>0 b*NI5I5c"5 PRESERVICE INSPECTION
SUMMARY
REPORT FOR CLASS 1, CLASS 2 AND CLASS 3
COMPONENT SUPPORTS at the O
SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION-UNIT 2
P.O. Box 308 Bay City, Texas 77414 Owner:
Houston Lighting & Power Company City Public Service Board of San Antonio Central Power and Light Company City of Austin Address:
P.O. BOX 1700 Houston, Texas 77001 issue Date:
DECEMBER 1988
- wun.uw o
n
'V(h' t
PRESERVICE INSPECTION
SUMMARY
REPORT FOR CIASS 1, CLASS 2 AND CIASS 3 COMPONENT SUPPORTS SOUTH TEXAS PROJECT ELECTRIC CENERATINf. STATION UNIT N0. 2 USNRC DOCKET No.: 50 499 OPERATING LICENSE NO: N/A j
i COMMERCIAL OPERATION DATE: JUNE 1989 (EST.)
t Prepared by:
M/ A. SteVart PII Coordinator - Component Supports j
Revleved by:
Q h ln suYx
$w kb bw&Y Y$h.
L. Beverly
/upervising Eng.
yI/ISI
[
A. C. McIntyref Manager uphort Engineering Departdant-h,4.SC7he h.
A,, roved by:
i I
t i
I
)
i t
O t
r f
b
i TABLE OF CONTENTS j
Page a
LIST OF TABLES................................................
i LIST OF ABBREVIATIONS......................................... 11
1.0 INTRODUCTION
1 1.1 Scope of Su==4ry Report............................
1
[
1.2 Description of the F1 ant...........................
1 1.3 Description of the Examination Program.............
1 1.4 Scheduling of PSI Examinations.....................
2 i
{
2.0 BASES DOCUMENTS FOR PSI EXAMINATIONS......................
2 r
4 t
i 2.1 Applicable Documents...............................
2 I
2.2 Discussion of Basis Documents......................
3 l
1 3.0 SCOPE OF PSI EXAMINATIONS.................................
6 3.1 Class 1 Components.................................
6 3.2 C1:ss 2 Components.................................
6 4
3.3 Class 3 Components.................................
9 l
3.4 Class 3 Integral Attachments.....................
12 3.5 Augmented PSI Program............................
12 4.0 EXAMINATIOI! PERSONNEL, PROCEDURES, AND EQUIPMENT.........
15 i
s 4.1 Visual Examination Personnel Qualifications.......
15 l
4.2 HL&P Administrative and Examination Procedures....
15 i
3 i,
I 5.0 CONTROL OF EXAMINATION DOCUMENTATION.....................
15 4
i 5.1 Description of Design Document control Program....
15 i
6.0
SUMMARY
OF EXAMINATIONS..................................
16 l
l 6.1 0v e rv i e w..........................................
16 i
6.2 P:e HFT Examinations.............................
16 6.3 PSI Examinations During HFT.......................
17 l
6.4 Post HFT PS! Examinations........................
17 1
6.5 Augmented PSI Examinations........................
17 l
l 7.0 EXAMINATION RESULTS AND CORRECTIVE MEASURES..............
17 I
i
]
8.0 SNUBBER TESTING..........................................
18 i
i t
i 9.0 CERTIFICATION OF INSPECTIONS....................
18 10.0 REMAINING PSI EXAMINATIONS...............................
18 i
l f
i t
i
$3/E048/rr I
l-
?
l
.. -. - =.
TABLE OF CONTENTS (CONT.)
i APPENDICES I
4 l
A.
Listing of Personnel Qualifications B
Listing of HL&P Administrative Procedures j
j C.
Listing of HL&P Examination Procedures D.
Class 1 Examinstion Summary Tables E.
Class 2 Exarination Summary Tables i
F.
Class 3 Examination Summary Tables i
G.
Exempt and Non Safety Supports Containing Snubbers H.
NIS 1 Forms 1
i a
i i
I l
I i
i Y
L l
I I
i i
l I
l J
I 1
1 i
l i
i
?
r i
l i
f I
t l
f i
i S3/E048/rr
LIST OF TABLES Table Title Page 1
Summary of Applicable Relief Requests...................
5 2
Exempted Class 2 Components 8
3 Exempted Class 3 Components 10, 11 4
Augmented PSI Visual Examination Implementation........
14 i
i i
i i
l i
L i
i r
i i
l
[
f l
I l
t i
I I
i
$3/E048/rr i
LIST OF ABBREVIATIONS
[
As Built Reconciliation Program ABR Auxiliary Feedwater AF Authorized Nuclear Inservice Inspector ANII American Society of Mechanical Engineers ASME Boiler and Pressure Vessel Code B&PV Component Cooling Water F4 Code of Federal Regulations CFR Containment Spray CS Chemical & Volume Control CV Design Change Disposition Fora DCD Essential Cooling Water EW W
Feedwater Hot Functional Testing HFT High Head Safety Injection HHSI Houston Lighting & Power Company H1AP Interdepartmental Procedure IP ISI Inservice Inspection Motor Operated Valve MOV Main Steam MS Nominal Pipe S.ze NPS Nuclear Regulatory Commission NRC Operations Engineering Procedure OEP Operations Quality Assurance Plan OQAP PAT Power Ascension Testing PDN Potential Deficiency Notification Plant Engineering Department PED O
PSI Preservice Inspection Quality Assurance QA Quality Control QC Reactor Coolant RC Residual Heat Removal RH Pli Reactor Make up Water Safety Evaluation Report SER SI Safety Injection SSP Standard Site Procedure STPECS South Texas Project Electric Generating Station VT Visual Examination 11 S3/E048/rr
1.0 INTRODUCTION
1.1 Scope of Summary Report p,
(,)
This document is the Summary Rotort for Preservice Inspection (PSI) examinations of C1.ss 1, Class 2 - E "lass 3 component supports of the South Texas Project Electric Ge' a Station, Unit 2 (STPECS 2).
This report summarizes the PJI Fions conducted in accordance with Title 10, Code of Federal R-tlons Part 50 (10CTR50), the American Society of Mechanical Enssn<4rs (ASME) Boiler and Pressure Vessel (B&PV) Code Section XI, rnd specified regulatory, Code, and project documents as described in Section 2 d.
This summary report has been prepared in af.cordance vb.h IVA 6000 of Section XI.
This summary report reviews the bases for the PSI program and describes the scope of PSI examinations in terms of specific systems, components, and examination areas. The major elements of the examination program, v tuding personnel qualification, procedures, equipment and controls i discussed and documenten.
The PSI examinations performed, the results of these examinations, co :ective actions taken, and dis.
position t.l examination results tra documented herein. Certifications of the PSI examinations by the Authorized Nuclear Inservice Inspector (ANII) on NIS 1 forms and descriptions of remaining PSI examinations are also included.
This summary report documents the PSI examinations performed as required by Subsection IWF of Cection XI for Class 1, Class 2, and Class 3 component supports, and Subsection IVD for Class 3 integral attachments.
1.2 Description of the Plant The Touth Texas Project Electric Cenerating Station is located near Wadsworth, Texas. The plant Neelear Regulatory Commission (NRC) Docket Number for STPECS 2 is 50 499. The station is a two (2) unit pressurized water reactor plant.
Each reactor is a Westinghouse 4 loop system.
The output of each unit is 1250 MVe.
Unit 2 is scheduled to enter commercial operation in June 1989 (est.).
1.3 Description of the Examination Program The PSI examination program for component supports has been developed and implemented by utilizing discrece portions of several existing project programs relating to componeut supports.
The cumulative results of these programs have satisfied all of the elements of PSI examination required by the Code.
?V S3/E048/rr 1
1
Specifically, PSI Visual Examinations (VT) were performed during one or mora of the following phases:
(,)
(1)
Pre HFT examinations. - These examinations were conducted after Quality Control (QC) acceptance of support construction to verify both structural condition and structural integrity on supports selected for PSI, which were not subject to heat up during either Hot Functional Testing (HFT) or Power Ascension Testing (PAT). Additionally these examinations verified structural condition on those PSI qupports which were subject to heat up during HFT or PAT.
(2)
HFT examinations.
These examinations were conducted during HFT to verify the structural integrity (setting, clearances) of PSI variable supports (springs and snubbers) subject to heat up testing.
(3)
Post HFT examinations.
These examinations were conducted subsequent to the cool down from HFT to reverify the structural condition of PSI supporte subject to heat up testing during HPT as well as to verify structural integrity of non variable PSI supports subject to heat-up testing.
The cumulative reruits of the above listed examinations fulfilled the examination requirements of component supports selected for PSI examination. A simitr* multi phase examination approach is planned for component supports whien were not subject to heat up during HFT but are subject to the heat-up during PAT (see Section 10.0).
For details of the implementation of the multiple phases of examination, refer to
('^x)
Section 6.0.
1.4 Scheduling of PSI Examinations The initial phase of PSI examinations began in January 1988. These baseline examinations, it. coordination with plant access conditions and support construction completion, were conducted through November 19C8.
The HPT related examinations were conducted in conjunction with the plant heat up during July and August of 1988, while the Post HFT examinations commenced after cool down from HFT and were concluded in November 1988. All PSI examinations of Class 1, 2, and 3 components supports and Class 3 integral attachment welds have been completed and are summarized herein with the exception of those items described in Section 10.0.
2.0 BASES DOCUMENTS FOR PSI EXAMINATIONS 2.1 Applicable Documents The following documents were used to develop, implement, and document the STPECS 2 PSI program:
t U
S3/E048/rr 2
1
2.1.1 Title 10, Code of Federal Regulations Part 50, Article 55a (10CFR50.55a), "Codes and Standards".
o (K ')
2.1.2 Section XI of the ASME B&PV Code, "Rules for Inservice Inspection of Nuclear Power Plant Components," 1980 Edition with Addenda chrough Vinter 1981 (80W81).
2.1.3 Section XI of the ASME B&PV Code, 1974 Edition with Addenda through Summer 1975 (74S75) as applicable (per 10CFR50.55a) to Class 2 piping.
2.1.4 Section XI of the ASME E&PV Code, 1983 Edition with Addenda through Vinter 1983 (83W83) as applicable to inspection of Class 2 piping.
2.1.5 ASME B&PV Code Section XI Interpretation XI-18312R 2 2.1.6 ASME B&PV Code Section XI Interpretation XI 1-83 30 2.1.7 NRC Letter, R. L. Tedesco to C. W. Oprea Jr., Transmitted to HL&P under document ST AE HL 608, dated October 17, 1980.
2.1.8 Houston Lighting and Power Company (HL&P) Requests for Relief from Section XI Requirements (see Section 2.2).
2.1.9 Safety Evaluation Report (SER) related to the operation of South Texas Project Units 1 and 2, through Supplement 5.
f-'S 2.1.10 HL&P Specification No. 5UO36JS0002, latest revision, "Pre s e rvic e
(
)
Inspection Examination of Component Supports of South Texas Project Electric Cenerating Station - Unit 2".
2.1.11 HL&P Operations Quality Assurance Plan (OQAP), Latest Revision.
2.2 Discussion of Basis Documents The STPECS-2 PSI program was developed in accordance with Section XI as required by 10CFR50.55a.
The 80V81 Section XI Code was used for STPEGS 2 PSI for compatibility with the STPECS 1 PSI program. ThisSection XI Code vintage is in excess of 10CFR50.55a requirements.
The 74S75 Section XI Code was used to dutermine the extent of PSI for Class 2 piping velds as required by 10CFR50.55a(b)(2)(iv) and, therefore, the extent of component supports requiring oxamination.
The 83W83 Section XI Code was utilized as the basis for optionally adding some Cless 2 component supports to the scope of those requiring PSI examinations.
This was done in order to obtain baseline data for use in the Inservice Inspection (ISI) Program.
ASME Code Interpretations XI-1-83 12R-2 and XI 1 83 30 were used to clarify the selection process of component supports requiring examination as well as the boundary or extent of the examinations of the specific support structure, respectively.
[\\
S3/E048/rr 3
Th3 NRC lottor en Pros 3rvico Insp;ction cnd Tosting of Snubbers (2.1.7) was used as a basis for developing the program for augmented preservice inspection of snubbers.
x,,/
Requests for relief from Section XI requirements were previously filed with NRC pursuant to 10CFR50.55a.
The relief requests applicable to the scope of PSI examinations contained herein are listed and summarized in Table 1.
NRC approval of the request for relief from scheduling the PSI examinations after initiation of HFT has been received in the STPEGS SER, Supplement 2 (2.1.9).
NRC approval of relief request No RR.ENG 01 was received in Supplement 3 of the SER.
HL&P Specification $UO36JS0002 (2.1.10) was developed as the controlling document for the PSI examination and testing of component supports.
It defines the Code, regulatory and procedural bases for the preservice program, and contains the examination plan for the component supports.
The HLAP OQAP (2.1.11) contains the quality assurance program requirements applicable to the PSI /ISI program.
O i
i l
N-S3/E048/tr 4
I
i.
TABLE 1 Summary of Applicable Relief Requests a-w felief Request No.
Description f
.a ENG-01 Requests exemption of open ended portions l
of the Containment Spray (CS) System beyond the containment isolation valves j
(Class 2 components and their supports).
l
.l Not Nr'ered Requests relief from scheduling all PSI f
i (Tra..:,u.itte i via H14P component support examinations following
.~T hl AE 1665 dated initiation of hot functional tests.
May 22, 1986) 1 i
4 i
l l
1 l
t I
t 1
I i
f 1
i
{
i I
h a
6 l
[
L i
k i
l 1
i
)
?
t I
I
[
t
[
I f
t I
i i
S3/E048/rr 5
i l
l J
3.0 SCOPE OF PSI EXAMINATIONS The scope of ASME Code Class 1, Class 2, and Class 3 component supports included within the STPEGS 2 PSI examination program was determined by n
applying the rules and requirements of the 80W81 Section XI Code and the 74S75 Section XI Code as required by 10CFR50.55a(b)(2)(iv) for specified Class 2 piping systems.
Since Subsection IWF of Section XI, 1980 Edition through Winter 1981 Addenda, does not specify exemptions for supports (IWF exemptions are currently in the course of preparation), the exemptions for Class 1, 2, and 3 pressure retaining components, as described in Subsection IWB, IWC and IWD respectively, were applied to component supports as well, This was done in accordance with IWF 2510(a).
The examination methods utilized to perform all PSI examinations of component supports were in accordance with 80W81 Section XI requirements.
3.1 Class 1 Components Supports of components classified as ASME Code Class 1 by project design documents were considered for PSI examination in accordance with the requirements of Subsections IVA and IWB of 80V81 Section XI Code.
Class 1 components were censidered exempt from examination during PSI if they met the exemption criteria of IVB 1220 of the 80V81 Section XI code as follows:
Component Section XI Exemption Criterion Piping $ one inch nominal pipe size IVB 1220(b) (1)
(NPSI) except for steam generator tubing.
Component Supports of the following Class 1 components and systems were included in the STPEGS 2 PSI program:
Pressurizer Steam Generators Reactor Coolant (RC) System Piping Chemical 6 Volume Control (CV) System Piping Residual Heat Removal (RH) System Piping Safety Injection (SI) System Piping Reactor Coolant Pumps 3.2 Class 2 Components Supports of components classified as ASME Code Class 2 by project design doctments were considered for inclusion in the non exempt PSI boundary in accordance with Subsections IWA and IWC of 80W81 Section XI Code.
The extent of the non exempt boundary within the Class 2 portions of RH, SI, and CS piping systems was determined in accordance with the requirements of 74S75 Section XI Code as required by 10CFR50.55a(b)(2)(iv). Additional Class 2 piping was included in the non exempt PSI boundary to achieve compatibility with future ISI programs.
O S3/E048/rr 6
Sp2cificc11y, the C1 css 2 ntn cxtzpt bcundary was dsfined in cecord:nce with the requirements of IWC 1220 (exemption criteria). Table 2 lists the Class 2 components exempted from the PSI boundary along with the O
IWC 1220 exemption criteria applied to each component or group of compenents.
Component supports on piping NPS 2 through MPS 4 in the high head safety injection (HHSI) portion of the SI system were optionally included in the PSI boundary to obtain baseline data in accordance with the requirements of 83W83 Section XI Code.
The Class 2 components and systems listed below comprise the Class 2 non exempt boundary.
Regenerative Heat Exchanger Residual Heat Removal Heat Exchangers Letdown Heat Exchanger Excess LAtdtv.s Hest Exchanger Reactor Coolant Filters Seal Water Injection Filters Pulsation Dampener Auxiliary Feedwater (AF) System Piping Component Cooling Watet (CC) System Piping Containment Spray (CS) System Piping Feedw ter (W) System Piping Hain Steam (HS) System Piping Residual Heat Removal (RH) System Piping Safety Injection (SI) System Piping Containment Spray Pumps O
Residual Heat Removal Pumps Low Head Safety Injection Pumps High Head Safety Injection Pumps Applicable Section XI selection criteria O WF 2510) were applied to the non exempt Class 2 boundary to determine the specific component supports required to be examined during PSI.
In the case of multiple components of similar design, size, and service, components were considered to be either piping, vessels, pumps, etc. as defined in IVA 2110(h) of Section XI.
The PSI program referred to a grouping of these items as trains, where a multiple train is more than one component, piping run, etc. of similar design, function and service.
All component supports within the Class 2 non exempt boundary were identified as being connected to a single or multiple train. All non exempt supports on a single train were examined during the PSI while only the supports of one of the trains of a multiple train were examined. The train with the most supports was selected.
If all trains of a multiple had the same number of supports, the train selection was random.
The multiple train selection concept was not applied to the examination of Class 1 supports.
O S3/E048/rr 7
TABLE 2 Exempted Class 2 Components s
I
)
xm/
Exemption Section XI Component criterion Code Accumulator Tanks IWC 1220(a) 80V81 Volume control Tank IWC 1220(b) 80W01 Refueling Vater Storage Tank IWC-1220(a) 80V81 Seal Water Heat Exchanger IWC 1220(b) 80W81 Seal Water Return Filter IWC.1220(b) 80V81 Component connections, piping, valves, and IWC 1220(c) 80W81 vessels and their attachment $ NPS4 of AF, FW, and MS systems component connections, piping, valves, and IWC 1220(d) 74S75 vessels and their supports i NPS4 of RH, SI, and CS systems Piping (e' cept for RH, SI, and CS) and IWC 1220(b) dOW81 a
components with operating temperature $ 200 degrees F and operating pressure $ 275
(~~)3
(
temperature $ 200 degrees F and design pressure $ 275 psig O
S3/E048/rr 8
t 3.3 Class 3 Comp +nents l
Supports of components classified as ASME Code Class 3 by project i
O design documents were considered for inclusion in the non exempt PSI boundary in accordance with Subsections IVA and IVD of 80V81 Section XI J
- Code, i
specifically, the Class 3 non exempt boundary was defined in accordance with the requirements of IVD 1220 (exception criteria) and Table IVD 2500 1.
Table 3 lists the Class 3 components and systems or
[
portions of systems exempted from the PSI boundary along with the IVD -
1220 exemption criteria applied to each.
In the Auxiliary Feedwater I
System, since IVD 1220.1 does not identify a site exemption, it was l
interpreted that the exemption criteria should not be more stringent than the Class 1 requirements, h refore, an NPS1 and smaller i
exception was applied to this system.
[
a 1
l l
The Class 3 components and systems listed below comprise the Class 3 non exempt boundary.
{
Auxiliary Feedwater (AT) System Piping Auxiliary Feedwate; Pumps t
j Component Cooling (CC) System Piping l
Component Cooling Pumps Component Cooling H,,at Exchengers Component Cooling Surge Tank
)
Reactor Coolant Purification Pumps i
latdown Filter i
Mixed Bed Demineralizers l
l Cation Bed Dominerclizers Standby Diesel Generator Tuel Oil Storale Tank l
Standby Diesel Generator Starting Air Receivers
[
i Standby Diesel Generator Auxiliary Skid l
Standby Diesel Generator Lube 011 System Piping t
l Standby Diesel Generator Lube Oil Circulation Pump
[
j Stand 1; Diesel Generator tube 011 Filter t
Standby Diesel Generator Lube Oil Heater
[
Standby Diesel Generator Lube 011 Heat Exchanger Standby Diesel Generator Jacket Water System Piping I
Standby Diesel Generator Jacket Water Circulation Pump Standby Diesel Generator Jacket Water Heat Eachanger Standby Diesel Generator Jacket Vater Heater Standby Diesel Generator Jacket Water Standby Pump Standby Diesel Cenerator Jacket Water Stand Pipe l
)
Essential Cooling Vater (EV) System Piping l
l Essential cooling Water Pumps l
Essential Cooling Vater Self Cleaning Strainer Essential Cooling Water Screen Wash Booster Pumps Reactor Make up Water (RM) System Piping Reactor Make up Vater Storage Tank I
i Applicable Section XI selection criteria (IVT 2510) were applied to the non exempt boundary to determine specific component supports required
[
to be examined during PSI. Class 3 component supports were selected for i
PSI examination based on the multiple train concept and selection
[
l criteria discussed in Section 3.2 for Class 2 ccaponents.
}
S3/E048/rr 9
[
t I
,,-n_,
- - - - - = -
-- - - ~----
. e..
TA51.E 3 Y
i Exempted Class 3 Components Portions of Systems /
Fxemption 1
System Components Criterion Auxiliary Piping $ NPS1 IWD 1220.1 (Interpretation) j Feedwater
]
All Class 3 Piping 5 NPS4 IWD.1220.1 Chemical and Boric Acid Tank 2A and 2B IVD 1220.2 j
Volume Control Boric Acid Transfer Pump 1
2A and 25 Boric Acid Filter 2A Component CC to and from the IVD 1220.2 Cooling Water Centrifugal Charging Pumps from the first branch motor operated a
valve (MOV) upstream of the 30" CC Supply Header to the last valve (MOV) of the return to the CC Pump i
supply (3 valves typical).
i CC to and from the Reactor IVD.1220.2 Coolant Pumps from (and it.cluding) the 30" CC supply header to (and including) the 30" CC l
return header.
l
}
CC to and from the Spent IWD.1220.2 Fuel Fool Heat Exchangerg i
from the first valve (MOV) l upstream of 30" CC supply i,
header to the first valve l
(MOV) downstream of the 30" 1
CC return header (3 valves typical),
i CC to and from the Seal IVD.1220.2 Water Heat Exchangur fron the 6" supply header for 25 charging pump to the i
tie in for the 25 charging punp return.
Spent Fuel Fool Heat IWD 1220.2 i
Exchanger 2A and 25 4
l O
S3/E048/rr 10 L
TABI.E 3 CONTINUED O,
Component Seal Water Heat Exchanger IWD 1220.2 Cooling Water 2A Containment Spray Additive Tank 2A, 28, IWD.1220.2 Spray and 2C Diesel Fuel Diesel Oil overflow froni IUD 1220.2 011 tank e21, 22. and 23.
Essential All IWD.1220.2 l
' chilled Vater 6
Essentist EW to and from the IWD.1220.2 Cooling Water essential chillers, from i
the EW 30" supply line to the EV 30" return line.
[
Essential Chillers 21A, IWD 1220.2 218, 210, 22A, 223 and i
22C.
EW Booster Pumps 2A, 28, IWD.1220.2 and 20.
Spent Fuel All IWD 1220.2 Pool Cooling i
l i
l S3/E048/rr 11 I
i i
3.4 Class 3 Integral Attachments ASME Section XI examination requirements for integral attachments to p)
Class 3 components have been included in the component supports PSI program.
The scope of ASME Code Class 3 components, with integral attachments, included in the non exempt boundary was developed as described in Section 3.3.
Since the Code prescribed exauination method for Class 3 integral attachments in the same as that used for Class 3 supports, and since the criteria l'or selection of integral attachments for examination is the same (Table YVD 2500 1, Note 3), the selection process described in Section 3.3 was used.
Integral attachments of the following Clas.s 3 components or systems were included in the STPECS 2 PSI program:
Auxiliary Feedwater (AP) System Piping Component Cooling (CC) System Piping Component Cooling Heat Exchanger Component Cooling Surge Tank Cation Bed Demineralizer 1,etdown Filter Mixed Bed Dominera11:er standby Diesel Generator Starting Air Receivers Standby Diesel Generator Fuel Oil Storage Tank Stat dby Diesel Generator Auxiliary Skid Components Including:
Standby Diesel Generator Jacket Water Heat Exchanger Standby Diesel Generator Jacket Water Heater Standby Diesel Generator Jacket Water Stand Pipe Standby Diesel Generator 1,ube Oil Filter Standby Diesel Generator Lube Oil Heat Exchanger Standby Diesel Generator 1,ube Oil Heater Essential Cooling Vater (EU) System Piping Essential Cooling Water Pv7p Essential Cooling Vater Self Cleaning Strainer Residual Heat 9emoval Heat Exchanger 3.5 Augmented PSI Program In additic,n to the Code required PSI program for components supports, an augntnted FSI program for snubber supports was implemented. This program was required by the NRC as defined in their letter to HIAP (document No. ST AE HL 608) of October 17, 1980.
Since this directive referenced the standard technical specifications as the listing of snubbert, subject to the requirements of the program, it was conservatively interpreted to apply to all snubbers.
O S3/E048/rr 12
f i
The augmented PSI examination was then implemented on each snubber of STPECS Unit 2.
Each applicable examination requirement was implemented and documented nu part of either the PSI program or the pre operational testing program.
The implementation of the program is described in Table 4.
Exempt and non safety supports containing snubbers which were included in the program are listed in Appendix G.
When a snubber support required both PSI and au5mented PSI examinations, the requirements were implemented concurrently, and the examination listed i
in the appropriate Appendix D, E, or F.
The augmented PSI program was implemented after snubber installation j.
but not more than six months prior to initial system preoperational j-
, testing.
]
Q i
)
i i
a i
l
- O 1
s l
l l
l
}
]
l i
l
{
O S3/E048/rr 13 L
TABLE 4 AUCMENTED PSI VISUAL EXAMINATION IMPLEMENTATION AUGMENTED PSI EXAMINED UTILIZING DOCUMENTED EXAMINATION REQUIREMENT PROCEDURE No.
SECTION NO.
ON i
(1) Visible Damage OEP 9.06Q 6.7.2 b VT 4 Exam. Rec.
(VT 4) 6.7.2.1 a,b c Form Part B (mech.)
6.7.2.2 a,b VT 4 Exam. Rec.
(hydr)
Form Part B (2) a) Location OEP 9.05Q 6.6.1 a VT 3 Exam. Rec.
(VT 3)
Form Part C b) Orientation OEP 9.05Q 6.6.1 a VT 3 Exam. Rec.
(VT 3)
Form Part C
- c) Position Setting OEP 9.06Q 6.7.3 c,d,e VT 4 Exam Rec.
(VT 4)
Form Part C d) Configuration OEP 9.05Q 6.6.1 a VT 3 Exam. Rec.
(VT 3)
Form Part C i
(3) Not Seized or Frozen SSP 9 5.6.7.3.8 Pipe Support Snubber Inspection Report
]
(4) Swing Clearance OEP 9.05Q 6.6.5 a VT 3 Exam Rec.
i (VT 3)
Form Part C 4
(5) Fluid Level / Leakage OEP 9.06Q 6.7.2.2 c.d VT 4 Exam. Rec.
(VT 4)
Form Part B l
(6) Structural Connections OEP 9.05Q 6.6.6 c,b VT 3 Exam. Rec.
j (VT-3)
Form Part C For those snubbers subject to heat up during HFT, position settings were verified using the Preoperational Test Procedure 2-RC P 07.
Position settings were documented on applicable system data sheets in Section 9.0 of this procedure.
d 1
i 1
1 i
S3/E048/rr 14
4.0 EXAMINATION PERSONNE
L. PROCEDURE
S, AND EQUIPMENT 4.1 Visual Examination Personnel Qualifications OC All STPEGS 2 PSI examinations reported herein were performed by site personnel qualified and certified to visual examination methods VT 3 and VT 4 as defined by ASME B&PV Code Section XI, 1980 Edition through Vinter 1981 Addenda. All augmented PSI examinations reported herein were perforred by site personnel qualified and certified as indicated above, with the exception of snubber stroking at time of installation.
This activity was performed by a select group of craft personnel specially trained for such snubber activities. This stroking activity was witnessed and documeated by Construction Field Engineering as described in the Pipe Support Installation Procedure, SSP 9.
The qualification and certification of site personnel to the VT 3 and VT 4 methods was conducted in accordance with HIAP's Personnel Qualifi-cation Procedure for Visual Examination (OEP 9.04Q). Appendix A lists the qualification levels for site personnel who were certified to perform examinations during the STPNS-2 PSI.
Certification records for these personnel were reviewed by HIAP Quality Assurance (QA) personnel and the ANII during the PSI.
Copies of these certification records are available for inspection at the STPECS site, 4.2 HIAP Administrative and Examination Procedures The HIAP administrative procedures and examination procedures listed in Appendices B and C, respectively, were utilized to conduct the STPECS 2 i
PSI program.
These procedures were approved in accordance with project procedures controlling safety related activities.
5.0 CONTROL OF EXAMINATION DOCUMENTATION 5.1 Description of Design Document Control Program a
Because of the many revisions to component support designs during the plant construction and initial startup phases, design document control is of major importance to the PSI program.
The Design Document Control Program provides a continuous monitoring of the validity of the completed PSI examination. This program provides for a 1004 review of all amendments or revisions to design documents issued subsequent to the completed PSI examination.
This review is conducted to determine if the revision / amendment has any impact on the PSI examination.
If impact is identified, the examination or portions of the examination are reperformed.
If no impact is identified, this is so documented. This review process has been conducted by the As-Built Reconciliation (ABR) Croup as described in SSP 34.
The review of each amendment / revision is documented on a Design Change Disposition (DCD) Form.
The reports contained in Appendices D, E, and F list the complete history of the design documentation, by.upport, as they pertain to the PSI examination phase. This history is complete through November 18, 1988. Any amendment / revision received and/or reviewed subsequent to this date will be reported in an amendment to this O
summary report.
(See Section 10.0)
S3/E048/rr 15
6.0
SUMMARY
OF EXAMINATIONS 6.1 overview 7'N PSI examinations were performed on component supports of all major Class 1 components including the pressurizer, steam generators, reactor coolant pumps and piping > NPSI.
Overall, one hundred forty six (146)
Class 1 piping and seventy (70) Class 1 equipment supports were examined using the VI 3 examination method, and the VT 4 examination method where applicable. All of the Class 1 component supports were subject to the heat up during HPT and were appropriately examined in conjunction with the heat up. (See Section 1.3).
Appendix D presents a summary of the PSI examinations performed on Class 1 component supports.
PSI examinations were also performed on component supports of Class 2 components including heat exchanges, filt9rs, pumps and high pressure temperature piping > NPf4 (> NPS2 for HHSI). Overall, two hundred fifty eight (258) Class 2 piping supports and twenty (20) Class 2 equipment supports were examined using the VT 3 and VT 4 methods as applicable. Only a portion of the Class 2 PSI scope was subject to the heat up during HPT. Appendix E presents a summary of all PSI examinations performed on Class 2 component supports.
Additionally, PSI examinations were performed on component supports and integral attachments of Class 3 components including heat exchangers, filters, demineralizers, pumps, tanks, strainers, heaters and piping >
NPS4 (: NPS1 for AF).
Overall, two hundred sixty nine (269) Class 3 piping supports and forty five (45) Clara 3 equipment supports were examined using the VT 3 and VT 4 methods as applicable. Additionally, y
fifty two (52) integral attachments to Class 3 components were examined. With the exception of the RER heat exchanger integral attachment, none of the examined Class 3 component supports were subject to heat up during HTT. Appendix F presents a summary of all PSI examinations performed on Class 3 component supports.
6.2 Pre HFT Examinations As briefly described in Section 1.3, pre HPT PSI examinations were ccnducted on PSI supports by certified ABR personnel during their as built reconciliation walkdowns. These PSI exams were conducted after QC acceptance of support construction and, in most cases, prior to HPT.
Examinations were conducted in accordanca with HIAP visual examination procedures.
For supports which were not subject to the heat up during HPT or PAT.
it was acceptable for the PSI examintion requirements to be completely I
satisfied during this examination r,hase.
These examination requirements consisted of a VT 3 examination of all PSI supports in this category and a VT 4 examination of those PSI supports in this category which contained springs or snubbers.
The VT 4 examination included a verification of the cold (baseline) setting of the springs and snubbers in this category.
S3/E048/rr 16 l
For those component supports subject to the heat.up during either H N or PAT, the examination requirements consisted of a VT 3 examination of n
all PSI supports in this category and a VT 4 examination of those PSI (V) supports in this category which contained springs or snubbers. The VT 4 examination of springs and snubbers in this category did ng include a verification of cold (baseline) settings.
The verification of settings (hot and cold) for these supports was conducted during the H M examination phase described in Section 6.3.
For all PSI supports in this category, a reexamination was conducted, by the ABR personnel, after cooldsvn from H N as described in Section 6.4 6.3 PSI Examinations During H G The PSI examination requirements, completed durina this phase of the program, pertained primarily to the VT 4 attributes (verification of settings, freedom of motion). These requirements were satisfied coincidently with the STPEGS 2 Thermal Expansion Test Program.
During ti.is phase, PSI component supports were monitored throughout the heat up and cool dovn plateaus by VT certified start up personnel.
Spring can and snubber settings were exarained, recorded and compared to design documents ano acceptance criteria.
In addition, all portions of components and piping systems subject to the heat up were monitored for freedom of motion.
This program was implemented utilizing the preoparational test procedure 2.RC P.07.
6.4 Post HPT PSI Examinations Subsequent to the cooldown from HN, ABR personnel performed n
reexaminations on all previously examined PSI supports subject to the Q'
heat up.
These examinations were conducted utilizing the H14P VT procedures and verified that the subject component supports had not been damaged as a result of the heat-up testing.
If the initial PSI examination was conducted during this phase of the program, a reexamination for damage assessment was not required.
6.5 Augmented PSI Examinations Augmented PSI examinations of snubbers were conducted and documented as pcrt of the PSI component supports program.
These examinations were conducted on all snubbers installed in STPECS 2.
A total of three hundred sixty six (366) mechanical snubber units comprising three hundred two (302) component supports and sixteen (16) hydraulic snubbers were examined in this program.
The program was implemented as described in Table 4 and was initiated with the installation of the snubbers at STPEGS 2.
The augmented examination was re;'orformed whenever a snubber unit was replaced in the plant.
7.0 EXAMINATION RESULTS AND CORRECTIVE MEASURES
'Ihe results of the PSI examinations were initially evaluated by Level II or Level III VT examination personnel in accordance with the applicable procedures.
If the results of the evaluation indicated an unacceptable condition, a PSI Potential Deficiency Notification (PDN) was then written to S3/E048/rr 17
communicate the problem. A subsequent review of the PDN by Engineering, QC, and Construction resulted in either an acceptance of the condition or generation of appropriate paper work to effect correction of the condition.
O Issuance of this correction paperwork then entered the design document control program and was dispositioned as described in Section 5.1.
One hundred forty six (146) PDN's were written during the PSI examinations.
Esch of these PDN's were closed out by either repair, replacement or acceptance by evaluation or test.
The completed PDNs were added to the permanent record files of the PSI support examinations.
8.0 SNUBBER TESTING As required by 80W81 Section XI Code, IWF.5400, testing for snubbers le:s than fifty (50) kips is a requirement during the PSI pro 5 ram. As permitted by IWF.5200, snubber functional testing was performed on each STPEGS 2 mechanical snubber by the manufacturer.
This snubber testing program was conducted in accordance with Anchor Darling (the manufacturer) inspection and testing procedures. Records of the required testing have been obtained and made part of the permanent PSI examination records package.
Copies of the testing procedures and test records ate available for review at the STPEGS site.
