Notice of Violation from Insp on 990710.Violation Noted:From 990224-0325,River Bend Station Operated in Mode I Without Three Operable EDGs
ML20212L977
Person / Time
Site: River Bend Entergy icon.png
Issue date: 10/05/1999
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20212L975 List:
References
50-458-99-07, EA-99-158, NUDOCS 9910080067
Download: ML20212L977 (2)


Text

~

i NOTICE OF VlOLATION j Entergy Operations. Inc. Docket No. 50-458 ,

River Bend Station License No. NPF-47 1 EA 99-158 iDuring an NRC inspection completed July 10,1999, violations of NRC requirements were

. identified. In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violations are listed below:

River Bend Station Technical Specification 3.8.1.b requires that three diesel generators be operable in Modes 1,2 and 3. Technical Specification 1.1 defines OPERABLE as follows: "A system . . . shall Le OPERABLE or have OPERABILITY when it is capable of performing its specified safety function (s) . . ." The emergency diesel generator's safety function is to provide an afternate safety-related electrical power source in response to an event involving the loss of off site power, for the duration cf the event.

10 CFR Part 50, Appendix B, Criterion V requires, in part, that activities affecting quality be prescribed by documented instructions, procedures, or drawings, of a type appropriate to the circumstances.

l The River Bend Station " Maintenance Planning Guideline," Revision 6, Section 6.5.9.5  !

states, in part, " Reference all procedures, vendor procedures, and design documents '

required to perform the work instruction and to icturn the . . . system . . . to operational or desired status." )

Contrary to the above:

1. From February 24 to March 25,1999 River Bend Station operated in Mode l without three operable emergency diesel generators. Specifically, the Division i emergency diesel generator was inoperable during this period due to an improperly staked fuel booster pump coupling pin. The coupling pin came loose 55 minutes into a 1-hour sur/eillance run of the diesel on March 24,1999. It was subsequently determined that the diesel had been incapable of performing its '

intended safety function since the fuel booster pump coupling pin was j reassembled during maintenance on February 24,1999.

2. Maintenance Action Item 319116, which provided work instructions for the ,

February 23-24,1999, Division i emergency diesel generator fuel booster pump disassembly and repair, was not appropriate to the circumstances, in that it failed to reference all procedures, vendor procedures, and desigri documents required to perform the work instruction and to return the system to operational status.

- Specifically, the work pbnner did not specify the use of Loctite 680, an adhesive, when assembling the fuel booster pump coupling and did not reference the associated vendor instructions. The " Vendor Manual" contained Cooper-Enterprise Service Information Memo ( SIM 363), Revision 1, dated 12/2/93 which states, in part . . . " Reports have been received from the field that the. . .

fuel booster pump drive couplings have worked loose under certain operation conditions. Failure of this coupling will result in a loss of fuel oil pressure . . .

9910090067 991005

PDR AD3CK 05000458 a PDR

[1

b 1

2 c

The coupling should be instal!ed on the over speed governor drive assembly -I using Loctite 680."

These violations represent a Severity Level 111 problem (Supplement 1).

The NRC has concluded that information regarding the reason for the violations, the corrective actions taken and planned to correct the violations and prevent recurrence, and the date when :

full compliance was achieved is already adequately addressed on the docket in inspection Report 50-458/99-07, and in Entergy Operations, Inc.'s September 7 and September 24,1999,

- letters. However, you are required to submit a written statement or explanation pursuant to

' 10 CFR 2.201 if the description therein does not accurately reflect your corrective actions or

- your position.' in that case, or if you choose to respond, clearly mark your response as a " Reply to a Notice of Violation," and send it to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555 with a copy to the Regional Administrator, Region IV,611 Ryan Plaza Drive, Suite 400, Arlington, Texas 76011, and a copy to the NRC Resident inspector at River Bend Station facility within 30 days of the date of the letter transmitting this Notice of Violation (Notice).

If you contest this enforcement action, you should also provide a copy of your response, with the basis for your denial, to the Director, Office of Enforcement, United States Nuclear

- Regulatory Commission, Washington, DC 20555-0001.

l If you choose to respond, your response will be placed in the NRC Public Document Room (PDR). Therefore, to the extent possible, the response should not include any personal privacy,

. proprietary, or safeguards information so that it can be placed in the PDR without redaction. If personal privacy or proprietary information is necessary to provide an acceptable response,

- then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your response that deletes such information. If you request withholding of such material, you mynt specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of withholding

~

(e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2.790(b) to support a request for

- withholding confidential commercial or financial information). If safeguards information is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21. j Dated this day of October 1999

,