Rev 0 to San Onofre Nuclear Generating Station Unit 1 10CFR50,App R,Section Iii.G Compliance Evaluation
ML20133D318
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 09/30/1985
From:
ABB IMPELL CORP. (FORMERLY IMPELL CORP.)
To:
Shared Package
ML13323A454 List:
References
01-0310-1435, 01-0310-1435-R00, 1-310-1435, 1-310-1435-R, TAC-64883, NUDOCS 8510090033
Download: ML20133D318 (634)


Text

{{#Wiki_filter:__ 4 l l i SOUTIERN CALIFORNIA EDISON SAN ONOFRE NUCLEAR GENERATING STATION UNIT 1 i GENERIC LETTER 81-12 RESPONSE ENCLOSURE 1

,k sg
           $Bh1885SSbSlhS6 F

'(Gj

O SAN ON0FRE NUCLEAR GENERATING STATION UNIT 1 10CFR50 APPENDIX k, SECTION III.G COMPLIANCE EVALUATION Prepared for Southern California Edison Prepared by ' Impell Corporation

                                            ~350 Lennon Lane Walnut Creek, CA 94598                                                          .

Impell Report No. 01-0310-1435 Revision 0 September 1985 O

SAN Of0FRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION LIST OF EFFECTIVE PAGES Section Title Effective Pages Revision Title Page -- List of Effective Pages i Taole of Contents 11 1.0 Introduction 1-1 through 1-2 0 2.0 - Methodology 2-1 tnrougn 2-21 0 3.0 Fire Area / Zone Drawings 3-1 Figure 3-1 0 Figure 3-2 0 Figure 3-3 0 Figure 3-4 0 4.0 Detailed 10CFR50 Appendix R 4-1 0 0 Section III.G Compliance Evaluation C0-1 through C0-42 0 Containment Reactor Auxiliary Building AB-1 through AB-39 0 Yard Areas YD-1 through YD-90 0 Fuel Handling Building FH-1 through FH-27 0 Power Block PB-1 througn PB-266 0 Turbine Buildirig TB-1 tnrough TB-86 0 Diesel Generator Building DG-1 tnrough DG-52 0 Ventilation Equipment Room VN-1 tnrough VN-2 0 5.0 References 5-1 0 i , l Impell Corporation Report 01-0310-1435 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION O TABLE OF CONTENTS Section Page 1.0 Introduction 1-1 2.0 Methodology 2-1 3.0 Fire Area / Zone Drawings 3-1 4.0 Detailed 10CFR50 Appendix P, Section III.G Compliance Evaluation 4-1 5.0 References 5-1 O O Impell Corporation Report 01 Revision 0

                 .-0310-1435- . . - . - - - _ - - - - - . , . - - - . - . - . _ . - -

l SAN ON0FRE NUCLEAR GEPERATING STATION - UNIT 1 l 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION

1.0 INTRODUCTION

l This report has been prepared by Southern California Edison-San Onofre Nuclear Generating Station, Unit 1, in accordance with the requirements of 10CFR50 Appendix R, Section III.G, to demonstrate the capaDility to safely shut down the plant in the event of fire. The report is divided into five sections, including this introductory section. Tne second section of the report details the methodology used to perfonn the compliance evaluation. Figures wnich show the division of the plant into fire areas and fire zones are included in Section 3 of the report. The fourth section provides the detailed evaluation of the compliance of each fire area / zone to the requirements of 10CFR50, Appendix R, Section III.G. Tne final section lists the references used in the peformance of the evaluation. The evaluation is based on the systems required for safe shutdown in the event of fire as defined in Revision 1 to the Updated Fire Hazards Analysis for San Onofre Nuclear Generating Station, Units 1, 2, and 3, except as noted below:

           -    the consideration of the effects of the spurious operation of components which define the high/ low pressure interface on the primary system;
           -    the consideration of the effects of the spurious operation of O

v boundary components of support and secondary systems;

            -   the inclusion of the dedicated shutdown system;
            -   the conceptual design for the dedicated shutdown system, as submitted to the Nuclear Regulatory Commission on April 24, 1984, and Revision 1 to the conceptual design (submitted in response to NRC questions);
            -   the review of normal, alternate, and dedicated shutdown systems against the functional requirement of 10CFR50, Appendix R, Section III.L.