9.0 CERTIFICATION OF INSPECTIONS Section XI NIS 1 forms, "Owner's Report for Inservice Inspections", have been prepared to certify the Section XI STPEGS 2 PSI examinations and tests described in this summary report.
The forms have been included in Appendix 0
H.
These forms oscument the PSI examinations and tests described herein and are certified by the ANII, Lumbermens Mutual Casualty Co.
10.0 REMAINING PSI EXAMINATIONS Additional PSI exkainations may be required on Class 1 Class 2 or Class 3 component supports during the time period between filing of this summary report and start of commercial operation of STPEGS 2.
The need for such examination may result from testing programs, maintenance activities, or repair and/or replacements performed during this time frame.
Several outstanding PSI examinations of component supports have been identified and scheduled at this time.
All of these examinations are associated with t.'ie heat up during PAT ano include verification of settings, freedom of motion and post heat up damage (where accessible).
The applicable component supports in the AF and FW systems have been included in the scope of PAT.
Portions of the examinations will be accomplished by the use of remote monitoring instrumentation, since radiation exposure will limit personnel access.
An amendment to this summary report will be filvd within sixty (60) days after start of commercial operation for STPEGS.2 to document and certify the completion of the PSI examinations.
The amendment will document and certify any other ?SI examinations performed on Class 1, Class 2 or Class 3 component supports subsequent to the filing of this report and prior to commercial operation of STPEGS.2.
S3/E048/rr 18
1 1
1 i
I 1
I l
\\
l I
J i
i
]
i APPENDIX A i
J i
)
LISTING OF PERSONNEL QUALIFICATIONS l
i I
I I
l i
1 i
1
!. O 1
?
d l
l 4
i l
1 l.
f i
r
+
l l
l 1
'i 4
i I
I i
1 I
i S3/E048/rr l
t t
i_-__-._,...
APPENDIX A LISTING OF PERSONNEL QUALIFICATIONS
)
LEVEL OF CERTIFICATION v
LEVEL OF CERTIFICATION NAME VT 3 VT 4 ORGANIZATION Bodner, D.
II II ABR Huerta, H.S.
II II ABR Lingad, V.
II II ABR McCuistion, C.
II II ABR Nguyen, H.T.
II II ABR Parikh, H.M.
II II ABR Pasang, V.C.
II II ABR Bargas, A.
II II PED Blinka, H. S.
II II PED Fisher, D. C.
II II PED Thormashlev E. J.
II 11 PED Vard, R.K.
II II PED Vorley, R. E., Jr.
II II PED Lane, K. C.
II II PED Bechem, A. J.
II II START UP Campbell, M.S.
II II START UP Carabeo, S. J.
II II START-UP Carroll, W. E.
II II START UP
(]
Cruise, B.R.
II II START UP q~,j George, C. R.
II II START UP Gibson, J. C.
II II START UP Cuthrie, J. S.
II II START UP Humbrect, P. J.
II II START UP Jenkins, R. T.
II II START UP Johns, S. V.
II II START UP Joy, D. T.
II II START UP NIcholson, B. W.
II II START UP Schue rmann, L. L.
II II START UP Skinne r, J. D.
II II START UP Stevens, D. M.
II II START UP Stokes, R.C.
II II START UP Svinney, D. R.
II II START UP Svinney, J. A.
II II START UP Taylor, T. A.
II II START UP Thorin, R. V.
II II START UP Ule ry, J. R.
II II START UP Murdock, D.A.
II II ENGINEERING Stewart, M.A.
II II ENGINEERING Langston, D.
II II OPERATIONS QC O'Kelley, L. L.
III III ENGINEERING Armstrong, R.E.
III III ENGINEERING
/~'s A1 S3/E048/rr
i i @
I 4
i f
1 I
l I
i 4
)
APPENDIX B
)
LISTING OF H1AP ADMINISTRATIVE PROCEDURES l
i i
)
i i
I i
[
l S3/E048/rr
APPENDIX B r
(v)
LISTING OF HLAP ADMINISTRATIVE PROCEDURES TITLE PROCEDURE NO.
Interdepartmental Procedures (IP)
IP.1.01Q Records Management IP.'. 02Q Preparations and Review of Submittals IP 1.04Q to the Nuclear Regulatory Commission Document Control IP 1.13Q Document Type List IP 1.31Q Preservice and Inservice Inspection IP.3.04Q Program Non Conformance Control IP 4.1Q Training Records Documentation Syrtem IP.8.4Q Operations Quality Assurance Plan SECTION 18 7T Preparation and Control of Operations OEP 5.01Q
( )
Engineering Procedures (OEP)
Personnel Certification Procedure for OEP.9.04Q Visual Examination Per ASME B&PV Code,Section XI Preparation and Control of OEP 3.02Q Specifications Preservice Inspection Examination of Specification No.
Component Supports of South Texas 5UO36JS0002 Project Electric Generating Station.
i Unit 2 B.i S3/E048/rr
I L
O i
i 1
l l
I h
t APPENDIX C I
l LISTING OF HLAP EXAMINATION PROCEDUR'*
I 1
I i
i I'
i
(
i i
I i
l i
i f
I O
S3/E048/rr
r__-_..
APPENDIX C LISTING OF HLAP EXAMINATION PROCEDURES Illg PROCEDURE NO, Operations Engineering Procedure VT 3 OEP 9,05Q Visual Examination of Component j
Supports l
I Operations Engineering Procedure VT.4 OEP.9.06Q Visual Examination of Component supports Pipe support Installation SSP.9 Technical Requirements and Walkdown SSP.34 Procedure for As.Suilding of Piping Systems Preoperational Test Procedure Thermal 2.RC.F.07 Expansion Monitoring Test O
i I
f I
O C.i 53/E048/rr i
4
~ - - -
--l
a
!O l
!j 2
,i i
1 APPENDIX D i
l 3
CIASS 1 EXAMINATION
SUMMARY
TA31.ES
'f PIPING SUPPORTS (PACES 1 THRU 13) 1 EQUIPMENT SUPPORTS (PAGES 1 THRU 25) i 1
1
!O l
1 l
l 1
l 4
O S3/E048/rr
PSI EXAMINATION
SUMMARY
REPORT APPENDICES 1.ECEND O
Column Headinz Definition Snubber Serial Number SN5R #
Examinations:
DMC Post Heat up Damage AUG Augmented PSI. Snubbers TYP Amendment Type CCP. Configuration Control Package DCN Design Change Notice FCN. Field change Notice FSN Field Sketch Notice j
IDC Interia Design Change Notice NCC + Nonconformance Report. Closed NCC. Nonconformance Report. Open NCR Nonconformance Report PDN. 'otential Deficiency Notice DS3 Disposition of Revision / Amendment Review DS4 First Position:
H Hardware Impat:t I
Documentation Impact 0. Original Disposition t
N. No Impact l
X Pending Disposition 1
Affects Unit 1 Only. No Impact tecond Position:
l C
Revalk Complete N
Rewalk Not Required l
W. Revalk Required O
D1 S3/E048/rr
1 Pg g r -, ___..t Seapports (parsngs f or Syst ee*
CV anas tclase 1 DATE1 16-MOV-se 15*57156 PAGE1 1
i EEAMS%eT10NS HessGER seuMEsCR SNEme tiss9sse VY; VY4 tr4E AUG LOCUMENT NUMSEN SetET flEV DE3 TVP APENDe DS4 l
CV-2OOS-ML5001 C
C C
CV-9001-NL5001 000001 0003 0 FCR DJ-s* 57 O FCR EJ-6843 O 0004 N 000002 0004 N
[
Cv-2 91-ME5001 C
C CV-M 21-ME5001 000001 0003 0 FCR EV-3144 O 0004 N CV-2121*+ets5002 C
C C
'.v-9121-MS5002 000001 0004 0 fCR EV-4520 0_
0005 N 000002 0005 N CV-2128-etE5004 C
C C
CV-9121-MB5004 000001 0004 O FCR EV-3145 O_
0005 N CV-2121-MG5005 C
C CV-9121-MS5005 000001 0003 0 FCR EV-4296 O 0004 88 l
000002 0003 0 0004 N l
CV-2121-ME5006 C
C CV-T$21-MS5006 c.
sJ1 0001 O FCR EV-4470 0 0002 N 000002 0002 N CV-2121-+953007 775 C
C C
C CV-9121-MS5007 000001 0004 0 FCW EV-1441 O~
FCR EV-2902 O FCR EV-5993 N 0005 N 000002 OOro N CV-2121-HE300e C
C CV-9121-HS500s 000001 0002 O F3 EV-434C O~
FCp EV-4499 O FCR EY-76es N NCC SS-3513 HC 0003 as CV-2121-*eS5009 454 C
C C
C CV-9121-**S5009 000001 0003 O F3 EV-4345 O~
FCR EY-4552 O FCR EV-7505 se
- CR SV-CO36 N FOR SV-CO39 N 0004 e6 CV-2121 -+fS5010 456 C
C C
C CV-9121 -*tSA10 000001 0002 O FCR EV-4390 0_
FCR EV-4553 O FCR EV-7495 N FCR SV-OO37 N FCR SV-CO3G N 0003 N CV-2122-HS5003 C
C CV-9122-HS5003 000001 Orm3 m pCR DJ-1695 N_
FCR DV-0994 O FCR DV-3723 O FCR EV-412' O adCC $5-5614 N 0004 MC 000002 0004 #C _,_
CV-2124-+tS5003 C
C CV-9124-MS5003 000001 OfA3 0 FCM DvW59 0_
FDt DV-2926 O FCR E3-5482 O NCC $$-5506 N
~-,___-- __-- --.
~ - - --.- - - - -- -.-. - - - -
OV PSI Cet Sneports detesagt for Systesa:
CV anos q,c3.s. I 141C: 36-MOV-SS 55 37;,6 PAGE:
2 E R AM!se4T IOW.'a MAseGER NUMBER SMGfee X-- -? VY3 VT4 SME AUG farur"1meENT NUMeut SetET feEV DS3 TYP Anome 054
.. = = - -
.~
~~~
CV-2824-**ESOO3 a
C CV-9124-*es5003 000001 0004 m 000002 0004 se CV-23 26-4953OO6 C
C CV-9126-MG3006 O @)O1 0002 O 104 EV-3699 O_
FCR EV-4I00 O FDs EV-4277.,O FCR EV-stS4 HC 0003 N 000002 0003 M CV-212e49sSOO3 C
C cv4129-eeG5001 000001 0002 O esCC C5-5348 O FCN DV-8213 O 0003 N SECC TV-52SO N SCC S5-5739 N 000002 0003 as seCC EV-5230 N asCC SS-3739 N CV-2828-HESCO3 C
C CV-9129-HS5003 0000'** 0000 O FCR BV-1290 0 FCR DV-3722 O FDtEV 6 O 9001 HC 000002 000s teC CV-23 4 8-9463003 C
C C
CV-9 3 41-**S3003 000003 0003 O FCR EV-3ee7 O FCR EV-4048 O SCC NE-3143 se 0004 M 000002 0003 0 SEX:_ 985-3143 N 0004 M CV-2141 -*e63OO7 C
C C
CV-9 8 41-**GSOO7 00000 0002 O esCC CS-3133 M_
FOt EV-3eO4 O FCSE EV-4234 0 0003 N l
l
.. ~,._~__
a6.
ry
('~)
Y,l w
PS1 Component Suppor tm (paping) f or-Synt ese:
RC and q_ class 1 DATE1 16-NOV-88 15:57156 PAGE:
3 r.
EIAr11 NATIONS HANGER MJr1BER SNSRe SNSRs VT3 VT4 9HG.'W,.9 DOCL*1ENT NUr1BER SHEET ~ f DS3 TYP AMENDe DS4 RC-2OOO-RROOO1 C
C RC-9000-RROOO1 000001 0002 0 0003 N 000002 0003 N RC W SHOOO2 C
C C
RC *?OOO-SHOCO2 Ci> COOL M *
- cCR 12.-6.:23 O_,_
(W-4 M 000002 OGO4 N RC-2OOO-SSOOO1 444 C
C L
C RC-%4 4-SSOO' 000001 0004 O FCR EJ,799 HC t~,C S5-5664 1N 0005 N RC-2OO3-HL5001 C
C RC-9( O-HLSOO1 000001 0002 O NCC SS-5311 HC 0003 N RC-2OO3-HL5003 C
C C
RC-9003-HL5003 000001 0003 0 FCR EJ-e459 O 0004 N 000002 OOC 3 0 NCC SS-3655 IN 0004 N 2
RC-2OO3-HL5004 C
C RC-9003-HL5004 000001 0003 0 HC 0004 N NCC SS-5741 RC-2OO3-HL5005 C
C C
RC-9003-HL5005 000001 0004 0 FCR EJ-5790 0 NCC SS-5655 IN 0005 N RC-2OO3-HL5006 622 C
C C
C RC-9003-HL5006 000001 0004 0 FCR EJ-5791 O_
NCC SS-5554 N 0005 N 000002 0005 N RC-2OO3-HLSOO7 C
C RC-9003-HL5007 000001 0002 O NCC CS-5044 O NCC SS-5318 1N 0003 N RC-2OO3-HL5008 C
C RC-9003-HL500d 000001 0003 0 0004 N RC-2OO3-HL5009 623 C
C C
C RC-9003-HL5009 000001 0007 0 0008 N RC-2OO3-RHOOO6 C
C RC-9003-RROOO6 000001 0002 O FCR DJ-6752 O,__
0003 N RC-2OO3-RROOO7 C
C RC-9003-RROOO7 000001 0002 O NCC CS-5053 O__
FCR DJ-6751 O 0003 N RC-2112-HL5001 C
C RC-9112-HL5001 000001 0003 0 FCR EJ-4069 0 0004 N FCR EY-OOO5 O RC-2112-+4 5002 677 C
C C
C RC-9112-HLS)O2 000001 0003 0 NCC BS-4241 O FCR EJ-4643 0 FCR EJ-0238 0 FCR EJ-8273 O FCR EJ-8296 HC NCC S5-5602 N 0004 N 000002 0003 O FCR DJ-9142 O,,,_,
FCR EJ-4683 0 FCR EJ-0273 O FCR EJ-0296 HC FCR EY-GOO 5 0 NCC SS-5602 N
\\
\\
%)
\\v PSI Cosaponent Suppor t m (p a p a r.9) f or-Syst esa:
RC and q_ class 1 DATE: 16-NOV-88 15:57:56 PAGE:
4 EXAr11 NATIONS HANGER PAJMDER SNSRs SNSRs VT3 VT4 DP1G AUG DOCUMENT NuttbER SHEET REV DS3 TYP At1END# DS4 RC-2112-HLSOO2 677 C
C C
C RC-9112-HLSOO2 000002 O G 00000 0004 N RC-2121-HS5002 C
C C
RC-9121-HSSOO2 OOFA1 0004 0 0005 N RC-2123-HL5003 C
C RC-9123-HLSOO3 000001 0004 O FCR EJ-5625 0_,,_
0005 N RC-2123-HL5005 C
C RC-9123-HL5005 000001 0004 0 FCR EJ-3946 0 0005 N RC-2123-HLSOO6 C
C RC-9123-HL5006 000001 0006 0 NCC CS-4772 O__
NCC CS-5178 0 FCR EJ-2174 0 0007 N 000002 0006 O
__,_,DCN 0000001 O_,,,_
NCC CS-5178 O FCR EJ-2174 0 0007 N RC-2123-HL5008 C
C C
RC-9123-HL5008 000001 0005 0 FCR EJ-4407 O FCR EJ-5333 0 FCR EJ-6252 O NCC SS-5635 IN 0006 N 000002 0006 N RC-2123-HL5010 C
C RC-9123-HL5010 000001 0003 0 FCR EJ-6217 0__,,
0004 N RC-2123-HL5011 C
C RC-9123-HL5011 000001 0002 0 0003 N RC-2123-HL5012 C
C RC-9123-HL5012 000001 0004 O FCR EJ-6278 0_
0005 N RC-2123-HL5013 642 C
C C
C RC-9123-HL5013 000001 0004 0 NCC BS-O186 O FCR DJ-7644 0 FCR EJ-6103 O FCR CJ-0175 O 0005 N RC-2123-RROOO1 C
C RC-9123-RROOO1 000001 0003 0 FCR EJ-4112 O__
0004 N RC-2123-RROOO5 C
C RC-9123-HROOO5 000001 0004 O 0005 N NCC SS-5741 HC RC-2123-RROOO6 C
C RC-9123-RROOO6 000001 0004 O FCR EJ-6344 O 0005 N 000002 0005 N RC-2123-RROOO9 C
C RC-9123-RROOO9 000001 0004 0 0005 N RC-2123-RROO10 C
C RC-9123-RROO10 000001 0003 0 FCR EJ-4087 0_,_
0004 N RC-2123-RROO13 C
C RC-9123-RROO13 000001 0003 0 0004 N RC-2123-RROO14 C
C RC-9123-RROO14 000001 0004 0 0003 N RC-2123-RROO16 C
C RC-9123-RROOl6 000001 0002 0 0003 N RC-2123-SHOOO2 C
C C
RC-9123-SHOOO2 000001 0004 0 NCC SS-5635 IN
m fV s
PSI Component Supports (papangt f or-System:
RC and q_ class 1 DATE: 16-NOV-08 15:57:56 PAGE:
5 t
EXAMINATIONS HAN(iER MJMBER SNSRe SNSRe VT3 VT4 Dr1G AUG DOCUMENT NUrtBER SHEET REV DS3 TYP AMENDe DS4 RC-2123-SHOOO2 C
C C
RC-9123-SHOOO2 000001 0005 N RC-2123-SHOOce C
C C
RC-9123-SHOOOO 000001 0004 N FCR EJ-6059 O NCC SS-5655 IN 0005 N RC-2125-HL5001 679 C
C C
C RC-9125-HL5001 000001 0005 N FCR CJ-6179 O FCR EJ-7849 O NCC SS-5598 N 0006 N RC-2125-M 5003 C
C RC-9125-HL5003 000001 0005 N FCR EJ-6140 0_,._
0006 N NCC SS-5259 N 000002 0005 0 0006 N RC-2125-HL5004 C
C RC-9125-HL5004 000001 0004 0 FCR EJ-6157 0 FCR EJ-6375 O 0005 N 000002 0004 0 FCR EJ-6157 O_
0005 N 000003 0005 N RC-2125-HL5007 C
C C
RC-9125-HL5007 000001 0004 0 FCR EJ-6415 O 0005 N 000002 0005 N RC-2125-HL5000 289 C
C C
C RC-9125-HLSOO8 000001 0005 O FCR EJ-5672 O_
0006 N RC-2125-HL5009 C
C C
RC-9125-HL5009 000001 0006 0 FCR EJ-4161 O FCR EJ-6339 0 FCR EJ-6495 0 FCR EY-22O4 0 0007 N 000002 0006 0 FCR EJ-6339 0_
0007 N RC-2125-HL5010 C
C RC-9125-HL5010 000001 0004 0 NCC CS-5163 0 FCR EJ-5645 0 FCR EJ-6088 0 0005 N RC-2126-SHOOO1 C
C C
RC-9126-SHOOO1 000001 0003 O DCN 0000004 N NCC CS-5138 N FCR CJ-4557 O 0004 N RC-2212-HLSOO1 C
C C
RC-9212-HL5001 000001 0005 O FCN 2J-OLU7 0 NCC BS-5102 O NCC CS-5168 0 FCR EJ-5714 0 0006 N 000002 0005 0 FCN 2J-O",87 0_
FCR EJ-5714 0 0006 N 000003 0006 N RC-2220-HS5001 C
C C
RC-9220-He m !
000001 0004 0 FCR EY-4086 O_
FCR EY-4313 0 0005 N FCR EY-81",0 IC NCC 55-5635 N
y_
- f)
V PSI Component Supports (ptpang) f or-System:
RC and o,_ class 1 DATE: 16-NOV-88 15157:56 FAGE:
6
-l EXAMINATIONS HANGER NUMBER SNSRe SNSRe VT3 VT4 DMG AUG DOCurENT NUMBER SHEET 9EV DS3 TYP AMENDe DS4 RC-2220-HS5001 C
C C
RC-9220-HS5001 000002 0004 0 f
0005 N NCC SS-5636 N.,,,,_
RC-2221-HL5001 560 0
C C
C RC-9221-HL5001 000001 0005 O FCR EJ-6185 0 FCR EJ-8092 O l
0006 N 0007 N I
000002 0005 O FCR EJ-6185 0 0006 N j
WM7 N RC-2221-HLSOO2 C
C C
RC-9221-HL5002 000001 0005 O FCR EJ-5355 0 0006 N 000002 0006 N l
RC-2221-HL5003 649 C
C C
C RC-9221-HL5003 000001 0004 O FCR EJ-6263 0_
0005 N 000002 0004 0 l
0005 N 000003 0005 N RC-2221-NL5004 602 C
C C
C RC-9221-HLSOO4 000001 0006 O FCR EJ-5329 O_
FCR EJ-6130 0 NCC SS-5631 HC i
0007 N i
000002 0007 N i
RC-2221-HLSOO5 604 C
C C
C RC-9221-HL5005 000001 0005 0 l
0006 N RC-2221-HL5006 660 C
C C
C RC-9221-HL5006 000001 0003 0 FCR EJ-6125 O FCR EJ-7908 O l
0004 N j
000002 0004 N
{
RC-2221-HLSOO7 621 C
C C
C RC-9221 -HL. ".,007 000001 0004 0 FCR EJ-6129 0 NCC SS-5581 HC l
0005 N j
RC-2221-44.5008 C
C C
RC-9221-HL5008 000001 0004 O FCR EJ-5268 0__
0005 N FCR BJ-1759 N FCR EJ-8390 HC 0006 N 000002 0005 N 0006 N 4
RC-2312-HL5001 C
C RC-9312-HL5001 000001 0003 N NCC CS-5039 N_
FCR EJ-5657 0 I
0004 N RC-2312-NL5002 C
C RC-9312-HL5002 000001 0004 O DCN 0000001 0 1
FCR EJ-6189 O l
0005 N 000002 0005 N RC-23* N 2 521 C
C C
C RC-9320-HLSOO2 000001 0003 O FCR EJ-5176 0_
FCR EJ-8228 O i
0004 N 000o02 OoO4 N j
RC-2320-HL5003 C
C C
RC-9320-HL5003 000001 0003 0 FCR EJ-5323 0 0004 N j
m.
0 0
/
'1 V
PSI Casuponent Supports (ptping) for Syst een:
RC and q_ class 1 DATE: 16-NOV-88 15:57:56 PAGE:
7 EXAMINATIONS HANGER NUMBER SNSRG SNSRs VT3 VT4 Dr1G AUG DOCUMENT NUMBER SHEET REV DS3 TYP APENDO DS4 RC-2320-tC5003 C
C C
RC-9320-HL5003 000002 0004 N RC-2320-NLSOO4 829 C
C C
C RC-9320-tL5004 000001 0003 0 FCR EJ-7200 0_
FCR EJ-7652 O 0004 N 000002 0004 N RC-2321-HSSOO1 C
C C
RC-9321-HS5OO1 000001 0002 O FCR EY-4660 0 FCR EY-8105 HC FCR EY-8178 HC 000002 0002 O FCR EY-4660 0 FCR EY-8105 HC FCR EY-8178 HC RC-2412-HL5001 C
C RC-9412-HL5001 000001 0002 O FCR EJ-5716 0 0003 N NCC SS-5741 HC RC-2412-HL5004 C
C RC-9412-HL5004 000001 0002 O DCN 0000001 O FCR BJ-1170 0 FCR BJ-1608 0 NCC CS-4879 IN NCC CS-5174 N FCR DJ-6694 0 FCR DJ-7851 O NCC HS-5154 N 0003 N RC-2418-HS5001 C
C C
RC-9418-HSSOO1 000001 0002 O FCR EY-3395 0_
0003 N RC-2419-HS5001 C
C C
RC-9419-HSSOO1 000001 0002 O FCR EY-4049 0_
0003 N 000002 0002 O FCR EY-4049 0_
0003 N RC-2419-HS3006 C
C C
RC-9419-HS5006 000001 0005 0 FCR CY-4052 O_
0006 N 000002 0005 0 0006 N RC-2422-HL5001 C
C C
RC-9422-HL5001 000001 0004 O FCR EJ-6166 0_
0005 N RC-2422-HL5002 C
C RC-9422-HL5002 000001 0003 0 0004 N RC-2422-HL".,003 C
C RC-9422-HL5003 000001 0003 O NCC C3-5167 0 0004 N RC-2422-HL5004 C
C C
RC-9422-HL5004 000001 0001 N FCR EJ-5344 O_
NCC SS-5635 IN 0002 N RC-2422-HL5006 C
C RC-9422-HL5006 000001 0004 0 FCR DJ-7133 0 FCR EJ-4308 0 0005 N 000002 0005 N RC-2422-HL5008 C
C RC-9422-HL5008 000001 0003 O FCN 2J-0733 N_
NCC CS-5187 O FCR EJ-3291 O FCR EJ-6628 O FCR EJ-7344 HC NCC SS-5741 HC
m
(%
\\
k (O
)
PS: Couponent SuPPor-t m (P1 Ping 1 f or-System:
RC and q_ class 1 DATE: 16-NOV-88 15:57156 PAGE:
8 EX Art 1NATlONS HANGER MJrtBER SNGRG SNSRe VT3 VT4 DMG AUG DOCut1ENT NUMBER S1EET REV DS3 TYP ArtEND# DS4 l
1 RC-2422-NL5008 C
C RC-9422-HL5000 000001 0004 N RC-2422-HL5009 C
C RC-9422-HL5009 000001 0004 0 NCC BS-0190 0 0005 N RC-2422-NL5010 C
C RC-9422-HL5010 000001 0003 0 FCR EJ-3924 E RC-2422-HL.,011 C
C RC-9422-HL5011 000001 0003 0 0004 N FCR EJ-5625 0 000002 0004 N l
0004 N i
RC-2422-ML5012 C
C RC-9422-HL5012 000001 0002 O FCR EJ-5625 0 NCC SS-5313 HC 0003 N RC-2422-HL5013 C
C RC-5422-HL5013 000001 0004 O FCN 2J-0644 _
0-NCC CS-4744 0 j
0005 N 000002 0005 N RC-2422-HL5014 C
C RC-9422-HL5014 000001 0004 O DCN 0000002 O NCC CS-4908 0 1
FCR EJ-3853 0 l
NCC SS-5738 HC 0005 N RC-2422-NL5015 C
C RC-9422-HL5015 000001 0004 O FCR EJ-2655 0_
NCC SS-5312 HC 0005 N RC-2422-HL5016 C
C C
RC-9422-HL5016 000001 0003 0 NCC BS-4182 O NCC SS-5655 IN 0004 N RC-2422-HL5018 C
C C
RC-9422-HL5018 000001 0002 O NCC SS-5655 IN 0003 N RC-2422-HL5019 831 C
C C
C RC-9422-HL5019 000001 0004 0 NCC CS-5162 O FCR DJ-7214 0 000002 0004 0 FCR DJ-7214 0 0005 N RC-2422-RROOO" C
C RC-9422-RROOO3 000001 0004 0 FCR EJ-5604 0_
0005 N
O O
O PSI Component Suppor-t m (ptping) f or-Syst ers:
RH and oclass 1 DATE1 16-NOV-88 15157:56 PAGE1 9
EX ArtINATIONS HANGER MJMSER SNSRe SNSRe VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYP AMENDe DS4 RH-2101-HL5001 303 C
C C
C RH-9101-HL5001 000001 0004 O FCR EJ-4835 0 0005 N OO(MX)2 0005 N RH-2101-HL5002 295 C
C C
C RH-9101-HL5002 000001 0004 0 NCC CS-5100 0 FCR DJ-9117 0 FCR EJ-4318 0 0005 N RH-2101-94 5003 527 C
C C
C RH-9101-HL5003 000001 0005 0 FCR EJ-4173 O.,_
FCR EJ-6120 G 0006 N RH-2101-HL5006 630 C
C C
C RH-9101 -FN6 000001 0002 O FCR BJ-1526 O__
FCR EJ-5889 0 FCR EY-2923 0 NCC HS-4725 0 0003 N NCC SS-5568 N 000002 0003 N RH-2101-HL5009 487 C
C C
C RH-910i-HL5009 000001 0007 0 FCR BJ-1663 0_
FCR EJ-6114 0 0000 N 000002 0007 O FCR BJ-1663 O FCR EJ-6114 O NCC 55-5479 N WBN RH-2101-HL5010 C
C C
PJt-9701-HL5010 000001 JOO7 0 FCR EJ-6330 0_
0000 N NCC SS-3659 N 000002 0007 O FCR EJ-6330 0 0000 N RH-2101-HL5011 C
C RH-9101-HL5011 000001 0001 O FCR BJ-1746 HC__
FCR EJ-6121 O 0002 N 000002 0002 N RH-2101-RROOO3 C
C RM-9101-RROOO3 000001 0003 N 0004 O NCC BS-O319 N__
NCC SS-5481 N 0005 N RH-2101-SHOOO1 C
C C
RH-9101-SHOOO1 000001 0003 0 NCC CS-5112 O_
0004 N RH-2100-HL5002 C
C RH-9100-HL5002 000001 0003 0 0004 N RH-2108-HL5003 C
C RH-9100-HL5003 000001 0005 0 NCC BS-0349 0_,,_
FCR EJ-6000 0 0006 N RH-2100-HL5004 C
C RH-9AOG-HL5004 000001 0003 O FCR EJ-3139 0 0004 N 000002 0003 0 FCR EJ-5139 O_,,,_
0004 N RH-2100-HL5005 C
C RH-9100-HL5005 000001 0003 0 RH-2201-HL5001 554 C
C C
C RH-9201-HL5001 000001 0007 O FCR EJ-4650 0_,_
0004 N FCR CJ-GO26 O NCO SS-5646 N
.~
.=-
. =
~
O i
d PSI Component Supports (papang) f or-System!
RH and q_ class 1 DATER 16-NOV-08 15157156 PAGE1 10 EX Art 1NAT 10NS HANGER paJrtBER SNSRW SNSRe VT3 VT4 DMG AUG DOCur1ENT PAJMBER SHEET REV DS3 TYP AMENDe DS4 RM-2?O 1-HL.5001 554 C
C C
C RH-9201-HL5001 000001 0000 N NCC SS-3646 N RH-2201-HL5002 C
C RH-9201-HL5002 000001 0009 0 FCR EJ-4052 O 0010 N 000002 0009 0 0010 N RH-2201-HL5004 C
C RH-9201-HL5004 000001 0006 0 0007 N RH-2201-HL5006 SOS C
C C
C SH-9201-HL5006 000001 0005 0 F3 2J-0616 O~
FCR BJ-119$ 0 FCR EJ-7734 HC FCR EJ-0031 HC NCC SS-5576 N 0006 N 000002 0006 N RH-2201-HL5009 C
C C
RH-9201-HLSOO9 000001 0003 0 FCN 2J-0699 0 0004 N RH-2201-HL5010 C
C C
RH-9201--HL5010 000001 0004 0 FCR EJ-4514 0_
FCR EJ-8001 N NCC HS-4747 O NCR SS-5551 N 000002 0004 0 RH-2201-RROOO4 C
C RH-9201-RROOO4 000001 0004 0 0005 N RH-2201-RROOO5 C
C RH-9201-RROOn3 000001 0005 0 NCC CS-4621 0 FCR EJ-3286 0 FCR EJ-6028 0 0006 N 000002 0005 O FCR EJ-6028 0_
0006 N RH-2201-RROOO6 C
C RH-9201-RROOO6 000001 0005 O FCR EJ-6065 0_
0006 N RH-2201-SHOOO1 C
C C
RH-9201-SHOOO1 000001 0007 0 0000 N RH-22OO-HL5001 C
C RH-92OO-HL5001 600001 0003 0 FCR EJ-2770 O~
0004 N NCC CS-4351 O RH-2200-HL'A03 C
C RH-92OO-HL5003 000001 0007 0 FCR EJ-5049 O 0000 N RH-22 %-HL5004 C
C RH-92OO-HL5GO4 000001 0003 0 FCR EJ-6293 0_
0004 N 000002 0004 N RM-22OO-HL5005 C
C C
RH-9208-HL5005 000001 0005 O FCR EJ-5330 0___
0006 N 000002 0005 N RH-22OO-EROOO1 C
C RH-92GO-RROOO1 000001 0005 O FCR EJ-6221 O_
0006 N 000002 0005 O FCR EJ-6221 O~
0006 N RM-2301-HL5001 C
C RH-9301-HL5001 000001 0005 O FCR DJ-5927 0_
NCC SS -5565 HC 0006 N RH-2301-RROOO2 C
C RH-9J01-RROOO2 000001 0004 O NCC CS-5100 N_
_,,~
am
.. D[
/"%. -
6 3-
. wf -
PSI Component SupPor t s (P& Pang) f or-Syst een:
fut and q_ class 1 DATE: 16-NOV-OS 15:57:56 PAGE: 11 EXf#tINATIONS HA80GEft 9&JPtBER SNSRS SNSRS VT3 VT4 DMG AUG DOCUMENT NUNtpER SHEET REV DS3 TYP AMENDS DS4 MH-2301-RROOO2 C
C RM-9301-;E1)OO2 000001 0004 O FCR EJ-1604 0 0005 N RH-2303-SHOOO1 C
C C
RH-9301-SHOOC1 000001 0006 O FCR EJ-6020 0_
0007 N 000002 0006 0 0007 N RM-2308-HL5002 C
C RH-9300-HL5002 000001 0004 O FCR EJ-E)64 0_
0005 N 000002 0005 N RM-23OS-HL5005 C
C RH-9300-HLSOO5 000001 0004 O NCC AS-5189 O_
FCR EJ-6427 O FCR EJ-6530 0 NCC HS-4177 O 0005 N 000002 0004 0 FCR EJ-6427 O FCR EJ-6530 0 0005 N 000003 0005 N t
V 1
l l
l l
i-. -- - -
., -,.. ~ - -., -. - -. -,,. - -. _. _..,. _ - - -.
_ ~. - -.._- -.. -
~
R Iv)
~
PSI Component Support s (P1 Pang) f or-Syst erm:
SI anc q_ class 1 DATE: 16-NOV-BO 15: 57: ~,6 PArz : g; EXArtINATIOfG HANGER NureCR SMSRO SNSPe VT3 VT4 Dr1G AUG LOCur1CNT huribER SHEET REV DS3 TYP APIENDO DS4 CI-2100-NL5001 496 C
C C
C SI-9100-HLSOO1 000001 0007 0 FCR EJ-4667 O FCR EJ-5902 O 0000 N LCN OOsNOO1 N 000002 0007 0 0008 N 000003 0000 N GI-2108-tC".,002 C
C SI-9100-HLSOO2 00000', 0004 O FCR EJ-3397 O 0005 N 000002 0004 O FCR EJ-3397 0 0005 N SI-2108-NL5003 830 C
C C
C SI-9108-HL5003 000001 0007 0 FCR EJ-6133 0_
NCC SS-5192 N NCC SS-5578 N 0006 N 000002 0007 O FCR EJ-6133 0_
NCC SS-5192 N NCC SS-5578 N 0008 N 000003 0006 N SI-2208-HLSOO1 C
C SI-92OO-H 5001 000001 0003 0 FCR EJ-5746 0,,.,
FCR EJ-6124 0 0004 N SI-22OO-HL5002 C
C C
SI-92OO-HL5002 000001 0003 O FCR BJ '"
- O FCR EJ~ 735 u FCR EJ-h:2M 0004 N 000002 0003 0 FCR BJ-1573 O~
FCR EJ-4735 0 0004 N SI-2200-NL5003 C
C SI-9200-HL OO3 000001 0003 O FCR EJ-6257 O~
0004 N 000002 0003 0 FCR EJ-6257 0_
0004 N 000003 0003 0 FCR EJ-6257 O~
0004 N SI-22OG-64.5005 514 C
C C
C SI-9200-fL5005 Ov0001 OmM O 0005 N 000002 0004 0 0005 N SI-2208-RROOO1 C
C SI-9200-RROOO1 000001 0004 O FCR EJ-t 4% 0_
0005 N 000002 Occ4 0 l
0005 N SI-23OO-HLSOO1 630 C
C C
C SI-9300-HL5001 000001 0003 O FCR EJ-9093 0_
FCR EJ-8208 O 0004 N SI-2315-HL5001 C
C C
SI-9315-HL5001 000001 0004 O NCC CS-5159 0 FCR EJ-6238 0 0005 N 4
000002 0005 N S1-2315-905003 c:2 C
C C
C SI-93'5-HLSOO3 000001 0003 0 FCM BJ-16"a O_
m
l 4
v.
