PNO-IV-88-013A, on 880221,reactor Scram Occurred During Shell Warming of Main Turbine.Caution Added in Turbine Startup Procedure Re Possibility of Reactor Scram Because of Turbine First Stop Pressure During Shell Warming
ML20196E102 | |
Person / Time | |
---|---|
Site: | River Bend ![]() |
Issue date: | 02/22/1988 |
From: | Holler E NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
To: | |
References | |
PNO-IV-88-013A, PNO-IV-88-13A, NUDOCS 8802290017 | |
Download: ML20196E102 (2) | |
Similar Documents at River Bend | |
---|---|
Category:PRELIMINARY NOTIFICATION OF EVENT OR OCCURRENCE (PNO
MONTHYEARPNO-IV-98-016, on 980413,operators at River Bend Station Initiated Normal Reactor Shutdown.Plant Shutdown Deemed Necessary After Operators Identified Main Generator Hydrogen Seal Oil Leak at Main Generator Casing1998-04-14014 April 1998
[Table view]PNO-IV-98-016:on 980413,operators at River Bend Station Initiated Normal Reactor Shutdown.Plant Shutdown Deemed Necessary After Operators Identified Main Generator Hydrogen Seal Oil Leak at Main Generator Casing PNO-IV-97-043A, on 970724,licensee Entered Forced Shutdown of Reactor,Due to Decreasing Second Stage Pressure on Reactor Recirculation Pump a Seal & Rising Drywell Unidentified Leakage.Inspectors Will Continue to Monitor Startup1997-07-31031 July 1997 PNO-IV-97-043A:on 970724,licensee Entered Forced Shutdown of Reactor,Due to Decreasing Second Stage Pressure on Reactor Recirculation Pump a Seal & Rising Drywell Unidentified Leakage.Inspectors Will Continue to Monitor Startup PNO-IV-97-043, on 970724,licensee Commenced Reactor Shutdown Because of Decreasing Second Stage Pressure on Reactor Recirculation Pump Seal & Rising Drywell Unidentified Leakage.Licensee Did Not Enter Any Emergency Procedures1997-07-28028 July 1997 PNO-IV-97-043:on 970724,licensee Commenced Reactor Shutdown Because of Decreasing Second Stage Pressure on Reactor Recirculation Pump Seal & Rising Drywell Unidentified Leakage.Licensee Did Not Enter Any Emergency Procedures PNO-IV-97-026A, on 970507,shutdown Greater than 72 H After Manual Scram Update Made.Workers Removing Fire Seal Matl from Penetration in Turbine Bldg to Run Addl Cable Through Penetration in Accordance W/Authorized Station Mod1997-05-0808 May 1997 PNO-IV-97-026A:on 970507,shutdown Greater than 72 H After Manual Scram Update Made.Workers Removing Fire Seal Matl from Penetration in Turbine Bldg to Run Addl Cable Through Penetration in Accordance W/Authorized Station Mod PNO-IV-97-026, on 970506,shutdown Greater than 72 H After Manual Scram Occurred.Div II & III EDGs Started Automatically & Provided Power to safety-related Loads. Licensee Plans to Commence Outage to Repair1997-05-0606 May 1997 PNO-IV-97-026:on 970506,shutdown Greater than 72 H After Manual Scram Occurred.Div II & III EDGs Started Automatically & Provided Power to safety-related Loads. Licensee Plans to Commence Outage to Repair PNO-IV-93-023, on 930810,reactor Scram Occurred Due to MSIVs Going Closed.Licensee Initiated Task Team to Review Event & Develop Action Plan to Address Turbine Control Problems. State of Louisiana Informed1993-08-12012 August 1993 PNO-IV-93-023:on 930810,reactor Scram Occurred Due to MSIVs Going Closed.Licensee Initiated Task Team to Review Event & Develop Action Plan to Address Turbine Control Problems. State of Louisiana Informed PNO-IV-92-042, on 921206,reactor Manually Scrammed to Complete Planned Shutdown.Indications of Degraded Inboard Seal Noted.Outage Scope May Be Increased to Include Recirculation Pump a Seal Package1992-12-0707 December 1992 PNO-IV-92-042:on 921206,reactor Manually Scrammed to Complete Planned Shutdown.Indications of Degraded Inboard Seal Noted.Outage Scope May Be Increased to Include Recirculation Pump a Seal Package PNO-IV-91-004A, on 910226,industrial Accident Occurred During Removal of Pipe Fittings from Halon Cylinder in