval fran 08/25/88 to 08/25/98
10. Abstract of Runinations. Include a list of examinations and a statement concernirs status of work twquired for current interval. Refer to Supplanantal !hmet Page 3 of 3.
11. Abstract of Conditions hoted No relevant emdities affecting pressure retaining beundaries were noted.
12. Abstract of Corrective Measures Recennended and Taken Refer to kpplenental !heet Page 3 of 3.

We certify that the statenants made in this tiport are correct and the eneminations and corrective naasures taken conform to the rules of the A!MC Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Empirati m Date N/A Date MwV 'dC 19 % Signed Housten Liahtira er Power Co. By( h 1 w Owner X 9. Hg, Jr.

I GREIFICAIE & INSERVIG DEFICTICN Z, the undersigned, holding a valid cannissim issued by the National Boarr' of Boiler and Pressure Vessel Inspectors and the State or Province of hxas and enployed by _Arkwright HLatual Insurance Co. of Norwood, MASS. have inspected tha + 4.nts described in this Omer's Report durirg the period G -//- To _

+o 7-dA - To , and state that to the best of ny knowledge and belief, the owner has performed e e ninstions and taken corrective neasures described la this owner's Paport in accordance with the inspection plan and as requirid by the ASE Code,Section XI.

By signing this certificate neither the Inspector nor his anployer makes any warranty, expressed or inplied, concerning the examinatims and corrective naasures described in this Owner's Report. Furthernere, neither the Inspector nor his enployer anall be liable in any manner for any personal irdury or property danage er a Ices of any kirsi arising fran or cenected with this inspection.

FACIIRY WIUAL SYSIEM g_- Canmissions 'IX-826 B. R. Russell, Inspector's Signature National Board, State, Province, and Ehdorsements Date %76- 19 90 NISI.CLI.1RE02

ATTACHMENT i- *

' ST-HL AE. s56 3 yggg 3 ,g 3 PAGE S OF T  :

Stcruz.nu al.

Le' FOR ASME CODE CLASS 1 PIPING AND COMPONENTS

1 1
1. Odner Houston Llahtira 8r Power Ccupany Electric h r, P. O. Box 1700, Houston, TK 77C01

)

(Name and Addn as of Owner)  ;

2. Plant South Texas Project Electric Generatire Station P. O. Best 289, Wadsworth, 'IX 77483 l (N as and Address of Plant) j
3. Plant thit 1 4. Owner Cartificate of Authorization (if mquired) N/A
5. Connercial Service Date : 06/25/88 6. National Board Nisaber for thit N/A
10. ABSTRACT OF EXAMINATIONS A System Leakage Test as prescribed by IWA-5211(a) for all ASME Code Class 1-Pressure Retaining Components was conducted in accordance with Table IWB-2500-1, Examination Category B-P, Item Nos. B15.10, B15.20, .;

B15.30, B15.40, B15.50, B15.60 and B15.70.

The Pressure Test and VT-2 visual examinations were conducted in accordance with Plant Surveillance Pressure Test Procedure, 1 PSP 15-RC-0001, Reactor Coolant System Leakage Pressure Test (Rev. 2) at the conclusion of the second refueling outage. ASME Code Class 1 piping and valves are specifically identified in the above referenced procedure. '

In addition, the.above System Leakage Test also satisfied the requirement '

for a System Pressure Test subsequent to the disassembly and reassembly of n.ochanical joints in ASME Code Class I components as prescribed by IWA 5214(e). '

Also, Setem Pressure Tests subsequent'to the disassembly and reassembly of mechanical *etnts in ASME Code Class 1 components at prescribed by IWA-5214(e) were conducted in accordance with OPGP03-ZE-0027, ASME Section XI Post-Maintenance Pressure Tests (Rev. 3) for individual work items performed outside the scope of the second refueling outage.

12. ABSTRACT OF CORRECTIVE MEASURES RECOMMENDED AND TAKEN j The Visual Examinations (VT-2) performed during these Pressure Tests found only minor leakage at mechanical joint's such as valve stems and flanged ,

connections. These leaks were evaluated and determined acceptable for continued system operation. Appropriate corrective action was initiated to correct these leaks.

K NISI.CLI.1RE02

ATTACHMENT L ', .