~
PSI Component Supports spaping) for Systene:
S1 and q_ class 1 DATE* 16-NOV-US 15:57:56 PAGE: 13 EIAMINATIONS HANGER NureER SMSRe $NSRe VT3 VT4 DMG AUG DOCUME NUMBER SHEET REV DS3 TYP DMENDe DS4 SI-2315-ML5003 62 C
C C
C SI-9315-HLSOO3 000001 0003 0 FCR EJ-5917 0 FCR EJ-6112 O FCR EJ-8227 N FCR EJ-8277 N FCR EJ-8330 N 0004 N 000002 0003 O FCR BJ-1658 0_,,,_
FCR EJ-5917 O FCR EJ-6112 O FCR EJ-8227 N FCR EJ-8330 N FCR EY-8277 N FCR EY-8330 N 0004 N 000003 0004 N 000004 0004 N 000005 0004 N 000006 0004 N SI-2315-ee.5004 603 C
C C
C SI-9315-HL* M 000001 0004 O FCR EJ-6367 0_
0005 N 000002 0004 0 0005 N c1-2327-+4.5001 547 C
C C
C SI-9327-HL5001 000001 0005 0 FCR EJ-5489 0___
0006 N 000002 0006 N SI-2327-HL5004 C
C SI-9327-HLSOO4 000001 0003 0 FCR EJ-3284--_ _,,,_
O 0004 N 000002 0003 O FCR EJ-5204 _
O 0004 N SI-2327-HL5005 C
C SI-9327-HLSOO3 000001 0001 O NCC CS-5165 O___
NCC SS-5718 IN 0002 N NCC SS-5718 IN 000002 0001 0 DCN 0000001 O FCR EJ-6066 O NCC SS-5718 IN 0002 N NCC CS-5165 N NCC SS ".718 IN SI-2327-HL5006 C
C SI-9327-HL5006 000001 0001 O FCR EJ-4056 0 FCR EJ-6161 O FCR EY-3088 0 0002 N
~
i --
O O
U r%
PSI Ceapenent Supports (equipment) for System:RC and t_cl.ss 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
1 EXAMINATIONS 4ASCER NUMSER SN6Re VT3 VT4 DNQ AUQ DOCtJMENT NUMBER SHEET REV DS3 TYP AMENOS DS4 1
l 3c43 C
C C
0957-00000-363 8
0 FCR BN-OOO1 O FCR BN-OO12 O FCR DM-0104 0 FCR EM-OO14 0 FCR EM-OO22 O FCR EM-OO43 0 FCR EN-OOOO O I
FCR EM-0103 O FCR EM-0107 O l
0957-00018-363 C
0 FCR BM-0253 0 1
FCR DN-OO98 O FCR EM-0328 O l
FCR EM-0663 O FCR EM-0717 O FCR EM-0723 0 FCR EN-0111 0 367 C
C C
0937-00000-367 8
O FCR BN-OOO1 O l
FCR BN-OO12 O FCR DM-0104 O FCR EN-OO14 0 FCR EM-OO22 O FCR EM-OO45 0 FCR EN-OOOO O FCR EN-0103 0 FCR EN-0107 0 0937-00018-367 C
O FCR BN-0233 O FCR DN-OO99 O FCR EM-0328 O FCR EM-0663 O FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 368 C
C C
0937-00000-368 8
O FCR BN-OOO1 O FCR BN-OO12 O FCR DM-0104 O FCR EN-OO14 0 FCR EN-OO22 O FCR EN-OO45 O FCR EM-OOOO O FCR EM-0103 0 FCR EN-0107 O 0957-00019-368 C
O FCR BN-0253 0 FCR DN-OOTS O FCR EM-0528 0 FCR EM-0663 0 FCR EM-0717 0 FCR EM-0723 0 FCR EM-0111 0 369 C
C C
0937-00000-369 8
O FCR BN-OOO1 O FCR BN-OO12 O FCR DM-0104 0
am O
~O O
PS1 Ccapenent Supports teguipment) for System RC and g_c14ss 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
2 EXAMINATI M tsArr4R NurtBER SMSAs VT3 VT4 ONO AUG DOCl?iENT Nuf1bER SHEET REV DS3 TYP AnENOW DS4 361P C
C C
0937-0G000-369 8
O FCR EN-OO14 0 FCR EN-OO22 O FCR EN-OO45 O FCR EN-OOOO O FCR EN-0103 0 FCR EN-0107 0 0957-00018-369 C
0 FCR BN-0253 0 FCR E*4-OO98 0 FCR EM-0328 O FCR EM-0663 O FCR EM-0717 0 FCR EM-0723 O FCR EN-0111 0 370 C
C C
0957-00008-370 8
0 FCR EN-OOO1 O FCR BN-OO12 O FCR DM-0104 O FCR EN-OO14 0 FCR EN-OO22 O FCR EM-OO45 0 FCR EN M O FCR EN-0103 0 FCR EN-0107 0 0957-00018-370 C
0 FCR SN-0253 0 FCR DN-OO98 0 FCR EM-0528 0 FCR En-0665 0 FCR EM-O/17 0 FCR EM-0723 0 FCR EN-0111 0 371 C
C C
0937-00000-371 B
O FCR SN-OOO1 O FCR BN-OO12 O FCR Dn-0104 0 FCR EN-OO14 O FCR EN-OOJ2 O FCR EN-OO43 0 FCR EM-OOOO O FCR EN-0103 O FCR EN-0107 0 0957-00018-371 C
0 FCR BN-0233 0 FCR DN-OO98 0 FCR EM-OS28 O i
FCR EM-066: O l
FCT4 EM-0717 C#
FCR En-0723 O FCR EN-0111 O 372 C
C C
0937-00008-372 5
O FCR SN-OOO1 O i
FCR BN-OO12 0 FCR Dn-0104 0 FCR Ete-0014 0 l
FCR EN-OO22 O l
FCR FN-OO43 0 i
O O
O PS1 Component Supports teguspoenti for System:RC and g_ class 1 DATE: 17-NOV-88 13:27:21 PAGE:
3 EXAMINATIONS we,ER NUNSER SNSRd VT3 VT4 Dnc AUQ DOCOMENT Nur"8ER SHEET REV DS3 TYP AMENDO D64 372 C
C C
0937-00000-372 8
O FCR EN-OOOO O FCR EN-0103 0 FCR EN-0107 0 0937-00018-372 C
0 FCR SN-0233 O FCR DN-OO98 0 FCR EM-0328 0 FCR EM-0663 0 FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 373 C
C C
0937-00000-373 S
O FCR SN-OOO1 O FCR BN-OO12 O FCR DM-0104 O FCR EN-OO14 0 FCR EN-OO22 O FCR EN-OO43 0 FCR EN-OOOO O FCR EN-0103 0 FCR EN-0107 O 0937-00018-373 C
O FCR BN-0233 0 FCR DN-OO98 0 FCR EM-C328 0 FCR EM-0663 O FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 374 C
C C
0937-00000-374 3
0 FCR BN-OOO1 O FCR SN-OO12 O FCR DM-0104 O FCR EN-OO14 0 FCR EN-OO22 O FCR D4-OO43 0 FCR EN-OOOO O FCR EN-0103 0 FCR EH-0107 0 0937-00018-374 C
0 FCR 8t4-0233 0 FCR DN-OO98 O FCR EM-0328 O FCR EM-0663 0 FCR EM-0717 0 l
FCR EM-0723 O FCR EN-0111 0 373 C
C C
0937-00000-373 S
O FCR SN-OOO1 O FCR BN-OO12 O FCR DM-0104 0 FCR EN-OO14 0 FCR EN-OO22 O FCR EN-OO43 0 FCR EN-OOOO O FCR EN-0103 0 FCR D4-0107 0
O O
O l
PS1 Cee.genent Supports (egwapment) for System RC and g_cl2Gs 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
4 EXArlINATIONS WdeX3 NLA1SER SN5Re VT3 VT4 DrtG AUG DOCLR1EN7 NUrtBER ENEET REV DS3 TYP M1ENDe DS4 l
i 373 C
C C
0937-00018-373 C
0 FCR DN-0233 O FCR DN-OO98 0 FCR EM-0328 O l
FCR Ert-0665 O l
FCR EM-0717 0 l
FCR EM-0723 0 FCR EN-0111 0 376 C
C C
0957-00008-376 8
0 FCR BN-OOO1 O FCR SN-OO12 O FCR Dei-0104 0 FCR EN-OO14 0 FCR EN-OO22 O FCR EM-OO43 O FCR EN-OOOO O FCR EN-0103 0 l
FCR EN-0107 0 0937-00018-376 C
0 FCR BN-025J O i
FCR DN-OO98 0 FCR EM-0528 0 FCR EM-0663 0 FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 377 C
C C
0937-00008-377 3
0 FCR BN-OOO1 O FCR 8N-OO12 O FCR DM-0104 0 FCR EN-OO14 O FCR EM-OO22 O FCR EN-OO43 0 FCR EN-OO80 0 FCR EN-0103 0 FCR EN-0107 0 0937-teOO18-377 C
O FCR BN-0233 0 i
l FCR DN-OO98 0 i
FCR EM-0328 0 l
FCR EM-0665 O FCR EM-0717 O FCR EM-0723 O FCR EN-0111 0 373 C
C C
0937-00003-378 8
0 FCR BN-OOO1 O FCR BN-OO12 O FCR DM-0104 0 i
(
FC't EN-OO14 0 FCR EN-OO22 O i
I FCR EN-OO45 0 I
FCR EN-OOOO O FCR EN-0103 O FCR EN-0107 0 0937-00018-378 C
0 FCR BN-0253 0 FCR DN-OO98 0 FCR EM-0528 0
PSI Co panent Supports (eguapment) for System:PC and q_ class a DATE: 17-NOV-88 13:27:21 PAGE:
5 EXAMINATIONS N OER NUttaER SNSRG VT3 VT4 DMC AUG DOCUMENT HUNCER SHEET REV DS3 TYP AMENDS DS4 373 C
C C
0957-00018-378 C
0 FCR EM--0665 O FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 379 C
C C
0957-00008-379 5
0 FCR BN-DOO1 0 FCR BN-OO12 O FCR DM-0104 0 FCK EN-OO14 0 FCR EN-OO22 O FCR EN-0045 0 FCR EN-OOOO O FCR EM-0103 0 FCR EN-0107 0 0957-00018-379 C
0 FCR BN-0253 0 FCR DN-OO98 0 FCR EM-0328 0 FCR EM-0665 0 FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 0 300 C
C C
0957-00008-300 S
O FCR BN-OOO1 0 FCR BN-OO12 O FCR DM-0104 0 FCR EN-OO14 0 FCR EN-OO22 0 FCR EN-OO45 0 FCR EN-OOOO O FCR EN-0103 0 FCN EN-0107 0 0957-00018-380 C
0 FCN BN-0253 0 FCR DN-OO98 O FCR EM-0328 0 FCR EM-0665 0 FCR EM-0717 0 FCR EM-0723 0 FCR EN-0111 b 362 C
C C
0957-00008-382 8
0 FCR BH-OOO1 0 FCR BN-OO12 O FCR Det-0104 0 FCR EN-OO14 0 FCR EN-OO22 0
+
FCR EM-OO45 0 FCR FN-OOOO O FCR EN-0103 0 FCR EN-0107 0 0957-00010-382 C
0 FCR DN-0253 0 FCR DN-OO98 0 FCR EM-0328 0 FCR EM-0665 0 FCR EM-0717 0 FCR EM-0723 0
O V
P31 C4mponent Supports (eguipmenti for System:RC and q_ class 1 DATE: 17-NOV-R8 13: 27: 21 PAGE:
6 EXArtINATIONS e4 ANGER NUMBER SNERS VT3 VT4 DMG AUG DOCUMENT NUrtSER SHEET REV D63 TYP AMEPeDe D64 302 C
C C
0957-OC018-302 C
0 FCR EN-0111 0 PRP1 C
C 0130-OOOO3-PR81 C
0 FCR BE-1608 0 0957-OOO10-PRB1 7
0 FCR BN-OOO7 0 FCR BN-OO15 0 FCR CM-0131 O FCR DN-OO97 0 FCR EN-OO81 0 3C01-2-C-1518-PRB1 0008 0 FCN 2C-0279 0 FCR SC-3617 0 FCR CC-4749 0 F(.R EC-0850 0 3C01-2-C-1556-PP81 COO 9 O FCR EC-2172 O PRS 1 C
C 0140-00047-P3S1 D
0 FCR Bet-1304 0 FCR Bet -1327 0 FCR DN-OO67 0 FCR DN-OO69 0 FCR DN-OO90 0 FCR EM-0432 O FCR EM-0443 0 FCR EM-0346 0 FCR EN-OO2O O FOR EN-OO28 O FCR EN-OO41 O FCR EN-OO63 0 FCR EN-OO64 O FCR EP-2798 0 FCR EP-2859 0 FCR EP-2999 0 FCR EP-3182 O FCR SM-0510 0 0140-OOO50-PRS 1 D
0 FCR EM-0295 O FCR EM-0546 0 FCR EN-OO41 O FCR EN-OO63 0 FCR EN-OO64 0 FCR EP-3182 O FCR Set-0510 0 0140-OOO51-PRS 1 D
0 FCR DN-OO68 O FCR EM-OO29 0 FCR EM-OO41 O FCR EM-0295 O FCR EM-0546 0 FCR EN-OO63 0 FCR EN-OO64 0 FCR EP-2798 0 FCR EP-2999 O FCR EP-3182 O FCR SM-0483 0 FCR SM-0510 0 0140-OOOS2-FRS1 C
O 0140-COO 53-PRS 1 B
O FCR DM-OO61 0
O O
O PS1 Component Supports (eguipmenta for System:ftC and g_ class 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
7 EXAMINATI9dS HAWAR Nue1EER SNSpe VT3 VT4 DMO AUG DOC',91ENT NUMBER SHEET REV DS3 TYP AMENDe DS4 PRS 1 C
C 0140-OOOS4-PRS 1 B
O FCR EM-0144 0 0140-OOO35-PRS 1 C
O FCR EM-0213 0 PRut C
C 0130-OOOO1-PRU1 A
O FCR BN-OOOS O FCR BN-0301 O 0937-OOO10-PRU1 F
0 FCR BN-OOO7 0 FCR SN-OO15 0 FCR CM-0131 O FCR DN-OO97 0 FCR EN-OOS1 O FCR EN-0119 HC 1C01-9-S-1332-PRU1 0008 O FCR EC-2083 O FCR EC-2142 0 1CG1-9-S-1337-PRU1 0002 O FCR EC-1739 0 FCR EC-1910 0 1C01-9-6-1537-PRU1 0002 0 PRU2 C
C C130-COOO1-PRU2 A
O FCR BN-OO68 0_
FCR S:4-0301 O 0937-OC010-PRU2 F
0 FCR SN-OOO7 O FCR BN-OO13 0 FCR CM-0131 O FCR DN-C097 0 FCR EM-OO61 O FCR EN-0119 HC 1C01-9-S-1332-PRU2 0008 0 FCR EC-2003 O FCR EC-2142 O PRU3 C
C 0130-OOOO1-PRU3 A
O FCR BN-OOO8 O FCR BN-0301 O 0937-OOO10-PRU3 F
0 FCR BN-OOO7 O FCR BN-OO13 0 FCR CM-0131 O FCR DN-OO97 O FCR EN-OO61 O FCR EN-0119 HC 1C01-9-S-1532-PRU3 0008 O FCR EC-2003 0 FCR EC-2142 0 1C01-9-5-1533-PRU3 0003 0 FCR EC-1918 O FCR EC-2408 C PRu4 C
C 0130-OOOO1-PRU4 A
O FCR 8N-OOS8 0 FCR BN-0301 O 0937-OOO10-PRU4 F
0 FCR BN-OOO7 O FCR BN-OO13 0 FCR CM-0131 O FCR DN-OO97 0 FCR EN-OOS1 O FCR EM-0119 HC 1C01-9-C-1532-PRU4 0008 O FCR EC-2083 0 FCR EC-2142 O SPC1A C
C 0937-OOOO2-RPC1A A
O 0937-OOOO3-RPC1A B
O FCN 2M-OOO3 0 FCR SM-1670 0 FCR SN-OOO3 0
m O
O O
PSI Component Supports (etuapsent) for System:RC and q_tlass 1 DATE: 17-fdN-08 13: 27: 21 PAGE:
8 ERAMINATIONS tenemKR sounSER Ses5Me VT3 VT4 OnQ AUQ 00 CURE.NT Nure:M SHECT Rt V D63 TYP AMDeDe DS4 RPC1A C
C 0937-OOOO3-RPC1A B
O FCR SN-OO17 0 FCR SN-OO19 0 FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR Ch-0166 O FCR CM-0167 0 FCR CM-0173 0 FCR DM-OOO3 0 FCR DM-0144 O FCR DN-0953 0 NCR HM-OSSO O NCR SN-3760 F#4 RPC15 C
C 0937-OOOO2-RFCIS A
O 0937-00003-RPC1B B
O FCM 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0 FCR BN-OO17 0 FCR BN-OO19 0 FCR CM-0152 O FCR CM4156 O FCR CM-0162 O FCR CM-0166 O FCR CM-Ot67 O FCP CM-0173 O FCR DM-OOO3 0 FCR DM-0144 0 FCR DN-OO33 0 NCR HM-OSSO O NCR SN-3760 tot RPC1C C
C 0937-40v02-RPC1C A
O 0937-OMO3-RPCIC F
0 FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0 FCR SN-OO17 O FCR BN-OO19 0 FCR CM-0152 O FCR CM-0136 0 FCR CM-0162 O FCR CM-0166 O FCR CM-0167 0 FCR CM-0173 0 FCR DM-OOO3 O FCR DM-0144 0 FCR DN-OO33 O NCR HM-O3SO O NCR SN-3760 tee CPC1D C
C 0937-OOOO2-RPCID A
O
]
0957-00003-RPC1D 8
O FCN 2f1-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0
.p p
O b
b PSI Component Supporte segwspoent) for Syste=: 4C and g. class 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
9 EXAMINATICNS nae.M PANER SNSpe VT3 VT4 DMO AUG DOC 4 W T NUMBER SHEET REV DS3 TYP AMENDe DS4
- - =
RPC1D C
C 0957-OOOO3-RPC1D 8
O FCR BN-OO17 0 FCR BN-OO19 O FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 0 FCR CM-0173 0 FCR DM-OOO3 0 FCR Det-0144 0 FCR DN-OO53 0 NCR Hrt-OSSO O NCR SN-3760 ted RPCIA C
C 0937-OOOO2-RPC2A A
O 0937-OOOO3-RPC2A B
O FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0 FCR BN-OO17 0 FCR BN-OO19 0 FCA CM-0152 O FCR CM-0156 O FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 0 FCR CM-0173 0 FCR DM-OOO3 0 FCR Det-0144 0 FCR DN-OO53 0 NCR Hrt-OSSO O NCR SN-3760 ted RFC2B C
C 0957-OOOO2-RPC25 A
O 0937-OOOO3-RPC2B B
O FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0 FCR BN-OO17 0 FCR BN-OO19 0 FCR CM-0132 O FCR CM-0156 0 FCR CM-0162 O FCR CM-0166 0 FCr CM-0167 0 FCR CM-0173 0 FCR DM-OOO3 0 FCR DM-0144 0 FCR DN-OO53 0 NCR HM-OSSO O NCR SM-3760 tot RPC2C C
C 0937-OOOO2-RPC2C.
A O
0937-OOOO3-RPC2C B
O FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0
~
h O
O O
PS1 Comp onent S pports segulpmenti f or System:::C and g_cless 1 UATE: 17-NOV-88 13: 27: 21 PAGE:
10 C AMINATIONS eme.xn M.wn sessRe VT3 v74 DMG AuG DOCUMENT NUMBER SHEET REV DS3 TYP AMENDe DS4
=_
APC2C C
C 0937-OOOO3-RPC2C 3
0 FCR BN-OO17 O l
FCR SN-OO19 0 FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR CH-0166 0 FCR CM-0167 O FCR CM-0173 0 FCR DM-OOO3 0 FCR DM-0144 0 FCR DN-OO33 0 hCR HM-OSSO O NCR SN-3760 HN RPC2D C
C 09 37-OOOO2-RPC2D A
O 0937-M 3-RPC2D B
O FCN 2M-OOO3 0 FCR Bid-1670 0 FCR BN-OOO3 O FCR BN-OO17 O FCR BN-OO19 0 FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 0 FCR rM-0173 O FCR DM-OOO3 0 FCR DM-0144 0 FCR DN-OO33 0 NCR HM-OSSO O NCR SN-3760 Fed CPC3A C
C 0917-(rOOO2-RPC3A A
O 0937-OOOQ3-RPC3A S
FCR BM-1670 0 FCR SN-OOO3 0 FCR BN-OO17 O FCR BN-OO19 O FCR CM-0152 O FCR CM-0156 O FCR CM-0162 O FCR CM-0166 O FCR CM-0167 O FCR CM-0173 O FCR DP:-0144 O FCR DN-OO53 0 NCR HM-0330 0 NCR SM-3760 tes RPC38 C
C 0937-OOOO2-RPC3s A
O
~
0937-OOOO3-RPC3a B
O FCN 2M-OOO3 O FCR SM-1670 0 FCR BN-OOO3 0 FCR BN-OO17 0
l G
. V PS1 Ceap anent hyperts tegespeenti for System'RC and q_ class 1 LATE: 17-NOV-98 13. 27: 21 PAGE:
'11 EXArt1NATICMS tthe40R NUMSOE SpeSRe VT3 VT4 DMG AUG DOCL;Mk NT MJMBER SHEET REV DS3 TYP AMENOe DS4 RPC3s C
C 0937-OOOO3-NPC38 3
0 FCR 50.-0019 0 FCR CM-0152 0 FCR CM-0136 0 FCR CM-0162 0 FCR CM-0166 0 FCR CM-0167 0 FCR CM-0173 0 FCR DM-0144 0 FCR DN-OOS3 0 FCR HM-OSSO O FCR SN-3760 Hpe RPC3C C
C 0937-OOOO2-dPC3C A
0 0937-OOOO3-RPC3C 5
0 FCN 2M-OOO3 0 FCR SM-1670 0 FCR BN-OOO3 0 FCR BN-0017 O FCR SN-OO19 0 FCR CM-0152 O FCR CM-0136 0 FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 0 FCR Crt-0173 0 FCR DM-0144 0 FCR DN-OOS3 0 NCR HM-OSSO O NCR GN-3760 ted CPC33 C
C 0937-OOOO2-RPC3D A
0 0937-OOOO3-RPC3D 5
0 FCN 2M-OOO3 0 FCR SM-1670 0 FCR SN- 0003 0 FCR Sh 0017 0 i
FCR BN-OO19 O l
FCR CM-0132 0 FCR CM-0156 0 FCR CM-0162 0 FCR CM-0166 O FCR CM-0167 O FCR CM-0173 0 FCR DM-0144 0 FCR DN-OOS3 0 NCR HM-OSSO O NCR SN-3760 HN RPRIA C
C 0937-OOC 07-6PR1A C
0 FCN 1M-OOO3 0 FCR SN-OOO6 O FCR DN-OOl6 0 FCR BN-OO23 0 FCR BN-OO61 O FCR CM-0143 0 FCR DM-0146 0 FCR EN-OO23 0
~
O O
r f
V PS1 Ceepenent Supports (eguspoent) for System.RC and g_ class 1 DATE: 17-NOV-98 13: 27: 21 PAGE:
12 EPAMINATIONS e nunsER sesERe VT3 VT4 DMG Auc DocunENT NUMBER SHEET REV D63 TYP AMENDe D64 RPRIA C
C 0937-OOOO7-RPRIA C
O FCR EM-OO34 0 FCR EM-OO90 0 FCR EM-0118 0 FCA EN-0122 O FCR EN-0123 O FCR EM-0127 0 1C01-9-S-1333-RPRIA 0003 0 1C01-9-5-133G-RPeta 0002 O FCR EC-1856 0 FCR EC-2083 0 3CO2-2-C-1350-Rest 1 A 0012 O FCR SC-3a13 0 FCR EC-2133 0 FCR EC-2205 0 FCR EC-2408 O RPR15 C
C 0957-OOOO7-RPR13 C
O FCN 1M-OOO3 O FCR BN-OOO6 0 FCR BN-OOle O FCR SN-OO23 0 FCR DN-OO61 O FCR CM-0143 O FCR DM-0146 0 FCR EN-OO23 0 FCR EM-OO34 0 FCR EM-OO90 0 FCR EM-0118 0 FCR EN-0122 O FCR EN-0123 0 FCR EN-0127 0 1C01-9-S-1333-NPR15 0003 0 1C01-9-S-1331.-RPRt3 0002 O FCR EC-1836 0 FCR EC-2083 0 3CO2-2-C-1550-RPJt its 0012 O FCR SC-3913 0 FCR EC-2133 0 FCR EC-2203 O FCR EC-2408 0 RPRIC C
C 0937-OOOO7-RPR1C C
0 FCN 1M-OOO3 0 FCR BN-OOO6 0 FCR BN-OOt6 O FCR BN-OO25 0 FCR BN-OO61 O FCR CM-0143 0 FCR DM-0146 0 FCR EN-OO23 0 FCR ENH3034 O FCR CH-OO90 0 FCR EM-0118 O FCR EM-0122 O FCR EM-0123 0 FCR EN-0127 0 1C01-9-S-1333-RPR1C 0003 0 1C01-9-S-1336-RPR1C 0002 O FCR EC-1836 0 FCR EC-2033 0
. - ~ -.
i 1
=
O 0
0 PS1 Ceepsment S pports (egesament) for Syst.c RC and (close 1 DATE: 17-8sOV-88 13: 27: 21 PAGE:
13 EIMEINATIODeS l
DenfesER NUMSER SBsERe VT3 V' DMG AUG DOCtM4ENT NUNSEk SHEET REV DS3 TYP AnDeDe D64 l
RPRIC C
C 3CO2-2-C-1530-RPRIC 0012 O FCR SC-3913 0 l
FCR EC-2133 0 FCR EC-2205 0 FCR EC-2406 0 RPR1D C
C 0957-OOOO7-RPR1D C
0 FCN 1M-OOO3 0 FCR SN-OOO6 0 l
FCR BN-OOle O i
FCR BN-OO23 0 1
FCR DN-OO61 O FCR CM-0143 0 FCR DM-0146 O FCR EM-3023 0 FCR EM-OO34 0 FCR EN-OO90 0 FCR FcO118 0 FCA G.-0122 O FCR EM-0123 O FCR EM-0127 0 1C01-9-S-1333-RPRID 0003 0 1C01-9-S-1336-RPR1D 0002 O FCR EC-1836 O FCR EC-2083 0 3CO2-2-C-13SS-RPR1D 0012 O FCR SC-3913 0 FCR EC-2133 0 FCR EC-2203 0 FCR EC-2408 0 RPS2A C
C 0907-COOO7-RPR2A C
0 FCN In-OOO3 O FCR SN-OOO6 0 FCR 3N-0016 O FCR DN-OO25 0 FCR EN-Oost O FCR CM-0143 0 FCR DM-0146 O FCR EM-OO2S O FCR EN-OO34 0 FCA EN-OO90 0 FCR De-0118 0 FCR EM-0122 O FCR EH-0123 0 FCR EM-0127 0
(
1C01-9-S-1333-RPR2A 0003 0 1C01-9-S-1336-RPR2A 0002 O FCR EC-18S6 O FCR EC-2083 O CPF2B C
C 0937-COOO7-RPR28 C
0 FCN In-OOO3 0 FCR BN-OOO6 O FCR SN-OOle O FCR BN-OO2S O FCR BN-OO61 O FCR CM-0143 0 FCR DM-0146 O FCR EM-OO23 0 FCR EN-OO34 0
O O
O-
~
'I PEI Ceepenent supports (equapmenti for syseea:RC and g_ class 1 DATE: 17.W88 13: 27: 21 PAGE: 14 EXAMINATI(nee eenseGER souneet SneRe vY3 vie enG AUG DOCUMOeT M.*et.R SnEET RL'V 053 TVP AMDIDe D84 l
~~
RPR2s C
C 0937-COO 97-RPR29 C
O FCR EM-OO90 0 FCR EM-0115 O FCR EN-0122 O FCR EM-0123 0' FCR EM-0127 0 2001-9-S-1333-RPR2B 0003 0
_.'01-9-S-1336-RPR 28 0002 O FCR EC-ISS6 0___
i FCR EC-2003 O RPR2C C
C 0937-OCOO7-RPR2C C
0 FCN 1M-OOO3 O FCR Be:-0006 O FCR BN-OOle O FCR ON-OO25 O FCR DN-OO61 O I
FCA CM-0143 0 1
FCR DM-0146 O FCR EM-OO25 O FCR EM-OO34 0 FCR EN-OO90 0 FCR EM-0118 O FCR D4-0122 O FCR EM-0123 O FCR EM-0127 0 1C01-9-S-1333-RPR2C 0003 0 1C01-9-s-1336-PPs2C 0002 O rCR EC-teS6 0 FClu EC-2063 0 EFE2D C
C 0957-COOO7-RPR2D C
O FCN 1M-OCO3 0 FCR BN-OOO6 O FCR BN-OO16 O FCR BN-OO23 O FCR BN-OO61 O FCR CM-0143 0 FCR DM-0146 0 FCR EN-OO23 0 FCR EN-OO34 0 FCR EM-OO90 O FCR EM-0118 O FCR EM-0122 O FCR EM-0123 0 FCR EN-0127 0 1C01-9-S-1336-RPR2D 0002 O FCR EC-1836 O FCR EC-2083 O CPR3A C
C 0957-OCOO7-RPR3A C
0 FCN 1M-OOO3 O FCR BM-OOO6 0 FCR BN-OOle O FCR SN-OO2S O FOR DN-OO61 O FCR CM-0143 0 FCR DM-0146 0 FCR EM-OO2S O FCR EH-OO34 O FCR EM-OO90 0
__ --- -,--. ~ _ _ _ _ _,,
.--~._., _ --,,,_ _ _._.- _,-- _ _. - -
~
1 l
O O
O I
PSI Ceepeneet Supports (e4wnpments for System RC and (_Ctess &
DATE: 17-NOV-98 13: 27: 21 PAGE:
15 EEAMINATI3NS 6 seUMEER SesEme VT3 VT4 Ento AUO DOCUMENT NureER SMEET REV DS3 TYP AMENDS D64 I
RM3A C
C 09S7-COOO7-RPR3A C
O FCR EM-0118 O FCR EM-0122 0 j
FCR EM-0123 0 i
FCR EN-0127 0 l
1C01-9-S-IS33-RPR34 0003 0 IC01-9-S-1536-RPR3A 0002 O FCA EC-18% 0 4
FCA EC-2083 0
)
Rea3s C
C 0957-00007-RPR38 C
O FCN 1M-OOO3 0 FCA BN-OOO6 0 i
FCA DN-OOle O FCR DN-OO2S O FCR 3N-0061 O l
FCA CM-0143 0 1
FCA DM-0146 0 FCR EM-OO23 0 FCA EM-OO34 0
]
FCA EM-OO90 0
]
rCR EM-Olle O FCR EN-0122 O 4
l FCR EN-0123 0
)
FCR EM-0127 0 4
1C01-9-3-1333-9PR3e 0003 0 3C01-9-6-1336-RPW3e 0002 O FCR EC-18Sh 0 FCR EC-20e3 0 1
RPR3C C
C 0937-OOOO7-RPR3C C
0 FCN 1M-OOO3 O FCR DN-OOO6 0 FCR SM-OOte O
)
FCR 34-002S 0 i.