Preparation for Weighing Bottle.Hospitalized Individual Developed Blood Pressure Problems & Test Continued to Determine Reason1991-03-0101 March 1991 PNO-IV-91-004A:on 910226,industrial Accident Occurred During Removal of Pipe Fittings from Halon Cylinder in Preparation for Weighing Bottle.Hospitalized Individual Developed Blood Pressure Problems & Test Continued to Determine Reason PNO-IV-89-049, on 890808,reactor Shutdown to Stop Drywell Leakage.Shutdown to Last 7 Days to Replace Recirculation Pump Seal1989-08-0808 August 1989 PNO-IV-89-049:on 890808,reactor Shutdown to Stop Drywell Leakage.Shutdown to Last 7 Days to Replace Recirculation Pump Seal PNO-IV-89-043, on 890626,licensed Operator Radiologically Contaminated When Valve Packing Blew Out While Operator Operating Valve.Approx 2,000 Square Ft of Turbine Bldg Contaminated.Valve Repacked & Returned to Normal Position1989-06-27027 June 1989 PNO-IV-89-043:on 890626,licensed Operator Radiologically Contaminated When Valve Packing Blew Out While Operator Operating Valve.Approx 2,000 Square Ft of Turbine Bldg Contaminated.Valve Repacked & Returned to Normal Position PNO-IV-89-041, on 890623,licensee Synchronized Main Generator to Grid,Completing 101 Day Outage.Refueling Outage Consisted of Replacing Approx One Third of Fuel Elements in Core & Repairs to Svc Water Sys Due to Failed Transformer1989-06-26026 June 1989 PNO-IV-89-041:on 890623,licensee Synchronized Main Generator to Grid,Completing 101 Day Outage.Refueling Outage Consisted of Replacing Approx One Third of Fuel Elements in Core & Repairs to Svc Water Sys Due to Failed Transformer PNO-IV-89-037, on 890529,nonsafety-related 230-kV Transformer Ruptured & Caught Fire When Energized.Caused by Possible Internal Fault.Licensee & NRC Responding to News Media Inquiries1989-05-30030 May 1989 PNO-IV-89-037:on 890529,nonsafety-related 230-kV Transformer Ruptured & Caught Fire When Energized.Caused by Possible Internal Fault.Licensee & NRC Responding to News Media Inquiries PNO-IV-89-030A, on 890419,freeze Seal Failed on 6-inch Standby Svc Water Line.Caused by Flooding Portions of Auxiliary Bldg.Svc Water Sys Isolated & RHR Restarted1989-04-24024 April 1989 PNO-IV-89-030A:on 890419,freeze Seal Failed on 6-inch Standby Svc Water Line.Caused by Flooding Portions of Auxiliary Bldg.Svc Water Sys Isolated & RHR Restarted PNO-IV-89-030, on 890414,freeze Seal on 6-inch Svc Water Line Failed,Resulting in Flooding Portion of Auxiliary Bldg Before Svc Water Sys Could Be Isolated.Lost Electrical Sys Will Be Repaired & Returned to Svc1989-04-20020 April 1989 PNO-IV-89-030:on 890414,freeze Seal on 6-inch Svc Water Line Failed,Resulting in Flooding Portion of Auxiliary Bldg Before Svc Water Sys Could Be Isolated.Lost Electrical Sys Will Be Repaired & Returned to Svc PNO-IV-89-027, on 890413,stop Work Order Issued to Two Contractors During Refueling Outage Due to Instances Where Contractors Failed to Adequately Implement Licensee Clearance Program.Work to Resume Under New Work Rules1989-04-13013 April 1989 PNO-IV-89-027:on 890413,stop Work Order Issued to Two Contractors During Refueling Outage Due to Instances Where Contractors Failed to Adequately Implement Licensee Clearance Program.Work to Resume Under New Work Rules PNO-IV-89-023, on 890327,loss of Shutdown Cooling Occurred for 12 Minutes While Tagging Out 120-volt Dc Breakers.On 890329,loss of Shutdown Cooling Occurred While Performing Work in Div I Transmitter Cabinet in Control Room1989-03-30030 March 1989 PNO-IV-89-023:on 890327,loss of Shutdown Cooling Occurred for 12 Minutes While Tagging Out 120-volt Dc Breakers.On 890329,loss of Shutdown Cooling Occurred While Performing Work in Div I Transmitter Cabinet in Control Room PNO-IV-89-021, on 890324,stop-work Order Issued to Contractor (S&W).Contract Mechanics Were to Conduct Planned Pipe Cut on Portion of RHR Sys Train a Test Return Line to