d COVER SHEET 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION, UNIT 2 P. O. Box 289 Wadsworth, Texas - 77483 P
USNRC DOCKET NO.: 50-499 OPERATING LICENSE NO.: NPF-80 COMMERCIAL OPERATION DATE: June 19,1989 Prepared by:
g;/M4 b 2u-oy ATP. Piithak Consulting Engineer Reviewed by:
f d b v.- Or C L-., rig 6-7f -W S. Timthbraju Sr. Consulting Engineer Approved by: I-8
'/
f M.'D. 61eier Manager - engineering Programs Division 1
9409070107 890619 PDR-ADOCK 05000499 O
~ SOUTH TEXAS PP.OJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPNS NOJ (IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2 91-085 FW-110635 B2FWFV7145A VALTEK VALVE REPLACED PLUG B. RUSSELL 7/12/94 SN: 34752-14 TX-826 2 91-105 S1116538 N2SIFV3960 AMETEK VALVE REPLACED VALVE, PIPE B. RUSSELL 8/11/94 SN: 51-35-48 AND ELBOW TX-826 2-91-131 CV-152993 2R172TCV0251A ROCKWELL VALVE REPLACED VALVE B. RUSSELL 6/14/94 SN: CB-117 TX.-826 2-91-141 AP-11164 2 C2APR/2458 TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/19/94 SN: 6 TX-8 26 2-92-003 SG-160104 1R122NSG201D WESTINGHOUSE STEAM GENERATOR REPLACED HANDHOLE B. RUSSELL 6/14/94 SN: 2154 COVER TX-826 NB: 32 2-92-022 SB-164211 A2SBFV4187A TARGET ROCK VALVE REPLACED VALVE B. RUSSELL 7/12/94' SN: 18 AND FLANGE TX-826 2-92-031 SB-164492 2S202TSB0338 KEROTEST VALVE REPLACED VALVE, PIPE B. RUSSELL 6/14/94 SN: ALQ1-27 AND ELBOW TX-826 2-92-034 SB-80795 A2SBFV4187A TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/18/94 SN: 12 TX-826 2-92-045 CV-175638 1R172TCV00368 BORG WARNER VALVE REPLACED SEAL VELD B. RUSSELL 8/9/94 SN: 48097 TX-826 2-92-047 CV-175642 1R172TCV00378 BORG WARNER VALVE REPLACED SEAL WELD B. RUSSELL 7/19/94 SN: 48094 TX-826 Pagel'
- - ~
.~
_m SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM ITPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DisSCRIPTION AMI DATE 2 92-057 CV-175645 2R172XCV0639 ROCKWELL VALVE REPLACED VALVE.
B. RUSSELL 7/12/94 SN: CD-866 REPLACED SEAL WELD TX-826 2 92 060 RC-166691 A2RCPCV0655A GARRETT VALVE REPLACED PLUG AND B. RUSSELL 7/12/94 SN: P-140 BONNET NUTS TX-826 2-92-084 CC-176204 2R202TCC0138 TRW MISSION VALVE REPLACED VALVE B. RUSSELL 6/14/94 SN: S-2308 TX-826 2-92-089 AF-148374 2S132TAF0308 ANCHOR DARLING VALVE DRILLED AND TAPPED HOLES B. RUSSELL 8/11/94 SN: E3326-751 ON THE HINGE COVER FLANGE TX-826 2-92-095 SG-154855 1R122NSG201D WESTINGHOUSE STEAM GENERATOR REPAIRED STEAM CUTS B. RUSSELL 6/14/94 SN: 2154 ON HANDHOLE COVER TX-826 NB: 32 2-92-100 RC 91092 N2RCPCV0655C FISHER VALVE REf LACED BALL B. RUSSELL 7/12/94 SN: 6449026 TX-286 NB:5094 2 92-109 PS-110334 82PSFV4450 TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/27/94 f,N: 6 TX-826 2-92-110 MS-147602 A2MSPV7411 CONTROL COMPONENTS VALVE REPLACED VALVE PLUG B. RUSSELL 8/11/94 SN: 352001-1 TX-826 2-92-115 CV-118252 2R172TCV0007 EDWARD VALVE REPLACED VALVE B. RUSSELL 7/19/94 SN: 49AFJ TX-826 2-92 123 S1-89987 2N122TS10120B ANDERSON-GREENWOOD VALVE.