For the purpose of this evaluation, tne plant fire areas and zones, as defined in Revision 1 to the Updated Fire Hazards Analysis, have Deen revised to reflect the division of the plant into those fire areas / zones whose boundaries may be expected to contain a fire due to the in situ comoustibles. The revision of the plant fire area / zones may be summarized as follows:

            -   A new fire area was created for the roof of the power block (1-PB-56-33).
            -   The yard, formerly fire zone 1-AB-14-2J, has been redefined as a zone of the yard fire area (1-YD-14-4D).

C Impell Corporation Report 01-0310-1435 1-1 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION The penetration area, formerly fire area 1-PE-20-23, has been redefined as three zones within the yard fire area: east penetration area (1-YD-20-4A) west penetration area (1-YD-20-48) doghouse (1-YD-20-4C)

      -   The circulating water pump well, formerly fire zone 1-AB-(-7)-2M, has been redefined as a zone of the yard fire area (1-YD-(-7)-4E).
      -   The condensate storage tank area, formerly fire zone 1-AB-14-2K, has been redefined as a zone of the yard fire area (1-YD-14-4F).
      -   The PASS compartments, formerly 1-PE-7-27 and 1-PE-7-28, were renamed as 1-YD-7-27 and 1-YD-7-28, respectively.

~

       -  The pipe tunnels, formerly 1-AB-11-2E and 1-AB-14-2Q, have been redefined as fire areas 1-AB-11-34 and 1-AB-14-35 respectively.
       -  A new fire zone was created for the ramp (1-TB-14-9E).
       -  The boric acid injection pump room (1-AB-20-28) has been redefined as part of the fire zone which contains the reactor auxiliary building lower level (1-AB-(-3)-2A).

The revised fire area / zone boundaries are shown on Figures 3-1 throupb 3-4 in Section 3 of this report. O Impe11 Corporation Report 01-0310-1435 1-2 Pevision 0

SAN CNCFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G CCMPLIANCE EVALUATION n V 2.0 METHODOLOGY The evaluation of plant compliance to 10CFR50, Appendix R, Section III.G requires that the plant demonstrate that: a single fire will not damage redundant systems required for safe shutdown; damage to associated non-safety circuits of concern which could prevent operation or cause maloperation due to hot shorts, open circuits, or shcrts to around will not result in the loss of redundant systems required for safe shutdown. In accordance with the guidance provided by Generic Letter 81-12, plant compliance to these requirements was analyzed by the perforwance of the following tasks: Development of the Safe Shutdown Equipment List Development of the Minimum Required Circuits List Safe Shutdown Circuit Routing Comon Power Supply Analysis Comon Enclosure Analysis Circuit Analysis Review of Fire Area / Zone Boundaries Evaluation of Compliance to 10CFR50, Appendix R, Section III.G The criteria, assumptions and methodology used to perform each of these tasks are outlined below. 2.1 Criteria The criteria used to perform the evaluation are as follows:

                - The plant shall be evaluated against the requirements of 100FR50, Appendix R, Section III.G, Fire Protection of Safe Shutdown Capability. Clarification of the requirements of Appendix R shall be obtained from the following guidance documents:

Generic Letter 81-12 (1,2) Generic Letter 83-33 (3) IE Information Notice 84-09 (4)

                     , Generic Letter 85 Draft (5)

Impe11 Corporation Report No. 01-0310-1435 2-1 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 l 10CFR50 APPENDIX P, SECTION III.G COMPLIANCE EVALUATION j l

 +

O - Those plant fire area / zones for which alternate or dedicated shutdown capability is credited shall be additionally evaluated

                                                                                                                          )

4 aoainst the requirements of 10CFR50, Appendix P, Section III.L. Alternative or Dedicated Shutdown Capability. ,