ST-HL-AE ts'l PAGE 1 cf 3 i PAGE _ .L_. OF i

,9 FORM NIS-1 OWNER'S Rein.en rum IfBIP.5!CE INSP1tCTIONS j As required by the Provis1oas of the ABME Code Rules  !

=r

1. Owner Houston 1.ishtira in Power Cagaany Electric 'Ibwer, P. O. Besc 1700, Houston, TK 77001 '!

(Nans and Mdress of Owner)

2. Plant South Texas Project Electric Gnneratira Station P. O. Box 289, Wadsworth, TK 77183 {

g (Nans ar:1 Address of Plant) '

3. ' Plant Unit 1 4. Ownnr Certificate of Authorization (if required) N/A ,

i

< 5. Ocnnercial Service Date 08/25/88 6. National Board Enbar for thi* N/A-  ;

7. CP nts Inspected ASE ONE CASS 2 PIPDG AND CHQ4ENTS Manufacturer Ocmpcment or Manufacturer or Installer State or National Appartenance or Installer Serial No. Prwinee No. Board No.

CIASS 2 FIPDG EBASCO (I) N/A N/A N/A  ;

CLASS 2 VA!NES VARICUS N/A N/A N/A i b

I L

+

NOIE: Supplenental sheets in form of lists, sketches, or drawings may be used, prwided (1) l size is 81/2 in. X 11 in., (2) information in items 1 through 6 en this report is included on I

each sheet, and (3) each sheet is ntabered and the ntnber of sheets is recorded at the top of l

l, this form.

l l' NIS1,CL2.1RE02

) --

PAGE 2 sf 3' ,

FORM NIS-1 (Back) .

8. Enamination Dates _11/02/89 to__06/21/90 9. Inspection Interval frcro 08/25/88 to 08/25/98 f
10. Abstract of Emaninations. Include a list of exminations and a statenant ccreerning status of work l required for current interval. Refer to S.pplanental $heet Page 3 of 3.
11. Abstract of Conditicns Noted No relevant conditions affectirig prows e retaining boundaries were noted.
12. Abstract of Corrective Haasures Recamanded and Taken Refer to Supplanantal Sheet Page 3 of 3. I

.We certify that the statanants made in this report are correct and the exminations and corrective neasures taken conform to the rules of the ADE Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Expiration Date X/A - .i Date_ 3 N n dC- 193 0 Signed Houston Lightina & Power Co. By . :s. [

Omer W.' H. KQy, Jr._

l t

GRTIHCA2E & DGRVIG DGICTICN f I, the undersigned, holding a valid conn.ission issued by the National Board of Boiler and Pressure Vessel 1 Ins;meton and the State or Prwince of 'Ihxas and enployed by Arkwright ititual Irwurance Co.' of '

Norwood, MASS. have inspected the ccriponents described in this I Owner's_ Report during the period 3-E To to 7-2.3-9o , and state that to the best of sqy knowledge and telief, the Owner has perfonned exeninations and taken corrective '

neasures described in this Owner's Report in accordance with the inspection plan and as required by the A9E Code,Section XI.

By signirs this certificate neither the Inspector nor his enployer ' makes any warranty, expressed l or inplied, concerning the exmfaations and corrective naasuns described in this Owner's Report. Pbrthermore, neither the Inspector nor his anployer shall be liable in any manner for any personal irduty or property ,

danage or a loss of any kind' arising frtra or connected with this inspection.

.A FACIORY tiTIUAL SYSIliM -

t Ccrimissions 'IX-826 i B. R. Russell, Inspector's Signatute National Board, State, Province, and Endoreanents >

D*.te 7- 2 3 ~ ,,19 */ o l

lc~ -

NISI.CL2.lRE02 ,

j

=-- -

a  ;

)

PAGE 3 of 3 j FORM NIS-1 (Back) -

8.' Insninstion Dates 11/02/89 to 06/21/90 9. Inspection interval fran 08/25/88 to 08/25/9B I

10. Abstract of Emaninatims. Include a list of ereninations and a statement concernirs status of work required for current interval. Refer to %pplemental Smet Page 3 of 3.
11. Abstract of Ccriditions Noted No relevant conditions affectire pressure retaining bei.rularies unre noted.
12. Abstract of Corrective Measures Roccnnanded and Taken  !