REPLACED SEAL WELD B. RUSSELL 7/12/34 SN: A3873 AND DISC TX-826 Page 2
~
t F
t SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R
. COMP.
NO.
NO.
ITEM (TPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2 92-129 RC-111501-EP02 1R142TRC0132 EDWARD VALVE REPLACED VALVE B. RUSSELL 6/29/94 SN: 40AEN TX-826 2-92-136 RC-146307 N2RCPCV06558 FISHER VALVE REPLACED BALL B. RUSSELL 7/19/94 SN: 6449025 TX-826 2 92-138 St-116620 2N122TS10142 KEROTEST VALVE REPLACED VALVE B. RUSSELL 6/29/94 SN: ARA 1-25 TX 826 2-93-002
' RC-111501-EP01 N/A N/A REACTOR HEAD VENT REPLACED BOLTS B. RUSSELL 6/29/94 GUIDE TX-826 2-93 018 AF-178281 2S132TAF0308 ANCHOR DARLING VALVE REPLACED HINGE pin COVER, B. RUSSELL 8/11/94 SN: E3326-75-1 STUDS AND NUTS. REPLACED TX-826 BONNET AND GASKET RETAINER. REPAIRED HINGE PIN COVER SEATING SURFACE
-2 93-019 CV-178455 2R172TCV02368 ANDERSON. GREEN-VALVE REPLACED VALVE B. RUSSELL 7/27/94 WOOD TX-826 SN: A3887 2 93-027 FW-148147 FW-2052 E SOUTHWEST FAB.
PIPtNG SPOOLS REPLACED ORIFICE PLATE, B. RUSSELL 8/11/94 FW-2052-D SN:38884 FLANGE FASTENERS AND TX-826 SN: 38883 REPAIRED FLANGES 2-93 034 MT-155736 B2MTFV7903A TARGET ROCK VALVE REPLACED SEAL WELG B. RUSSELL 7/27/94 SN: 8 AND DLiC TX-82 6 2-93 035 MT-155737 82MTFV7902A TARGET ROCK VALVE REPLACED SEAL WELD
- 8. RUSSELL 7/27/94 SN: 7 AND DISC TX-826 Page 3 i
,..s
i SOUTH TEXAS PROJECT UNIT - 2 j
^
l ASME CODE SECTION - XI l
2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF
- MFG..SN AND N8 ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2-93-036 MT-155738 A2MTFV7901 A TARGET ROCK.
VALVE REPLACED SEAL WELD -
B. RUSSELL 7/19/94 SN: 6 AND DISC TX-826 2-93-037 MT-155739 A2MTFV7900A TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/27/94 l
SN: 5 AND DISC TX-826 2-93-057 AP-172321 C2APFV2457 TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/19/94 SN: 24 AND BONNET T0826 2-93-059 SG-157321 1R122NSG201A WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS
- 8. RUSSELL 7/12/94 SN: 2151 TX-826 NB: 29 2-93-060 SG 57322 1R122NSG201B WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS
- 8. RUSSELL 7/12/94 SN: 2152 TX-826 NB: 80 2-93-061 SG-157323 1R122NSG201C WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS
- 8. RUSSELL 7/12/94 SN: 2153 TX-826 NB: 31 L
2-93-062 SG 157324 1R122NSG201D WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS B. RUSSELL 7/12/94 SN: 2154 TX-826 NB: 32 2-93-074 RC-165963 1R142TRC0058A KEROTEST VALVE REPLACED DISC B. i3SSELL 8/9/94 SN: CAB 13-20 TX-b 26 i
2 93-077 RC-165963 1R142TRC0057C KEROTEST VALVE REPLACED DISC B. RUSSELL 8/9/94 SN: CAQ13-20 TX-826 Page 4 m
a
.r--
a-----w
-.-.-s--.+-
,.-v r
-. +. -
w ww.
4 SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS
. (CI. ASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
No.
ITEM ITPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANf!
DATE 2 93-079 FW-179739 2S132TFWO222 KEROTEST VALVE REPLACED DISC B. RUSSELL 7/19i94 SN: ZN4-16 TX-826 2-93 088 SG-176314 1R122NSG2018 WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS.