FCR SM-CO61 O FCA CM-0143 O FCR DM-0146 O FCR EM-OO23 0 FCR EM-OO34 O FCA EM-OO90 0 FCR EM-Otte O FCR EN-0122 O FCA EM-0123 O FCA EM-0127 0 1CC1-9-6-1333-RPR3C 0003 0
_ EC-te h O_
1C01-9-5-1336-RPR3C 0002 O FCR FCN EC-2083 O SP830 C
C 0937-00007-Rf'R30 C
0 FCN IM-OOO3 O FCR DN-OOO6 0 FCR BN-OOl6 0 FCR DN-OO23 0 FCR BN-OO61 O FCR CM-0143 O FCR DM-0146 0 FCR EM-OO23 0 FCR EM-OO34 0 FCA De-OO90 0
[
,l J
PSI Ceapement supports tegwipmentt for System RC and g_ class 1 DATE; 17-NOV-88 13:27:21 PAGE:
16 EMan1 NATIONS MAse;Ot asungER SNORE VT3 VT4 Lao AUG DOctJnt.NT NUMSER SHEET REV E*,3 TYP APENDO DS4 RPR30 C
C 0937-OoOO7-RPR30 C
0 FCR EM-Otte O FCR EM-0122 O FCA EM-0123 0 FCR EM-0127 0 1C01-9-S-1333-RPR3D 0003 0 1C01-9-5-1336-RPR30 0002 O FCR EC-1936 O FCR EC-2083 O SGCIA C
C 0937-OOOO2-SCC 1A A
O 0937-OOOO3-SCCIA B
O FCN 2M-OOO3 O FCR SM-1670 0 FCR SM-OOO3 0 FCR BN-OO17 O FCR BN-OO19 0 FCR CM-0152 O FCR CM-0156 O FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 O FCR CM-0173 O FCR DM4144 O FCR DN-OOS3 O SGC18 C
C 0937-OOOO2-SCC 1B A
O OV37-OOOO3-SGC15 5
O FCN 2M M A O FCR 9M-sb70 0 FCR sN-OOO3 O Tdt SN-OO17 0 FCR DN-OO19 0 FCR CM-0132 O FCR CM-0136 O FCR CM-0162 O FCR CM-0166 O FCH CM-0167 0 FCR CM-0173 0 FCR DM-0144 0 FCR DN-OO33 0 MCIC C
C 0937-O W SCC C A
O 0937-OOOO3-SCC 1C 3
O FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 O FCR BN-OO17 0 FCR SM-OO19 O FCR CM-0132 O FCR CM-0136 O FCR CM-0162 O FCR CM-Ol66 0 FCA CM-0167 O FCR CM-0173 0 FCR DM-0144 0 FCR DN-OO53 O MCID C
C 0937-COOO2-SCC 10 A
O 0937-OOOO3-SCCID 3
0 FCN 2~1-0003 0
O
'O O
0.
fer 5 st'e:RC and g_ class 1 DATE: 17-NOV-88 13: 27: 21 PAGE:
17 751 Ceapsaent Sweports (e4wipmentl 1
EXAMIh6TIONS tema.XR MUMS 4R SesSRe VT3 VT4 DetG M80 DOCurCNT NUMSER SHEET REV DS3 TYP AMENOG DS4
__~
SGCSD C
C 0957-OOOO3-SGC1D 3
0 FCR SM-1670 0 FCR BN-OOO3 0 FCR BM-OO17 O FCR BM-OO19 O FCR CM-0132 O FCR CM-Ot h O FCR CM-0162 O FCR CM-Otu O FCR CM-0167 0 FCR CM-0173 O FCR Det-0144 0-FCR D0e-0033 O SGC2A C
C 0937-OOOO2-SGC2A A
O 0937-COOO3-SGC2A 8
0 FCN 2M-OOO3 0 FCR DM-1670 0 FCR DN-OOO3 0 FCR DN-OO17 O FCR DN-OO19 0 FCR CM-0132 O FCR CM-0136 O FCR CM-0162 O FCR CM-0166 0 FCR CM-0167 O FCR CM-0173 0 FCR DM-0144 0 FCR DN-OOS3 O SGC2s C
C 0937-00002-5CC28 A
O 0937-COOO3-SGC2B 3
0 FCN 2M-OOO3 0 FCR SM-1670 0 FCR BN-COO 3 0 FCR DN-OO17 O FCR DN-OO19 0 FCR CM-0152 O FCR CM-01% 0 FCR CM-0162 O FCR CM-0166 O FCR CM-0167 0 FCR CM-0173 O FCR Get4144 O FCR DN-OOS3 O SGC2C C
C 0937-OOOO2-SGC2C A
O 0937-OOOO3-SGC2C 3
0 FCN 2M-OOO3 0 FCR SM-1670 0 FCR BM-OOO3 O FCR 9N-0017 0 FCR BN-OO19 0 FCR CM-0152 O FCR CM-01% 0 FCR CM-0162 O FCR CM-Ol u O FCR Crt-0167 0
(
)
v
- St Component Supports leguapment) for System.RC and g_ class 1 DATE: 17-NOV-88 13: 27: 20 PAGE:
18 EXAMINATIONS HAecER kJ:*SCM SN5fe# VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYF AMEMOS DS4 SCC 2C C
C 0957-OOOO3-SGC2C 5
0 FCR CM-0173 O FCR DW O144 O FCR DN-OOS3 O SCC 2D C
C 0937-OOOO2-SCC 2D A
O 0937-COOO3-SCC 2D 5
O FCN 2M-OOOJ O FCR BM-1670 0 FCN SM-OOO3 0 FCN DNMM)17 0 FCN SM-OO19 0 FCN CM-0152 O FCM CM-01% 0 FCN CM-0162 O FCN CM 1166 O FCN CM-0167 0 FCM CM-0173 0 FCN DM-0144 0 FCN LM-OOS3 O SCC 3A C
C 0957-OOOO2-SGC3A A
O 0937-OOOO3-SOC'.3A 3
D FCN 2M-OOO3 O FCR BM-1670 0 FCR DN-OOO3 0 FCR DN-OO17 O FCR DN-0019 0 FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR CM-0166 O FCR CM-Ol67 O FCR CM-0173 O FCR DM-01*4 O FCR DN-OOS3 O SCC 3B C
C 0957-OOOO2-SOC 3s A
O 0937-OOOO3-CCC38 3
0 FCN 2M-OOO3 U FCR BM-1670 0 FCR DN-OOO3 O FCR BN-OO17 0 FCR BN-OO19 0 FCR CM-0152 O FCR CM-01% 0 FCR CM-0162 O FCR CM-01L - 0 FCR CM-OS67 0 j
FCR CM-0173 0 FCR DM-0144 0 FCR DN-OOS3 0 FA;C 3C C
C 0957-OOOO2-SCC 3C A
O l
0957-OOOO3-SCC 3C P
O FCN 2M-OOO3 9 FCR SM-1670 0 FCR DN-OOO3 0 FCR DN-OO17 0 FCR SN-OO19 0
y A
-4 O
O
~
O Pt;1 Component Supports 8etuspoentl for System.RC and g_ class 1 DATE. 17-NOV-99 13: 27: 21 PAGE:
19 CNAM1 NATIONS HAVi3 NUMBER SNSRG VT3 VT4 DM2 AUG DOCUMENT NUMSCR SHECT REV DS3 TV' AfENDO DS4
- ~ - -
SGC3C C
C 0937-OOOO3-SCC 3C 3
0 FCR CM-O132 O FCR CM-0156 0 F4R CM-Ose2 O FCR CM-Oth O FCR CM-0167 0 FCR CM-0173 0 FCR DM-0144 0 FCR 1m-OOS3 O SCC 3D C
C 0937-OOOO2-SCC 3D A
O 0957-OOOO3-SCC 30 3
O FCN 2M-OOO3 0 FCR SM-1670 0 FCR SM-OOO3 0 FCR SM-OO17 3 FCR SN-OORT O FCR CM-O132 O FCR CM-0136 O FCR CM-OIL'l O FCR CM-0166 0 FCR CM-0167 0 FCR CM-0173 0 i
FCR Det-0144 0 FCR DN-OOS3 O SGC4A C
C 0937-OOOO2-SGC4A A
O 0957-OOOO3-SCC 4A B
O FCN 2M-OOO3 0 FCR SM-1670 0 FCR DN-OOO3 0 FCR SM-OO17 O FCR SM-OORT O FCR CM-0152 O FCR CM-0136 0 FCR CM-C162 O FCR CM-0166 0 FCR CM-0167 0 FCR Ch-0173 0 FCR DM-0144 0 FCR DN-OOS3 O SGC48 C
C 0937-OOOO2-SGC43 A
O 0937-OOOO3-SGC43 3
O FCN 2r9-OOO3 0 FCR BM-1670 0 FCR DN-OOO3 O FCR SM-OO17 0 FCR DN-OO19 0 FCR CM-0152 O FCR CM-0136 0 FCR CM-0162 O FCR CM-0166 0
'R CM-0167 0 CH-0173 0 tCH DM-0144 0
)
FCR DN-OOS3 0 SCC 4C C
C 0957-OOOO2-SGC4C A
O
O O
~
O PSI Component Supports (egw&pment) for Systee: RC and (class 1 DATE: 17-NOV-88 13: 27: 21 PAGE: 20 ENAMINATIONS HAncEn NUMtCR SNene VT3 VT4 DMG A8JO DOCUMENT NUMSER SHEET REV DS3 TYP AMDeDe D64 i
SCC 4C C
C 0957-OOOO3-SCC 4C 3
O FCN 2M-OOO3 0 FCR BM-1670 0 FCR BN-OOO3 0 FCR BM-OO17 0 FCR BN-OO19 O FCR CM-0152 O FCR CM-0156 0 FCR CM-0162 O FCR CM-0166 0 FCR CM-Ol67 0 FCR CM-0173 0 FCR DM-0144 0 FCR DN-OO53 0 GCC4D C
C 0957-OOOO2-SCC 4D A
O 0937-OOOO3-SCC 4D B
O FCN PM-OOO3 0 FCR '.3M-1670 0 FCR BN-OOO3 0 FCR SM-OO17 0 FCR BN-OO19 O FCR CM-0152 O FCR CM-0156 O FCR CM-0162 O FCR CM-0166 O FCR CM-0167 O FCR CM-0173 O FCR DM-0144 0 FCR DN-OO53 O SCL1A C
C 0937-OOOO4-SQL1A B
O FCR BM-OG68 0 FCR BM-1164 0 FCR BM-1176 O FCR BM-1189 0 FCR SM-1228 O FCR BM-1237 O FCR DM-1262 O FCR BM-1303 0 FCR BM-1441 O FCR BM-1500 0 l
FCR BM-1673 0 i
FCR BM-1751 O l
FCA DN-OOO4 0 FCR BN-0379 0 FCR CM-0184 0 FCR DN-OO48 0 FCR EK-4717 0 FCR EM-OO55 O FCR EM-0104 0 FCR EM-0115 O FCR EM-0116 0 FCR EN-0126 0 FCR EM-0128 0 i
l FCR EM-0130 0
~
s
+m O
O O
P01 Component Supporte (eguipment) for Svetem:RC and (class 1 DATE: 17-NOV-08 13: 27: 21 PAGE: 21 EXAMINATIONS 8W4XR NLduBEA SNSRe VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYP AMENDe DS4 SGL1A C
C 0957-OOOO4-SCL1A B
O FCR EN-0131 O 0957-08VA)S-SGLI A B
O FCR BM-0930 0 FCd SN-0261 O FOR BN-0337 0 FCR C*t-0212 O FCR LN-OOO7 O SGL1B C
C 0937-OOOO4-SQLIB B
O FCR BM-OS68 O FCR BM-1164 0 FCR BM-1576 0 FCR BM-1189 0 FCR BM-1229 0 FCR BM-1237 0 FCR Bft-1262 O FCR BM-1303 0 FCR BM-1441 O FCR BM-1SOO O FCR BM-1673 0 FCR BM-1751 O FCR BN-OOO4 O FCR BN-0379 0 FCR CM-0184 0 FCR DN-OO48 0 FCR EK-4717 0 FCR EN-OOSS O F' R EN-0104 0 t :8 EN-0113 0 FCR EN-0116 0 FCR EN-0126 O FCR EN-0128 0 FCR EM-0130 0 FCR EM-0131 O 0937-OOOOS-SGL1B B
O FCR BM-0930 0 FCR BN-0261 O FCR BN-0337 0 FCR DM-0212 O FCR DN-OOO7 O SGLIC C
C 0957-OOOO4-SGL1C 3
O FCR BM-OS68 O FCR BM-1164 0 FCR BM-1176 O FCR BM-1199 0 FCA BM-1228 O FCR BM-1237 0 FCR BM-1262 O FCR BM-1303 0 FCR BM-1441 O FCR BM-1SOO O FCR BM-1673 0 FCR BM-1731 O FCR BN-OOO4 0 F A BN-0379 0 FCA CM-0184 0 l
_..._m
.c 1
O O
O PCI Ceepenent Supporte (egespeenti for Sgetea RC and g_ class 1 EATE: 17-NOV-88 13: 27: 21 PAGE: 22
)
EXAMINATIONE I
HAesGER NUMSER SMSRs VT3 VT4 Dre0 ADO E tJMENT MUMBER 5eEET REV D53 TYP ME8Se D94
~ ~ ~ ~
f l
SGLIC C
C 0957-OOOO4-50LIC 3
O FCR 04-0048 O i
i FCR EM-4717 O i
FCR EM-OOSS O j
)
FCR EM-0104 0 i
FCR EM-0115 0 l
FCR EM-Otte O l
FCA EM-0126 O FCR EM-012e O FCR EM-0130 0 l
FCR EM-0131 0 l
0957-OOOOS-90LIC 5
0 FCR SM-0930 0 l
FCR DN-0261 O FCR DN-0337 O FCA LM-0212 0 FCR DM-OOO7 0 j
t SCL1D C
C 0957-00004-SQLID 5
O FCR an-OS68 0 FCR BM-1164 O j
FCR SM-1176 O FCA SM-1189 O FCR SM-1228 0 FCA BM-1237 0 FCR 3M-1262 O I
FCR BM-1303 0 i
FCR BM-1441 0 FCR BM-1SOO O i
FCR BM-1673 0 FCR BM-1731 O FCW BN-OOO4 O FCR BN-0379 0 I
FCR CM-0184 0 i
j FCR DM-OO48 0 j
FCA EM-4717 0 FCR EN-DOSS O FCR EM-0104 0 FCR EM-0113 O I
FCR EM-0116 O l
FCR EM-0126 0 FCR EM-0128 O FCR EM-0130 O l
FCR EM-0131 O j
0957-00003-SQL1D 5
O FCR BM-OV30 0 i
FCR 94-0261 O l
FCR 04-9337 0 j
FCR DM-0212 0
{
FCR DN-OOO7 0 i
SGu1A C
C 0937-00008-SOURA 3
0 FCR DN-0001 O A
FCR 306-0012 0 FCR Det-0104 0 FCR EM-OO14 0 i
FCR EM-OO22 O I
FCR EM-OO45 O l
~
O O
%./
PSI Component Supporte fetw&pment) for Svetee:RC and 4_ class 1 DATE: 17-NOV-93 13: 27: 21 PAGE: 23 EKAMINATIONS hap."iR NUMBER SNGRG VT3 VT4 DMG AUG DOCUMENT 9eJMcER SHEET REV DS3 TYP AME966 DS4 SGU1A C
C 0937-00006-SGU1A 5
0 FCR EN-OOOO O FCR EN-0103 0 FCR EM-0107 O FCR EM-0124 O FCR EM-0125 C' FCR EM-0126 0 FCR EN-0130 0 0937-OOOO9-SGU1A B
O FCR BN-OOO1 O FCR BN-OO12 O FCR DN-OO30 0 FCA D99-0085 0 FCR DM-024S O FCR DN-OO94 O FCR EM-OO14 O FCR EM-OO17 0 FCR EM-OO21 O FCR EM-OO33 O FCR EM-OO58 0 FCR EM-0103 0 0957-OOO15-SGU1A 3
0 FCR BN-OOO1 O FCR BN-0337 0 FCR DM-0211 0 FCR EM-OOO3 O FCR EM-OO23 0 FCR EM-OO36 0 FCR EM-OO38 0 FCR EM-OO42 O FCR EN-0106 O SGU15 C
C 0937-OOOOS-SGU1B B
O FCR BM-OOO1 O FCR SN-OO12 O FCR Def-0104 0 FCR EN-OO14 0 l
FCR EN-OO22 0 FCR EM-OO45 0 FCR EM-OOOO O FCR EN-0103 0 FCR EM-0107 0 FCR EM-0124 0 FCR EN4123 O l
FCR EM-0126 0 FCR EM-0130 0 0957-00009-50U13 3
0 FCR BN-OOO1 O FCR BN-OO12 O FCR BN-OO50 0 FCR Det-OOO5 0 FCR Det-0243 0 FCR DN-OO94 0 FCR EN-OO14 O FCR EM-OC17 0 FCR EM-OO21 O FCR EM-OO33 0
~ - - - - -
O O
O PSI Component Supports (eguipment) for System:RC and Lclass 1 DaTE: 17-NOV-88 13. 27: 21 PAGE: 24 EXAftINATIONS H m ;ER NUMSER $NSRS VT3 VT4 DRG AUC DOCUMEhT NUMSER SHEET REV DS3 TYP AMOeDe D64 SGute C
C 0937-00004-50015 a
O FCR EM-OOSe O FCR EM-0105 O 0937-OOO13-SG313 5
O FCR DN-OA1 O FCR BM-e337 0 FCR DM-0211 O FCR EM-OOOS 1 FCR EM-OO23 J FCR EM-OO36 3 FCR EM-OO3e 3 FCR EM-OO42 3 FCR EM-010d> D SGU1C C
C 49S7-OOOOS-SOU1C 3
O FCR BM-OOO1 O FCR BN-OO12 O FCR DM-0104 0 FCR EN-OO14 O FCR EM-OO22 O FCR EM-OO43 0 FCR EM-OOOO O FCR EM-0103 O FCR EM-0107 O FCR E'N-0124 O FCR EM-0123 0 FCR EM-0126 0 FCR EM-0130 0 0937-OOOO9-SCU1C 3
O FCR SN-OOO1 O FCR BM-OO12 O FCR BN-OOSO O FCR DM-OOSS O FCR DM-0243 0 FCR DN-OO94 0 FCR EM-OO14 O FCR EP-OO17 O FCR EN-OO2L G FCR EM-OO35 O FCR EN-OOS8 0 FCR EM-010S O 0937-OOO13-SCU1C 8
0 FCR BM-OOO1 O FCd BN-0337 0 FCR Det-0211 O FCR EM-OOOS O FC2 EM-OO23 0 i
FCR En-OO36 0 FCR EM-OO3G O l
FCR EM-OO42 O FCR EM-0106 O SGU1D C
C 0937-00008-5001D 3
O FCR SM-OOO1 O FCR 8t,-0012 0 FCR M-0104 O l
FCR De-0014 0 i
l FCR EM-OO22 O FCR EN-OO45 O
}
O o
v PSI Component Supports (egutpoent) for System.RC and (class 1 DATE: 17-f40V-8G 13:27 21 PAGE: 25 l
EXAMINATIONS t<At4CR NUNSER SNSAs VT3 VT4 Droo AUG DOCUMENT MUrtSER SHEET REV CS3 TYP AMENDS D64 SOU1D C
C 0957-OOOOS-SGUID B
O FCR D*-OO90 0 FCR EM-0103 0 FCR EM-0107 O FCR EM-0124 O FCR EM-012S O FCR EM-0126 O FCR EM-0130 0 0957-00009-SGU1D 3
0 FCR SM-OOO1 O FCR BN-OO12 O FCR BN-OOSO O FCR DM-OOS5 O FCR DM-0245 O FCR DN-OO94 O FCR EM-OO14 0 FCR EM-OO17 O FCR EM-OO21 O FCR EN-OO3S O FCR EM-OO58 O FCR EM-0105 0 0957-OOO15-SQUID 3
0 FCR 9N-0001 O FCR BN-0337 O FCR DM-0211 O FCR EM-OOOS O FCR EM-OO23 0 FCR EM-OO36 0 FCR EM-OO38 0 FCR EM-OO42 O FCR EM-0106 O
O APPENDIX E i
CIASS 2 EXAMINATION
SUMMARY
TABLES PIPING SUPPORT (PAGES 14 THRU 28) i EQUIPMENT SUPPORTS (PAGES 26 THRU 29) i
!O i
i i
i f
I J
1 b
i,
!O 1
S3/E048/rr l
i 1
e i
r PSI EXAMINATION
SUMMARY
REPORT APPENDICES 1.ECEND l
O l
Column Headinz Definition I
t SNSR e.
Snubber Serial Number Examinations
TYP Amendment Type f
CCP Configuration Control Fackage DCN. Design Change Notice FCN Field Change Notice r
FSN Field Sketch Notice IDC Interim Design Change Notice i
NCC Nonconformance Report. Closed l
NCO Nonconformance Report. Open NCR Nonconformance Report
(
PDN Potential Deficiency Notice DS3 Disposition of Revision / Amendment Review DS4 First Position:
I O
H. Hardware Impact I. Doe" tr.t.'iti. I pat j
0 Original Disposition N
No Impact i
X Pending Disposition
(
1 Affects Unit 1 Only No Impact
[
l Second Position:
l t
C Revalk Complete I
N. Revalk Not Required V
Rewalk Rsquired l
l I
t I
O E1 l
S3/E048/rr i
i i
_?
e.
O.
l PSI Component Swport s (ptpingt f or Syst een:
M. sod re class 2 DATE1 16-NOV-88 15:571*,6 PAGE:
14 ENAMINAT10NS j
HANGEA1 NUPGER iiNEiRG SMSRS VT3 VT4 DMG AUG FMim1ENT NUPWER SHEET REV DS3 TYP APE.MOS D64 i
i i
AF-2012-HL5002 C
AF-9012-NL5002 000001 0002 O FCR EJ-6613 0 FCR EJ-6962 O M-2012-HL5004 C
AF-9012-HL5004 000001 0005 O NCC 35-3621 N FCR EJ-6535 O FCR EJ-714O O Om2 0005 O FcR Es-7140 0 AF-2012-HL5005 C
AF-9012-HL5005 OOOOC? 0005 0 000002 bM", C AF-2012-NL5007 C
AF-9012-HL5007 000001 0002 O FCR DJ-1519 O MCC 55-5562 O AF-2012-HL*d)OV C
AF-9012-14.5009 000001 0003 0 FCR EJ-3e31 O FCR EJ-7004 0 NCC SS-5484 X NCC 55-5553 N AF-2012-M.;,J10 C
AF-9012-ML5010000001 0003 O FCR EJ-4268 0 NCC HS-4693 Def AF-2012-NL5011 C
AF-9012-tt5011 000001 0005 O FCR EJ-4007 0 j
FCR EJ-5215 0 i
Ar-2012-HL5012 C
AF-9012-HL5012 000001 0001 0 AF-2012-HL5014 294 296 C
C C
AF-9012-94 5014 000001 0903 O FCR BJ-1637 O FCR EJ-7187 0 000002 0003 O FCR DJ-1637 0 FCR EJ-7187 0 AF-2012-HL5015 C
C AF-9012-ML5015000001 0002 O NCC CS-3244 0 AF-2012-ML5016 C
C M-9012-ML5016000001 0002 0 AF-2012-HLSO17 SST C
C C
AF-9012-ML5017000001 0001 O FCR EJ-h % 0 FCR EJ-6231 O NCC 55-3610 X l
000002 0001 O FCR EJ-5656 O MCC 55-5610 E AF-2012-HL5019 495 C
C C
AF-9012-+4 5018 000001 0003 0 FCR DJ-8303 0 FCR EJ-6939 0
)
AF-2012-HL5020 551 C
C C
AF-9012-HL*A20 000001 0003 O FCR EJ-6534 0 AF-2012-ML5021 C
AF-9012-HL5021 000001 0002 O FCR EJ-5263 O FCR EJ-6774 O AF-2012-HL5022 C
AF-9012-HL".k)22 000001 0004 O FCR EJ-6450 0 AF-2012-HL5024 618 C
C C
AF-9012-HL5024 000901 0003 O FCR EJ-7083 0 000002 0003 O FCR EJ-7063 0 l
AF-2012-HL*,.eO25 C
AF-9012-ML5025000001 0002 0 l
AF-2012-ML5026 C
AF-9012-NL5026 000n01 0002 0 l
AF-2012-HL5027 607 C
C C
AF-9012-NL5027 OOOnOI 0006 0 i
000002 0006 0 j
AF-2012-HL5029 C
AF-9012-HL5029 000001 0001 O FCR EJ-4016 0 FCR EJ-4455 O FCR EY-3705 0 AF-2012-HL5032 C
C AF-9012-HL5032 000001 0004 O FCN 2J-0622 O AF-2012-NL*.W)35 C
C AF-9012-HL5035 000001 0004 0 DCN 00CO302 O NCC CS-44U1 O NCC CS-4816 0 FCR EJ-4424 O I
AF-2012-HL5036 C
AF-9012-HL5036 000001 0005 0 NCC CS-4570 N
=
6 O
rm b/
x PSI Component Supports (ptptngs for Syst em:
AF end q_ class 2 DATE! 16-96/-00 1315T136 FAGE:
15 E R ArtINAT 10Pr3 HANGER MJrtDLR LNSRS W Je VT3 VT4 Et1G AUG DOCUr1LNT NUrtbER SHEET REV DS3 TYP AP1 ENDS DS4 AF-2012-HL.SO36 C
AF-9012-HL3036 000002 0005 0 AF-2012-HL5030 591 590 C
C C
AF-9012-Ht_SO30 000001 0003 0 FEH EJ-7319 0_
FCR EJ-7394 0 000002 0003 0 000003 0003 0 1
=
g
/
/
N k
)
l l
PSI Cons,*)nent Supports 8 P S P 4 F' 3D for Syst eren:
CC.ond et_ Class 2 DATE: 16-NOV-88 15:",7:36 PAGC:
16 l
[3AMINATIOrG l
HANGER NUMt<R StGRe SNSAe VT3 VT4 Dr1G AUG DOCur1LNT NUMDER SHEET REV DS3 TYP AMENDe DS4 CC-2312-HL*.,001 C
C CC-93 3 2-HL".A.01 000001 0003 O FCR EJ-4".,90 0 CC-2310-HL*,oO!
C C
CC-9318 rEL*,001 000W 1 0005 O FCR EJ-21".,3 0 CC-2318-94.3002 C
CC-9310-NL*,002 OOOOO! 0004 O NCC CS-4936 N FCR EJ-2340 0 000002 0004 0 NCC CS-4936 N l
l l
im (m.
,ex n
)
\\&
(l PSI Coagnonent Supports (papings for Syst ese:
CS and q_rtass 2 DATE* 16-NOV-88 15:57:56 pAGE*
17 EI AF11NAT IOrci HANGER NUNis0R SNSRO SNShe VT3 VT4 DMG AUG DOCUMENT NUNDER SHEET REV DS3 TYP AMENDe DS4 C3-2301-HLSOO2 C
CS-9301-HL5002 000001 0004 0 FCR EJ-4440 0 NCC SS-5558 0 C3-2301-HL5003 C
G-9301-HL5001 000001 0004 0 DCN OCKu>OO1 O NCC C3-4010 0 FCR EJ-4440 0 FCR EJ-4!0% O NCC SS-5558 0 000002 0004 0 NCC G-4810 0 FCR EJ-4b84 0 C-2301 -RROOO2 C
CS-9301-RROOO2 000001 0003 O NCC CS-5150 0 FCR EJ-55~.A) O C3-2302-HL5002 C
CS-9302-HL"A>O2 000001 0003 0 CO-2302-HLSOO3 C
G-9302-HL5003 000001 0003 O FCR EJ-7334 O C3-2302-HL5004 C
G-9302-HLLOO4 OOCKKs1 0001 0 000002 0001 0 CS-2302-RHOOO4 C
CS-9302-Re K)4 000001 0004 O FCN 2J-0678 0 G-2302-febOOO3 C
CS-9302-AftOOO5 000001 0004 0 FCR EJ-7335 O CS-2302-SHOOO3 C
C CS-9302-SHOOO3 000001 0002 O FCR EJ-5104 0 G -2303-HL"./>O1 C
CS-v303-ML5001000001 (005 O C3-2303-HLSOO2 C
CS-9303-HL5002 000001 0005 0 NCC BS-0303 N FCR EJ-6241 O FCR EJ-6512 O C3-2303-HLLOO3 C
CS-9303-HLSOO3 000001 0004 O FCpt EJ-2966 0 CS-2303-HLLOO4 C
CS-9303-HLs>O4 000001 0001 0 CS-2303-HLLOO3 C
CS-93n3-tt 5005 000001 0000 O F CR EJ-7292 O G-2303-HLLOO6 C
G-9303-HL5006 000001 0001 O FCR DJ-6197 O FCR EJ-5983 0
m O.
PS3 Comeponent Supports 8P1 Ping) f or-System:
FW and q class 2 DATE: 16-NOV-85 15157:56 PAGE1 IS EEAMINATIONS HANGER NUMisCR SMSRe SNSRe VT3 VT4 DNFa 9UG DOCUPENT MJPthER S6EET REV DS3 TYP RPENDe DS4 FW-2016-91LSOO1 C
FM-9016-tLSOO1 000001 0004 0 FW-2016-HLSOO2 C
FW-9016-ML5002000001 0003 O FCR BJ-1659 O FCR EJ-2217 0 FCR EJ-7021 O FCR EJ-7183 0 FW-2016-HL5003 681 C
C C
F W-9016-HL*,003 000001 0004 0 FW-2016-HL5004 666 C
C C
FW-9016-HL5004 000001 0002 O FFR DJ-7137 0 FCR EJ-7201 O FW-2016-ML5005 C
FW-9016-94 5005 000001 0003 O FCR EJ-6979 0 NCC 55-5523 N NCC SS-5571 HW NCC SS-5603 HW 000002 0003 0 NCC 55-5571 X NCC 5S-5603 X FD-2016-HL5006 616 C
C C
FW-9016-HL5006 OOOnot 0003 0 FCR EJ-6401 O 000002 0003 0
(
FW-2016-MLSOO7 623 C
C C
FW-9016-HL5nO7 000001 08sO3 O FCR EJ-6999 0_
FW-2016-HL5008 633 C
C C
FW-9016-M 5000 000001 0002 O FCR EJ-7135 0 j
FW-2016-HL5009 63 C
C C
FW-9016-HL5009 000001 0003 O FCR EJ-7366 0 1
FCR EV-6398 0 i
000002 0003 0
{
FW-2016-NL5010 614 C
C C
FW-9016-HL5010 000001 0004 0 FW-2016-HL5011 613 C
C C
F W-9016-ML5011000001 0002 O NCC WS-03*J O FCR EJ-6938 0
)
FCR EJ-6900 0 FCR EJ-7402 O f
FW-2016-HL5012 C
FW-9016-ML5012000001 0004 0 NCC CS-5301 N I
FCR EJ-4688 0 FCR EJ-7147 0 l
000002 0004 O FCR EJ-4688 0 1
FW-2016-HL5013 C
C FW-9016-et3013 000001 0005 0 FCR EJ-5378 0 FW-2016-HL5015 C
FW-9016-et3015 000001 0002 0 FW-2016-SHOOO1 C
C FW-9016-SHOOO1 000001 0002 O FCR BJ-1284 0 FCR DJ-1588 0 i
000002 0002 O FCR BJ-1284 0 Fts-2016-SHOOO2 C
C FW-9016-SHOOO2 000001 0003 0 NCC CS-4357 0 FCR EC-1370 0 l
FCR EJ-6988 0
)
FW-2031-HLSOO1 C
C F W-9031 -HL5901 000001 0002 O FCR EJ-4887 O 2
NCC SS-5574 N 1
FW-2031-HL5002 423 539 C
C C
FW-9031-HLSOO2 000001 0005 O FCR EJ-4048 0 g
FCR EJ-4987 0 j
FCR EJ-8117 N NCC 85-5555 N FW-2031-HL5003 301 C
C C
FW-9031-HL5003 000001 0004 O FCR EJ-4904 0
m O
O O
PSI Component Supports (papangt ftp-Syst eemt Pts and % Class 2 DATE1 16-NOV-96 15157156 FAGE1 19 EN ArtINAT 10NS HANGER NUMasCR SM5he SMSEe VT3 VT4 DMG AUG nnristLNr wungsER SHEET REV DS3 TYP AMENDe DS4 P13-20034C5002 C
C MS-9003-ML5002000001 0003 0 Pts-2OO3-HL5003 C
C C
pts-9003-te *,003 000001 0004 O FCR EJ-7222 O 000002 0004 O FCR EJ-7222 O 000003 0004 0 000004 0004 0 FCR EJ-7222 O 000005 0004 O FCR EJ-7222 O MS-2OO3-HL5004 637 C
C C
C pts-9003-HL5004 000001 0006 O FCR SJ-1654 O FCR EJ-6793 0 NCC SS-5716 HC 000002 0006 0 FCR BJ-1654 0 FCR EJ-6793 O NCC SS-5716 X pts-2OO3-NL5005 C
C pts-9003-HL5005 000001 0006 0 FCR EJ-5416 O MS-2OO3-HL5006 C
C pts-9003-HL-A06 000001 0003 0 FCR EJ-6022 O ttS-2OO3-HL5006 C
C C
pts-9003-64 5000 000001 0004 0 FCR EJ-6461 O 000002 0004 O FCR EJ-6461 O 000003 0004 0 pts-2OO3-NL5011 C
C C
FTS-9003-HL5011 000001 0005 0 NCC CS-4915 X_
FCR EJ-7423 0 71S-2OO3-HL5012 73 C
C C
C MS-9003-HL5012 000001 0005 O FCR EJ-7432 O 000002 OOCC 0 MS-2OO3-HL5013 665 C
C C
C PTS-9003-HL5013 000001 0004 0 MS-2OO3-HL5014 586 C
C C
C pts-9003-HL5u14 000001 0006 O FCR EJ-8233 N FCR EJ-8286 HC NCC SS-5716 HC MS-2OO3-HL5015 552 557 C
C C
C pts-9003-ML5015000001 0003 0 FCR DJ-3059 O FCR EJ-3603 O FCR EJ-5345 O FCH EJ-0079 O MS-2OO3-HL5016 634 635 C
C C
C FTS-9003-HL5016 000001 0005 O FCR EJ-4978 0 ftS-2OO3-HL5017 274 310 C
C C
C ttS-9003-HL5017 000001 0004 O DCN 000u002 O FCR DJ-3061 O FCR DJ-6320 0 FCR EJ-dol 6 N PTS-2OO3-HL5018 C
C C
ttS-9003-HL5010 OOOC41 0004 0 000002 0004 0 ttS-2OO3-HL5019 C
C C
pts-9003-HL5019 000001 0002 O FCR DJ-3301 N NCC SS-3650 X NCC SS-5676 N ttS-2104-HL5002 C
C C
FTS-9104-HL5002 000001 0003 0 NCC SS-56*A N
~
A A
.-N Q)
(
I
(
)
I w/
v PSI Component Suppor-t m (ptpangt f or-Syst em:
RH and (class 2 LATE: 16-NOV-UG 1*s:57:56 PAGE: 20 EEANINATIONS HANGER NUNDER SNSRs SNSRs VT3 VT4 DP1G AUG DCF1Jf1ENT PetDER SHEET REV DS3 TYP AMENLW DS4 RH-2102-SHOOO1 C
C C
hH-9102-SHOOO1 000001 0001 O FCR EJ-4291 O 0002 N RH-2103-HL5001 C
C RH-9103-HL5001 000001 0006 0 NCC BS-0259 N 000002 0006 0 RH-2103-HL5004 C
C RH-9103-HL5004 000001 0002 O FCR EJ-5826 0_
RH-2103-HROOO3 C
C RH-9103-RRO' w)3 000001 0003 0 RH-2103-RROOO4 C
C RH-9103-RROOO4 000001 0003 0 RH-2103-HROOO6 C
C RH-9103-RROOO6 000001 0000 0 FCR DJ-7942 O FCR EJ-4U36 0 RH-2103-RROOO7 C
C RH-9103-RROOO7 000001 0007 O FCR DJ-UO71 O FCR EJ-4V69 0 000002 0007 O FCR DJ-BO71 O FCR EJ-4969 O RH-2103+ROOO9 C
C RH-9103-RHru)Oy 000o01 0003 0 FCR EJ-4223 0 RH-2103-RROO11 C
C RH-9103-RROO11 000001 0007 O FCR EJ-4996 O FCR EJ-5888 O RH-2103-SHOOO5 C
C C
RH-9103-SHOOO3 000001 0004 0 RH-2103-SHOOOO C
C C
RH-9103-SHOOOO 000031 0004 O DCN 00083001 O NCC HS-LOO 7 N HH-2103-SHOO 10 C
C C
RH-9103-SHOO 10 000001 0003 0 RH-2104-RROOO1 C
C RH-9104-RROOO1 000001 0007 0 000002 0007 O FCR EJ-4963 0 RH-2104-RROOO2 C
C RH-9104-RROOO2 000001 0004 0 RH-2104-RROOO3 C
C RH-9104-RROOO3 000001 0004 O FCR EJ-4962 O NCC SS-3719 HC RH-2106-HLSOO3 C
C RH-9106-M-3003 000001 0003 O FCR EJ-3770 0 FCR EJ-5514 0 0004 N 000002 0003 0 l'CR EJ-5514 0 0404 N 000003 0004 N HH-2106-RROOO3 C
C RH-9106-RROOO3 000001 0003 0 0004 N RH-2106-SHOOO1 C
C C
RH-9106-SHOOG1 000001 0005 0 FCR EJ-3306 0 NCC SS-3719 HC OOv002 0005 O NCC SS-3719 HC RH-2110-HL5002 631 C
C C
C RH-9110-HL5002 000001 0001 O FCR EJ-5809 0 0002 N RH-2110-HL5003 C
C RH-9110-tt.5003 000001 0002 O FCR BJ-1595 O FCR EJ-3062 O 0003 N 000002 0002 O FCR EJ-306? O 0003 N RH-2110-HL5004 C
C RH-9110-HL5004 000001 0005 0 FCR EJ-Sa93 O FCR SJ-OO34 HC FCR SJ-OO36 N NCC 55-5368 HC NCC S5-5586 N 0006 N 000002 000".,O NCC 55-5368 HC 0006 N
e,
%)
~
es! Compon nt s.ecore. spipsass to - Systes=:
Fei.no sc1.