Reier to Supplemental Sheet P me 3 of 3.

We certify that the statements made in this report are correct and the exaninations and corrective neasures takan conform to the rules of the ADE Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Empiration Date X/A Date 7du" dT- 19"JO Signed Houston Lightira le Power Co. By h ( ,

i Owner W.' H. KQy, Jr. [

CERTIFICME & DERVICE DCIPICTICN 2, the undersigned, holdirg a valid ccranission issued by the National Board of Boiler and Pressure Vessel .

Inspectors and the State or Province of ' hxas and enployed by Arkwright M2tual Insurance Co. of Norvocd. MASS. have inspected the conpanents described in this Chener's Report durits the period hnA., 4b to 7-ES-90 , and state  ;

that to the best of ny knowledge and belief, the - Owner has performed exaninations and taken correr.tive neasures described in this owner's Report in accordance with the inspection plan and as required by t!w A9.'?

Code,Section XI.

By signirs this certificate neither the Inspector nor his anployer makes any warranty, expressed or inplied, conceming the exaninations and corrective measures described in this Owner's Report. Furthernere, rtDither the Inspector nor his anployer shall be liable in any manner for any personal irdury or property

' damage or a loss of any kind arising frun or connected with this inspection.

FACIORY liTIUAL SYSniM '

Conmissions, TX-826 i

B. Es Rassell, Inspector's Signature National Board, State, Province, and lihdorsenents l

Ete_ '7-23 199o l

l l

l l

N1SA.CL2.1RE02

i l

' ATTACHMENT ,

ST HL-AE-254,2 PAGE 3 Cf 3 supgggg[ - @ - ,

c FOR ASME CODE CLASS 2 PIPING AND COMPONENTS

1. Ovner Houston Liarc% & Penser Ccmpany Electric Tbwer. P. O. Best 1700. Ibustcm.1X 77001 (Nane ard Address of Owner)
2. Plant _ South Texas ProjeM Elec:ric Generatira Station P. O. Besc 289. Wadsworth, TX 77483  ;

(Nas and Address of Plant) -

3. Plant thit 1 4. Owner Certificate of Authorization (if required) N/A
5. Camercial Service Date 08/25/8L 6. National Bc.an! Naber for thit N/A 10 .' ABSTRACT OF EXAMINATIONS System Inservice Tests as prescribed by IWA-5211(c) were conducted on selected ASME Code Class 2 Pressure Retaining Components in accordance with .

Table IWC-2500-1, Examination Category C-H, Item Nos. C7.30 and C7.70. '

The Pressure Tests and VT-2 visual examinations were conducted in ,  ;

accordance with *he following Plant Surveillance Pressure Test Procedures:

IPSP15-MS-0001 - Main Steam System Inservice fressure Test (Rev. 3) 1 PSP 15-3B-0001 - Steam Generstor Blowdown System Inservice Pressure Test-(Rev. 2)

IPSP15-TW-0001 - Feedwater System Inservice Pressure Test (Rev. 2) r p (inside contai unent portion only)  !

l IPSP15-RC-0001 - Reactor Coolant System Leakage Pressure Test (Rev. 2)  ;

ASME Cods Class 2 piping and valves are specifically identified in the above referenced procedures. These test procedures were conducted during the time period of March 26, 1990 to June 21, 1990.

12. ABSTRACT OF CORRECTIVE MEASURES RECOMMENDED AND TAKEN r i The Visual Examinations (VT-2) periormed during these Pressure Tests found I only minor leakage at mechanical joints such as valve stems and flanged ,

H connections. These leaks were evaluated and determined acceptable for

  • continued system operation. Appropriate corrective action was initiated to correct these leaks. '

i V

NISI.CL2.1RE02

, _ ~ - -

I i.

~ ~ ATTACHMENT 1

', ST HL-AE ?n3 l PAGE- P 0F $. PAGE 1 cf 3 l o'.