B. RUSSELL 8/9/94 SN: 2152 REWORKED / REPAIRED TX-826 NB: 30 PADS AND COVERS.
REWORKED WRAPPER PLUG AND WRAPPER PLUG SLEEVE THREADS.
2 93-089 SG-176313 1R122NSG201A WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS
- 8. RUSSELL 8/11/94 -
SN:2151 AND REPAIRED HELICOIL TX-826 NB: 29 HOLES AND INSTALLED HELICOIL REWORKED PORT PADS.
REWORKED WRAPPER PLUG AND WRAPPER PLUG SLEEVE THREADS.
2-93-090 SG-176315 1R122NSG201C WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS B. RUSSELL 8/11/94 SN:2153 AND REPAIRED HELIColl TX-826 NB: 31 HOLES AND INSTALLED HELICOIL. REWORKED PADS AND COVERS. REWORKED WRAPPER PLUG AND WRAPPER PLUG SLEEVE THEARDS. REPAIRED BOLT THREADED INSERT.
Page 5
~
~
4
^
SOUTH TEXAS PROJECT UNIT - 2
- ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG.,SN AND NB ITEM / COMP R OR R COMP.
4 NO.
NO.
ITEM ITPNS NOJ OF ANY) OF COMP.
DESCRIPTION DESCR!PTION ANil DATE 2 93-091 SG-176316 1R122NSG2010 WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS AND B. RUSSELL 8/9/94 SN: 2154 REPAIRED HELtCOtt HOLES TX-826 NB: 32 AND INSTALLED HELICOtLS.
p RWORKED PORT PADS.
PLUG AND WRAPPER PLUG SLEEVE THREADS.
2-93'093 CV-168242 1R172TCV0038C KEROTEST VAL'K REPLACED VALVE AND B. RUSSELL 7/27/94 1R172TCV0595C SN: ARA 1-11 PIPING ON SPOOL TX-826 SN: ARA 1-12 CV-2126-C-A2 2-93-095 CV-188973 A2CVHCV0206 TARGET ROCK VALVE REPLACED SEAL WELD B. RUSSELL 7/19/94 SN: 52 TX-826 NU:686 2-93-096 CV-168247 1R172TCV0038A KEROTEST VALVE REPLACED VALVES AND B. RUSSELL 7/19/94 1R172TCV0595A SN: ARA 1-22 P! PING ON SPOOL TX-826 SN: ARA 1-24 CV-2122-C-A 2 2-93-101 CV-168241 1R172TCV0038D KEROTEST VALVE REPLACED VALVES AND B. RUSSELL 7/19/94 1R172TCV0595D SN: ARA 1-23 PIPING ON SPOOL TX-826 i
SN: ARA 1-34 CV-2128-C-A2 2-93-104 CV-175031 2R172XCV0003 WESTINGHOUSE VALVE REWORKED VALVE.
8 RUSSELL 8/9/94 SN: W750004 REPLACED VALVE STEM TX-826
- NB: W20112 i
2-93-105 CV-165774 A2CVFCV0205 COPES-VALCAN VALVE REPLACED PLUG B. RUSSELL 8/9/94 i
i SN: 76209540092 TX 826 NB: 1675 t
i Page 6 4-rw
SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE 'NSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG. SN AND NB ITEM / COMP R OR R COMP.
3 NO-ITEM (TPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2-93-107 CV-171211 N2CVPCV0135 COPES VULCAN VALVE REPLACED PLUG B. RUSSELL 7/12/94 SN:7620-95400 7-2 TX-826 NB:1641 2-93 111 MS-170101 N2MSPSV7430 DRESSERIND.
VALVE REPLACED DISC AND B. RUSSELL 7/19/94 SN: BT-2188 SPRING TX-8 26 2-93-115 SN 178731 CV-2002 HL5012 ANCHOR / DARLING COMPONENT SUPPORT REPLACED SNUBBER B. RUSSELL 6/14/94 SN: 586 (AD-71)
TX-826 2-93-116 SN-178727 FW-2018-HL5003 ANCHOR / DARLING COMPONENT SUPPORT REPLACED SNUBBER B. RUSSELL 6/14/94 SN: 722 (AD-5501)
TX-8 26 2-93-117 SN-178733 SI-2206-HL5012 ANCHOR / DARLING COMPONENT SUPPORT REPLACED SNU8BER B. RUSSELL 6/14/94 SN: ')48 (AD-501)
TX-826 2-93-123 SI-170097 2N122XS10039C WESTINGHOUSE VALVE REPLACED VALVE STEM B. RUSSELL 8/11/94 SN: W750005 AND BACK SEAT. ALSO TX-826 NB: W17780 MACHINED NEW STEM 2-93-124 MS-147830 A2MSFSV7444 ATWOOD & MORRIL VALVE REPAlRED HANDSURFACING B. RUSSELL 7/28/94 SN: 7-13839 OF POPET SEAT IN VALVE TX-826 BODY 2 93-129 SI-132799 N2SlFV3950 AMETEK VALVE REPLACED VALVE.