Suppression Pool.Rhr B Inadvertently Cut.On 890327,order to Be Lifted1989-03-24024 March 1989 PNO-IV-89-021:on 890324,stop-work Order Issued to Contractor (S&W).Contract Mechanics Were to Conduct Planned Pipe Cut on Portion of RHR Sys Train a Test Return Line to Suppression Pool.Rhr B Inadvertently Cut.On 890327,order to Be Lifted PNO-IV-89-014, on 890301,util Announced Reorganization of Physical Security Program at Plant Involving Util Security Dept & Burns Intl.Announced Changes Resulted from Util & Burns Intl Audits of Operations at Site1989-03-0202 March 1989 PNO-IV-89-014:on 890301,util Announced Reorganization of Physical Security Program at Plant Involving Util Security Dept & Burns Intl.Announced Changes Resulted from Util & Burns Intl Audits of Operations at Site PNO-IV-88-098, on 881221,oil Filled Breaker in Gsu Substation Caught Fire Resulting in Complete Loss of Substation1988-12-22022 December 1988 PNO-IV-88-098:on 881221,oil Filled Breaker in Gsu Substation Caught Fire Resulting in Complete Loss of Substation PNO-IV-88-081, on 880930,two of Eight Solenoid Operated Valves Failed During Test of MSIVs Per Info Notice 88-043. Reactor Shutdown Commenced from 4 to 7 Days1988-10-0303 October 1988 PNO-IV-88-081:on 880930,two of Eight Solenoid Operated Valves Failed During Test of MSIVs Per Info Notice 88-043. Reactor Shutdown Commenced from 4 to 7 Days PNO-IV-88-075, on 880906,reactor Scrammed from 100% Power. Caused by Main Generator Trip Due to Loss of Normal Station Transformer,Probably Caused by Cat Crawling Into Transformer.Noue Declared Because HPCS & RCIC Sys Initiated1988-09-0606 September 1988 PNO-IV-88-075:on 880906,reactor Scrammed from 100% Power. Caused by Main Generator Trip Due to Loss of Normal Station Transformer,Probably Caused by Cat Crawling Into Transformer.Noue Declared Because HPCS & RCIC Sys Initiated PNO-IV-88-070, on 880825,reactor Scrammed Due Trip of Main Turbine After Brush Failure of Main Generator Exciter. Although Water Level Has Not Dropped to Level 2,HPCS Pump Did Start & May Have Injected.Power Restored to Div III Bus1988-08-25025 August 1988 PNO-IV-88-070:on 880825,reactor Scrammed Due Trip of Main Turbine After Brush Failure of Main Generator Exciter. Although Water Level Has Not Dropped to Level 2,HPCS Pump Did Start & May Have Injected.Power Restored to Div III Bus PNO-IV-88-013A, on 880221,reactor Scram Occurred During Shell Warming of Main Turbine.Caution Added in Turbine Startup Procedure Re Possibility of Reactor Scram Because of Turbine First Stop Pressure During Shell Warming1988-02-22022 February 1988 PNO-IV-88-013A:on 880221,reactor Scram Occurred During Shell Warming of Main Turbine.Caution Added in Turbine Startup Procedure Re Possibility of Reactor Scram Because of Turbine First Stop Pressure During Shell Warming PNO-IV-88-013, on 880219,reactor Circulation Pump Motor Tripped on over-current Condition.Caused by Low Megger Readings to Pump Motor.Orderly Plant Shutdown Continued W/ Plans to Go to Cold Shutdown for Necessary Repairs1988-02-19019 February 1988 PNO-IV-88-013:on 880219,reactor Circulation Pump Motor Tripped on over-current Condition.Caused by Low Megger Readings to Pump Motor.Orderly Plant Shutdown Continued W/ Plans to Go to Cold Shutdown for Necessary Repairs PNO-IV-87-057, on 871022 & 26,temporary Worker Alarmed Portal Monitor While Exiting Radiation Control Area.Survey Identified Co-60 Particle on Workers Sleeve.Shirt Had Been Taken Home,Washed & Worn Again.Nothing Found at Residence1987-10-30030 October 1987 PNO-IV-87-057:on 871022 & 26,temporary Worker Alarmed Portal Monitor While Exiting Radiation Control Area.Survey Identified Co-60 Particle on Workers Sleeve.Shirt Had Been Taken Home,Washed & Worn Again.Nothing Found at Residence PNO-IV-87-048, on 870920,upper Fuel Pool Partially Drained. Caused by Attempt to Increase Water Level During Refueling. Region