2 DATE: 16-NOv-se 15:57:56 PAGE: 21 EN ArtINAT IONS HANGER NUrtWEN istdisse Sossese VT3 VT4 DrgG AUG DOCurENT NUMBER SDECT F(v DS3 TYP APENDe DS4 RH-2110-ML5004 C
C RH-9110-HL5004 000003 0006 N MM-2111-HLSOO1 C
C RH-9111-HL5001 000001 0002 O FCR EJ-Set 31 O_
0003 N MH-2204-HL5001 803 C
C C
C RH-9204-HL3OO1 000001 0003 O DCN 0000002 O FCM 2J-0669 0 NCC CS-5114 O 0004 N MH-2204-NL5002 C
C RH-9204-HL5GO2 000001 0001 O FCR EJ-5244 0 0002 N MH-2204-NL5003 C
C C
RH-9204-HL5003 000001 0003 O FCR BJ-1752 N_
FCR EJ-5841 O 0004 N RH-2204-HL5004 C
C pet-9204-HL5004 000001 0001 0 0002 N RH-2204-MLSOO5 C
C RH-92O4-HL5005 000001 0004 O FCR EJ-3539 0_
0005 N pH-2204-HLSOOe C
C Fee-9204-HL5000 000001 0005 0 0006 N 000002 0005 O TCR EJ-4411 O_
l 0006 N RH-2204-HL5009 C
C RH-9204-HL5009 000001 0002 0 0003 M 000002 0003 N j
RH-2204-tt5011 C
C RH-9204-HL5011 000001 0004 O FCR EJ-3841 O_
FCR EJ-7851 N NCC SS-5529 IN 0005 N 000002 0004 O FCR EJ-7ts51 N_
0005 N 000003 NKJ5 N RH-2MM-HL3012 C
C Fet-9204-HL5012 000001 0003 0 0004 N RH-2204-MROOO2 C
C RH-9204-AROOO2 000001 0002 0 0003 N RH-2204-PeROOO3 C
C RH-9204-RROOO3 000001 0004 0 000",N peH-2204-RROOO4 C
C RH-9204-RROOO4 000001 0003 G FCR EJ-3445 0 0004 N RH-2204-RROOO7 C
C RH-9204-RROOO7 000001 0002 O FCR EJ-4095 0_,,,
0003 N Fe4-2204-RROO10 C
C Fee-9204-RROO10 000001 0003 0 0004 N Fet-2205-MLSOO1 C
Fet-9205-HL5001 000001 0002 0 RM-2205-MLSOO7 C
C RM-9205-MLSOO7 000001 N>O4 0 RH-2205-HL5006 C
Fet-9205-ML5000000001 0003 O FCR EC-13OO O_
Fet-2205-HL5009 C
Fot-9205-HLSOO9 000001 0003 0 RH-2205-HL'I.A)10 C
C RH-9205-ML5010000001 "M)O2 O FCR EC-13OO O FCR EJ-2581 O 000002 0002 0 pot-220,,-HLSO11 C
NH-9205-9(3011 000001 0002 O FCM EJ-2394 O_
l l
FCR EJ-5206 0 i
/
\\
/
'd
(
! _,)
PSI Component Segports (p1pingp f tr Syst em:
RH and q_c lau 2 DATE: 16-NOV-08 15: 57:56 PAGE: 22 Ener11NAT IONS HArdaER Nur11CR WAe br(J<a VT3 VT4 Dr1G AuG DOC 1Jr10NT NUMi{R SHEFT REV DS3 TYP Ar1END# DS4
=-
HH-2205-HL5011 C
AH-92(.O-+C3011 000001 0002 O FCR EV-19s4 0 kH-22OL-HL5013 C
C AH-92(0-NL5013 000001 0002 O FCR EJ-5677 0 RH-2205-HL5014 C
RH-92U5-HL5014 000001 0002 O FCR EJ-5677 0 RH-2205-hNOOO4 C
RH-9205-kROOO4 000001 0003 0 RH-2205-NROOO3 C
614-92CO-RRnOO5 Ory;not 0003 0 000002 0003 0 RH-2205-HROOO6 C
RH-92O3-RROOO6 OO(Xm)1 0002 0 RH-2205-SHOO 10 C
C RH-9.WSHOO 10 000001 0005 0 FCR EC-1360 0_
FCR EJ-2629 0 1
l
7
[
O.
l PSI Component Sepports (ptpangt f or Syst em:
51 and at class 2 DATE! 16-9sDV-stb 15:57156 PWK: 23 l
Emmet 1 NATIONS j
MtseIKR NUMBER Seene SpeSme VT3 V14 IME AUG I)OC1JRENT DEJMSEft SHEET REV DS3 TYP dRfENDe DS4 i
CI-2101-6eLsOO4 C
S I-9101-HL SOO4 000001 0003 0 j
O.-2101-*eL5005 C
C SI-9101-94LSOOS 000001 0005 O FCR EJ-4659 0 CI-2101-HLSOOS C
C St-9101-+a.5008 000001 0004 O NCC CS-5048 O NCC CS-5099 O CI-2101-stL5010 C
C SI-9101-HL5010 000001 0005 0 FCR EJ-5937 O SI-2101-HL5013 C
SI-9101-ML5013000001 0003 0 NCC CS-5014 0 CI-2101-+eL5016 C
SI-9101-HL5016 000001 0003 O FCR SJ-1272 O FCR BJ-1296 0 FCR DJ-8316 O CI'2101-NLSO18 C
SI-9101-M 5015 000001 0003 O NCC CS-4144 0 peCC CS-4204 O NCC MS-4SO3 O SI-2101-ML5019 C
SI-9101-teL5019 000U01 0003 0 EI-2101-*L5020 C
SI-9101-ta_5020 000001 0002 O FCR DJ-9317 O_
CI-2101-ML5021 C
C SI-9101-ML5021000001 0004 0 FCR EJ-2901 O 000002 0004 O FCR EJ-2SO1 0 SI-2101-HL5022 C
SI-9101-HL5022 000001 0002 O NCC CS-4259 O FCR EJ-2499 O 000002 0002 O seCC CS-4259 O FCR EJ-W D SI-2101-HL5023 C
SI-9101-ML5023000001 0003 0 FCR EJ-Mi7 G CI-2101-MLSO24 C
SI-9101-ML5024000001 OOOL 0 FCR SJ-1330 0 NCC CS-4206 O FCR EJ-3 1 O SI-2101-ML5025 C
SI-9101-HL5025 000001 0002 0 SI-2101-ML5026 C
SI-9101-ML5026000001 0001 O FCR EJ-2873 0 SI-2101-feHOOO7 C
SI-9101-FeHOOO7 000001 0007 0 SI-2101-FeHOO21 C
SI-9101-HHoo21 000001 0006 0 SI-2101-feROO15 C
SI-9101-BROO15 000001 0007 0 FCN 2J-0481 O FCR EJ-2526 O SI-2101-BROO19 C
SI-9101-BROO19 000001 0006 O FCR EJ-2456 0 FCR EJ-2605 O SI-2101-RkOO2O C
SI-9101-AROO2O 000001 0006 O NCC CS-4152 O SI-2101-RROO23 C
SI-9101-RROO23 000001 0003 0 St-2101-BROO24 C
SI-9101-BROO24 000001 0005 0 SI-2101-RROO26 C
SI-9101-fdeOO26 000001 0004 0 SI-2101-SHOO 10 C
C SI-9103-SHOO 10 000001 0004 0 FCR EJ-1708 O St-2101-SHOO 11 C
C SI-9101 3.440011 000001 OO(s6 O SI-2101'.4+0013 C
S t-9101-SteXs13 000001 C e O FCR EJ-4708 O SI-2101-f440014 C
SI-4101-SHv014 000001 0004 O FCR EJ-6079 O SI-2101-SSOOOG 624 641 C
C C
S1-9101-550008 000001 0005 O FCR EJ-5022 O FCR EJ-5313 O FCR EJ-7225 O SI-2102-HL5001 C
SI-9102-HL5001 000001 0003 0 SI-2102-HL5004 C
SI-9102-ML5004000001 0002 0 S1-2102-9040007 C
SI-9102-HHOOO7 000001 0003 0 FCR EJ-4707 0 51-2102-940003 C
SI-9102-RRUCO3 000001 0004 O DCN 0000002 O FCR DJ-4543 O FCR EJ-7232 O NCC MS-4761 N NCC SS *.E,60 NC
am
,r n
N
}
)
v
,,/
PSI Componernt Supports (p a p a ra g) for S y st ann:
SI and q_ class 2 DATE1 16-NOV 00 15:57*56 par;E: 24 EIAPt1 NATIONS HANGER NUPWER SN5Re SNSAs VT3 VT4 DPv3 AUG DOCurtNT P4E%sER W ET REV DS3 TYP ArENDe DS4 SI-2102-RHOOO4 C
SI-9102-RROvo4 OOOUO! 0002 O FCR EJ-4349 0 NCC 5S *560 HC CI-2102-RROOOU C
SI-9102-RRuooU 000001 0007 0 C I -2102-SHCC09 C
C SI-9102-SHooO9 00<O01 0004 O F CR EJ-4860 0_
CI-2105-HLLOO1 C
C SI-910544L5mO1 600001 0003 O NCC 5S-5566 6M CI-2105-HL5094 C
C 51 -9105-+4.5004 000001 0001 0 SI-2105-RHOOO1 C
SI-9105-HHov01 000001 00's5 O C1-2105-4<HOO35 C
C SI-9105-RHOO33 000001 0004 0
[
000002 0004 O FCR EJ-5789 O CI-2105-RROO21 C
C SI-9105-RHv021 OOvv01 0003 0 NCC CS-4577 N SI-2105-RROO22 C
C SI-9105-RROO22 000001 0003 O
~
CI-2105-RROO23 C
C SI-9105-RROO23 000001 0003 0 CI-2105-RROO24 C
C SI-9105-RROO24 000001 0004 0 NCC CS-0771 N CI-2105-RR0025 C
C SI-9105-RROo25 000001 0002 O NCC SS-5717 HC C1-2105-RROO26 C
C SI-9105-RROU26 000001 0004 O PCC CS-5121 N F CR EJ-5170 0 NCC SS *s566 tM SI-2105-RROO27 C
C S t -9105-RF:OO27 000001 0004 O FCR EJ-5825 O CI-2105-RROO28 C
C SI-9105-RROU2O OOOv01 0002 O NCC HS-3830 N SI-2105-RROO29 C
C SI-9105-RROO29 000001 0003 O FCR EJ-5857 0 CI-2105-RROO31 C
C SI-9105-RROv31 000001 0003 O SI-2105-RROO32 C
C SI-9105-Rhoo32 000001 0005 O SI-2105-RROO33 C
C SI-9105-RROO33 000001 0005 0 NCC CS-4370 E NCC HS-0743 N SI-2105-kROO34 C
C SI-9144-RROO34 000001 0U05 O NCC SS-5549 X SI-2105-RhoO36 C
C St-9105-RRt036 000001 0005 O FCR EJ-2485 O SI-2105-RROO37 C
C SI-9105-RRov37 000001 0005 0 CI-210",-RROO38 C
C SI-9105-RROO38 000001 Ov06 0 000002 0006 0 SI-2105-RROO40 C
C SI-9105-RhoO40 000001 0002 O NCC G-4074 _
X S I -210".,-RROO41 C
C SI-9105-HHuv41 000001 0002 0 0003 N SI-21C5-SHOO 39 C
C C
SI-9105-SHOO 39 000001 0006 0 FCH EJ-5850 0 SI-2105-SHOO 42 C
C C
SI-9105-SHv042 OOOv01 0003 O FCR EJ-; m O NCC HS-4174 N SI-2106-GUOO79 C
C SI-9106-Guvo70 000001 0002 O FCR DJ-9177 O FCR EJ-3337 0 0003 N 000002 0003 N S I -2106-NF 3014 C
SI-2106-tW5014 000001 0001 0 C1-2106-HL5001 C
C S3-9106-94.5001 000001 0001 O FCR EJ-3700 0_
0002 N 5I-2106-HLLOO6 C
SI-9106-NL5006 000001 0002 O FCR EJ-5861 O 000002 0002 O FCR EJ,861 O GI-2106-HL5009 C
C SI-9106-HL5009 000001 0003 O F CR EJ-3338 0 000A N Cl-2106-HL5010 C
C SI-9196-HL5910 C00001 0002 O NCC SS *s491 54C OssO3 N GI-2106-HL5011 C
St-9106-NL5011 000001 0909 0 SI-2106-HL5012 C
C S I -4106-HL*ks 12 000v01 0003 O FCH EJ-3391 O 0004 N
)
~
[
,m.
(
i
\\
V) y/
L.
PSI Component Supporte spipingt for S yst een:
SI anJ q_C lasm 2 DATER 16-NOV-83 15:57156 FWZ: 25 EXANINATIONS HANGER NUP1bCR SNLR9 SNShe VT3 VT4 DMG AUG DOCUMLNT NUMBER SHEET REV DS3 TYP AMENLe D34 C1-2106-HL5012 C
C S I -9106-HL*/> 12 000002 0003 O FCR EJ-3391 O FCR EJ-5 BOO O OOCA N CI-2106-HL5013 C
SI-9106-HL5013 000001 0000 0 CI-2106-HS5001 C
S I -91 %-HS""O 1 000001 0002 O F CR EV-3169 O FCR EY-4614 0 31-2106-RHOOv5 C
SI-9106-RH0005 000001 0003 0 CI-2106-HHOOO6 C
SI-9106-RHOOO6 000001 0003 0 SI-2106-HHOOOO C
5I-9106-RHOOOO 000001 0004 O FCR DJ-1560 0 FCR EJ-5357 0 NCC SS ~s604 HC CI-2106-RHOO64 C
C SI-9106-RHOO64 000001 0003 0 0004 N CI-2106-RROOO4 C
St-9106-RROOO4 000u01 OOso O OnOOO2 0005 O DCN OO W KJ3 0_
CI-2106-RROOO9 C
SI-9106-RROOO9 000001 0004 O FCN 2J-0612 O FCR EJ-5337 0 NCC 55-5606 HC CI-2106-RROO12 C
SI-9106-RROO12 000001 0003 0 CI-2106-RROO51 C
C St-7106-N s1 000001 0000 0 DCN 0000003 0_
NCC CS-5130 0 FCR EJ-3013 0 FCR EJ-3935 0 0009 N SI-2106-RROOS2 C
C SI-9106-RROO52 On% t 0005 O FCR EJ-3714 0 JCR EJ-3012 O 0006 N SI-2106-RROOS4 C
SI-9106-RROO54 000001 0004 N F CR EJ-5892 O C005 N CI-2106-RROO55 C
C SI-9106-RROO55 000001 0005 0 0006 N CI-2106-RROOS6 C
C St-9106-hROO36 000001 0005 0 F CR EJ-3570 0___
COU6 N 000002 0005 O FCR BJ-1280 O FCR EJ-3578 0 0006 N SI-2106-RROO57 C
C UI-9106-RROvs7 000001 0005 O NCC CS-4141 O FCR EJ-5705 O 0006 N 000002 0005 0 0006 N SI-2106-RROO58 C
C SI-91n6-RRoc",8 000001 OOn3 0 NCC SS-3310 HC 0004 N SI-2106-RROO59 C
C S I-9106-hMOo* 9 000001 0005 0 NCC SS ~AIS N 0006 N SI-2106-RROO60 C
C SI-4106-Rhou60 000001 0004 O DCN OOCwAC3 0_
NCC CS-5109 0 FCR EJ-5719 O 0005 N SI-2106-RROO61 C
C SI-9106-RRv061 000001 0003 0 0004 N
,9 (m
,^
(V V
(/
i 1
i PJ1 Component Supports epspangt for Sy st em s S1 and se_c l a n.m 2 DATE1 16-NOV-BU 15157156 F#eGE
- 26 EXAMINATIONS HANGER NUMBER
$NSRS SNSke VT3 VT4 Dr1G #suG DOCUMENT NUM1(R SHEET REV DS3 TYP AMENDe DS4 m-_
CI-2106-RROO63 C
C SI-91C4-RROO63 000001 0003 0 DCN 0000001 O PCC CS-5124 N NCC SS-5578 N 0004 N CI-2106-RROO67 C
C S I-9106+ROO67 000001 0004 0 NCC 5S-5492 HC NCC 55-5".,46 N 000",N CI-2106-RROO69 C
C SI-9106-Rwo069 000001 0003 0 FCR DJ-9434 O 0004 N CI-2106-RROO72 C
C SI-9106-RROO72 000001 0003 O FCR EJ-3315 O_
FCR EJ-3817 O OuG4 N CI-2106-RROO73 C
C SI-9106-RROO73 000001 0003 0 0004 N CI-2106-RROO74 C
C SI-9I06-RROO74 000001 0003 O FCR BJ-1754 HC NCC SS-5310 HC NCC 55-5679 N 000002 0003 O FCR EJ-3847 0 NCC SS-7,310 HC NCC 55-5679 N CI-2106-RROO75 C
C SI-9106-RROO75 000001 0003 O FCR EJ-3047 O 0004 N SI-2106-RROO76 C
C SI-9106-RROO76 000001 0004 O FCR EJ-4959 0 NCC 55 ",488 HC 0v05 N 000002 0004 0 NCC SS-5400 HC 0005 N SI-2106-kROO77 C
C SI-9106-RROO77 000001 0003 0 FCR DJ-9079 0 FCR CJ-5881 O 0004 N 000002 OOC 4 N e.1-2106-RROO78 C
C SI-9106-RROO70 000001 OCKC 0 F CR EJ-Suut O_
0003 N 000002 0003 N SI-2106-SHOO 10 C
C SI-9106-SHOO 10 000001 0005 0 FCR EJ-3196 O_
SI-2106-940000 C
C S t -9106-9exeo 000001 0005 0 0006 N 000002 0005 O FCR DJ-9195 0_
0006 N SI-2106-SSOO53 C
C SI-9106-SSOO53 000001 0004 O FCR DJ-9107 O FCR EJ-5991 O 0005 N FCR EJ-7297 DC NCC SS-5579 N 0006 N 000002 0005 N FCR EJ-7297 HC FCR EJ-7579 HC NCC 55-5493 N NCC 55-5579 N 0006 N S1-2107-HL5001 Bio 026 C
C C
C SI-9107-HL5001 000001 00 % 0 (CR EJ-4416 0_
0007 N
1
,a
,m i
l
)
\\
,/
l PSI Cosaponent Support s (espings e us-Syst em:
S1 and ag_ class 2 DATE* 16-NOV-08 13:57:36 FAGE1 27 EIAr11 NATIONS 3%NGER NUrtDER SNSRe SN%e VT3 VT4 DP1G AUG DOCur10NT NUrtisER SHEET REV DS3 TYP Ar1ENDe CS4 C1-2107-HLSOO1 016 026 C
C C
C SI-9107-HLSOO1 000002 0007 N C1-2107-SSOO59 C
C S1-9107-S50039 000001 0005 0 F CR EJ-3072 o_
0006 N 000002 0003 O F CR EJ-38 72 O FCR EJ-4703 0 0006 N C1-2107-SSOO61 640 C
E C
C S1-9107-550061 000001 0005 O FCR EJ-5293 0 00(4 N SI-2109-HLSOO3 C
C SI-9109-HLSOO3 000001 0005 0 FCR EJ-3944 0 0006 N 000002 0903 0 0006 N SI-2109-HLSOO3 C
C St-9109-HLLOv5 000001 0003 O FCR EJ-3944 0 0004 N SI-2110-HL5001 C
C SI-9110-HL3OO1 000001 0005 O F CR EJ-5231 O_
Ovo6 N SI-2118-HLSOO6 C
SI-9118-HL5006 000001 0000 O CCP 2FtST283 0__
FCR EJ-8522 N SI-2110-HLSOO7 C
St-9110-HLLOO7 000001 OO(W) O CCP 2ftST2U5 82 FCR EJ-8329 N FCR EY-7083 O SI-2110-HLSOOO C
SI-9110-HL5000 000001 0001 0 CCP 2rtST285 O FCR EJ-2493 0 FCR EJ-0532 N SI-2110 *CSOO9 C
SI-9110-HL5009 000001 0002 O CCP 2rtST283 O C1-2118-HLSO10 C
SI-9110-HL5010 000U01 OOOO O CCP 2ftST285 O FCR CJ-BS28 N SI-2110-HLSO11 C
SI-9110-tL5011 000001 0000 0 CCP 2PTST285 O FCR EJ-8521 N S I-2118-HL*,012 C
SI-9118-HL3012 000001 0001 0 CCP 2ftST285 0 NCC CS-4260 0 FCR EJ-2875 O FCR EJ-0243 3 FCR EJ-8535 M NCC S5 '.,563 D SI-2110-HLSO13 C
SI-9110-HL*A13 000001 0000 0 FCR EJ-8527 N St-2110-RHOOO2 C
SI-9118-rho'>O2 000001 0005 O CCP 2FtST203 0 NCC CS-0640 0 FCR EJ-G530 M NCC SS *s677 N SI-2110-RHOvo9 C
SI-9110-RHvoO9 000001 0004 O CCP 2ftST285 0 FCR EJ-0523 %
S!-2118-RHOO11 C
SI-9110-Rte >011 000001 0003 O CCP 2t10T285 0 FCR EJ-8518 D SI-2110-RHOO12 C
SI-9118-RHOO12 000001 0003 O CCP 2rtST285 O S I-2139-tf*A01 C
St-9139-HFLOO1 000001 OrXC O SI-2139-HF3002 C
SI-9139-ef3002 000001 OUN) O S I-2139-+4 5003 C
SI-913v-HF3003 000001 0000 0 SI-2139-HF 3004 C
SI-9139-HF3OO4 000001 0000 0 St-2139-HFLaV35 C
SI-9137-NF 3OO3 000001 0000 0 SI -2139-tf 3OO6 C
SI-9139-tfLOO6 000001 0001 0
/
'\\
O V
(s PSI Component Supew t s (papangt tw System:
SI and ag_ class 2 DATE* 16-NOV-88 15: 37 ' *.A>
f* AGE
- 20 EEAMINATIONS HANGER NUMiiR LN'J< # 'M e VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYP AMENDe DS4 C1-2216-HLSOOR C
C
- 5! ". S L-HL Ac t 000001 0003 O FCR EJ s593 0 0064 N Cl-2217-HLSOO1 C
C
- 9.17-HL3C01 000001 0002 O FCR BJ-1*sS4 O_
0003 N SI-2217-HL"A)O6 C
C SI-9217-HLSOO6 000001 0002 O FCR EJ-34*s7 0_
NCC SS-3342 HC 0003 N SI-2217-HL5007 C
C SI-9217-HLLOO7 000001 0005 0 FCR EJ-5303 O 0006 N SI-2217-HL5008 C
C C
SI-9217-HL5008 000001 0003 O FCR EJ-6139 O__
FCR EJ-9263 HC 0004 N 000002 0003 0 0004 N GI-2217-HLSOO9 353 C
C C
C SI-9217-HLLOO9 000001 0084 0 0006 N CI-2217-HROOO6 C
C SI-9217-RROOO6 000001 O(CS O DCN OOCKm3 0 NCC CS *sO31 O 0006 N SI-2217-HHOOO7 C
C S I-9217-f<ROOO7 000001 04:01 0 0002 N l
~
O O
O 1
PEI Ceepenent Suppeets tegv6peemts for Sgetee.CS and g_ctose 2 DATE: 176-ee 13-27:21 PeeE: 26 Es meleanTIt3ss pete.ets seusgets assene vf3 vie sees muG SOCustpeT ssWRGER 9 MEET stEV 953TVP m See CC1C C
0205-OOOaO-C5tC A
O FCR 889-9630 O FCS See-93tS O F",a CM-OO44 O FCA EM-Ot43 0 '
3Fe2-9-C-3065-CstC 0007 O FCa SC-DOS 2 P
~
A O
O pet Component Supports (egespoemtB fee Sgetem.CV and telmes 2 UATE: 17-wov-es 13. 27: 21 PmOE: 27 ERAM!se4TI(DeE HedeGER seuMECR Ges3Rm wr3 VYe DMG AUG DOCUMENT esWM908 GHCET 84N D53 TVP M4Esepe 384
== -
~
ENHut C
C 0210-OOOO3-EsHE1 A
O FCR DM-OOSS O FCR 3M-0428 0 3 cot-2-C-tM7-ERHE1 0008 O FCR EC-OS49 O Capr2 C
C 02tO-00003-EEME2 A
O FCR BM-OOGO O FC6' BMHD428 0 3CO 3 C-8 %7-75 HE2 0008 O FCR EC-OS49 O LDHst C
C 02tO-00007-*DMut A
O FCR BM-0442 0 3MO1 H -4132-LisHE1 00 % 0 LDHs2 C
C 02to-OOOO7-4.DML2 A
O FCR BM-0442 0 3 Mon-9-C-4tS2-LIMs2 00 % 0 r01 C
3MO1-9-C-4133-FD1 0007 0 R308-00015-701 A
O OCFIA C
0215-OOOOS-ACFSA A
O FCA_
SM-0423 0 FCR 380-0237 O I
FCR CM-OO73 0 3MO1-9-C-45M-RCF1A 0032 0 CCF2A C
O FCR_ BM-0423 O_
l FCR See-0237 O FCR CM-OO73 0 3M01-9-C-4 t d.2-RCF2A 0002 0 RCf3A C
O FCR DM-0423 0_
FCR SM-0237 O I
eCA CM-OO75 0 j
3M01-9-C 4.t M-RCF3A 0002 O RCF4A C
O FCA 380-0237 O_
FCR CMME373 O RM25 C
C 0210-OOOO2-RMst A
O FCA SM-0427 O FCR Srt-1324 0 3 cot-2-C-t h 9-RHER 0003 O FCR CC-Sees O PHN2 C
C 02tO-OOOO2-RHE2 A
O FCR SM-0427 O FCR DM-1324 O l
3C01-2-C-s hT-RHa2 0003 L FCR CC-S4es O RH83 C
C 02tO-OOOO2-MMN3 A
O FCR DM-0427 O FCR DM-1324 0 l
3C01-2-C-1 %9-AME3 0003 O FCA CC-Sees O SIFRA C
C 0213-Oo019-stF A A
O FCR art-0430 0 3 MOI-9-C-41 M-SIF1A 0002 0
O O
O PS! Ceepenent Swpports tegwspoents for Sgetem.RM and g_ class 2 DATE: 17-sep/-SS 13:27.21 PaeE: 20 ERAnteenT 10mS teaseGER seusgeCR See9Re VT3 VY4 SeeG AuG SOCURDef seWrte[A SME.CT REV 963 Tw Ampage See
= __
~~ ~
~
RMP1A C
C OaOS-OOO31-Re4P1A A
O FCR See-DO42 O FCR See-0282 O FCR CM-0217 O FCR EZ-0467 0 3C01-9-5-1600-eeeP14 0009 O FCR 3C-3393 O FCR SC-4102 N FCR EC-2OOS O RHu1A C
0210 6 10-#HU1A A
O FCR SE-17 % O FCR SM-OOe3 O FCR BR-1991 O seCR CC-2SS2 O FCR CM-OO46 O FCR EM-OO69 0 peCR 64M-3270 0 3C01-9-5-1600-eHU S A 0009 0 FCA SC-3 M O FCR SC-4102 m FCR EC-2OOe O RHU2A C
0210-OOO; N A
O FCR DE-17% O F C R 3s9-0 0 8 3 O FCR 359-1391 O seCR CC-2SS2 O FCR Cn-90% 0 FCR De-OO69 O esCR te 3270 0 3C01-9-5-1600-#Mu2A 0009 0 FCR SC-3393 O FCR SC-4102 se FCR EC-2OOS S RHuth C
0210-OOO10-MHN1A A
O FCR SE-17 % O FCA 3s9-0083 O l
FCR 389-1391 f seCR CC-23S2 3 FCR Crt-OO4# 7 FCR Ese-OO'r4 +
peCR 94M-32 2*",.!
3C01-2-C-1369-RMN1A 0005 0 FCR CC-h N
O.
, "N x) j PSI Coupenent Supports (equirmes.t) for System:SI and g_ class 2 DATE: 17-NOV-88 13:27:21 PAGE: 29 EXAMIM4TIONG HANXR NUf18ER SMSRG VT3 VT4 DnG AUG DOct# TENT Nut 18ER SHEET RC/ DS3 TYP AMENDe DS4
~ '
HHIA C
0205-OOO12-HHIA A
O FCR BM-0650 0 FCR BN-0268 O FCR CP-0638 0 FCR eft-0663 0 3F02-9-C-306*J-HHIA 0007 O FCR SC-OO12 O LHIA C
0203-OOO12-LH1A A
O FCR BM-0650 0 FCR BN-0268 0 FCR CP-0638 0 FCR EM-0663 u 3FC2-9-C-3065-LHIA 0007 0 FCR SC-OO12 0
I l
i l
APPE
j CIASS 3 EXAMINATIC 1 ABLES PIPING SUPPORTS,
JES ?'
THRU 39)
EQUIPMENT SUPPORT ( N '.s 30 THRU 43)
'l t
t I
F t
1 i
i l
l i
f
(
S3/E048/rr I
PSI EXAMINATION
SUMMARY
REPORT APPENDICES LEGEND V
Column Heading Definition Snubber Serial Number SNSR #
Examinations:
DMG Post Heat-up Damage AUG Augmented PSI - Snubbers TYP Amendment Type CCP - Configuration Control Package DCN - Design Change Notice FCN - Field Change Notice FSN - Field Sketch Notice IDC - Interim Design Change Notice NCC Nonconformance Repc;t - Closed NCO Nonconformance Report Open NCR - Nonconformance Report PDN - Potential Deficiency Notice DS3 Disposition of Revision / Amendment Review DS4 First Position:
H - Hardware Impact I - Documentation Impact 0
Original Disposition N - No Impact X - Pending Disposition 1 - Affects Unit 1 Only - No Impact Second Position:
C - Rewalk Complete N - Revalk Not Required W - Rewalk Required O
F1 S3/E048/rr
m NN PSI Component Suppor ts (papangt f or Syst are:
AF and q_ class 3 DATE: 16-NOV-88 15:57:56 PAGE: 29 EXAMINATIONS HANGER NUPtBER SNSRe SNSRe VT3 VT4 Dt1G AUG DOC 1Jt1ENT NUrtBER SHEET REV DS3 TYP AMENDO DS4 AF-2011-HL5001 C
AF-9011-HL5001 0 % O01 0003 0 AF-2011-HL5002 C
AF-9011-HL5002 000001 0002 0 000002 0002 0 AF-2011-HL5003 C
AF-9011-HL5003 000001 0002 O FCR EJ-4116 O_._
AF-2011-HL5004 C
AF-9011-HL5004 000001 0003 0 FCR EJ-4705 0 000002 OOOJ O FCR EJ-4705 0 AF-2011-HL5005 C
AF-9011-HL5005 000001 0003 0 AF-2011-HLSOO6 C
AF-9011-FL*,006 000001 OOOJ O FCR EJ-4527 0 NCC 55-5567 HW d
000002 0003 0 NCC SS-5567 X AF-2030-HF5001 C
AF-2030-HF5001 000001 OOC 4 O AF-2047-HL5001 C
AF-9047-HL5001 000001 0003 0 FCR EJ-5209 0 000002 0003 O FCR EJ-5209 O AF-2047-R5002 C
AF-9047-HL5002 000001 0002 0 000002 0002 0 AF-2047-HL5003 C
AF-9047-HL5003 000001 0002 0 AF-2047-HL5004 C
AF-9047-HL5004 000001 0001 O FCR EJ-4272 O AF-2047-HL5005 C
AF-9047-HL5005 000001 0002 O DCN 000tX>01 O NCC CS-4651 N FCR EJ-4103 O AF-2047-HL5013 C
AF-904'-HL5013 000001 0001 O FCR EJ-8471 O FCR EJ-8474 O AF-2047-HL5014 C
AF-9047-HL5014 000001 0001 O FCR EJ-8444 O 000002 0001 0 AF-2047-HL5015 C
AF-9047-HL5015 000001 0002 O FCR EJ-8403 O FCR EJ-8427 O AF-2053-HF5001 C
AF-2053-HF5001 000001 0000 0 NCC SS-5319 0 AF-2053-HF5002 C
AF-2053-HF5002 000001 0000 O NCC SS-5318 O NCC SS-5518 X AF-2053-HF5003 C
AF-2053-HFLOO3 000001 0001 0 AF-2053-HF5004 C
AF-2053-HF5004 000001 0001 0 AF-2053-NF5005 C
AF-2053-HF",005 000001 0000 0 AF-2053-HF5006 C
AF-2053-HF5006 000001 0001 0 AF-2053-HF5007 C
AF-2053-HF5007 000001 0001 0 AF-2053-HS5001 C
AF-9053-HS5001 000001 0002 0 AF-2054-HL5001 C
AF-9054-HL5001 000001 0001 0 AF-2054-HL5002 C
AF-9054-HL5002 000001 0003 O FCR EJ-5367 O_,_
AF-2054-HL5003 C
C AF-9054-HL5003 000001 0004 0 NCC CS-5049 0 FCR EJ-5326 0 j
AF-2054-HL5004 307 325 C
C C
AF-9054-HL5004 000001 0001 O FCR EJ-5278 0 000002 0001 O FCR EJ-5278 O AF-2054-HL5005 C
AF-9054-HL"A)O5 000001 0000 O W-2054-HL5006 C
AF-9054-HL5006 000001 0002 O FCR EJ-5375 0 000002 0002 0 AF-2054-HL5007 C
C AF-9054-HL5007 000001 0001 O FCR EJ-5106 O_
i 000002 0001 0 AF-2054-HL5000 C
AF-9054-HL5008 000001 0003 0 FCR EJ-5264 0 j
AF-2079-HL5001 C
AF-9079-HL5001 000001 0001 0 j
A' -2079-HL"X)O2 C
AF-9079-HL".,002 000001 0001 O FCR EJ-4573 0 AF-2079-HL5003 C
AF-9079-HL5003 000001 0002 O FCR EJ-3747 O FCR EJ-4916 0
_.~
em.