B. RUSSELL 8/11/94 SN: 51-35-033 TX-826 NB: 36 2-93-133 CC-161949 2R202TCC0049 ROCKWELL VALVE REPLACED VALVE STEM B. RUSSELL 8/23/94 i
SN: 8-984 AND DISC TX-826 Page 7
SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - I'l 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAlRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPNS NO.!
(fF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANit DATE 2-93-137 CS-162836 CS SYSTEM N/A FLANGE CONNECTION REPLACED STUDS AND B. RUSSELL 6/29/94 NUTS BETWEEN TX-826 2N102NPS201C AND SPOOL CS-2301 -8 2-93-141 CV-164140 5R172NHX202A JOSEPH-OAT CORP.
HEAT EXCHANGER REPLACED FASTENERS
- 8. RUSSELL 7/19/94 SN: 2312-1 B TX-826 NB: 987 2 93 142 FW-179738 2S132TFWO220 BW/IP VALVE REPLACED VALVE B. RUSSELL 7/19/94 SN:931H0212 TX-826 2-93-145 CV-101889 2R172XCV8348 VELAN VALVE REPLACED STEM AND B. RUSSELL 8/11/94 SN: 847123 DISC TX-826 2 93-149 RH-309967 2R162NPA201A PACIFIC PUMPS VALVE REPLACED FASTENERS B. RUSSELL 8/11/94 SN: 51734 TX-826 NB: 363 2-93-154 FW-16797 7 82FWFV7146A VALTEK VALVE REPLACED PLUG B. RUSSELL 8/9/94 SN: 34752-15 TX-826 2-93-155 S1-179892 2R162XRH0031A WESTINGHOUSE VALVE REMOVED SHARP EDGES
- 8. RUSSELL 8/11/94 SN: W750014 ON DISC AND REFINISHED TX-826 NB: 11 VALVE BODY AT DAMAGED AREA 2-93-156 SI-178306 2R162XRH0031B WEST!NGHOUSE VALVE REPLACED STEM AND B. RUSSELL 8/18/94 SN: W750008 REPAIRED VALVE BODY TX-826 NB: W17921 AND DISC SEATING SURFAC't Page 8
= _ _ _. -
SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
NO-ITEM (TPNS NO.]
(tF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2-93 157 Sb178305 2R162XRH0031C WESTINGHOUSE VALVE REMOVED SHARP EDGES B. RUSSELL 8/11/94 SN: W750012 ON DISC AND REFINtSHED TX-826 NB: W19955 VALVE BODY AT DAMAGED AREA 2-93-161 MS-154170 C2MSPV7431 CONTROL COMPONENT VALVE REPAtRED BODY, BONNET B. RUSSELL 7/28/94 SN: 35200-1-3 AND PLUG MA!N SEAT TX-826 2-93-166 CC-176207 2R202TCC0319 TRW MISSION VALVE REPLACED VALVE B. RUSSELL 6/29/94 SN: Q-0726 TX-826 2-93-167 Sl-168943 SI SYSTEM N/A N/A REPLACED SPACER B. RUSSELL 6/29/94 PLATE AT 2N122NPA202A TX-826 2-93-168 CV-169128 2R172XCV0023 WESTINGHOUSE VALVE MACHINED WEDGE GUIDE B. RUSSELL 8/11/94 SN: W750007 SURFACE TX-8265 NB: W17603 I
2-93 174 SG-310305 1R122NSG201A WESTINGHOUSE STEAM GENERATOR REPLACED FASTENERS B. RUSSELL 7/12/94 SN: 2151 TX-826 NB:29 2-93-181 SI-309886 2N122XSl00088 WESTINGHOUSE VALVE REPA1 RED VALVE BODY, B. RUSSELL 8/18/94 SN: W750010 BONNET BACKSEAT AND TX-826 NB: W17914 INCREASED BACKSEAT THROAT DIAMETER. ALSO REPLACED LEAKOFF LINE 2-93 183 ZZ-187141 N/A ROCKWELL VALVE (SPARE)
REPLACED SEAL WELD B. RUSSELL 6/14/94 SN: CD864 TX-826 Page 9
SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2) l R OR R S.1 PROJ. ID OF MFG. SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPN 3 NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANil DATE i
2-93-185 RC-157 319 1R102NRb202 WESTINGHOUSE MISS!LE SHIELD ENLARGED LIFT NUTS B. RUSSELL 6/14/94 SN:1WPT-3064 HOLES.