~

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS I As required by the Provisions of the AmtE Code Rules i

1. Owrer Houston Liahtira fr Power Comany Electrie '1buer. P. O. Scoc 1700 Houston, H 77001 (Nee and Address of Owner)
2. Plant South Texas Project Electric Generatire Staticm P. O. Best 289, Wadsworth, 'IX 77483 (Nas and Addrons d Plant) . .
3. Plant thit 1 4. bner Certificate of Autlerir.stica (if required) N/A l l
5. Cersnercial Service Date 08/25/88

~

6. Naticmal Board Maber for thit N/A t
7. Ccapenents Inspected ASE C0tE QASS 3 PIPING AND CDENENIS Mararacturer

[

P nt or Herufacturer or Installer State or National Aprurtenance or Installer Serial No. Prwinee No. Board No. '

APWP #14 BIN 2iAM  ;

3S1411eA% WIIIAf! TIE (M) 1A-137 N/A NB-555 A!WP #14 Turb.  !

011 Cooler 3S1411M DI #f!'IEK (M) 79161 N/A 344 SFTC B9A 1 3R211NPA101A GI D S PG PS (M) N242B076-2 N/A 363 SFT HK 1A A71AS INRISTRIA. HEU./

3R211) E 101A WESTIN300SE (M) 3757 N/A 3107 i

SFPC Dip 1B 3R21INPA101B rrnunm RNS (M) N242B076-1 N/A 362 SFP HK 1B AHAS INDUSIRIAL IfU./

3R211) M 101B WESTIN300SE (M) 3758 N/A 3108 QASS 3 PIPING EBAS00 (I) N/A N/A N/A CASS 3 VALVES VARIalS N/A N/A N/A i

ICIE: Supplanental sheets in form of lists, sketches, or drawings rnay te used, provided (1) size is 81/2 in. X 11 in., (2) Information in itens 1 through 6 en this report is included on I each sheet, and (3) each sheet is rarnbered and the rarnber of sheets is recorded at the top of this form.

NISA.CL3.1RE02

..A b- ,

1 PAGE 2 ef 3' .--

FORM NIS-1 (Back)

8. Rumination Dates. _ 11/02/89 to 06/21/90 9. Inspection intatval fran 08/25/88 to 08/25/98
10. Abstract of Buminations. Include a list of examinations and a statsnant concerning status of work required for current interval. Refer to ikgplanntal Ehnet Page 3 of 3. t
11. Abstract of Conditions Noted No rvlevant ceditions affecting pressure retaining bour:1 aries were noted.
12. Abstract of Carrective Measures Roccmnerded and Taken Refer to !hJpplemental !heet Page 3 of 3.

l We certify that the statenenta made in this report are correct and the examinations and corrective -

naasures taken conform to the rules of the ASE Code,Section XI.

Certificate of Authorisation No. (if applicable) N/A Enpiratien Date N/A Date - 1 td ,( M 1997' Signed huston Lightira Er Power Co. By M td V

Chmer W. H. KinsleyJ Jr.

QRTIFICME CF DENWIG DSPE:TIGI 8, the undersigned, holdire a valid canaission issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Prwince of Texas and enployed by Arkwriaht htual Insurance Co. of Norwood, MASS have inspected the caipments described in this Omer's Report durirg the period 3 .Fo-9o to _ 7-23-90 , and state that to the best of nce knowledge and belief, the Omer has performed examinations and taken corrective neasures described in this Owner's Report in accordance with the inspection plan and as required by the A9E Code,Section XI. ,

By signirs this certificate neither the Inspector nor his enployer makes any . warranty, expressed or inplied, concerning the examinations and corrective measures described in this owner's Report. Furthermore, neither the Inspector nor his enployer shall be liable ' in any manner for any personal irdury or property damaae or a less of any kind arisits fran or emnocted with this inspection.

FACKPJ WIUAL SYSIDI a : ' >p Cannissions 'IX-826 B. R. Russell, Inspector's Signature National Board, State, Prwince, ar[&dorsements hte 7-E8 19 (7 0 i

1 NIS1.CL3.1RE02 j

i

' . i

. PAGE 2 of 3 FORM NIS-1 (Back)

8. Eraninstion Dates !!/02/89 to 06/21/"., 9. Inspection Interval fran 08/25/88 to 08/25/08 l
10. ,untract of Sunninations. Include a 41st of emaninations ad a statenant concernirs status of work 4 required for current interval. Refer to Sgplanantal 9 met Page 3 of 3.  !
11. Atstract of Conditions Noted No relevant ceditions affectire pressure retainirs bomdaries were noted.  !
12. Abstract of Corrective Hessures W ard Taken l l Refer to Sgplarmental Smet Page 3 of 3.

l i

We certify that the statsaants made in this report are correct and the exarninaticms and corrective neasures taken conform to the rules of the ASE Code,Section XI.