A
\\
V PS1 Component Sepport s (ptp1ngt f or Syst eren:
AF and st_ class 3 DATE: 16-NOV-88 15:57:56 FAGE: 30 EI ArtINAT ItaW HANGER saJnipER SNSRe SNSRG VT3 VT4 DnG AUG DOCur1ENT Nur1BER SHEET REV DS3 TYP AMENDS DS4 l
M-2079-et_5004 C
Ar-9079-HL5004 000001 0000 O FCR EJ-4373 O M-2079-+4.5005 C
AF-9079-HL5005 000001 0002 O FCR EJ-4336 O AF-2079-et.5006 C
AF-9079-HLSOO6 000001 0001 O FCN 2J-0623 0 AF. M -NF5001 C
AF-2086-HF5001 000001 0000 O M -2006-NF5002 C
AF-2OO6-HF5()O2 000001 0001 O NCC CS-5026 N AF-2006-NF5003 C
AF-2006-HF5003 000001 0000 0 M-2006-NF5004 C
AF-2OO6-HF5004 000001 0001 0 AF-2006-NFSOO5 C
AF-2006-HC5005 000001 0000 0 AF-2086-NL5001 C
AF-9086-HL5001 000001 0002 O FCR EJ-46 O AF-2006-ML5002 C
AF-9006-HL5002 000001 0001 0 AF-2006-ML5003 C
AF-9086-HL5003 000001 0002 O FCR EJ-3930 C l
AF-2006 6 >4 C
AF-9086-HL5004 000001 0002 O FCR EJ-4847 0 l
AF-2006-MLSOO3 C
AF-9066-FE5005 000001 0002 0 AF-2006-HL5006 C
AF-9006-HL5006 000001 0002 0
I j
Q q;
l PSI Cworwnt Supports (ptptogi for Systann:
CC and q_ class 1 DATE: 16-NOV-88 15:57*56 PAGE: 31 EX Ar11 PEAT IONS HANGER MJHDER SNSRG SNSRe VT3 VT4 Dr1G AUG DOCut1CNT I4JPtBER SHEET REV DS3 TYP AMENDO DS4 CC-2101-HL5001 C
CC-9101-HL5001 000001 0004 0 FCR EJ-4768 O 000002 0004 0 CC-2101-HLSOO2 C
CC-9101-HL",002 000001 0003 O NCC CS-4890 N CC 2101-94.5003 C
C CC-9101-HLSOO3 000001 0003 O FCR EJ-5306 O 000002 0003 O CC-2101-HL5004 C
CC-9101-HL5004 000001 0002 O CC-2101-NLSOO" C
1 -9101-HL5005 000001 0003 0 CC-2101-SHOOO6 C
CC-9101-SHOOO6 000001 0002 0 CC-2102-GUOOO2 C
CC-9102-GUGOO2 000001 0005 0
~
CC-2102-GUOOO4 C
CC-9102-GUOOO4 000001 0004 0 FCR DJ-9456 O FCR EJ-3140 0 000002 0004 0 CC-2102-HL5001 C
CC 102-HL5001 000001 0003 O DCN 0000001 O NCC CS-4944 N CC-2102-HLSOO2 C
CC-9102-HL5002 000001 0003 0 NCC CS-4320 HW NCC CS-4672 N 000002 0003 0 NCC CS-4320 HW NCC CS-4672 N CC-2102-RROOO6 C
CC-9102-RROOO6 000001 0003 0 NCC SS-5577 X CC-2103-HL5001 C
C CC-9103-HL5001 000001 0003 0 FCR EJ-4793 0 CC-2103-HL5002 C
CC-9103-K_5002 000001 0003 0 NCC SS-5536 X CC-2103-HL5003 C
CC-9103-HL5003 000001 0003 0 CC-2103-HLSOO6 C
CC-9103-HLSOO6 000001 0004 0 NCC CS-3519 N FCR EJ-2612 O NCC SS-5535 N CC-2103-HL5007 C
CC-9103-HL5007 000001 0004 0 FCN 2J-0572 O 000002 0004 0 CC-2103-HL5010 C
CC-9103-HL5010 000001 0004 0 CC-2103-HL5011 C
CC-9103-HL5011 000001 0004 0 FCR BJ-1465 O 000002 0004 0 FCR BJ-1465 0 000003 0004 O FCR BJ-1465 O CC-2103-SHOO 12 C
C CC-9103-SHOO 12 000001 0005 O FCR DJ-9338 O FCR EJ-4757 O 000002 0005 0 FCR EJ-4757 O CC-2163-SHOO 13 C
CC-9103-SH0013 000001 0003 0 CC-2105-HL3OO1 C
CC-9105-HL"OO1 000001 0002 O NCO BS-3791 N CC-2105-HL5002 C
CC-9105-HL5002 000001 0005 O CC-2105-HL5004 625 C
C C
CC-9105-HLLOO4 000001 0003 0 FCR DJ-8722 O FCR EJ-3225 O FCR EJ-7902 X CC-2105-HL5005 C
CC-9105-HL5005 OCCOO1 0001 O NCC CS-3839 N FCR EJ-5682 O FCR EJ-5781 0 CC-2103-HL5006 C
CC-9105-HLSOO6 000001 0002 0 CC-2105-tt 5007 C
CC-9105-HL5007 000001 0003 0 CC-2105-HL5009 670 C
C C
CC-9105-HL5009 000001 0002 O NCC CS-5106 X FCR DJ-8908 0 FCR DJ-8976 0 FCR EJ-5686 O CC-2105-RHOOO4 C
CC-9105-RHOOO4 000001 0004 0 0,,,,,_
CC-2105-RROOO2 C
CC-9105-RROOO2 000001 0003 O DCN 000002
[ ]
~
PSI Component Suppor-t m (piping) f or-Syst N:
CC and q_ class 3 DATE: 16-NOV-86 15:57156 PAGE: 32 EMArtINAT10NS i
HANGER NUrtEsER SNSRS SNSRe VT3 VT4 DrtG AUG DOC 1Jr1ENT NUMBER SHEET REV DS3 TYP AMENDS DS4 4
CC-2105-RROOO2 C
CC-9105-h5tOOO2 000001 0003 O DCN 000003 0 FCR EJ-4992 O 000002 0003 0 CC-2105-RROOO3 C
CC-9105-RRO(C3 000001 0002 O CC-2105-RROOO7 C
CC-9105-RROOO7 000001 0002 O CC-2105-HROO11 C
CC-9105-RROO11 000001 0002 O NCC SS -5537 N CC-2105-ftROO12 C
CC-9205-RROO12 000001 0002 O FCR EJ-5749 O CC-2105-RROO13 C
CC-9105-RROO13 000001 0003 O NCC CS-3890 N FCR EJ-4908 0 CC-2105-RROO14 C
CC-9105-RROO14 000001 0002 O CC-2105-RROO15 C
CC-9105-RROO15 000001 0002 O
[
CC-2105-RROOl6 C
CC-9105-RROOl6 040001 0002 0 CC-2105-SHOOO1 C
C CC-9105-SHOOO1 000001 0006 0 DCN 000003 X FCR EJ-3214 X FCR EJ-5993 0 000002 0006 0 FCR EJ-5993 0 CC-2106-HL5001 C
C CC-9106-HL5001 000001 0004 O FCR EJ-4011 O CC-2106-HL5002 C
CC-9106-HL5002 000001 0003 0 NCC SS-5544 HW CC-2106-HL5004 C
CC-9106-HL5004 000001 0004 O FCR BJ-1202 O FCR EJ-5315 O FCR EJ-5685 0 000002 0004 0 FCR EJ-5315 O CC-2106-HL5006 C
CC-9106-HL5006 000001 0001 O FCR EJ-3129 0 NCC SS-5540 X CC-2106-NL5007 C
CC-9106-HL5007 000001 0002 O NCC CS-4547 N FCR EJ-5354 0 FCR EJ-5708 0 CC-2106-HL5009 C
CC-9106-HL5009 000001 0002 O FCR DJ-6687 O FCR EJ-3062 O CC-2106-HL5010 C
CC-9106-HL5010 000001 0001 0 CC-2106-HL5013 C
CC-9106-HL5013 000001 0003 0 CC-2106-HL5014 C
CC-9106-HLLO14 000001 0001 O NCC CS-4075 N CC-2106-HL5015 C
CC-9106-HL5015 000001 0002 0 000002 0002 O FFit EJ-5750 0 CC-2106-HL5018 C
CC-9106-HL5018 000001 0001 O FCR EJ-1798 0 CC-2106-RHOO12 C
CC-9106-RHOO12 000001 0001 0 CC-2106-RHOO13 C
CC-9106-RHOO13 000001 0001 O NCC SS-5541 HW CC-2106-RROOO5 C
CC-9106-RROOO5 000001 0002 0 CC-2106-RROOO6 C
CC-9106-RROOO6 000001 0001 O FCR EJ-3034 O__
CC-2106-RROO14 C
CC-9106-RROO14 000001 0002 O NCC SS-5559 HW CC-2106-RROOt6 C
CC-9106-RROOl6 000001 0002 O FCR DJ-09"A O.
NCC SS-5580 HW CC-2106-RROO17 C
CC-9106-RROO17 000001 0001 0 CC-2106-RROO18 C
CC-9106-RROO18 C00001 0003 0 FCR EJ-5316 0 NCC SS-5544 HW CC-2106-RROO19 C
CC-9106-RROO19 000001 0001 O NCC SS-5544 HM CC-2106-SHOOO1 C
C CC-9106-SHOOO1 000001 0002 0 CC-2106-SHOOO7 C
C CC-9106-SHOOO7 000001 0006 0 NCC CS-5098 N 000002 0006 O NCC CS *A08 N 000003 0006 O NCC CS ",090 N CC-2109-HL5001 345 582 C
C C
CC-9109-HL5001 000001 0005 O NCC BS-0259 X
P
~
m NY s
PSI Component Supports (p1 Pang) for Systese*
CC and q_ class 3 DATE: 16-NOV-88 15:57:56 TAGE: 33 EXAr11 NATIONS HANGER NUMBER SNSRG SNSRe VT3 VT4 Dr1G AUG DOCur1ENT Nur1BER SHEET REV DS3 TYP AMENDS CS*
CC-2109-HL5002 C
C CC-9109-HL5002 000001 0003 0 FCR EJ-4420 0 FCR EJ-4534 0 NCC SS-5749 X 000002 0003 0 FCR EJ-4413 0 FCR EJ-4534 O SS-5749 CC-2109-HL5CO3 C
CC-9109-HL5003 000001 0003 0 CC-2109-HLSOO*
C CC-9109-HL5004 000001 0002 O FCR EJ-3793 0 CC-2109-HL5007 C
CC-9109-HL5007 000001 0001 0 CC-2109-HL5008 C
CC-9109-HL-AOB 000001 0003 0 CC-2109-HLSOO9 C
CC-9109-HLSOO9 000001 0002 0
[
CC-2109-RHOOO2 C
CC-9109-RW)OO2 000001 0004 O CC-2109-RHOO12 C
CC-9109-RHOO12 000001 0003 0 NCC SS-5524 HW NCC SS-5547 SN CC-2109-RROOO3 C
CC-9109-RROOO3 000001 0007 0 NCC BS-0319 N NCC SS-5541 N CC-2109-RROOO9 C
CC-9109-RROOO9 000001 0005 0 FCR EJ-4581 0 CC-2109-RROO11 C
CC-9109-RROO11 000001 0005 O FCR EJ-3515 O CC-2109-SHOOO1 C
C CC-9109-SHOOO1 000001 0002 O CC-2110-tL5001 559 C
C C
CC-9110-HL5001 000001 0004 0 NCC BS-0259 [
FCR EJ-4035 0 CC-2110-HL5002 C
CC-9110-HL5002 000001 0003 0 FCR DJ-9040 0 FCR DJ-9046 0 FCR EJ-2754 0 FCR EJ-5328 O 000002 0003 0 FCR DJ-9040 0 CC-2110-HL5004 C
CC-9110-HL5004 000001 0000 0 NCC CS-5038 X FCR EJ-5265 0 000002 0000 O NCC CS-5038 X FCR EJ-5265 O CC-2111-GUOOO1 C
CC-9111-GUOOO1 000001 0004 O DCN 0000001 O FCR EJ-3366 O CC-2111-HL5001 C
CC-9111-HL5001 000001 0002 O FCR DJ-6292 0 FCR DJ-7866 O FCR EJ-4008 O CC-2111-HL5002 C
C CC-9111-HL5002 000001 0003 0 FCR DC-1616 O l
FCR EJ-4387 0 FCR EJ43870 0 CC-2111-SHOOO2 C
CC-9111-SHOOO2 000001 0005 0 FCR BJ-1466 O CC-2114-GUOO12 C
CC-9114-GUOO12 000001 0005 0 000002 0005 0 CC-2114-GUOO19 C
CC-9114-GUOO19 000001 0003 0 FCN 2J-0621 0_
CC-2114-HL5001 C
CC-9114-HLsOO1 000001 0003 O FCR EJ-5233 0 000002 0003 0 CC-2114-HL5002 C
CC-9114-HL5002 000001 0003 0 CC-2114-HL5004 C
CC-9114-HL5004 000001 0003 0 NCC CS-3340 0 NCC CS-3693 0 FCR EJ-3221 0 CC-2114-HL'A O5 C
CC-9114-HL"/45 000001 0003 0 CC-2114-HL5006 C
CC-9114-HL5006 000001 0001 0 CC-2114-RHOOO7 C
CC-9114-RHOOO7 000001 0003 0 FCR EJ-4911 0
n O
O rh iV PSI Component Suppcw-t m (p ap a nsp f or-Syst eent CC and Lclass 3 DATE1 16-NOV-88 15157156 PAGE1 34 EX ArtINAT IONS HANGER NunBER SNSRe SNSRs VT3 VT4 Dt1G AUG DOCUMENT NUrtBER SHEET REV DS3 TYP AMENDe DS4 CC-2114-RHOOO7 C
CC-9114-RHOOO7 000001 0003 O NCC SS-3604 0 000002 0003 0 CC-2114-RROOO1 C
CC-9114-RROOO1 000001 0003 0 CC-2114-RROOO2 C
CC-9114-RROOO2 000001 0002 0 CC-2114-RROOO3 C
CC-9114-RROOO3 000001-0002 0 CC-2114-RROOOO C
CC-9114-RROOO8 000001 0003 0 NCC 55-5527 0 CC-2114-RROOO9 C
CC-9114-RROOO9 000001 0003 0 NCO SS-5526 X CC-2114-RROO10 C
CC-9114-RROO10 000001 0001 0 CC-2114-RROO11 C
CC-9114-RROO11 000001 0004 0 FCR EJ-o155 0 CC-2114-RROO14 C
CC-9114-RR0014 000001 0002 0 CC-2114-RROO15 C
CC-9114-RROO15 000001 0002 0 CC-2114-RROO16 C
CC-9114-RROOl6 000001 0005 O DCN 0000003 0 NCC HS-3907 O CC-2114-RROO18 C
CC-9114-RROO18 000001 0002 0 CC-2114-RROO21 C
CC -9114-RROO21 000001 0005 0 CC-2114-RROO23 C
CC-9114-RROO23 000001 0007 O NCC CS-4936 O FCR EJ-2147 0 000002 0007 0 DCN 0000001 O FCR EJ -2147 0 CC-2114-RROO24 C
CC-9114-RROO24 000001 0002 O FCR EJ-4566 0 000002 0002 0 000003 0002 0 CC-2114-RROO25 C
CC-9114-RROO25 000001 0004 0 NCO S3-5731 _._
IW CC-2114-RROO26 C
CC-9114-RROO26 000001 0004 0 FCR EJ-7115 0 CC-2114-RROO27 C
CC-9114-RROO27 000001 0005 0 FCR EJ.s962 O CC-2114-RROO28 C
CC-9114-RROO28 000001 0003 0 CC-2114-RROO29 C
CC-9114-RROO29 000001 0003 0 FCR EJ-4131 0 5
CC-2115-HL5001 C
CC-9115-itL5001 000001 0004 0 FCR EJ-3269 0 000002 0004 0 FCR EJ-3269 0 CC-2115-HL5002 C
CC-9115-HL5002 000001 0001 0 CC-2115-RROOO1 C
CC-9115-RROOO1 000001 0004 0 FCR EJ-5257 0 FCR CJ-5281 O CC-2115-RROOO3 C
CC-9115-RROOO3 000001 0002 0 NCC CS-5137 X NCC SS-5509 X FCR SS-5510 HW NCC SS-5573 X CC-2115-RROOO5 C
CC-9115-RROOO3 000001 0004 O DCN 0000001 0 CC-2115-RROOO6 C
CC-9115-RROOO6 000001 0003 0 FCR EJ 492 O 000002 0003 0 I
CC-211 N OOO7 C
CC-9115-RROOO7 000001 0002 O FCR EJ-4940 0._,_
CC-2115-RROOO9 C
CC-9115-RROOO9 000001 0004 0 NCC CS-4589 N FCR EJ-5126 O CC-2115-RROO10 C
CC-9115-RROO10 000001 0004 0 NCC CS-5102 N CC-2115-RetOO12 C
CC-9115-RROO12 000001 0003 0 000002 0003 0 i
CC-2115-RROO13 C
CC-9115-RROO13 000001 0001 O FCR EJ-6712 0_
NCC SS-5509 HW CC-2115-RROO14 C
CC-9115-Rh1X)14 000001 0005 0 FCR DJ-9479 0 FCR EJ-5931 0 CC-2115-RROO15 C
CC-9115-RROO15 000001 00(5 0 FCR EJ-3063 0 CC-2115-RROO16 C
CC-9115-RROOt6 000001 0003 O DCN OO(KaOO2 0
-- -- a
.__ m
,e, PSI Component Supports ( P & P 1** S for System:
CC and oc: lass 3 DATE: 16-NOV-88 15:57:56 PAGE: 35 EaAMINATIONS HANGER MJMWER SNGRe SNSRe VT3 VT4 DMG AUG DOCUMENT NUM6ER SHEET REV DS3 TYP AMENDe DS4 1
l CC-2115-RROOl6 C
CC-9115-RHOOl6 000001 0003 O NCO BS-3441 X 000002 0003 O DCN 0000001 O NCC BS-3441 N CC-2115-RROO17 C
CC-911& RROO17 000001 0005 0 NCO BS-3441 N CC-2115-RROO18 C
CC-9115-RROO18 000001 0003 0 CC-2115-RROO19 C
CC-9115-RROO19 000001 0003 0 CC-2115-RROO2O C
CC-9115-RROO2O 000001 0004 0 000002 0004 0 CC-2115-RROO21 C
CC-9115-RROO21 000001 0003 0 FCR DJ-8635 0_ _ _ _ _
CC-2115-RROO22 C
CC-9115-RROO22 000001 0005 0 CC-2115-RROO23 C
CC-9115-RROO23 000001 0003 0 NCC SS-5524 HW CC-2115-AROO24 C
CC-9115-RROO24 000001 0005 0 CC-2115-RROO25 C
CC-9115-RROO25 000001 0007 0 CC-2115-RROO26 C
CC-9115-RROO26 000001 0002 0 CC-2115-RROO27 C
CC-9115-RROO27 000001 0003 0 CC-2115-RROO28 C
CC-9115-RROO28 000001 0002 O FCR EJ-4913 C CC-2115-RR2029 C
CC-9115-RROO29 000001 0002 O NCC SS-5572 HM NCC SS-5608 X CC-2115-RROO30 C
CC-9115-RROO30 000001 0001 0 LJ-2115-RROO31 C
CC-9115-RROO31 000001 0003 O NCC SS-5572 HW CC-2115-RROO32 C
CC-9115-RROO32 000001 0003 0 CC-2116-HL5001 C
CC-9116-HL5001 000001 0004 0 000002 0004 0 CC-2116-HL5002 C
CC-9116-HL5002 000001 0003 0 CC-211t-HL5003 C
CC-9116-HL5003 000001 0005 0 000002 0005 0 CC-2116-et_5004 C
CC-9116-HL5004 000001 0004 0 CC-2116-ti 5005 C
CC-9116-HL5005 000001 0002 O NCC SS-5525 O CC-2116-te_5006 C
CC-9116-HL5006 000001 0001 D NCC SS-5528 O NCC taS-5746 N CC-2116-RROOO1 C
CC-9116-RROOO1 000001 0001 O FCR EJ 1632 O FCR EJ-5439 O CC-2116-RROOO2 C
CC-9116-RROOO2 000001 0001 O FCR EJ-4917 0 NCC SS-5600 0 NCC SS-5605 O CC-2116-RROOO4 C
CC-9116-RROOO4 000001 0003 0 CC-2116-RROOO3 C
CC-9116-Rh N 5 000001 0003 0 NCC CS-3551,_
0 CC-2116-RROOO6 C
CC-9116-RROOO5 000001 0001 0 CC-9116-RROOO6 000001 0003 0 CC-2116-RROOO7 C
CC-9116-RROOO7 000001 0005 0 FCR EJ-6159 0__,,
000002 0005 0 CC-2116-RROOO9 C
CC-9116-RROOO9 000001 0004 O DCN 0000003 O__
CC-2116-RROO10 C
CC-9116-RROO10 OOC 4)O1 0005 0 CC-2116-RROO11 C
CC-9116-RROO11 000001 0002 0 CC-2116-RROO17 C
CC-9116-RROO17 000001 0004 0 CC-2116-RROO18 C
CC-9116-RROO18 000001 000S 0 CC-2116-RROO19 C
CC-9116-RROO19 000001 0001 O FCR EJ-4967 0 CC-2116-RROO2O C
CC-9116-RROO2O 000001 (4)O4 O FCR EJ-4967 O CC-2117-HL5001 C
C CC-9117-HL5001 000001 N 4 0 NCC HS-3471 N CC-2117-HL5003 C
CC-9117-HL5003 000001 0003 0 NCC CS-3556 N CC-2117-HLSOO4 C
CC-9117-HL5004 000001 0001.O NCC fiS-5524 HW
~ _ - -,.
O O
v 1
O l
PSI Component Sapper-t m (pip 1 W for* System:
CC and q_. class 3 DATE:.16-NOV-88 15:":7:56 PAGE: 36 EXArt1 NATIONS HANGER HURSER SMSRG SNSRe VT3 VT4 Df1G AUG DOCUMENT NUMBER EnEET REV DS3 TYP AMENOG DS4 CC-2117-NL5005 C
CC-9117-HL5005 00e001 0001 O FCR EJ-4755 0 NCC SS-5507 HM CC-2117-tL5006 C
C CC-9117-HL5006 000001 0003 0 FCR EJ-5891 0 CC-2117-RROOO3 C
CC-9117-RR W 3 000001 0006 0 000002 0006 0 FCR CJ-3425 0 CC-2117-RROOO5 C
CC-9117-RE N 5 000001 0005 0 CC-2117-HROOO6 C
CC-9117-RRW)O6 000001 0005 0 000002 0005 0 CC-2117-HROOO7 C
CC-9117-RROOO7 000001 0005 0 F CR EJ-4937 0,,_
CC-2117-RROOO8 C
CC-9117-RROOOO 000001 0005 O FCf. EJ-5647 O 000002 0005 0 FCH EJ-5647 O CC-2117-RROOO9 C
CC-9117-RROOO9 000001 0003 0 FCR EJ-5647 O CC-2117-RROO10 C
CC-9117-RROO10 000001 0005 O FCR EJ-5907 0 007)O2 0005 0 FCR EJ-5907 O CC-2117-RROO11 C
CC-9117-RROO11 000001 0003 0 CC-2117-RROO13 C
CC-9117-RROO13 000001 0003 O CC-2117-RROO14 C
CC-9117-RROO14 000001 0003 0
[
CC-2117-RROO15 C
CC-9117-RROO15 000001 0002 O CC-2117-RROOt6 C
CC-9117-HROOl6 000001 0002 0 CC-2117-RROO17 C
CC-9117-RROO17 000001 0002 0 CC-2117-RROO18 C
CC-9117-RROO18 000001 0002 0 CC-2120-HL5001 C
CC-9120-HLSOO1 000001 0003 O FCR EJ-3345 O FCR EJ-5158 O CC-2120-tL5002 C
CC-9120-HL5002 000001 0002 C FCR EJ-4958 0 NCC SS-5545 HW CC-21 N 3 C
C CC-9120-HL5003 000001 0000 0 NCC CS-503S x CC-2120-RROOO1 C
CC-9120-RRCM)O1 000001 OOCC 0 CC-2120-RROOO2 C
CC-9120-RROOO2 000001 0007 0 NCC SS-3547 5 CC-2120-RROOO4 C
CC-912^-RROOO4 000001 0005 0 NCC CS-4839 N FCR EJ-5158 0
=
.f t
PSI C w onent Supports (p1 pings f or-Syst enal EW and q_ class 3 DATE1 16-NOV-88 15157156 PArz1 37 EXAPIINATIONS NR D4JrtBER SMSRe SMSRe VT3 VT4 DriG AUG DOC 1JMENT NurlbER SHEET REV DS3 TYP ArENDS DS4 EW-2101-HL5001 C
EW-2101-HL5001 000001 0000 O FCR BJ-1349 0 FCR EJ-1902 O EW-2101-HL5002 C
EW-2101-HL5002 000001 0000 O EM-2102-HL5001 C
EW-9102-HL5001 000001 0003 O FCR EJ-3904 0 FCR EJ-4263 0 NCC 55-4011 N EW-2102-HL5003 C
EW-9102-HL5003 000001 0004 O NCC CS-0894 N FCR EJ-4330 0 FCR EJ-4383 O 000002 0004 O FCR EJ-4383 O EW-2105-et.5001 C
EW-9105-HL5001 000001 0003 0 FCR EJ-3825 O EW-2105-HLSOO2 C
EW-9105-HLSOO2 000001 0002 0 EW-2105-HL5003 C
EW-9105-HL500J 000001 0003 O FCR EJ-3769 O EW-2105-HL5004 C
EW-9105-HL5004 000001 0003 0 FCR EJ-0744 0 EW-2105-et.5005 C
EW-9105-HL5005 000001 0003 0 EW-2105-ML5006 C
EW-9105-HL5OO6 000001 0003 O FCR EJ-3763 O EW-2105-44.5007 C
EW-9105-HL5007 000001 0002 O FCR EJ-2931 O EW-2106-HL5001 C
EW-9106-HL5001 000001 0001 0 EW-2107-NL5001 C
EW-9107-HLSOO1 000001 0002 O EW-2107-et.5002 C
EW-9107-HL5002 000001 0001 0 000002 0001 0 EW-2107-HL5003 C
EW-9107-HL5003 000001 0C01 0 EW-2107-HL5004 C
EW-9107-HLLOO4 000001 0004 0 FCR EJ-5785 0 000002 0004 0 FCR EJ-5785 0 EW-2107-MLSOO5 C
EW-9107-HL5005 000001 0003 C EM-2107-NL5006 C
EW-9107-HLSOO6 000001 0001 0 EW-2107-NL5007 C
EW-9107-HL5007 000001 0003 0 EM-2107-ML5008 C
EW-9107-HL5008 000001 0001 0 EW-2121-HL5001 C
EW-2121-HL5001 000001 0000 O FCR BJ-1433 O NCC CS-4585 N FCR EJ-3928 O EW-2125-et.5004.
C EW-9125-HL5004 030001 0001 0 EW-2125-et.".A)o5 C
EW-9125-HL5005 000001 0001 O FCR EJ-4883 0 EW-2125-et.5006 C
EW-9125-HL5006 000001 0000 O FCR EJ-4894 O EW-2125-HL*./47 C
CW-9125-HLSOO7 000001 0001 O FCR EJ-5189 O EW-2125-et.h >8 C
EW-9125-HL5008 000001 0001 0 DCN 0000001 O EW-2125-NL5009 C
EW-9125-HL5009 006001 0001 0 DCN 0000001 O FCR EJ-1862 O FCR EJ-5337 0 EW-2125-HL5010 C
EW-9125-HL50!O 000001 0001 O DCN 0000002 O FCR EJ-5307 0 EW-2127-NLSOO1 C
EW-9127-HL5001 000001 0001 O FCR EJ-3912 O FCR EJ ~*202 O EW-2127-HL5002 C
EW-9127-HL5002 000001 0002 0 EW-2127-94.5003 C
EW-9127-HL5003 000001 0002 O FCR EJ-5968 0 FCR EJ-7298 0 EW-2128-HL5001 C
EW-9128-HL5001 000001 0002 O FCR EJ-5331 O FCR EJ-5453 0 EW-2129-HL5002 C
EW-9120-HL5OO2 000001 0002 O FCR EJ-5555 0 FCR EJ-6132 O FCR EY-4210 0
~.
~
s G'
a PSI Component Supewt s (papangt fw System:
EW and oc14ss 3 DATE: 16-NOV-98 15:57:56 PAGE: 38 EMArt1NAT10NS DdNEiER pa#4SER SMSRe SNSAe VT3 VT4 DMG AUG m m1ENT NureER SMFET REV D53 TYP AfENDS DS4 j
EM-21. N 2 C
EW-9123-HL5002 000002 0002 O FCR EJ-6132 O FCR EY-4210 0 000003 0002 O FCR EJ-61"_ 9 j
EM-2129-9L5003 C
EW-9128-HL5003 000001 0001 0 EM-21SS-NL5001 C
EW-2188-HL5001 000001 0000 O FCR BJ-1342 O EW-21SS-ML5002 C
EW-2188-HL5002 000001 0000 O FCR EJ-4197 0 EW-2188-ML5007 C
EW-2108-HL5007 000001 0000 O FCR EJ-1393 O EM-21SS-ML5006 C
EW-2188-HL5006 000001 0001 O FCR EJ-1488 0 1
1 1
l
?%
fg_
'l.
O A
f.
'l 3
I S
W 7
El
!9 il i
i 11 O,I l
e
~
5
<< n i
a $$is i
1g!
1: 11 5!il
. cei
,i I
i i
1 O},l l.
l
,. i t
il
.d:
O 8
D 5
R 8
g h
1.: l l5-t nj
$i OQ g
~E B
lU t
W 8
Oe i
e
{U
~
5
.E Ct l
3 TA 4
Y::
I
.i n
xs
- E $1
! :ll
! !:l g>
- 41 o
i o i1 5
k
l O
O O
PSI Coma ment Supports (egvapsent) for System:CC and (class 3 DATE: 17-NOV-99 13: 27: 21 PAGE: 31 EXAMINATIONS HMe*4R NUM6ER SNGAG VT3 VT4 DMG AUO DOCUMENT NUMBER SHEET REV DS3 TfP AMENDG DS4 CCP1A C
3M01-9-C-4146-CCP1A 0006 0 NCR SM-4006 0 8022-01070-CCP1A a
O NCR AM-OO46 O FCR BM-0247 0 FCR 399-0629 0 FCR CM-0235 0 FCR EE-1190 0 NCR SM-3849 0 CCST1 C
3M01-9-C-34040-CCST1 0007 0
~
3M01-9-C-4168-CCST1 0011 O FCR EC-2301 O 6029-C1003-CCST1 A
O FCR CM-OO62 O CCST2 C
3M01-9-C-34040-CCST2 0007 0 3M01-9-C-4168-CCST2 OOOO O FCR EC-2301 0 6029-01003-CCST2 A
O FCR CM-OO62 O CCNEA C
3M01-9-C-4014-CCX1A 0008 O FCR EC-1936 0 OO10-01033-CCX1A D
0 CCN2A C
3M01-9-C-4014-CCX2A 0008 O FCR EC-1936 0_
8018-01033-CCX2A D
0 CC33A C
3M01-9-C-4014-CCX3A 0006 0 FCR EC-1936 O~
SO18-01033-CCX3A D
0
O O
O PS1 Companent Supports seguapment) for Systoa.CV and Eclass 3 DATE: 17-NOV-98 13: 27: 21 PAGE: 32 EXAftINAT10NS emeegtR asurgsEst SNeste VT3 VT4 DMG AUG DOCUME~NT NurtEER SMEET REV DS3 TYP AMDsDe DS4 CSD1A C
0233-OOO14-CBDIA A
O FCR 309-0004 0 3M01-9-C-4162-CSD1A 0002 0 LDFIA C
0213-COO 20-LDFIA A
O 3M01-9-C-4162-LDF1A 0002 0 LDF2A C
0213-OOO20-LDF2A A
O 3M01-9-C-4162-LDF2A 0002 O LDF3A C
0213-OOO20-1.DF3A A
O
[
3M01-9-C-4162-LDF3A 0002 0 LDF4A C
OA13-OOO20-LDF4A A
O 3h01-9-C-4162-LDF4A 0002 0 maria C
0213-OOO16-rtaDIA A
O FCR BM-OOSS O_
3M01-9-C-4162-MSD1A 0002 0 CCPP1 C
0203-COOO7-RCPP1 A
O FCR SM-0339 O__
FCR SM-0407 0 3M01-9-C-4162-RCPP1 0002 0
O a
l g
El lo o N
d I
kh 8
1 si 00 e
8 u
O:
8
.I g
l
? ?,
8 O
11
.i
.e E
! di ih
- yl
- wEl o
Ii
?-
O :i 5
s
e-ei
'L A
E g
ll ll.
N d
h_
21 se l
El I
G..I e
Oe i
5 i
i us pan +
s 1
I n
aan 1
$l 0!!Il 1
1.,
5[Elu I
i O
i l' s
9l k b
1
C.
O 53
- E GAP 1
7:
6-
_ _ [OO
_O 4
2 D
2 52 2
3 t
13 2
e 23 7
1 00 2
p S
E.
nt P
S r
f A
aE E
V
_AR _C O
P-R e
CC Y
t FF F
T
-7 D-3 1
6 OOO0O 00 E
m T
9 9
A V
0 0
D E
0 0
R BSB0A 0D TE EH
_ O3 if ss A
A a
1 1
l S
P c
B3BCA WA o
R 123S1 S1 E
PPF S
- P G
CCC1C 1 W d
N EEE3S 3S n
U
- - - O-O-
a N
444S7 S9 777 2
- 2 W
T 000C0 C1 E
N 1 1 1 1
1 E
00000 00 m
M e
U 00006 02 t
C 44423 22 s
O 000P0 P1 y
D 99938 38 S
re t
SA_
G
)
U ta N TD_
OG e
s IM s
a A
e u tT_
e4 g
nV e
s A
ET_
R3 s
V CCCC C
t ro e
p p
p a
n s
S t
s mE O
n e
n._
o p
t a
se eC 6
588A A
1 231 t
i s
PFPS e
P CCCC w
EEES S
~
i
~
m O
O O
PS1 Ceapanent Supports tegespeent) f or Sy s tem..A4 and g_c lass 3 DATE: 17-NOV-88 13: 27: 21 PAGE: 36 ERAMINATIONS W NUMeER 58s5Re VT3 VT4 Dreg AUC DOCUMENT NUMBER SHEET REV D53 TYP AMENDe DS4 l
--- ~
1 l
JCP1A C
8041-01240-JCP1A F
0 FCR BM-1333 O FCR BM-1335 O FCR SM-1636 0 FCR 3Z-2069 0 FCR EM-0370 0 FCR EM-0371 0 FCR EM-0397 0 l
FCR EM-0431 O l
FCA EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0495 O FCR SZ-1712 O JHalA C
9041-01240-JHX1A F
0 FCR SM-1SS3 0 FCR BM-1533 0 FCR BZ-2069 0 FCN EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCA EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0493 O FCR EZ-1712 O JHD2A C
9041-01240-JH12A F
0 FCR SM-1553 O FCR BM-1555 0 FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0495 0 FCR SZ-1712 0 0041-01240-JSP1A F
0 FCR BM-1533 O
,F/1 A C
FCR BM-1555 0 FCR BM-1636 O FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 O FCA EM-0440 0 FCR EM-0433 0 FCR EM-0482 O FCR EM-0495 O FCR SI-1712 0
.Ad1 A C
8041-01240-JW1A F
0 FCR BM-1333 0
r
~
l 1
O O
O F:TI Ceep seent Swpports segwspocati for Sgstaa.JW and (_ class 3 DATE: 17-Wav-se 13. 27:i; PAGE: 37 EXArtINATI(Des q
e asurg;ER See6ae VT3 VT4 Det3 AUG DOCtJMENT IsrJER SHEET REV DS3 TYP AMENDS DS4
.Ad1 A C
8041-01240-JW1A F
0 FCR SM-1555 O FCR BM-1636 O FCR RZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 O FCR EM-044(* D FCR EM-0453 0 FCR EM-0482 0 FCR EM-0495 0 FCR SZ-1712 O i
I JWH1A C
8041-01240-JWH1A F
0 FCR BM-1333 O FCR SM-1SSS C FCR SM-1636 O FCR SZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 0 FCR EM-0440 0 FCA EM-0453 0 FCA EM-0482 O FCA EM-0495 0 FCR SZ-1712 O JWH2A C
8041-01240-JWH2A F
0 FCR BM-1553 0 FCR BM-1553 0 FCR BM-1636 0 FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 0 FCR EM-0440 0 FCR EM-0433 0 FCR EM-0482 O FCR CM-0495 0 FCR SZ-1712 0 ndS1 A C
8041-01240-JWS1A F
0 FCR BM-1553 0 FCR DM-1535 0 FCR BM-1636 O FCR 5Z-2069 0 FCR EM-0370 0 FCR EM-0371 0 FCR EM-0397 0 FCR EM-0431 0 FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0493 O FCR SZ-1712 0
O O
O I
PSI Ceepenent Supports segusementa fer System LU and g_ class 3 DATE: 17-NOV-88 13: 27: 21 PAGE: 3e EXAMINATIONS 6 NUMSER SMSRe VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYP AMENDe D64 LCP1A C
6041-01240-LCP1A F
0 FCR BM-1333 C FCR BM-1555 0 FCR BM-1636 0 FCR SZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR FM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0493 0 FCR SZ-1712 O LM31A C
8041-01240-LHX1A F
0 FCR BM-1553 0 FCR SM-1555 0 FCR SM-1636 0 FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0433 0 FCR EM-0482 O FCR EM-0495 0 FCR SZ-1712 O LHs2A C
8041-01240-LHX2A F
0 FCR BM-1333 0 FCR BM-1SS3 0 FCR BM-1636 O FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 O FCR EM-0482 O FCR EM-0495 O FCR SZ-1712 O t_u1 A C
tsO41-01240-LU1 A F
0 FCR BM-1533 0 FCR BM-1533 0 FCR BM-1636 0 FCR BZ-2069 O FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 O FCR Ett-0440 0 FCR EM-0453 0 FCR EM-0482 O f
FCR EM-0497 0
6
/ j O
O
(
%s' PEI Comp went Supports seguipment) for System LU and g_ class 3 GATE: 17-Nov-98 13: 27: 21 PAGE:
39 EXAMINATIONS Nd40R NLWpCR $NSRG VT3 VT4 DMG AUC DOCUMENT NUMSCR SHEET REV DS3 TYP AMD400 DS4 LU1A C
8041-01240-LU1A F
0 FCR SZ-1712 O Lu2A C
8041-01240-LU2A F
0 FCR BM-1553 0 FCR BM-1SSS O FCR BM-1636 0 FCR BZ-2069 0 FCR D4-0370 0 FCR EM-C371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0493 0 FCR SZ-1712 O LU3A C
8041-01240-LU3A F
0 FCR BM-1553 0 FCR BM-1555 O FCR BM-1636 0 FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0495 0 FCR S4-1712 O LU44 C
8041-01240-LU4A F
0 FCR BM-1533 0 FCR 3f9-1553 0 FCR SM-1636 0 FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 O FCR EM-0495 O FCR SZ-1712 O LOSA C
8041-01240-LUSA F
0 FCR BM-1333 0 FCR BM-1353 0 FCR BM-1636 O FCR BZ-2069 0 FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 0 FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 0 FCR EM-0482 0
(- -
O O
O PSI Component Supports segunpoenti for Systea LU and g_ class 3 DATE: 17-teOV-88 13: 27: 21 PAGE: 40 EEAMINATIONS edea;ER NUMSER Spe5Re VT3 VT4 DMG AUC DOCUMENT Mur48ER SHEET REV D83 TYP Aseree 064 LUSA C
8041-01240-LUSA F
0 FCR EM-0493 O FCR 52-1712 O l
LM C
8041-01240-LU6A F
0 FCR 399-1553 0 FCR BM-1SSS O l
FCR SM-1636 0 FCR BZ-2069 O FCR EM-0370 0 FCR EM-0371 O FCR Ert-0397 0 FCR Ert-0431 O FCR EM-0440 0 FCR EM-04S3 0 i
FCR Ert-0482 O l
FCR EM-0413 0 l
FCR SZ-1712 0 LU T*.