Dispatching Supervisor to Site to Coordinate NRC Insp of Licensee Actions.Licensee Also Conducting Indepth Review1987-09-21021 September 1987 PNO-IV-87-048:on 870920,upper Fuel Pool Partially Drained. Caused by Attempt to Increase Water Level During Refueling. Region Dispatching Supervisor to Site to Coordinate NRC Insp of Licensee Actions.Licensee Also Conducting Indepth Review PNO-IV-87-029, on 870618,151 Days of Continuous Operation Terminated Due to Reactor Scram on High Water Level in Reactor Vessel.Licensee Investigating Cause.Plant to Be Shut Down for 7 Days for Maint Activities1987-06-18018 June 1987 PNO-IV-87-029:on 870618,151 Days of Continuous Operation Terminated Due to Reactor Scram on High Water Level in Reactor Vessel.Licensee Investigating Cause.Plant to Be Shut Down for 7 Days for Maint Activities PNO-IV-87-016, on 870410,S&W QC Inspector Fell While Performing Fire Barrier Insp in Fuel Bldg.Inspector Not Contaminated But Received Broken Tailbone & Left Elbow1987-04-13013 April 1987 PNO-IV-87-016:on 870410,S&W QC Inspector Fell While Performing Fire Barrier Insp in Fuel Bldg.Inspector Not Contaminated But Received Broken Tailbone & Left Elbow PNO-IV-86-023A, on 860708,gasket Failure Resulted in Steam Leak That Led to Reactor Scram.Caused by Inappropriate Gasket Matl & Improper Torque.Moisture Separator Reheater Drain Tank Manway Gaskets Replaced1986-07-10010 July 1986 PNO-IV-86-023A:on 860708,gasket Failure Resulted in Steam Leak That Led to Reactor Scram.Caused by Inappropriate Gasket Matl & Improper Torque.Moisture Separator Reheater Drain Tank Manway Gaskets Replaced PNO-IV-86-023, on 860708,facility Experienced Reactor Scram Due to MSIV Closure at 65% Power.Isolation Initiated Due to Turbine Bldg High Temp Resulting from Manway Gasket Failure. Personnel Evacuated1986-07-0909 July 1986 PNO-IV-86-023:on 860708,facility Experienced Reactor Scram Due to MSIV Closure at 65% Power.Isolation Initiated Due to Turbine Bldg High Temp Resulting from Manway Gasket Failure. Personnel Evacuated PNO-IV-86-021, on 860626,Hurricane Bonnie Came Ashore Near Port Arthur,Tx on Louisiana/Texas Border.Bonnie Described as Minimal Hurricane.Hurricane Protection Procedures Implemented as Required1986-06-26026 June 1986 PNO-IV-86-021:on 860626,Hurricane Bonnie Came Ashore Near Port Arthur,Tx on Louisiana/Texas Border.Bonnie Described as Minimal Hurricane.Hurricane Protection Procedures Implemented as Required PNO-IV-86-007, on 860301,reactor Tripped from 38% Power. Caused by Failure of Nonvital Electrical Transformer. Reactor Restarted.Resident Inspectors Monitoring Licensee Activities1986-03-0303 March 1986 PNO-IV-86-007:on 860301,reactor Tripped from 38% Power. Caused by Failure of Nonvital Electrical Transformer. Reactor Restarted.Resident Inspectors Monitoring Licensee Activities PNO-IV-86-003, on 860107,fire Prevention Deluge Sys Inadvertently Actuated in Auxiliary Bldg,Wetting Nonvital 480-volt Ac Load Ctr.Unit May Remain Shut Down in Excess of 2 Days During Evaluation & Drying Out of Load Ctr1986-01-0808 January 1986 PNO-IV-86-003:on 860107,fire Prevention Deluge Sys Inadvertently Actuated in Auxiliary Bldg,Wetting Nonvital 480-volt Ac Load Ctr.Unit May Remain Shut Down in Excess of 2 Days During Evaluation & Drying Out of Load Ctr PNO-IV-86-001A, on 860101,loss of Offsite Ac Power Experienced.Caused by Maloperation of Redundant Sys Used to Control Offsite Power Circuit Breakers.Tone Sys Circuit Problem Being Corrected by Licensee1986-01-0303 January 1986 PNO-IV-86-001A:on 860101,loss of Offsite Ac Power Experienced.Caused by Maloperation of Redundant Sys Used to Control Offsite Power Circuit Breakers.Tone Sys Circuit Problem Being Corrected by Licensee PNO-IV-85-062, on 851206,plant Offgas Sys Experienced Transient Upon Automatic Switchover from Dryer a to Dryer C. Caused by Failure of Discharge Valve on Dryer C to Open Resulting in Back