Certificate of Authorisation No. (if applicable) N/A Empiration Date N/A Date ltd ix V

M 19 % Signed Houston 1.ithtira 8r Power Co. By O w$%

Chmer W. H. Kinsity)Jr.  !

l GRTIFICM CF INERVIG INERETICN I, the trdersigned, holding a valid ocnrnission issued by the National Board of Boiler and Pressure Vessel l Inspectors and the State or Prwince of Texas and enployed by Arterriaht Wtual Insurance Co.' of Norwood, NASS - have inspected the congnnents described in this l Omer's Report durits the period 3- 3 o -9o to 7-23-90 , and state j that to the best of my knowledge and belief, the Owner has perforned exarninatiens and taken corrective neasures described in this Chmer's Report in accordance with the inspection plan and as required by the ASE N e,Section XI.

By signirs this certificate neither the Inspector nor his enployer makes any warranty, expressed or inplied, concerning the examinaties and corrective measures described in this owner's Report. Purthemore, neither the Inspector nor his enployer shall be liable in any menner for any personal irduty or property danage or a loss of any kind arisitt fran or econected with this inspection.

FACIIRY MJIUA1, SYSITH errMu Ccrirnissions TX-826-B. R. Russell, Inspector's Signature Naticnal Board, State, ' x:e, and Ehdorsenents l i i

Pc.e */ - E ,6 -

19 90 l

I 1

t i

I

)

l l

l b NIS1.CL3.1RE02

,,- < -w.-- - - - - ~ , - , - - - , .-w-,w-,- --,,,+oge

}

,., ATTACHMENT PAGE 3 cf 3 i st.HL-AE 8541

(

    • 7 l -

SUPPLEMEl(TnGE_ 4 .OF. i

!6 FOR l

ASME CODE CLASS 3 PIPING AND COMPONENTS f

' 1. CWar _ Houston Llahtira er Power Comany Electric Tower, P. O. Besc 1700, )buston, 'DC 77001 (Nane and Address of Owner) j

2. Plant _ South Texas Project Electric Generatira Station P. O. Boot 289, Wadsworth, 'DC 77483 '

(Name and Address of Plant)  :

i 3. Plant thit 1 4. Chener Certificate of Authorizatico (if rog, tired) N/A '

5. Connercial Service Date 08/25/88 6. Naticmal Board Naber for thit N/A
10. ABSTRACT OF EXAMINATION l System Functional.and Inservice Tests as prescribed by IWA-5211(b) and (c).  !

respectively, were conducted on selected ASME Code Class 3 Pressure l Retaining Systems / Components in accordance with Table IVD-2500-1,  ;

Examination Category D-A, ,ttem Po, D1.10 and Examination Category D-C,  ;

Item No. D3.10.

The Pressure Tests and VT-2 visual examinations were conducted in '

accordance with the following Plant Surveillance Pressure Test Procedures.  !

I IPSP15-FC-0001 - Spent Fuel Pool Cooling and Cleanup System Inservice Test Procedures (Rev. 1) l 1 PSP 15-AF-0001 - Auxiliary Teodwater System Functional Pressure Test  !

(Rev. 4) (AFWP #14 only)

ASME Code Class 3 piping and valves are specifically identified in the  ;

above referenced procedures. The above tests procedures were conducted during the time period of March 26, 1990 to June 21, 1990. ,

12. ABSTRACT OF CORRECTIVE HEASURES RECOMMENDED AND TAKEN TheVIsualExaminations(VT-2)performedduringthesePressureTestsfound  !

only minor leakage at mechanical joints such as valve stems and flanged [

connections. These leaks were evaluated and determined acceptable for continued system operation. Appropriate corrective action was initiated to correct these leaks.

Y t

b

)

NISI.CL3.1RE02  ;

i