C 8041-01240-LU7A F
0 FCR BM-1SS3 O l
FCR 589-1555 0 FCR Ret-1636 0 FCR BZ-2069 0 FCR EM-0370 0 l
FCR Ert-0371 O l
FCR Ert-0397 0 l
FCR EM-04Ju O l
FCR Ert-0440 0 l
FCR Ert-0453 O FCR Ert-0482 O FCR Ert-0495 0 FCR SZ-1712 O LUF1A C
8041-01240-LUF1A F
0 FCR 399-1553 O I
FCR 99t-153S O l
FCR BM-1636 O FCR EZ-2069 0 FCR EM-0370 0 FCR Ert-0371 O FCR Ert-0397 0 l
FCR Ert-0431 O l
FCR Er;-0440 0 l
FCR Ert-0453 0 FCR EM-0482 O FCR Ert-0493 0 FCR SZ-1712 O LUH1A C
8041-01240-LUH1A F
0 FCR 399-1333 0 FCR 399-1355 O FCR 899-1636 0 FCR 5Z-2069 O FCR Ert-0370 0 FCA EM-0371 O FCR Ert-0397 0 FCR Ert-0431 O FCR EM-0440 0 FCR Est-0453 0 l
__ ~.-
v' PS1 Ceapaner.t Sweverts (equspments for Systee'LU and at_ class 3 DATE: 17-teOV-Se 13:27;21 PAGE: 41 EEAMiteATI(des m e se.esER SostiRs VT3 VT4 Dreg AUG DOCUMENT pourtBER SHEET REV DS3 TYP A#ENDe D64 Lu> 1 A C
8041-01240-LUH1A F
0 FCR EM-0482 O FCA EM-0493 O FCR SZ-17 2 O L*Je42A C
8041-01240-LUH2A F
0 FC SM-1SS3 O FCR eM-1sss O FCR BM-1636 O FCR BZ-2069 O FCR EM-0370 0 FCR EM-0371 O FCR EM-0397 O FCR EM-0431 O FCR EM-0440 0 FCR EM-0453 O FCR EM-0482 O FCR EM-0495 0 FCR SZ-1712 O k
I
~
O O
PS1 Campsment Sepperts segwipmentt for Systee.aN and (class 3 DATE: 17-NOV-OS 13:27:21 PAGC
'42 EXA#etNAT1(BsE penseKm savnect assene VT3 vi4 Deta Aue DOCUMENT seURSUt SHEET stN D63 TYP AeqEpee 354 swtSin C
0149-010 M nSTE 3
0 FCs EM-0199 0 3nOS-9-C-4012-DNST1 0004 O FCR EC-1849 0 P
P b
5 I
I
=
O.O PS1 Ceapenent Scey,erts ( egw s poent ) for Systee:SD and oclass 3 DATE. 17-eden-GS 13:27:21 PAGE: 43 EEMtINAT1(des w,Xe esteista Sossee VT3 VT4 Dng AUG DOCureDsT asureSER SHEET ACJ 063 TYP AreDee D64 SATIA C
8041-00109-SATIA B
O FCR 989-0160 0 FCR Det-OS65 O SATIS C
GO41-00109-SAT 13 5
0 FCR Det-0140 0 FCR Drt-OS65 0 l
I
. -.,. -. - -.. -.,.. - -, - -, - - - - -, -. - - - -.. ~ - - - -
w
-- _ -.-.--, - ~.
I I
i 6
J f
l APPENDIX C i
l
~
EXEMPT AND MON SAFETY SUPPORTS CONTAINING SNUBBERS 1,
l (PAGES 1 THR't 20)
I L
I f
l l
i i
l l
r i
1 1
i I
I d
I
(
l 1
l f
i 1
i t
t
?
l t
t i
a l
S ~,/E048/rr l
I a---
-*-rvw---
-- 3
_p---y--wywy--
meg m~e; We-w e w W e e-wwe'...
. FwW TPm--
Y-'
E i
PSI EXAMINATION
SUMMARY
REPORT APPENDICES LECEND i
Column Headinz Definition SNSR w -
Snubber Serial Number Examinations:
DMG Post Heat up Damage AUG Augmented PSI Snubbers TYP Amendment Type CCP Configuration Control Package DON Design Change Notice
{
FCN - Field Change Notice l
TbN Field Skatch Notice IDC - Interia Design Change Notice I
NCC Nonconformance Report Closed i
NC0 Nonconformance Report Open NCR Nonconformance Report PDN. Potential Deficiency Notice i
DS3 Disposition of Revision / Amendment Review DS4 First Position:
H Hardware Impact I. Documentation Impact i
O. Original Disposition t
N No Impact i. Pending Disposition
,. Affects Unit 1 Only. No Impact I
Second Position:
(
C. Rewalk Complete N
Revalk Not Required W
Revalk Required i
4 l
i r
i t
f G-1 1
S3/E048/rr i
I i
=
0 0
0-PS1 Emesept Snubbers f or-System
- AF and q. Class 2 DATE: 16-NOV-88 15:57:44 PAGE:
1 EXAMINATIONS HANEiER MUNEfER fiiN8RS SNSRG VT3 VT4 DMG AUG DOCUMENT NUMBER SHEET REV DS3 TYP AMENOS DS4 l
AF-2OO6-HL5003 597 C
AF-9006-HL5003 000001 0003 0 FCR EJ-5819 0 FCR EJ-7097 0 i
i AF-2OO6-HL5015 606 C
AF-9006-HL5015 000001 0003 O FCR EJ-6876 0 j
AF-2006-HL5018 673 C
AF-9006-HL5019 000001 POO2 O FCR BJ-1660 0 FCR EJ-3139 0 s
FCR EJ-7005 0 1
J FCR EJ-7274 O d
NCC 55-5629 HW 000002 0002 O FCR EJ-3139 0 NCO SS-3629 X
{
AF-2OO6-HL5035 593 599 C
AF-9006-HL5035 000001 0003 O FCR 83-1635 0 FCR EJ-5942 O NCO SS-5629 HW 000002 0003 0 FCR DJ-1635 0 000003 0003 0 l
AF-2OOS-HL5028 647 C
AF-9008-HL5028 000001 0003 0 FCR EJ-7077 0_
NCC SS-5609 X NCO SS-5624 X AF-2OOS-HL5029 605 C
AF-9000-HL5029 000001 0004 0 FCR EJ-6740 0 i
AF-2OOS-HL5030 669 C
AF-9006-HL5030 000001 0003 O FCN 2J-0516 O FCR BJ-1561 O
)
AF-2OOS-HL5041 596 594 C
AF-9000-HL5041 000001 0003 0 FCR DJ-8860 0 l
FCR EJ-6879 0
)
FCR EJ-7168 O NCC SS-5532 X NCC S5-5668 X 000002 0003 0 FCR DJ-8860 0 FCJt EJ-6879 0 NCC SS-5552 X AF-2010-HL5002 671 672 C
AF-9010-HL5002 000001 0006 O FCR EJ-7373 0 000002 0006 O FCR EJ-7373 0 000003 0006 O FCR EJ-7373 0 000004 0006 0 FCR EJ-7373 O AF-2010-HLSOO7 392 601 C
AF-9010-HL5007 000001 0005 0 FCR EJ-6919 0 000002 0005 0 FCR EJ-6919 O 000003 0005 O FCR EJ-6919 0 000004 0005 0 AF-2010-HLSOOS 384 585 C
AF-9010-HL5008 000001 0005 O FCR EJ-7378 0_
000002 0005 0 FCR EJ-7378 0 000003 0005 0 FCR EJ-7378 0 000004 0005 0 AF-2010-HL".OO9 291 C
AF-9010-HL5009 000001 0005 O FCR EJ-7676 O_
AF-2010-ML5017 582 C
AF-9010-HL5017 000001 0002 O FCR EJ-7134 0 000002 0002 O FCR EJ-7134 O AF-2010-HL5018 537 C
AF-9010-HL5018 000001 0003 O FCR EJ-6902 O
)
FCR EJ-7239 0 AF-2010-HL5020 312 C
(E-9010-HL5020 000001 0002 O FCR EJ-6940 0 AF-2010-HL5026 556 C
AF-9010-HL5026 OOJOO1 0004 O NCC BS-0259 0 FCR EJ-7793 O 000002 0004 0 NCC 059259 0 FCR EJ-6974 0
O U
/^'%.
PS1 Exempt Snubbecs for System: AF and q_ class 2 DATE: 16-NOV-BG 15:57:44
- AGE:
2 EXAMINAT1DNS HANGER NUMBER SNGRe SeeSRe VT3 VT4 DME AUG DOCUMENT NUMBER SHEET REV DS3 TYP Ar4MDS DS4 AF-2010-HL5035 486 C
AF-9010-HL5035 000001 0002 O FCR EJ-7257 O MCC SS-5668 X AF-2061-HL5001 548 C
AF-9061-HL5001
'NXX)O1 0003 0 FCR EJ-6959 0 AF-2061-HL5002 290 C
AF-9061-HL5002 000001 0003 0 FCR EJ-6971 O peCC SS-5583 X NCC SS-5668 X AF-2062-HL5011 538 C
AF-9062-HL5011 000001 0002 O FCR EJ-6943 0 AF-2062-HL*.A)12 497 C
AF-9062-HL5012 000001 0001 O FCR EJ-6398 0 AF-2062-HL5015 430 C
AF-4362-HL5015 000001 0003 0 AF-2063-HL5002 555 0
AF-9063-HLSOO2 000001 0002 O FCR EJ-7105 O 000002 0002 0 AF-2O63-MLSOO3 308 C
AF-9063-HL5003 000001 0002 O FCR EJ-6723 0_
fW-2063-ML5005 549 C
AF-9063-HLSOO5 000001 0002 O FCR EJ-7061 O AF-206341L".A)O6 340 C
AF-9063-HL5006 000001 0001 O NCO CS-5195 X AF-2064-NL5004 275 C
AF-9064-HLSOO4 000001 0003 O FCR EJ-6272 0 r
1
.s O
O 4
f PS1 Exempt tinamenorm for Systeen: AP and q_ class 2 DATE: 16-NOV-SS 15:57:44 PAGE:
3 1
ExAn:NarroNs HANGER NUMSER SBSAS SMSRG VT3 VT4 DPEG AUG DOCl#EENT NUnSER SHEET REV DS3 TYP APEsse D64 AP-2OO3-HF5001 386 C
AP-2OO3-HFSOO1 000001 0000 O FCR EY-6518 O j
FCR EV-7JS6 0 i
i l
i I
1 t
d' i
i 1
4 1
i ll 4
i l
j i
5
..,.._..--.m.
_.,,.... -.. - -. - - - ~ - - - - - - -
s
[m}
O.
v FSI Faempt Sneheers far System: F.V and ag_c lass 2 DATE: 16-NOV-85 15:57:44 PNGE:
4 ENAr'iNATIONS HAN(iER NUPgER Sosime SeeGne VT3 */T4 DPUS Aug ranr184ENT paJNSER SHEET REV DE3 TVP As4ENDe D54 CV-2OO2-HL5002 514 C
CV-9002-HL50C2 000001 0004 O FCR EJ-4601 O 0005 N CV-2OO2-HL5003 506 C
CV-9002-64.5003 000001 0004 O NCC CS-5057 O FCR EJ-3574 C FCR EJ-7265 C j
0005 N CV-2OO2-HLSOO4 586 C
CV-9002-HLSOO4 000001 0004 O FCR EJ-3377 O_
j 000002 0005 N FCR EJ-5621 O FCR EJ-7258 HC j
0005 N FCR EJ-8091 HC 0006 N 000002 0005 N 0006 N CV-2OO2-NL5007 300 C
CV-9002-NL5007 000001 0003 O FCR EJ-5643 0 FCR EJ-7246 0 CV-2OO2-NL5008 504 C
CV-9002-HL5006 000001 0005 0 FCR BJ-1463 0 0006 N CV-2OO2-ML5009 319 C
CV-9002-HL5009 000001 0003 O FCN 2J-0560 0_
000002 0006 M l
FCR EJ-5792 O 0004 N CV-2OO2-HL5010 305 C
CV-9002-ML5010000001 0004 O FCR BJ-1661 O l
FCR SJ-1756 HC 6'Jt EJ-7407 0 FCR EJ-8409 N
{
NCC SS-5617 N l
CV-2OO2-HL5012 SOS C
CV-9002-C:L5012 000001 0003 O FCR EJ-5927 0 t
FCR EJ-5930 O FCR CJ-7770 N NCO SS-3498 M NCC S5-5498 N NCC SS-5628 HC 0004 N FCR EJ-8517 N j
000002 0003 0 FCR EJ-5927 O FCR EJ-7770 N NCO SS-5498 N NCC 5S-5628 HC 0004 N CV-2OO2-HL5019 295 C
CV-9002-HL5019 000001 0003 O FCR EJ-7203 0 0004 N CV-2OO2-HL5020 303 C
CV-9002-te 5020 000001 0004 O FCR BJ-1413 0_
FCR DJ-7948 0 FCR EJ-7059 0 NCC 55-5628 HC NCC SS-3667 N 0005 N FCR DJ-7848 N CV-2OO2-HL5021 348 C
CV *POO2-HL5021 000001 0003 0 FCR BJ-1656 0 NCC SS-5640 N NCO SS-5653 HC 0004 N j
--=
{
O O
O.
I
(
PSI Exempt Snumbers for Systeest CV and at_ class 2 DATE1 16-NOV-88 15157144 PAG 01 5
l EMAMINATIONS j
W4'M MUMEsER SNGRe SNSRs VT3 VT4 DMG AUG DOCUMENT NUMEsER SHEET REV DS3 TYP AMEMOG DS4 CV-N 2-HL5021 348 C
CV-9002-HL5021 000002 0004 N l
CV-2OO3-HFSOO3 296 C
CV-2OO3-HF5003 000001 0000 0 FCR EV-3411 O_
0001 HW FCR EY-7653 HN I
CV-2OO3-MLSOO3 578
- 1 C
CV-9003-HLSOO3 000001 0000 O FCR EJ-8421 O l
FCR EJ-8425 0 FCR EJ-8426 O CV-2OO4-NF5001 584 C
CV-2OO4-HF5001 000001 0000 O FCR EV-3219 0 l
FCR EY-7384 X 0001 HW FCR EY-7384 N CV-2OOS-HF",A)O1 574 C
CV-2OO5-HF5001 000001 0000 O FCR EY-2787 0 FCR EY-1219 0 FCR EV-7385 X NCC SS *,633 X l
0001 HW NCC SS-5633 HW CV-2OO6-HL5037 741 C
CV 4006-HL5037 000001 0006 0 000002 0006 O FCR EJ-5222 O CV-2011-t4 ",009 328 C
CV-9011-HL5009 000001 0002 0 CV-2006-SSnOO2 344 C
CV-9086-SSOOO2 000001 0001 0
_ __ p CV-2088-NL5002 768 C
CV-9000-HL5002 000001 0001 O NCC sS+0259 R FCR EJ-7874 0 NCC SS-5644 N NCC 55-5667 X CV-2116-HL5018 343 C
CV-9116 '4L5018 000001 0001 O FCR EJ-4384 O FCR EJ-7855 0 j
CV-2117-HF5054 773 C
CV-2117-HF5054 000001 0000 O 0001 N CV-2117-HL5005 351 C
CV-9117-HL5005 000001 0002 O FCN 1J-1617 O_, _
0003 N 000002 0003 N CV-2117-SSOOO6 546 C
CV-9117-SSOOO6 000001 0002 O FCR EJ-3744 0_
l FCR EJ-4450 0 NCC SS-5557 N 0004 N 000002 0004 N l
l w
=e v
ee-Tm-+
-g m-m wr-Tww M w--
my-- * -
v v
-T-m7---w i-w-----
T----
-7 y-T
=--a
---e m
_.. = _ _ __
L J
c.
4-
?
PSI Emwt Snumannes f or Systerm: FC and Eclass 2 DATE: 16-NOV-88 15:57:44 PAGE:
6
-1 EliartINAT IONS MANGER NJP9ER SNEiRS SNSne VT3 VT4 DMS AUG DOCunENT NUMBER Si6EET FEV DS3 TYP APEgee D64 FC-2011-HL5001 392 C
FC-9011-m 5001 000001 0003 0 FCR DJ-8397 O FCR EJ-6094 0 NCC MS-5283 0 t
i
~
t t
2 i
i h
h 4
t I
[
f I
i I-
-v-w-
= - -.www www r-s e-ww -~w%=w e rwwww w,m w w
+1
,--w-vc.verwn-w-i---,--
-w-'wm---,,we-=w=ww--www-
-rw
- w e, wee
-vweve<'w me*~wwwg-=i.
-w,--w-
-w
+--ee
<v
-e vet w--
mv
-w
m
~
o O
O O
PSI EmeMapt Snubber s for Systeent FW and Lclass 2 DATE1 16-NOV-88 15157144 PAGE:
7 EXArt1 NATIONS S9grRe SMSRe VT3 VT4 DrtG AUG DOCUPIENT PaJrtbER SHEET REV DS3 TYP AMENDe DS4 Hmm8ER paJPtbER a
FW-2012-ML5002627628 C
FW-9012-HL5002 000001 0005 0 FCR EJ-7184 0 000002 0005 0 FCR EJ-7184 0 FW-2012-HL5003 120 C
FW-9012-tL5003 000001 0004 0 NCC CS-4243 X FCR DJ-9037 O FCR DJ-9104 O FCR EJ-7362 O NCC SS *,539 K 000002 0004 O NCC CS-4243 X FCR EJ-7144 O NCO SC-5539 X FW-2012-MLSOO5 619 620 C
FW-9012-HL5005 000001 0005 0 FCR EJ-2573 O FCR EJ-6725 O FCR EJ-6861 O NCC 55-5584 X 000002 0005 0 FCR EJ-6725 0 FCR EJ-6861 O l
FW-2012-HL5008 70 C
FW-9012-HL5006 000001 0005 0 FCR EJ-6753 O FCR EJ-7436 O 000002 0005 0 FM-2012-*L5011 663 C
FW-9012-tL5011 000001 0001 O FCR EJ-7485 0___
FCR EJ-7847 O FW-2014-NL5001 609 626 C
FW-9014-M 500 000001 0007 O FCR BJ-1619 0 FCR EJ-7109 0 000002 0007 0 FCR BJ-1619 0 FW-2014-HL5002 123 C
FW-9014-HLLOG2 000001 0004 O NCO BS-4298 X FCR EJ-7794 0 FO-2014-HLSOO3 610 600 C
FW-9014-HL5003 000001 0004 0 NCC CS-5291 X FCR EJ-6981 O 000002 0004 O NCC CS-5291 X FCR EJ-6981 O FO-2014-HL5009 122 C
FW-9014-FL5009 000001 0005 0 NCO CS-3309 X FCR EJ-7130 0 FCR EJ-7623 0 NCC 55-5539 X FW-2014-HL5012 642 C
FW-9014-HL5012 000001 0002 O FCR EJ-5710 0 l
FCR EJ-6275 0 l
FCR EJ-7016 0 1
FCR EJ-7270 0 000002 0002 0 FW-2016-SSOOO6 587 C
FW-9016-SSOOO6 000001 0004 O FCR EJ-7143 0 j
FCR EJ-7670 O i
FW-2018-HL5003 682 C
FW-9018-HL5003 000001 0005 0 FCR EJ-6969 O l
000002 0005 O FCR EJ-6969 0 l
FW-2018-HL5004 593 C
FW-9018-HLSAO4 OOOsK)1 0003 O FCR EJ-6786 O FW-2018-HL5006 656 657 C
FW-9018-ML5006000001 0006 O FCN 1J-1675 O FCR DJ-1643 0 FCH EJ-6952 O I
FCR EJ-7088 0 j
000002 0006 0 i
000003 0006 O FCR BJ-1643 0 FO-2018-HL5007 664 661 C
FW-9018-HL5007 000001 0004 O NCC G-5485 X
i O
O O.
l l
PSI Esempt SnutH>ers for System: FW and tclass 2 DATE* 16-NOV-88 15*57144 PAGC1 8
l EIArtINATIONS HANGER NUM90R SNEiRS SeeSme VT3 VT4 DMG AUG DOCUMENT NUM3ER SHE. EEV DS3 TYP ArqENOS DS4 l
FW-2018-HL5007 664 661 C
FW-9018-HL5007 000001 0004 O FCR DJ-8901 0 FCR EJ-7186 0 FCR EJ-7487 O 000002 0004 O NCC CS-3485 X FW-2018-HL5006 29 C
FW-9018-HL5006 000001 0003 0 FCR DJ-8374 O FCR DJ-9064 0 FCR EJ-7051 O FCR EJ-7237 0 FCR EJ-7668 0 000002 0003 0 FCR EJ-7051 O FCR EJ-7237 0 l
FW-2018-HL5009 119 C
FW-9018-HL",009 000001 0003 0 FCR EJ-7052 O FCR EJ-7654 O FW-2018-SSOOO1 581 C
FW-9018-SSOOO1 000001 0001 O FCR EJ-6661 O i
FW-2018-S# h 583 C
FW-9018-SSOOO6 000001 0005 O FCR BJ-1653 0 FW-2018-SS @ 7 121 C
FW-9018-SSOOO7 000001 0004 O FCR BJ-1657 0 FCR EJ-5602 O FCR EJ-7434 O MCO SS-5539 X NCO SS-5618 X FO-2029-HL5002 304 526 C
FW-9029-HL5002 000n01 0005 0 FCR DJ-8779 0 FCR EJ-4046 0 FCR EJ-7936 X FW-2029-ML5003 294 C
FM-9029-HLSOO3 000001 0004 0 i
FW-2030-HL5002 298 435 C
FW-TOyJ-HLSOO2 000001 0005 O FCR EJ-4047 0 FW-2030-HL5003 396 C
FW-9030-tt5003 000001 0004 O FCR BJ-1689 0 FCR EJ-8097 X FW-2032-HL5002 414 445 C
FW-9032-HLSOO2 000001 0005 0 FCR EJ-4049 O FU-2032-NL5003 550 C
FW-9032-HL5003 000001 0004 0 FW-2117-HL5001 762 C
FW-9117-(t.5001 000001 0003 O FCR EJ-4042 O Ft3-2117-HL5003 593 C
FW-9117-NL5003 000001 0003 0 FCR BJ-1246 0 FCR EJ-5291 O FO-2117-HL5004 589 C
FW-9117-HL5004 000001 0002 O FCR CJ-7601 O MCC SS-5611 HW Ft3-2119-HL5001 591 C
FW-9119-HL5001 000001 0003 0 FCR CJ-4043 0
)
FCR EJ-7606 O FW-2119-HL5003 607 C
FW-9119-HL5003 000001 0003 0 FCR EJ-5224 0 FW-2119-HL5004 766 C
FW-9119-ML5004000001 0002 O FCR EJ-5031 0 j
NCC SS,611 HW FW-2121-HL5001 582 C
FW-9121-64 5001 000n01 0003 0 FCR EJ-4044 0 FW-2121-94_5003 603 C
FW-9121-NLSOO3 000001 0003 O FCN 2J-0684 O FCR EJ-5074 0 FW-2121-HL5004 578 C
FW-9121-HL5004 000001 0002 O FCR EJ-7594 O FW-2123-HL5001 767 C
FW-9123-HL5001 000001 0003 O FCR EJ-4045 0 FCR EJ-5004 O Ft3-2123-HL5003 771 C
FW-9123-tt 5003 000001 0002 O FCR BJ-1246 0 FW-2123-HL5004 772 C
FW-9123-HL5004 000001 0002 O FCR EJ-7598 0
- - -., - - - = - -.
PSI Emempt Sn h a for System: Pts anas (class 2 DATC: 16-NOV-88 15:57144 r* AGE:
9 EEdert!NAT 10NS HANGER NurtisER EN6AS SN6Re VT3 VT4 1996 AUG DOCUMENT NUMEsER SHEET FsEV DS3 TVP AMEfee DS4
- 95-2OOS-NL5004 615 C
PIS-9001-ML5004000001 0007 0 FCR EJ-este O 000002 0007 O FCR EJ-6814 O 000003 0007 0 FCR EJ-6814 0 000004 0007 O FCR EJ-6914 O MS-2OO1-ML5007 66 C
PTS-9001-HL5007 000001 0005 O FCR EJ-5932 O FCR EJ-72OO O FCR EJ-7363 0 000002 0005 0 POS-2OO1-44L5010 744 747 C
MS-9001-HL5010 000001 0005 0 FCR DJ-9545 O___
FCR EJ-7336 O MS-2OO1-ML5011624617 C
PES-9001-HL5011 000001 0006 O FCR DJ-3054 O FCR DJ-6409 O MS-2OO1-HL5012 518 746 C
MS-9001-HL5012 000001 0007 0 DCN 0000004 0 BCC CS-4960 X FCR DJ-3055 O FCR DJ-6410 0 POS-2OO1-HL5015 595 C
MS-9001-ML5015000001 0004 O FCR EJ-6820 0 000002 0004 O FCR EJ-6820 0 ftS-2OO2-HL5006 675 C
PIS-9002-HL5006 000001 0004 O FCR 2J-0719 0 NCC DS-4299 I FCR EJ-7012 O NCC SS-5592 X 000002 0004 O FCN 2J-0719 0 NCC DS-4298 X FCR EJ-7012 O NCC SS-5592 X PTS-2OO2-HL5007 68 C
r9S-9002-44.5007 000001 0004 O NCC DS-4298 X FCR EJ-eeS3 0 FCR EJ-7437 O FCR EJ-8234 X PIS-2OO2-HL5010 425 448 C
MS-9002-HL5010 000001 0007 O NCC CS-4859 X FCR EJ-2279 O FCR EJ-7332 O ttS-2OO2-HL5011 645 648 C
MS-9002-HL5011 0000G1 0006 O FCR DJ-6327 O pts-2OO2-HL5012 307 311 C
pts-9002-ML5012000001 0006 0 FCR DJ-3058 O FCR EJ-1734 3 FCR EJ-2278 0 fts-2OO2-HL5015 500 C
PTS-9002-HL5015 000001 0004 O FCR EJ-6383 O FC3t EJ-6893 0 000002 0004 O FCR EJ-6363 O FCR EJ-6893 0 ftS-2OO2-NL5016 453 C
MS-9002-HL5016 000001 0004 O FCR EJ-7114 0 000002 0004 O FCR EJ-7114 O MS-2OO4-HL5007 683 C
ttS-9004-ML:xsO7 000001 0007 O FCR EJ-7944 M PTS-2OO4-HL5012 67 C
ttS-9004-HL5012 000001 0010 0 FCR EJ-7433 O MS-2OO4-NL5013 65 C
MS-9004-ML5013000001 0005 O FCR EJ-6767 O FCR EJ-7004 O 000002 0005 O FCR EJ-7094 0 99S-2OO4-HL5014 64 C
P9S-90u4-HL5014 000001 0005 0 FCR EJ-4693 0 FCR EJ-6752 O FCR EJ-6846 0
r
'\\
l
~
l l
l l
PS1 Emmenet tinuenters for Systeen: ps and (class 2 DATE: 16-seOV-SIB 15:57:44 PNiE1 to EN Arelser.T IONS HaseGEst paJMest scene assiiste VT3 VT4 DPG AUG Ym=ENT saJrteER SHEET REV E33 TVP ArEpes DS4 MS-2OO4-NL5015 292 309 C
pts-9004-HL5015 000001 0004 O FCpt EJ-4e11 O l
000002 0004 O FCst EJ-4811 O MS-2OO4-HL5016 651 659 C
MS-9004-M.5016 000001 0005 0 MS-2OO4-HL5017 293 742 C
MS-9004 6 17 000001 0005 O DDe 0000002 O SCC CS-4567 I
i O
O O.
MI Emmenet 3roubbers for System: MH and (class 2 DATE: 16-Nov-se 13:57144 PAGE: 11 EXAM teamT 3ONS HApeGDt MUMBER Smens SNEAe VT3 VT4 DMS AUG DOCure.NT MuMWER SHEET REV DE3 TYP AfEsee DG4
)
l not-2202-SSOOO2 338 C
RM-9202-SSOOO2 000001 0005 0 FCR EJ-9027 0 0006 N 000002 0005 0 FCR EJ-6029 O l
0006 M i
RH-2203-NLSOO1 392 C
RM-9203-MLSOO1 000001 0002 O Fut EJ-4431 O 0003 N RM-2211-teLSOO2 805 als C
RH-9211-HLSOO2 000001 0007 O FDt EJ-9239 b FCst EY-6271 O 0008 M 000002 000e N Met-2303-MLSOO7 ett C
HH-9303-MLSOO7 000001 0004 0
-FDt EJ-30to3 0_
0005 N 000002 0005 N RH-2303-94_ SOOT 625 C
RH-9303-MLSOO9 000001 0002 O FCR EJ-SS27 O_
0003 N l
000002 0002 O FCR EJ-3027 0 0003 N h 2306-SSOOO1 806 C
RH-9306-SSOOOR 000001 0905 O FDt EJ-ST57 0
)
0006 M 000002 0006 N RH-2312-HL5002 446 C
RH-9312-M.3OO2 000001 0003 0 FCR EJ-4177 0 0004 N HH-2313-94_SOO3 4e1 4ee C
MH-9313-94_SOO3 000001 0006 0 FCR EJ-3920 0_
FCR EJ-5752 O FCR EJ-6843 O MCC SS-SSO2 N 0007 N 000002 0006 O FCR EJ-6843 0_
NCC 55-5502,N 0007 N l
r
~
a v
PS1 Emempt Snubbers f or Systens SS and ag_ class 2 DATE1 16-NOV-88 15157*44 PARE 1 12 ENAMINAT10N3 HANGER NUPIDER
$NGRe SNSne VT3 VT4 EMG AUG DOCUMENT NUrtbER SHEET FeEV DS3 TYP AMENDe DS4 l
l SS-2101-ML5007 306 C
SS-9101-HLSOO7 000001 0003 O NCC CS-4155 X FCR EJ-5480 0 NCC 55-5699 X l
SS-2101-HL5012 329 C
SB-9101-HL5012 000001 0002 O FCR EJ-6667 O SS-2301-HL5017 507 C
SS-9101-HL5017 000001 0002 0 000002 0002 0 SS-2101-HL5019 338 C
SB-9101-HL5019 000001 0001 O FCN 2J-0655
- O__,
l SS-2101-ML5020 827 C
58-9101-ML5020000001 0002 O FCN 2J-O",49 0 l
FCR EJ-4505 O l
SS-2101-HL5022 354 C
SB-9101-ML5022000001 0001 C FCR F s-ag55 O l
SS-2201-HLSOO4 287 C
SS-9201-HLSOO4 000001 0003 0 SS-2201-HL5010 305 C
SS-9201-ML5010000001 0002 0 000002 0002 0 SS-2201-HL5013 617 C
58-9201-f1L5013 000001 0005 O MCO NS-5730 X_
SS-2201-HL* '17 317 C
SS-9201-tL5017 000001 0002 O FCN 2J-0664 0 FCR DJ-9190 0 SS-2201-ML5018 335 C
SS-9201-HL5018 000001 0002 O FCR EJ-4744 O SS-2201-HL5020 af t9 C
SS-9201-HL5020 000001 0002 O FCR EJ-4629 O MCC 55 "582 HW SS-2202-HFSOO2 761 C
SS-2202-HF5002 000001 0000 O NCC 55-5607 HC 0001 0 SS N 5003 601 C
SS-2250-HF5003 000001 0000 O FCR EV-4901 O_
0001 O NCC SS-5650 0 SS-2301-HL5003 579 584 C
58-9301-ML5003000001 0003 0 NCC CS-5246 X FCR EJ-6999 O NCC SS "M X
000002 0003 O NCC G ".446 X FCR EJ-6999 0 NCC SS " E I SS-2301-NL5011 590 342 C
SS-9301-HL5011 000001 0004 0 FCR EJ-6381 O FCR CJ-6664 O FCR EJ-7086 0 l
NCC 55 "451 X i
000002 0004 O FCR EJ-6381 O FCR EJ-6664 O FCR EJ-7066 O NCC S5-5651 X 000003 0004 O NCC SS-5651 X SD-2301-HL5012 323 302 C
68-9301-HL5012 000001 0004 0 FCR G "242 O FCR EJ-7040 0 NCC SS-5651 I 000002 0004 0 FCR EJ-7040 0 NCC SS-5651 X SS-2301-HL5010 902 C
SS-9301-HL5018 000001 0003 O F CN 2J-0670 0 FCR SJ-1356 O FCR EJ-4641 O FCR EJ-4996 O SD-2301-HL5020 907 C
SB-9301-HL5020 000001 0001 0 SB-2301-HL5021 329 C
SB-9301-HL5021 000001 0001 O NCC SS-5701 X SS-2302-NF5003 32 C
SB-2302-HF5003 000001 0000 O FCR EV-5817 0 0001 0
.._ __ --- _ _ _ _.. - -. _~_ _ ___.__ _ _. _. - _.
