MONTHYEARML20153A9971978-03-29029 March 1978 Summary of 780214-15 Meeting W/Util Re Subj Facil Fire Protec Prog.All Mods Will Be Made Prior to Fuel Loading Project stage: Meeting ML20209C4421983-09-0707 September 1983 Approve 21 & Denies Five Requests for Deviations from Requirements of 10CFR50 App R.Evaluation Encl Project stage: Other ML20209C5511983-11-0101 November 1983 Forwards Evaluation of Util Requests for Approval of Deviations from 10CFR50,App R.Licensee Sept & Oct 1983 Ltrs Provided Info Sufficient to Close Four of Five Open Items. Emergency Lighting Info Under Auxiliary Sys Branch Review Project stage: Other ML20211F8641983-11-18018 November 1983 Safety Evaluation Re Applicant 830715,0923 & 1104 Requests for Deviation from 10CFR50,App R,Section Iii.J Concerning Emergency Lighting. Request Approved Project stage: Approval ML20209C6291983-11-18018 November 1983 Forwards SER Approving Applicant 830715,0923 & 1104 Requests for Deviations from Section III of App R to 10CFR50, Emergency Lighting Project stage: Approval DCL-84-377, Special Rept 84-14:on 841102,Unit 1 18-month Fire Barrier Insp Identified Six Conduits & One Cable Penetration Not Sealed in Accordance W/Installation Procedure DCP 2.Fire Watch Established.Related Correspondence1984-12-0707 December 1984 Special Rept 84-14:on 841102,Unit 1 18-month Fire Barrier Insp Identified Six Conduits & One Cable Penetration Not Sealed in Accordance W/Installation Procedure DCP 2.Fire Watch Established.Related Correspondence Project stage: Other ML20215E3281985-08-29029 August 1985 Requests That Auxiliary Sys Branch Fire Protection Reviewers Be Provided to Participate in App R Fire Protection/Safe Shutdown Insp Scheduled for 851118-22 Project stage: Other ML20207A6101985-12-0303 December 1985 Forwards List of Current Fire Protection Enforcement Actions,Per 851106 Request.Suggested Schedule for Affected Licensees to Comply W/App R Requirements Will Be Provided Project stage: Other 1983-09-07
[Table View] |
Text
- __ _
Y 1%;
UNITE 3 STATES 8
NUCLEAR REGULATORY COMMISSION o
,I wAsHinoTom. o. c.2 cess
\\,
/
II Docket No. 50-275 l
MEMORANDUM FOR: William V. Johnston, Assistant Director for Materials, l
Chemical and Environmental Technology, Division of Engineering FROM:
L. S. Rubenstein, Assistant Director for Core and Plant Systems, Division of, Systems Integration
SUBJECT:
REQUEST FOR APPROVED DEVIATIONS FROM THE REQUIREMENTS OF SECTION III.J OF APPENDIX R TO 10 CFR 50 - DIABLO CANYON UNIT 1 (TAC 52060)
As requested by the Chemical Engineering Branch (ChEB), the Auxiliary Systems Branch has reviewed the applicant's July 15, September 23. and November 4, 1983 submittals regarding the request for approved deviations from the requirements of Section III.J of Appendix R, " Emergency Lighting."
Based on our review, we conclude that the applicant has proposed an acceptable means of assuring adequate emergency lighting for the required access and egress, and the performance of safe shutdown functions in the event of a fire, equivalent to that achieved by compliance with Section III.J. Thus, we recomend that the applicant's.regoest for approved deviations be granted.
Our safety evaluation report is attached.
We understand that ChEB is currently evaluating new illumination level require-ments for emergency lighting systems.
The illumination level stated in this SER is to document the applicant's comitment to provide an illumination level that has been previously accepted by the staff.
b b wa u.
^- ~
L. S. Ru enstein Assistant Director for Core and Plant Systems Division of Systems Integration