Pressure Blowing Out Water Loop Seals1985-12-0606 December 1985 PNO-IV-85-062:on 851206,plant Offgas Sys Experienced Transient Upon Automatic Switchover from Dryer a to Dryer C. Caused by Failure of Discharge Valve on Dryer C to Open Resulting in Back Pressure Blowing Out Water Loop Seals PNO-IV-85-058A, on 851118,administrative 5% Thermal Power Limit of Section 2c of License NPF-40 Exceeded.Caused by Shift Supervisor Misunderstanding Commission Vote on Full Power License.Shift Supervisor Disciplined1985-11-19019 November 1985 PNO-IV-85-058A:on 851118,administrative 5% Thermal Power Limit of Section 2c of License NPF-40 Exceeded.Caused by Shift Supervisor Misunderstanding Commission Vote on Full Power License.Shift Supervisor Disciplined PNO-IV-85-058, on 851118,indicated License Limit of 5% of Rated Thermal Power Exceeded for 1 H.Arpms Apparently Calibr to Read High.Actual Thermal Power Probably Did Not Exceed Limit.Evaluation Initiated1985-11-18018 November 1985 PNO-IV-85-058:on 851118,indicated License Limit of 5% of Rated Thermal Power Exceeded for 1 H.Arpms Apparently Calibr to Read High.Actual Thermal Power Probably Did Not Exceed Limit.Evaluation Initiated PNO-IV-85-055, on 851031,initial Criticality Achieved. Criticality Occurred at Predicted Point in Rod Withdrawal Sequence1985-10-31031 October 1985 PNO-IV-85-055:on 851031,initial Criticality Achieved. Criticality Occurred at Predicted Point in Rod Withdrawal Sequence PNO-IV-85-046, on 850829,util Received Low Power License. Fuel Load Will Not Start Until Potential for Heavy Weather from Hurricane Elena Resolved.Util Estimates Actual Fuel Movement Will Begin on 8508301985-08-30030 August 1985 PNO-IV-85-046:on 850829,util Received Low Power License. Fuel Load Will Not Start Until Potential for Heavy Weather from Hurricane Elena Resolved.Util Estimates Actual Fuel Movement Will Begin on 850830 PNO-IV-85-038, on 850801,contractor Employee Attempted to Enter Protected Area W/Handgun in Purse.Employee Stated That Gun for Personal Protection Offsite.Site Access Denied & Contractor Employee Discharged1985-08-0101 August 1985 PNO-IV-85-038:on 850801,contractor Employee Attempted to Enter Protected Area W/Handgun in Purse.Employee Stated That Gun for Personal Protection Offsite.Site Access Denied & Contractor Employee Discharged ML20207G2411977-11-0404 November 1977 PNO-77-194:on 771024-28,significant Deficiencies Identified in Implementation of QA Program.Stop Work Order Was Issued by Gulf States Util to Trans America Steel,Which Applied to sub-suppliers Including Florida Steel Co 1998-04-14 Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS MONTHYEARIR 05000458/19990121999-10-19019 October 1999
[Table view]Insp Rept 50-458/99-12 on 990822-1002.Non-cited Violations Noted.Major Areas Inspected:Operations,Engineering, Maintenance & Plant Support ML20212L9771999-10-0505 October 1999 Notice of Violation from Insp on 990710.Violation Noted:From 990224-0325,River Bend Station Operated in Mode I Without Three Operable EDGs IR 05000458/19990101999-09-15015 September 1999 Insp Rept 50-458/99-10 on 990830-0903.No Violations Noted. Major Areas Inspected:Licensed Operators Requalification Program IR 05000458/19990081999-09-0808 September 1999 Insp Rept 50-458/99-08 on 990711-0821.Noncited Violations Identified.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000458/19990111999-08-17017 August 1999 Insp Rept 50-458/99-11 on 990719-23.No Violations Noted. Major Areas Inspected:Licensee Physical Security Program IR 05000458/19990091999-08-16016 August 1999 Replacement Pages 9-18 for Insp Rept 50-458/99-09 Issued on 990730 ML20210N1901999-08-0404 August 1999 Insp Rept 50-458/99-07 on 990530-0710.One Violation of NRC Requirements Occurred & Being Treated as Ncv.Major Areas Inspected:Aspects of Licensee,Operations,Maint,Engineering & Plant Support ML20210K1471999-07-30030 July 1999 Insp