. PRELIM 5 NARY [ NOTIFICATION F EVENT OR UNUSUAL OCCURRENCE--PNO-III-37-99 Date July 21e 1987 brh O LThis preliminary notification constitutes EARLY notice of events of POSSIBLE safety E or:public Tnterest significance. The information is as initially received without-

, verification or evaluation, and is ' basically all that is known by the Region III staff'on this date.

Facility: Commonwealth Edison Company Licensee Emergency Classification:

Braidwood Unit 1 Notification of an Unusual Event-Braceville, IL' 60407 Alert Site Area Emergency Docket No. 50-456 General Emergency X Not Applicable

Subject:

INOPERABLE DIESEL GENERATOR 0n July 17, 1987, the.. licensee declared the IB Diesel Generator inoperable following.an .i

.; unsatisfactory monthly. surveillance test. The diesel generator output had load swings of. I approximately 500 to 1000 kilowatts which prevented the licensee from maintaining a minimum 4

' load 'of:5500 kilowatts as required by Technical Specifications. The licensee is investigating the cause of the problem.

.The' resident inspectors are monitoring the licensee's activities. The unit has been 1 shutdown' for more than 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />. j The' State of 11'linois will be. notified.

i

.Thisinformationiscurrentasof10a.m.(CDT), July.21,1987.

-CONTACT:

eeaw P. Pelke .

agwig

,W. Little '

FTS 388-5560 FTS 388-5578 ,

l l

j l

I DISTRIBUTION:

2*dtkI B7 Chairmanbech 49 ED0 PA NRR E/W IE Willste NMSS Mail: ADM:DMB DOT:Trans only l

l

Comm. Roberts ELD- OIA RES i Comm. Asselstine AE0D NRC Ops Ctr / 33 .

l LComm. Bernthal Comm. Carr 'SP /y Regional Offices

INPO / NSAC /

CA RIII Resident Office PDR Licensee: / S5' (Corp. Office - Reactor Lic. Only)

Q73g5687072.1 Region III PNO-II I-87-099 PDR Rev. November 1c86 .