~
m PSI Emeset SnsAmbee o f or-Syst em: 59 and (class 2 DATE: 16-NOV-US 15:57*44 PRGE1 13 ENAMINAT10NS HAssGER peUMSER SNeme $NSfee VT3 VT4 DMG AUG r m 8EENT NUMSER SHEET REV DS3 TVP AffJee DS4
~~
SS-2303-HF5005 313 C
SS-2303-HFSOO5 000001 0000 O 0001 0 SS-2350-NF5016 779 C
58-2350-HF5016 000001 0000 O FCR EJ-7244 O~
0001 O NCC SS-5666 X 000002 0001 0 SS-2401-ML5003 517 C
SS-9401->L5003 000001 0005 O FCR EJ-9229 MW_, _
000002 0005 0 f
SS-2401-ML5011 ese C
SS-9401-NLSO11 000001 0002 O FCR EJ-6325 U NCC 55-5696 I l
SS-2401-HL5012 594 C
.3-94C1-HL5012 000001 0002 O FCR EJ-6698 0 j
FCR EJ-8207 HW 000002 0002 0 SB-2401-HL5016 309 324 C
58-9401-HL5016 000001 0005 0 FCR EJ-6717 0 4
FCR EJ-8213 HW I
{
NCC SS-5641 X NCC SS-5652 X 000002 0005 O FCR TJ-6717 0 i
MCC SS-5588 X NCC SS-5641 I NCC SS-5652 X
)
SS-2401-+L5019 589 C
SS-9401-tL5019 000001 0003 0 l
000002 0003 0 SB-2401-NL5020 810 C
SS-9401-9L5020 000001 0002 O FCR EJ-4927 0 58-2401-HL5022 587 C
SD-9401->L5022 000001 0002 O FCN 2J-0694 0 I
NCC G-5018 M j
I FCR EJ-4775 0 000002 0002 O FCR EJ-4775 O SD-2401-ML5023 341 C
SS-9401-HL5023 000001 0001 0 j
SS-2402-NF5002 356 C
58-2402-HF5002 000001 0000 O 0001 HW l
S3-2402-NF50c4 518 C
SS-2402-NF5004 000001 0000 O FCR EV-5829 0 0001 HW NCC SS-5589 HW l
000002 0000 O FCR EY-5829 0 0001 N l
SB-2403-HF*,002 294 C
SB-2403-HF5002 000001 0000 O FCR EY-4939 0_
MCC SS-5721 X i
1 i
k 1
1 I
i
--mm-.-,-
.,m
.~m..--
- -. -.. - ~ _. -. - -
~
e, Y
l ps! Exempt snussemers ear-Systeen: 51 meias q_ class 2 DATE1 to-MOV-se 15157144 PAGE1 14 EaArtINATIONS HANGER paJPEDER SBWRe See8Ae VT3 VT4 Dres AUG m *IENT NUPGER S*EET PEV DS3 TVP AMENOS DS4 j
CI-2201-HL5010 ele 639 C
SI-9201-HL5010 000001 0005 O FCR EJ-5021 O FCR EJ-5313 0 FCR EJ-5495 O MCC 95-5632 HN CI-2205-HL5022 SO4 C
SI-9205-HL5022 000001 0002 0 0003 N CI-2206 6 326 C
SI-9206-HLSOO8 000001 0004 O FCR DJ-9095 0 0005 N CI-2206-ML5012 909 C
SI-9206-ML5012000001 0003 O i
Due 0000003 O NCC CS-5097 N
(
FCR EJ-3671 O FCR EJ-5433 O t
(
FCR EV-4%7 0 0004 N 000002 0004 N 23-2 7-SS0001 581 C
S1-9207-S50001 000001 0005 0 FCR DJ-1586 O NCC CS-%95 N NCC-SS-% 72 HC 0006 N NCC CS-%95 N MCC 55-5672 HC 000002 0005 0 FCR DJ-1586 O MCC G-%95 N i
0006 N NCC CS-%95 N l
NCC SS-%72 HC 000003 0006 N NCC CS-5695 N l
MCC SS-%72 HC l
SI-2301-SSOOO5 620 632 C
S1-9301-550005 000001 0006 O FCR DJ-1480 0 FCR EJ-5313 0 FCR EJ-5495 O FCR EJ-7103 O SI-2306-HL*012 464 C
SI-9306-HL5012 000001 0002 O MCO SS-%21 HN SI-2314-HL5007 636 C
SI-9314-HL500) 000001 0003 0 0004 N l
SI-2326-HLSOO1 491 C
SI-9326-HL5001 000001 0004 O FCN 2J-0780 N~
i 0005 N l
l 1
1
[Nw
[*g
/""t
%,/
l PSI EmermPt Snebers f or-Syst are: WL and at_c l ass 2 DATE: 16-NOV-DU 15:57:44 FAGE:
15 EI Ar11NA T IONS HANGER NUMBER SNSRS SNSFie VT3 VT4 DP1G AUG DCCur1ENT P4JMDER SHEET REV DS3 TYP Ar1E NDe DS4 WL-2OO9-SSOOO!
- A55 575 C
WL-9009-SSOOO1 000001 0006 D DCN 0000001 O NCC CS-5171 O 000002 0006 0 1
l l
i l
f I
PS3 Esempt snuheers f or-Syst em: CC and ag_c tees 3 DATER 16-NOV-es 15157144 PAGER 16 EEArt1 MAT 10NS HANGER NUP9hER SHEAG SNEFee VT3 VT4 DME AUG Tm"ENT NUMSER SDEET REV DS3 T W Art.nDe DG4 CC-2205-MLSOO7 623 636 C
CCM205-ML5007000001 0006 O FCR DJ-6933 O FCR DJ-8672 O FCR EJ-5463 O l
CC-2206-MLCOOe 532 C
CC-9206-MLSOOS 000001 0004 0 FCR DJ-7256 0 CC-2209-ML5002 302 C
CC-9209-ML5002000001 0003 O FCR EJ-7963 O CC-2209-6LSOO3 308 C
CC-9209-ML Aw3 000001 0002 O FCR'DJ-9401 0 CC-2210-tC5001 740 C
CC-9210-HL5001 000001 0002 0 CC-2215-SSOOO2 517 C
CC-9215-SSOOO2 000001 0002 O esCC 95-0259 X FCR DJ-S345 O FCR DJ-8515 O FCR EJ-4515 O CC-2220-SSOOO2 334 339 C
CC-9220-SSOOO2 000001 0007 0 FCR EJ-39eo O FCR EJ-7960 O 000002 0007 O FCR EJ-3990 0 i
I CC-2309-SSOOO2 545 C
CC-9309-SSOOO2 000001 0004 O FCR EJ-3299 O l
FCR EJ-3764 O j
CC-2309-SSOOO3 277 500 C
CC-9309-SSOOO3 000001 0007 O FCR EJ-3963 0 CC-2311-SSOOO1 506 C
CC-9311-SSOOO1 000001 0006 O FCR EJ-4590 O l
CC-23. N 1 432 C
CC-9320-HL5001 000001 0004 O FCR EJ-4696 0 l
FCR EJ-SO25 O 000002 0004 0 CC-2425-ML5016 439 C
CC-9425 6 16 000001 0002 O FCR DJ-1353 O_
i FCR EJ-7060 0 i
l l
2
PSI Emeurt twowheers fon-Syst em: FC and q. class 3 DATE: 86-es0V-es 13:37:44 PAGE: 17 EsantesATIONS MasseEst asunmEst summe Sesame VY3 VT4 anS Aug nnrieENT paJneEst sesEET ftEV DS3 TW anEsse DS4 FC-2009-SS0001 See C
F C-6-SS0003 000005 0005 0 ssCC DS-0230 0 FC3t DJ-9922 O FDt EJ-7205 O FC-2082-NL3002 321 C
FC-9012-NL5002 000001 0004 O FC8t EJ-7435 O FOR EJ-8241 O BEC psS-5732 MC l
6 7--.
o e
g e
tl 5
w l
"$t O
~
E Wl 6
I 6i
)
k y
ai a
A g
a 5: 11 8 !:l 5>
00l
\\\\
s h
O rr.-er w
F
+ _. + -
m
\\
[
('
j g
)
(
)
' /
Q)
PSI Emempt 1,rnAsters f or-Syst em: CC and q_ Class 7 DATE: 16-NOV-pu 15:57:44 FWX:
19 EsAMINATIONS HANGER NUr1190R fJGhe W Je VT3 VY4 DMG AUG IOCUP10NT MJMEsCR LHEET HEV DS3 TYP AMENDe DS4
~. _ __ - ---
CC-2136-NL*.A)O2 332 C
CC-9136-NLLOO2 000001 0004 O FCM DJ-8".XW O CC-2613-fSOOO3 322 C
CC-9613-SSouo3 000001 0u01 O FCR EJ-30 A O FCR EJ-5432 0
l i
l l
PSI Emempt w e for System: ED and sc 3 mse 7 DME: 16 h es 13*57:44 PaeE: 20 i
1 EsantesATIONS tenssent asuneet sugne m vf3 WY4 DME mus DocufE.NT paJnWUt SDEET SC# 953 TYP AMEsse 384 J
CD-2307-+eLSoss 739 c
ED-93or-estsoa s 000001 ooos o rcst DJ-ev23 o I
I h
l l
i.
m
,~
,-mx j
(
)
\\v'
'n./
PSI Emeyt Snubbers for System: MD and ag_c lass 7 DATE! 16-NOV-88 15:57:44 FAGE: 21 ERAMINATIONS HANGER NUPTUER LN'Jte LPGs VT3 VT4 DP1G AUG W FIENT Nur1 DER SHEET f<EV DS3 TYP APW_NDO DS4 MD-2147-w 3OO2 330 C
MD-2147-w ".,002 000001 OCX*O O MD-2140-w 3OO2 511 C
ttD-2148-HF.XsO2 000001 0000 0 I
PS1 Emeert Enha f or Systeens es and (class 7 DATES 16-8eDV-SE 15157144 PRGE1 22 Ex M19 EAT 10h5 etessGER pduMesER Steine SiNShe VT3 VT4 DreS AUG DOCUMENT NunesER SHEET REV
'_JS3 TYP APE 9eDe -
954 79S-2005-550001 M7 668 C
PIS-9005-SSOOO1 000001 00 4 0 FCR EJ-2549 O FCR EJ-3068 0 j
FCR EJ-7Es61 O 00000 0003 0 FCR EJ-m 9 O FCR EJ-3068 0 FCR EJ-7861 O MS-2OO5-SSOOO2 612 629 C
P9S-9005-S50002 000001 0002 O FCR EJ-7777 O 000002 0002 O FCR EJ-7777 O MS-2OO6-SSOOO1 631 632 C
79S-9006-S50001 000001 0003 0 FCR EJ-7857 0 000002 0003 O FCR EJ-7857 O MS-2OO6-SSOOO2 641 652 C
P95-9006-S50002 000001 0002 O FCR EJ-7616 0 000002 0002 O FCR EJ-7616 O MS-2OO7-SSOOO2 638 640 C
MS-9007-SSOOO2 000001 0003 O FCR t"J-3156 0 FCR EJ-7424 0 FCR EJ-7905 0 000002 0003 O FCR EJ-7905 O 000003 0003 0 FCR EJ-31",6 0 FCR-EJ-7424 O MS-2OOS44L5001 654 C
PIS-9000-HL5001 000001 0003 0 MS-2OOe-SSOOO1 639 650 C
795-9008-550001 000001 0003 O FCR EJ-7440 0 FCR EJ-7441 O 000002 0003 0 FCR EJ-7443 0 FCR EJ-7441 O 000003 0003 t.1 FCR EJ-7440 0 FCR EJ-7441 O 99S-2013-64_5002 611 622 C
MS-9013-HLSOO2 000001 0000 O FCR EJ-6471 O FCR EJ-7442 O 000002 0000 O FCR EJ-6471 O FCR EJ-7442 O 000003 0000 0 FCR EJ-6471 O 79S-2013-NL*,003 674 C
MS-9013-HL5003 000U01 0000 0 MS-2013-HL5004 M2 C
PTS 4013-HL5004 000001 0000 O FCR EJ-d.982 O l
pts-2013-SSOOO2 658 643 C
MS-9013-SSOOO2 000001 0004 0 000002 0004 0 000003 0004 0 i
l
t 6
lO om "l$3 6e l
tI av l
El
!ii a
,I
).
P.
l
- 8 E
i 3
3g Il o
i 5 :ll t 1:i i
3
00l
.i b
R n
lI ),
O
' l6t
i i
1
)
}
ess E ce amm6er. ver sr.e 1 esc am sci 7
anrE: 16-mow-se 1s:37:44 Feat: 24
+
'l EEAR19e471(psE l
seemsswat seJMc De m Susene VT3 VT4 age aus m.ENTsdUReER SBEET aCV DE3 TVP deEsse 964
~
l i
fsC-2014-te 5001 653 C
- sC-9014-ML5001000001 0003 FCat EJ-7465 O 000002 0003 FCft EJ-7465 0 ftC-2014-*4.3003 372 373 C
- sC-9014-ML5003000001 0004 FCat EJ-3793 0 i
000002 0004 FCat EJ-3793 0 j
f:C-2014-+eLS003 374 376 C
puC-9014-ML5005000001 0006 FC3t EJ-6293 e i
i i
FCft EJ-7236 0 FCat EJ-8254 ted
}
000002 0006 FCst EJ-6293 0 l
FCst EJ-7236 O l
FDt EJ-92SS tes aC-2014-.a.5006
- e6 es5 C
aC-90:4-+eLSOO6 000001 0003 FCR EJ 336 0 j
j FCft EJ-5631 0 Fr1t EJ-7703 I
~
j 000002 W 3 FCst EJ-3336 0 j
FCat EJ-7703 I l
- 3 0003 1
MC-2014*4eLS009 618 C
fuC-9014-94 5009 000001 0001 l
aC-2014-*eLS012 370 573 C
puC-9014-$e.5012 000001 0002 FCfr EJ-6376 0 000002 0002 FCst EJ-6376 O l
MC-2014-ea.SO13 eos C
aC-9014-945013 000001 0002 i
mC-2014-ea.5013 397 C
mC-9014-SeLSO13 000001 0003 FCit EJ-5727 O
}
000002 0003 j
aC-2014-+eL5019 S69 371 C
RC-9014-eeLSO19 000001 0003 FCR EJ-4See O_
i seCC ss-350s se i
000002 00u3 FDt EJ-esos O
'l esc-2014-ML5026 426 C
psC-9015-teL5026 000001 0002 FDt EJ-e261 ted 8sC-2014-+eL5028 401 C
ftC-9014-SeLSO25 00000; 0004 FCft EJ-SASO O 000002 0004 FCat EJ-SS50 O i
4 1
4 ii i
l i
I i
I
7 O
O.
l PSI Essesmet Erhetsers f or Syst eren* $8 and (class 7 DATE1 16-NDV 98 15*57144 PAFE1 25 ENARIN4TIONS HessGER teJMMA
$N58ee SN5ese VT3 vf 4 Dour, Aug tsirtsqENT NUMWER SHEET REV DS3 TVP AMEMOe DS4
=
SS-2104-+4 5001 823 C
SS-9104-HLSUO1 000001 0001 O FCR EJ-4513 O SS-2104-HL5002 385 C
SS-9104-HLLOO2 000001 0002 0 bS-2104-94L5006 393 C
$8-9104-ML5006000001 0001 O FCR EJ-4525 O SS-2105-+4LSOO 1 591 C
SS-9105-ML5001000001 0001 0 SS-2107-*tF5001 758 C
SS-2107-Hr5001 000001 0000 O FCR EV-3037 O SS-2174-ee 5015 579 SOS C
SS-9174-ML5015000001 0002 O FCR EJ-4367 O SS-2204-$eL5001 615 C
SS-9204-ML5001000001 0002 O FCR EJ-2055 O SS-2204-ML5002 822 C
SS-9204-+4L5002 000001 0001 O FCR EJ-7914 O SS-2205-ML5003 297 C
SS-9205-SeL5003 000001 0001 O FCN 2J-0640 0 FCC DJ-8172 N SS-2207-+tF5001 769 C
SS-2207-HF5001 000001 0000 O SS-2274-ML5002306320 C
SS-9274--ML5002000001 0005 0 SS-2274-NL5016 318 347 C
SS-9274-ML5016000001 0002 O FCR EJ-5522 O
~
88-2304-+4 5001 514 C
SS-9304-ML5001000001 0001 O FCR EJ-4694 O
]
SS-2304-MLSOO2 591 C
SS-9304-HL5002 000001 0001 0 SS-2304-+e.5006 336 C
SS-9304-HL5006 000001 0001 O FCN 2J-0642 O FCs1 2J-6426 0 j
SS-2274-NL5014 924 E23 C
SS-9374-HL5014 000001 0002 O FCR EJ-5523 O SS-2404-+4L5001 528 C
SS-9404-HLSOO3 000001 0001 O
[
SS-2404-ML5002 313 C
SS-9404-NL5002 000001 0001 0 l
SS-2406-HL'V>07 753 C
SS-9406-NL/>O7 000001 0001 0 i
CB-2407-*tF5001 737 C
SS-2407-HF 5001 000001 0000 0 I
SS-2474-HL?AM)2 327 C
SS-9474-NL5002 (410001 0002 O FCN 2J-0648 0 l
l SS-2474-HLSO13 stb S2O C
SS-9474-HL5013 000001 0002 0 t
1 l
4
,l J
,J I
l
.s-u m
4
+
I i
PSI Emenset snestnesoro f or Syst em: esL and tctees 7 DATE: 16-MOV-SII 13:37:44 rwE: 26 f
EndetstemTIOess 4
1
.empseEm ammesEst asselte assene VT3 VY4 DME muG m=EteT suungsER St(EY REV I43 TVP AWEfee 954
)
1 20,,- -.
m c
-20,- =.
COOoo. <-- o FC.t.V-326.c FCR EV-4639 O FCR EV-7024 O FCft EV-St&2 GC 0001 M 000002 0001 N j
a I
i l
4
~
l i
I 1
i i
I l
4 l
s l
,_...--m
... _ _.... _ m.
,m.. t.
"I h
,s PSI Emerart Snubberm for Systess: FW and q_ class 8 DATE: 16-NOV-OS 15:57:44 FAGE:
27-EVArilta: M penserR NUP9ER SMSRG SMSRS VT3 VT4 Def. AUG DOCue1 EFT NUPIBER SEET REV DS3 TYP AMENDO DS4 -
FW-2150-HL5011 437 C
FW-2150-HL5011 40001 0000 0 FW-2151 6 12 525 C
FW-2151-HL5012 000001 0000 0 FN-2152-MLTC14 524 C
FW-2152-HL5014 000001 0000 0 i
t 1i i
r 1
~~
{-
7 l
i 1
3 l
i i
b 4
E f
s I
l 1,
-,~--e---
<-,--,---..n,--,,..
- -, - - - - - - - -. - ~ = - - -
-~m
-,,-,w,rwwn,-mnne--e-,n.,
r--.wv.
r
-ww-m
e sh 50.
^
t.
--Q-I I*
. T 4
PS3 Essept sneAnaner, w Systeen: HD and st_ class 8 DATE: 16-NOV-98 13:37:44 PAGE: 28 XArtINATIONS j
HANGER paJMSER SadE#it 94-AG VT3 VT4 DMG AUG DOCUMENT NunBER SHEET REV DS3 TYP APEpee DS4
)
HD-2731-MLSOO6 "t01 C
HD-9131-HL5006 000001 0000 0 t
5
{
L i
1 4
1 1
I s
I i
t PSI Emeert Sneebers for-Systeen: PtD and q_ class 9 DATE: 16-NOV-88 15:57:44 PAGE: 29 EXArtINATIONS VT3 VT4 DOCUMENT NUMEsER SHEET REV DS3 TYP AMENOS DS4
_ _ -DMG AUG reassGEst MUMBER N G SNbHG Mp-2149-tF5002 609 C
MD-2149-HF"M 2 000003 0000 0 IW-2150-te'5002 597 C
PtD-21".h-HF"A)O2 OOOC.
0000 0 4
I i
8:
1 t
l APPENDIX H NIS 1 FORMS i
i l
l i
t
(
1 L
I S3/E048/rr j
t
FORM NIS 1 OhNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
/h (v)
- 1. Owner ikmstm Listhtirm & Peer Ccuserry. P.O.__Bcut 1700. Housin_ Texas _.22001 (Name and Address of Owner) 2, Plant _ South Texas Proia t Electric Gemratijg_ Statim. P.O._Bga'308. Bev city. Ts===
7741/c ta (Name and Address of Plant)
- 3. Plant Unit 2
- 4. Owner Certificate of Authorization (if required)
N.A.
- 5. Commercial Service Date N.A.
- 6. National Board Number for Unit M.A.
- 7. Components Inspected Supports for A9E Code Class 1 Item Listal Below Manufacturer Component or Manufacturer or installer National Appurtenance or Installer Serial No.
Board No.
Stem Gmerator A
h:t f Mn w (M) 71%1
?Q Stem Gmerator B
Mutinsdumm (M) 2152 10 Ste2sn Gmcrator C
Entirvinm (M) 2153 31 Stean Cmcrator D
Mmtitulum (M) 21 %
32 Premirizer Hwtf ryduxw (M) 2161 19 Ih etor Cool mt 1080-l\\ g A Mwtf rvjum (M)
Il63E?fC01-14 N.A.
q)
Reactor Cou ant.
1081-l
}\\w B Mutirwinm (M) ll63F2f001-14 N.A.
Feu: tor Coolmt 1082-hwC Wstirshxm (M) ll63E2f/BI-14 N A.
Reactor Coolant 1083-hwD Wstirrinew (M) ll63E2fm l-14 N.A.
Clam 1 Pipiry Phrro(1)
N.A.
N.A.
Note: Supplemental sheets in form of bits, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in.,
(2)information in items I through 6 on this report is included on each sheet,and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
(12/86)
This Form It00029) may tie et,te ned from the Order Dept A5ME,3a5 E. 47th St., New York, N.Y.10017
FORM NIS 1 (Eack)
- 8. Examination Dates 1-24 to 11-1R-RR
- 9. Inspection Interval from to - ISI
- 10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval. See Sectim 6.0 of n==ry Report for Class 1, Class 2 and Cims 3 Qud Sapports II. Abstract of Conditions Noted See Sectim 7.0 cf %==ry Report for Class 1, Clcss 2 ard Class 3 Crapcoent SLpports
- 12. Abstract of Corrective Measures Recommended and Taken See Sectico 7.0 of Sumery Ikport for Class 1, Class 2 and Class 3 r gxnot Sqports a
We certify that the statements made in this report are correct and the examinations and conective mes-sures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authoriaation No. (if applicable)
N.A.
Expiration Date N.A.
Date 2 M Jo 19 Ab Signed Ibustm 14chtire & M. r_ By $.
m $a
/n I/, duf p
f)
Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of T=
and employed by in=4=nw.r.s Mut. Cas. CL of f r= f'rmt' 111-h ve inspected the components described in this Owner's Report during the period 1-24-88 II-M to
, and state that to the best of my knowledge and belief,the Owner has performed examinations and taken conective measures described in this Owner's Rr. It in accordance with the inspection plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any wananty, expressed or implied, concerning the examinations and conective treasures described in this Owner's Report. Furthermore, neither the Inspector not his employer shall be liable in any manner for any personalinjury or property damage or a loss of any kind arising from or connes ed with this inspection.
B.R. Russell '
X h Vt m / /( ' Commissions TgrasJ26 Inspector's Signature National Board, State, Province, and Endorsements Date
//b 3 d
19 <
(12/s2)
O
FORM NIS 1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions af the ASME Code Rules
/
i
- 1. Owner _ Houstm Lightirut & Power Ccuperry. P.O._Bqa !?00. Bomitsi. Tczas 77001 V
(Name s'id Address of Owner)
- 2. Plant South Texas Project Electric Cerieratirut Statim..P.O. Boa'308. Bev Ci%_T-= 77414 --
(Name and Addres;of Plant)
- 3. Plant Unit 2
- 4. Owner certificate of Authorization (if required)
NJL
- 5. Commercial Service Date N.A.
- 6. National Board Number for Unit NJL
- 7. Components inspected Sp for MPE Class 2 Itms Listed Belcw Manufacturer Component or Manufacturer or Installer National Appurtenance or installer Serial No.
Board No.
Ikypierative Ikat Fxhrwr Josetii Nt Corp. (M) 23RO-1B 2052 16R llcat Fxch1:wr 2A JostTh Ont Corp. (M)
?312-41) 993 letdown innat Fxh1rwr Jorush Ont Corp. (M) 2312-1B 987 Excess letdown ik'at Fxhlrwr Aux 4h N t Corp. (M) 2312-3B 989 Rex tor Coolant Filter 2A Bus! Trinity Micro Corp. (M) 5Fil-Sil9 M 19 % 1 Seal Water In). Filter 2A Paul Trinity rifero Corp. (M)
SF%- S1209-1 19022 p)
\\
Ibisaticsi Duquier Ainvrw Cmtrols (M)
M0440 178 Cmtairausit Spray heti 2C Pacific Baran (M) 51712 4%
RlR Bumi 2A Pacific Brr w (M) 51734 363 1861 Renn 2A Facific Rartw (H) 51698 400 IJEI bro 2A Pacific linos (M) 5170's 4D Class 2 Pipire Fhinco (T)
N.A.
N.A.
Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provid:d (1) site is 8% in. x !I in.,
(2) Information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
O (12/86)
This Form (E00029) may tie obts ned from the Order Dept., ASME. 345 E. 47th St< Nea York. N.Y.10017
FORM NIS 1 (Back) 11-18-88
- 9. Inspection Interval from to ISI
- 8. Examination Dates - I-24 to
- 10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for cunent interval. See Sectia) 6.0 of 4==ry Report for Class 1 Class 2 ard Class 3 nw t Sugxxts
- 11. Abstract of Conditions Noted See Sectiat 7.0 of Stamurry Report for Class 1. Class 2 ard Clas 3 Campment Steparts
- 12. Abstract of Corrective Measures Recommended and Taken Sm Sectia) 7.0 of Sumery kport for Class 1, clam 2 and Clam 3 Ccupcrumt Sq5erts We certify that the statements made in this report are conect and the examinations and conective mea +
sures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
H.A.
Expiration Date N.A.
M I. do Jd 19 88 Signed Jbugtrm 14ohtfrw & Rwr By
.u a
Date anu owner ~
/
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a vabd commission issued by the National Board of Boiler and Pressure VesselInspectors and the State or Province of Tim and empoyed by fi=4crums Hut. Cas. Co.
of imo CrIp T11-have inspected the coinponents described in this Owner's Report during the period 1-24-88 II-IM to
, and state that to the best of my knowledge and behef, the Owner has performed examinations and taken conective measures described in this Owner's Report in accordance with the inspection plan and as requi. red by the ASME Code,Section XI.
By signing this certificate neither the Inspector not his employer makes any wananty, expressed or implied, concerning the examinations and conective measures desenbed in this Owner's Report. Furthermore, neither the kind arising from or connec(tep with this inspection. Inspector nor his employe shall be liable in B.R. Ihrell
/
m it eMC - Commissions Tt:strLB26 Inspector's Signature National Board, State, Province, and Endorsements Date
// ~
'0 ' --
19 /1 ' '
(12/82)
O
FORM NIS 1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions af the ASME Code Rules 1
{%
l tL}
- 1. Owner _ Ibustcm 1.isdatism & Power Casemr. P.O._Bru 1700. 5Lr==tm. h 77001 (Name and Address of Owner)
- 2. Plant South Texas Project FJectric GeneratirgJtatim. P.O. Bam* 3E. Bev City. 'D=== 77414__
(Name and Addreas of Plant) l
(
- 3. Plant Unit 2
- 4. Owner Certificate of Authorization (if required)
NJL
- 5. Commercial Service Date W.A.
- 6. National Board Number for Unit MJL
- 7. Components inspected A9E Class 3 ]teus (Euwt I d 2)
Manufacturer Component or Manufacturer or Installer National Appurtenance or Installer Serial No.
Board No.
IWt 155xnn of t Aux. Finidater L\\mp Hn. 23 Birudvus Wil11amettc (b. (M) 1A140 W 675 GM Sury Ta* 2A lircho-Mirwapolis Tara (M) 464702B N.A.
[IN that Puhuwr 2A Struthern Wils Corp. (M) 1-7tM6-32%1-1
_y542
[IN Rap 2A ILmsm! Tyler Rav Co. (M) 804101 7
BC Purificatirn
(]
Rap 2A Callos Rmun Inc. (M)
N247BD79 367 V
letdam Filter 2A Rul Trinity Micro Corp. (M) 5FH-F9073-3 17444 Hinxi Bed limircralizer 2A Ewtfrufmr (M) 428/O W18544 Catirn ikxi Ihmirrralizer 2A Entirstme (M) 42838 W18542 IU Rel Oil Storarp Tark W.21 Brom-Mirwapolis Tm* (M)
Il53-01A N.A.
LU Aux.
Skid m. 21 Corter Drrry Servicm (M) 8I0101 N.A.
10 Startirg Air Rmelwr m. 21 Cruxer Berry Servicen (M)
BD'Al 10'A IE Startirg Air Rmelwr m. 22 Crrter Frrrgy Servicrn (M) fttt%01 1049 lDI Rap 2A ttmsmi Tyler Rao Co. (M) litWol 100 lim hap 2A Self-Cleantry. Strairrr Zurn Iruhwitrien Inc. (M) 75A8 N.A.
FDi Scnum Medi nonster Bue 2A Inmsin! Tyler Rap On. (M) 813301 144 Note: Supplemental sheets in forre > ; iists, sketches, or drawings may be used, provided (1) site is 8% in. x 11 in.,
(2)information in items I thrown 6 on this report isincluded on each sheet,and (3) each sheet is numbered and the number of sheets is recorde' at the top of this form.
\\
(12/86)
This Form tt00029) may be obtemed from the Order Dept.. ASMt. 345 E. 47th St., New York. N.Y.10017 l
FORM NIS.I (Back) ll-lM
- 8. Examination Dates 2W to
- 9. Inspection Interval from to PS'I O
- 10. Abstract of Examinations, include a list of examinations and a statement concerning status of work required for cunent interval. See Sectim 6.0 of n==my Report for Class 1 Class 2 ard Class 3
%=:ui Sqparts
- 11. Abstract of Conditions Noted See Sectim 7.0 of Sammary Report im d= 1, Class 2 and Class 3
% s t Sq parts
- 12. Abstract of Conective Measures Recommended and Taken See Sectim 7.0 of Smenry Report for Clami 1, dm 2 and d-3 Ctapxumt Sq9erts We certify that the statements made in this report are conect and the examinations and corrective mes-eures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
N.A.
Expiration Date N.A.
Date
+rM Jo 19 M Signed Ihwerm i4=htino & R-r_ By k I
( *ts M2. demtd
.o owner' Q
[ (j h
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure VesselInspectors and the State or Prodnce of h
and employed by I'd=mns thit. Cao Co.
of f e= t'rv=
fil -
have ins ected the components described in this Owner's Report during the period 1-24-88 II-I to
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken conective measures described in this Owner's Report in accordance with the inspection plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and conective measures described in this Owner's Report. Furthermore, neither the Inspector not his employer shall be liable in any manner for any personalinjury or property damage or a loss of any kind arising from or conne ted with this inspection.
B.R. Ih-11 k f - ~ <
(. -
Commissions TczaqJ26 Inspector's Signature National Board, State, Province, and Endorsements Date
- /- 8'-
19 b t12/82)
O
FORM NIS 1 OWNER'S REPORT FOR INSERYlCE INSPECT 10NS As required by the Provialons of the ASME Code Rules O's]
- 1. Owner Bxstm I.iJthtira & Fwer_rm. P.O. Em 1*AD. Sir==tm. h 77G)1 (Name and Address of Owner)
- 2. Plans S -eth Texas Project Electric Generatira Station. P.O..Da 308. Bev citv. h 77414 -
(Name and Addreas of Plant)
- 3. Plant Unit 2
- 4. Owner Certificate of Authorization (if required)
N.A.
- 5. Cornrr.erelal Service Date NA
- 6. National Board Number for Unit BA
- 7. Cor.sponents inspected A9E Code C1maa 3 Items (9 met 2 cf 2)
Manufacruter Component or Manufacturer or installer National Appurtenance or installer Serial No.
Board No.
kcactor W Jp Wtr. Stor. 'thk.2A Brrac-Mimmpolin Tma (M) llG106 N.A.
Clans 3 Pipim lhwrn (I)
N.A.
N.A.
Integral Attaduunts of t M 1h3at Fadvu w r 2A Struttern M'lla Corp. (M) 1-76-06-32941-1 14542 W Surgp TmA 2A Bnwn Mirvragolin Ta* (M) 464702B N.A.
Catir:1 Bai Ibnircralizer 2A Estirdrue (M) 4'E38 W18542 Ictdown Filter 2A Rul Trinity Micm Corp. (M) 91}-PX)73-3 17444 Hizal Bed limirrralizer 2A untirstuur (M) 428/4 W18544 W Startire Air Remiwr M3. 21 Cmper lirrgy Servicm (M)
EKO'Ol 1050 W Startirg Air Hrreiwr M). 22 CrxTer nrryy Servicrn (M) ft1%01 1(%9 W hel Oil Stor:w TmA Mi.21 Brue-Miruvarnlin Tmk (M)
Il 53-OlA N.A.
W Am.
fkid N3. 21 Corwr Pirruv Servicm (M) 81D101 N.A.
FW lino 2A ILrywrd Tyler Rep Co. (M)
IKXV)]
100 FW l\\np 2A Self-Clestire Strairer hirn Irutritrim Ire. (M) 7588 N.A.
HIR thut Fadvewr 2A Jcrn h Ont Corp. (M) 2312-4D 993 Clann 3 Pipire Fhern (I)
N.A.
N.A.
Note: Supplemental sheetsin form of hsts, sketches, or drawings may be used, provided (1) site is 8H in. x 11 in.,
(2)information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
(
112/86)
This Form (Er0029) may to ot>te.ned from the Ordet Dept., A5ME,345 E. 47th St.. Neve York, N.Y.10017
c FORM NIS 1 (Back)
- 8. Examination Dates 1-24-88 to 11-18-88
- 9. Inspection Interval from to PSI
- 10. Abstract of Examinations, include a list of examinations and a statement concerning status of work required for cunent interval. See Sectim 6.0 of n==ary Report for Class 1, Class 2 and Oman 3 Ccupmmt Si49 arts
- 11. Abstract of Conditions Noted See Sectim 7.0 of L-nary Report for daaa 1, d== 2 and Class 3 L W S ports 4
- 12. Abstract of Conective Measures Recommended and Taken See Sectim 7.0 of Sumnary Report for Class 1, umaa 2 and Class 3 rapment Sipports We certify that the statements made in this report are correct and the examinations and corrective mes-sures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorisation No. (if applicable)
N.A.
Expiration Date N.A.
Signed Ikxmtre f iohtine I. h= r By (}b d Date Id 19 Ab d 2 4.. b d ua Ow ner'
() }
t CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Bouer and Pressure VesselInspectors and the State or Province of T=a and employed by I'd s M. Cas. Co.
of fr= h, 111-have inspected the components described in this Owner's Report durir2 the period 1-2Tr-88 to 11-18-88
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken conective measures described in this Owner's Report in accordance with the inspection plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector not his employer makes any wananty, expressed or implied, conceming the examinations and conective measures described in this Owner's Report. Furthermore, neither the Inspector not his employer shall be liable in any manner for any personalinjury or property damage or a loss of any kind arising from or conne ted with this inspection.
B.R. Russe _Il M r-/ t IC Aommissions Tc @
Inspector's Signature National Bostd, State, Province, and Endorsements Date U - Y / "'
19, ' h #'
7 (12/s2)