Rept 50-458/99-09 on 990510-28 with in-office Insp Until 990701.Noncited Violations Identified.Major Areas Inspected:Review of Licensee Actions Re Testing & Cleaning of Auxiliary Bldg Unit Coolers ML20196L0551999-07-0606 July 1999 Revised Pages 4 of Report Details Section & 2 of Rept Attachment for Insp Rept 50-458/99-03.Corrections Made to Tracking Numbers Assigned to Seven Noncited Violations & to SRO Location During Refueling Activities IR 05000458/19990041999-06-30030 June 1999 Insp Rept 50-458/99-04 on 990412-16 & 28-29.Five Violations Occurred & Being Treated as Noncited Violations.Major Areas Inspected:Portions of Radiation Protection Program,Including Exposure Controls & Radiation Technical & Worker Practices IR 05000458/19990051999-06-18018 June 1999 Insp Rept 50-458/99-05 on 990418-0529.Nonccited Violations Noted.Major Areas Inspected:Aspects of Licensee Operations, Engineering,Maint & Plant Support IR 05000458/19990031999-05-18018 May 1999 Insp Rept 50-458/99-03 on 990307-0417.Noncited Violations Noted.Major Areas Inspected:Operation,Maintenance, Engineering & Plant Support IR 05000458/19990061999-05-15015 May 1999 Insp Rept 50-458/99-06 on 990419-23.No Violations Noted. Major Areas Inspected:Inservice Exam Program Plan & Schedule,Implementation of Program Plan for Facility & Maint & Engineering Followup Review of Previous Insp Findings ML20205A4601999-03-26026 March 1999 Insp Rept 50-458/98-10 on 990222-26.Violations Noted.Major Areas Inspected:Radiation Work Permit Program Implementation from Oct 1997 to Feb 1999 & Problem Identification & Resolution Program as Applied to Program Deficiencies IR 05000458/19990021999-03-26026 March 1999 Insp Rept 50-458/99-02 on 990124-0306.Violations Noted.Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Support ML20205A4131999-03-23023 March 1999 NRC Operator Licensing Exam Rept 50-458/99-301 (Including Completed & Graded Tests) for Tests Administered on 990222- 0303.All 14 Applicants Passed Exams ML20203A5351999-01-27027 January 1999 EN-99-005:on 990201,notice of Proposed Imposition of Civil Penalty in Amount of $55,000 Issued to Licensee.Action Based on Two Severity Level III Violations Involving Design Deficiency,Caused Uncertainty as to Ability of Div I & II IR 05000458/19990011999-01-25025 January 1999 Insp Rept 50-458/99-01 on 990104-08.No Violations Noted. Major Areas Inspected:Licensee Physical Security Program Including Alarm Stations,Communications,Access Control of Personnel,Packages,Vehicles & Assessment Aids IR 05000458/19980201999-01-0707 January 1999 Insp Rept 50-458/98-20 on 981101-1212.Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support ML20199E2111999-01-0707 January 1999 Notice of Violation from Insp on 981101-1212.Violation Noted:On 971022,radiation Protection Technicians Released One Container with Two Items Contaminated Above Limits Specified in Procedure RSP-0213 ML20199A2161999-01-0505 January 1999 Notice of Violation from Investigation Conducted on 971231. Violation Noted:On 971015,A Wells,Employee on Entergy Operations,Inc,Submitted to NRC Info Known to Be Inaccurate in Some Respect Matl to NRC ML20198T0691999-01-0505 January 1999 Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $55,000.Violation Noted:Info Was Provided to Senior Resident Inspector That Was Not Complete & Accurate in All Matl Respects Re 971010 of RWP 97-0002 ML20203A6601999-01-0505 January 1999 EN-99-001:on 990105,notice of Proposed Imposition of Civil Penalty in Amount of $55,000 Issued to Licensee.Action Based on Severity Level III Violation Involving Superintendent of Radiation Control at Licensee River Bend Station Facility ML20198N9311998-12-29029 December 1998 Insp Rept 50-458/98-16 on 980730-0807.Violations Noted. Major Areas Inspected:Engineering & Fire Protection.Also Reviewed,Status of Various Programs Which Were Planned or in Progress IR 05000458/19980161998-12-29029 