TX-826 NB:W20663 2-93-186 SG-178654 1R122NSG201D WESTINGHOUSE STEAM GENERATOR PLUGGED SG-TUBE B. RUSSELL 6/14/94 SN:2154 TX-826 NB:32 2-93-189 MS 148866 B2MSPV7421 CONTROL COMPONENTS VALVE REPAIRED VALVE BODY, B. RUSSELL 8/9/94 SN: 35200-1-2 BONNET AND PLUG TX-826 2-94 013 FW-212914 A2FWFV7189 VALTEK VALVE REPLACED PLUG B. RUSSELL 7/18/94 SN: 34752-35 TX-826 2-94-014 FW 212915 A2FWFV7190 VALTEK VALVE REPLACED PLUG B. RUSSELL 7/18/94 SN: 34752-36 TX-826 2-94-015 FW-212916 A2FWFV7191 VALTEK VALVE REPLACED PLUG B. RUSSELL 7/18/94 SN: 34752-37 TX-826 2-94-016 FW-212917 A2FWFV7192 VALTEK VALVE REPLACED PLUG B. RUSSELL 7/12/94 SN: 34752-38 TX-826 2-94-017 Sl-158232 2N122TS10120A ANCHOR DARLING VALVE REPLACED VALVE B. RUSSELL 6/29/94 SN: ET550-10-17 TX-826 2-94018 FW212117 A2FWFV7148A VALTEK VALVE REPLACED PLUG AND B. RUSSELL 7/18/94 SN: 34732-17 BONNET TX-826 2-94 019 FW-212114 B2FWFV7145A VALTEK VALVE REPLACED PLUG AND B.RUSS5LL 7/12/94 i
SN:. 34752-14 BONNET TX-826 Page 10
A SOUTH TEXAS PROJECT UNIT - 2 ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG..SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION ANII DATE 2-94-020 FW-212115 B2FWFV7146A VALTEK VALVE REPLACED PLUG AND B. RUSSELL 7/18/94 SN: 34752-15 BONNET TX-826 2-94-021 FW 212116 A2FWFV7147A VALTEK VALVE REPLACED PLUG AND B. RUSSELL 7/18/94 SN: 34752-16 BONNET TX-826 2-94 023 CC-176293 2R202TCC0183 C & S VALVE CO.
VALVE REPLACED VALVE B. RUSSELL 6/14/94 i
SN: 89-0761-01N-01 TX-826 2-94-024 CC-17 4632 N/A TRW MISSION VALVE (SPARE)
REPLACED PLATE AND B. RUSSELL 8/11/94 SN: S-6036 TACK VELDED SHIMS TX-826 2-94 f'25 CC-315539 2R202TCC0013 TRW MISSION VALVE REPLACED VALVE B. RUSSELL 8/9/94 SN: S-6036 TX-826 2-94-027 SN-209485 SB-2201-HL5020 ANCHOR / DARLING COMPONENT SUPPORT REPLACED SNUBBER B. RUSSELL 8/9/94 SN: 942 (AD 501)
TX-826 2-94-028 RC-2047 47 1Ii142XRC0001 A WESTINGHOUSE VALVE REPAIRED DISC SEATING B. RUSSELL 8/9/94 l
SN: W750007 SURFACE, DISC AND DISC TX-826 NB: W15182 GUIDE 2-94-029 RC-204748 1R142XRC00018 WESTINGHOUSE VALVE REPAIRED DISC SEATING B. RUSSELL 8/11/94 SN: W750008 SURFACE, BONNET STEM TX-826 N8: W15183 BUSHING, DISC AND IN-BODY DISC GUtDES 2 94-032 St-314038 2N122XS100048 WESTINGHOUSE VALVE REPLACED STEM AND B. RUSSELL 7/12/94 SN: W750005 REPAIRED DISC TX-826 NB: W17883 Page 11
5 SOUTH TEXAS PROJECT UNIT - 2 j
ASME CODE SECTION - XI 2RE03 INSERVICE INSPECTION
SUMMARY
REPORT FOR REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. ID OF MFG.,SN AND NB ITEM / COMP R OR R COMP.