December 1998 Insp Rept 50-458/98-16 on 980730-0807.Violations Noted. Major Areas Inspected:Engineering & Fire Protection.Also Reviewed,Status of Various Programs Which Were Planned or in Progress ML20198N9151998-12-29029 December 1998 Notice of Violation from Insp on 980720-0807.Violation Noted:On 980724,licensee Made Change to Facility as Described in Safety Analysis Rept,Which Created Unreviewed Safety Question,Without Prior Commission Approval IR 05000458/19980991998-12-22022 December 1998 SALP Rept 50-458/98-99 Canceled.Process Suspended for Two Yrs.No Insp Rept Will Be Issued for Number IR 05000458/19980181998-11-30030 November 1998 Insp Rept 50-458/98-18 on 980920-1031.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support ML20196G5161998-11-25025 November 1998 Insp Rept 50-458/98-10 Has Been Canceled.No Insp Rept Will Be Issued IR 05000458/19980191998-11-20020 November 1998 Insp Rept 50-458/98-19 on 981019-23.No Violations Noted. Major Areas Inspected:Operations IR 05000458/19980131998-10-27027 October 1998 Insp Rept 50-458/98-13 on 980608-12,22-26 & 0824-28.Apparent Violations Being Considered for Escalated Enforcement Action.Major Areas Inspected:Operations,Maint & Engineering IR 05000458/19980141998-10-21021 October 1998 Insp Rept 50-458/98-14 on 980928-1002.No Violations Noted. Major Areas Inspected:Operational Status of Licensee Emergency Preparedness Program IR 05000458/19980171998-10-0505 October 1998 Insp Rept 50-458/98-17 on 980809-0919.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000458/19980151998-08-28028 August 1998 Insp Rept 50-458/98-15 on 980628-0808.No Violations Noted. Major Areas Inspected:Operations,Maintenance,Engineering & Plant Support ML20154L7021998-08-17017 August 1998 Corrected Notice of Violation from Insp Completed on 980218. Corrected NOV Sent to Make Consistent with Ltr Sent on 980722 & to Make Clear That No Response Required ML20236V2081998-07-29029 July 1998 Notice of Violation from Insp on 980517-0627.Violation Noted:On 980601,while Accomplishing Clearance Order 98-0583, Operator Did Not Follow Sequence Shown on Clearance Order While Positioning Components IR 05000458/19980121998-07-29029 July 1998 Insp Rept 50-458/98-12 on 980517-0627.Violations Noted.Major Areas Inspected:Operations,Maint,Engineering & Plant Support ML20154M5531998-07-22022 July 1998 Notice of Violation from Investigation Completed on 980323. Violation Noted:On 970908,WJ Ginn,Employee of Contractor to Entergy Operations,Inc,Deliberately Submitted Info to Licensee That Was Incomplete & Inaccurate ML20154L7351998-07-22022 July 1998 Notice of Violation from Investigation Completed on 980218. Violation Noted:On 970711,DL Brown Employee of Contractor to Util Deliberatly Submitted Info to Licensee That Brown Knew Incomplete & Inaccurate on Security Questionnaire IR 05000458/19980071998-06-0808 June 1998 Insp Rept 50-458/98-07 on 980518-21.No Violations Noted. Major Areas Inspected:Implementation of Radiological Environ Monitoring & Meteorological Monitoring Programs IR 05000458/19980081998-06-0505 June 1998 Insp Rept 50-458/98-08 on 980405-0516.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000458/19980111998-06-0404 June 1998 Insp Rept 50-458/98-11 on 980518-21.No Violations Noted. Major Areas Inspected:Maint IR 05000458/19980061998-05-19019 May 1998 Insp Rept 50-458/98-06 on 980427-0501.No Violations Noted. Major Areas Inspected:Implementation of Liquid & Gaseous Radioactive Effluent Waste Mgt Program IR 05000458/19980091998-04-30030 April 1998 Informs That Insp Rept 50-458/98-09 Has Been Canceled ML20217A4461998-04-17017 April 1998 Notice of Violation from Insp on 980222-0404.Violation Noted:Established Measures Did Not Assure That Deviation from Environ Design Criteria Was Controlled ML20217A4801998-04-17017 April 1998 Insp Rept 50-458/98-05 on 980222-0404.Violations Noted. Major Areas