NO.
NO.
ITEM (TPNS NO.I UF ANYI OF COMP.
DESCRIPTION DESCRIPTION ANil DATE 2-94-033 CV-315546 2R172TCV3033A KEROTEST VALVE REPLACED VALVE B. RUSSELL 8/9/94 SN: AOJ5-2 TX-826 2-94-035 FW-148722 FW-2054-D SOUTHWEST FAB.
PIPING SPOOLS REPLACED ORIFICE PLATE, B. RUSSELL 8/11/94 FW-2054-E SN: 32897 FLANGE FASTENERS AND TX-826 SN:38898 REPAIRED FLANGES 2 94-040 CV-311748 2R172TCV0249A EDWARD VALVE REPLACED VALVE B. RUSSELL 1/28/94 SN: 88ACI TX-826 I
2-94-041 CS-311717 2N102TCS0044C EDWARD VALVE REPLACED VALVE B. RUSSELL 7/18/94 SN: 45AEN TX-826 2-94-042 CV-188973 A2CVHCV0206 TARGET ROCK VALVE REPLACED BONNET AND B. RUSSELL 7/19/94 SN: 52 SEAL WELD TX-826 NB.686 2-94-049 FW-214256 2S132TFWD222 BW/IP VALVE REPLACED VALVE B. RUSSELL 8/8/94 SN: 931H0210 TX-826 2-94-051 CV-202050 2R172TCV0250A ANCHOR DARLING VALVE REPLACED VALVE AND B. RUSSELL 7/12/94 SN: ET550-10-3 ADJACENT PlPING TX-826 r
2 94-053 CV-165790 2R172TCV0675 KEROTEST
-VALVE REPLACED VALVES AND B. RUSSELL 7/28/94 2R172TCV0508 SN: ARA 1-35 DRAIN LINE CV-2105 TX-826 SN: ARA 1-16 2-94-054 CC-304030 2R202TCC0138 TRW MISSION VALVE REPLACED VALVE B. RUSSELL 6/29/94 7
SN: N-956 TX 826 Page 12
SOUTH TEXAS PROJECT UNIT - 2
~
ASME CODE SECTION - XI i
2RE03 INSERVICE INSPECTION
SUMMARY
P.EPORT FOR l
j REPAIRS AND REPLACEMENTS (CLASS 1 & 2)
R OR R SR PROJ. !D OF MFG.,SN AND NB ITEM / COMP R OR R COMP.
NO, NO.
ITEM (TPNS NO.)
(IF ANY) OF COMP.
DESCRIPTION DESCRIPTION AMI DATE 2-94-056 SN-311252.
SB-2301-HL5012 ANCHOR DARLING COMPONENT SUPPORT.
REPLACED SNUBBER B. RUSSELL 7/25/94 i
SN: 1085 (AD151)
TX-826 2-94 071 CV-301177 2R172XCV8377A WESTINGHOUSE VALVE REPAIRED DISC B. RUSSELL 7/12/94
' SN: W750021 TX-826 NB: W15116 2-94-073 CV-309542 2R172TCV0481 KEROTEST VALVE REPLACED VALVE B. RUSSELL 7/18/94 SN: YW194 TX-826 2-94-074 RH-301186 1R162XRH00618 V4STINGHOUSE VALVE REPLACED STEM AND B. RUSSELL 7/28/94 SN: W750008 SEAL WELD TX-826 NB: W1749 i
2-94-075 S1-301137 A2SlHCV0900 TARGET ROCK VALVE REPLACED VALVE.
B. RUSSELL 7/28/94 j
SN: 23 REPLACED DISC AND TX-826 TACK WELD t
e 4
I Page 13 i
.