Inspected:Operations,Main,Engineering & Plant Support PNO-IV-98-016, on 980413,operators at River Bend Station Initiated Normal Reactor Shutdown.Plant Shutdown Deemed Necessary After Operators Identified Main Generator Hydrogen Seal Oil Leak at Main Generator Casing1998-04-14014 April 1998 PNO-IV-98-016:on 980413,operators at River Bend Station Initiated Normal Reactor Shutdown.Plant Shutdown Deemed Necessary After Operators Identified Main Generator Hydrogen Seal Oil Leak at Main Generator Casing ML20217B4701998-03-24024 March 1998 Notice of Violation from Insp on 980223-26.Violation Noted: Licensee Not Maintained Records of Reviews of Radiation Protection Program Content & Implementation ML20217B4951998-03-24024 March 1998 Insp Rept 50-458/98-03 on 980223-26.Violations Noted.Major Areas Inspected:Review of Radiation Protection Program Activities IR 05000458/19972011998-03-20020 March 1998 Fire Protection Insp Rept 50-458/97-201 on 970615-20, 0629-0703,0819,980120 & 0305.No Violations Noted.Major Areas Inspected:Comprehensive Evaluation of Fire Protection Program & Post Fire Safe Shutdown Capability 1999-09-08 |
~
}
}
-dx a February 22,_1988 PRELIMINARY NOTIFICATION 0F EVENT OR UNUSUAL OCCURRENCE -- PN0-IV-88-13A
~
- This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The information is as initially received
'without verification or evaluation, and is. basically all that is known by the Region IV staff on this date.
FACILITY: Licensee Emergency Classification:
Gulf States Utilities Notification of Unusual Event-River Bend Station ~'- Al e rt St. Francisville, Louisiana: Site Area' Emergency General Emergency DN: 50-458 X Not Applicable
SUBJECT:
SHUTDOWN IN EXC iSS OF 48 HOURS This PN updates PN0-IV-88-13, issued on' February 19, 1988.
The licensee entered an anticipated 7-day outage on February 19,-1988, to investigate and repair the ' A' reactor recirculation pump motor which had tripped on an over-current condition while the plant was at 100% power. The licensee determined that moisture in the pump motor cable conduit was the~. source of tb ground to the pump' motor. After effecting repairs to the electrical terminations on the 'A' reactor recirculation pump motor and other unrelated maintenance, the license comenced a reactor startup.
On February 21,1988, at 10:26 p.m. (CST) with the reactor at 4 percent power, a reacto.' scram occurred during shell warming of the main turbine. The licensee allowed turbine first stage pressure during the wann up to exceed a pressure equivalent to that at 40 percent power. With the turbine tripped and turbine first stage pressure greater than the equivalent at 40 percent power, an automatic reactor scram occurs.
The licensee has adoed a caution in the turbine startup procedure regarding the possibility of a reactor scram because of turbine first stop pressure during shell warming. Reactor startup is expected to comence during the day shift on February 22, 1988. The senior resident inspector is monitoring the licensee's actions.
There have been no news media inquiries-regarding this matter.
Neither the licensee nor the NRC plans to issue a press release.
The state of Louisiana will be infonned.
Region IV received notification of this occurrence by telephone from the Senior Resident Inspector at 7:30 a.m. (CST) on February 22, 1988. Region IV has informed NRR.
I This information has been confirmed with a licensee representative.
CONTACT- E Y . Holler, FTS 8-8287 h DRP LJ 1an:gb RA RDMa n h I 2/ 88 2/4/88 0 22 17 800222 PHO-IV-88-013A DCD
a MSTFPByTION: ,
MAIL:
H. St. MNBB E/W Willste UC5-(Original ) -
Chairman Zech AE00 0IA .NMSS -D0T:(Transonly).
Comm. Roberts PA 01
. Comm. Bernthal 0GC- LFAX:
'Comm. Carr ED0 TRF0 Comm. Rogers ARM '
NSAC SECY- RRI CA NRC OC PDR Phillips AirRights LICENSEEi~-
OGC-H NRR SLITP (Reactor Licensee)
GPA ACRS Nicholson Lane Regional Offices RES Tr smitted via~ 20:-
, Ja//E - /1. ,
L