                                -   Plant transients resulting from the most severe of the following spurious operations shall not result in an unrestorable condition (5):                                                                        ;
a. The safe shutdown capability should not be adversely affected by l any one spurious actuation or signal resulting from a fire in any i plant area. l
b. The safe shutdown capability should not be adversely affected by a fire in any plant area which results in the loss of all automatic function (signals, logic) from the circuits located in
          -                             the area in conjunction with one worst case spurious actuation or                 l t                                       signal resulting from the fire.                                                   I
c. The safe shutdown capability should not be adversely affected by a fire in any plant area which results in the simultaneous spurious actuation of all valves in high/ low pressure interface i

lines. I 2.2 Assumptions l The assumptions used to perform the evaluation are as follows:

                                 -  The plant is assumed to be at full power operation.
                                 -  Plant accidents or the most severe natural phenomena are not i                                    postulated to occur simultaneously with the fire or subsequent plant shutdown.

4

                                 -  The fire occurs concurrent with a loss of offsite power. Power for the operation of safe shutdown equipment is available from the 4                                   emergency diesel generators, or the dedicated diesel generator.
                                 -  Simultaneous fires in separate fire areas or fire zones are not
postulated.
                                 -  Manual actions may be taken to locally control systems / components which are nomally automatically controlled.
                                  - Loss of piping and passive components (i.e. check valves, tanks, etc.) is not postulated to occur as a result of the fire.
                                  - The reactor cavity cooling fans are required to provide coolina for                   l the source range monitors. Existing procedures provide required cooling for other safe shutdown components in the event HVAC is lost, by natural ventilation through openings, open doors, and the use of portable exhaust fans.

4 Impe11 Corporation Report No. 01-0310-1435 2-2 Revision 0 l

               &          r.-                                                 m - -. -                  '  -           1+ -L SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION O                  -        Offsite power was assumed to be available for those spurious operations which could adversely affect safe shutdown of the plant, until such time as operator action is taken to isolate the offsite power. No credit is taken for offsite power availability if the spurious actuation could result in assisting plant shutdown.

A three phase to three phase hot short between 480V AC power cables is not considered credible. 2.3 Development of the Safe Shutdown Equipment List The systems and components needed for post-fire shutdown are those systems necessary to perfom the shutdown functions defined in 10CFP50, Appendix P, Section III.L, Alternative or Dedicated Shutdown Capability. These guidelines also apply to the systems needed for normal post-fire shutdown capability (3). The acceptance criterion for post-fire shutdown systems is also defined in 1 Section III.L: During the post-fire shutdown, the reactor coolant system process variables shall be maintained within those predicted for a loss of normal AC power, and the fission product boundary integrity shall not be affected: 1.e. there shall be no fuel clad damage, rupture of any primary coolant boundary, or rupture of any of the containment boundary. The post-fire shutdown systems shall be capable of achieving the following functional requirements, assuming a loss of normal AC power:

                        -       The reactivity control function shall be capable of achieving and maintaining cold shutdown reactivity conditions.
                        -       The reactor coolant makeup function shall be capable of maintaining the reactor coolant level within the level indication in the pressurizer.
                        -       The reactor heat removal function shall be capable of achieving and maintaining decay heat removal.
                        -       The process monitoring function shall be capable of providing direct

. readings of the process variables necessary to perform and control the above functions.

                        -       The supporting functions shall be capable of providing process cooling, lubrication, etc., necessary to permit the operation of the
equipment used for safe shutdown functions.

l The systems required for safe shutdown in the event of fire were identified in Appendix A of Pevision 1 to the Updated Fire Hazards Analysis (6), These safe  ; ' shutdown systems were reviewed in two stages to insure that the safe shutdown l systems identified were in compliance with the Appendix R requirements. l l Impe11 Corporation Report No. 01-0310-1435 2-3 Revision 0 i l

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX P, SECTION III.G COMPLIANCE EVALUATION During the first stage of the review, the safe shutdown systems were evaluated ) against the perfomance goals for shutdown functions listed above. In the i i second stage of the review, the flow path required for the operability of the safe shutdown . system was highlighted on the system piping and instrumentation diagram (P8ID). The highlighted P& ids were then studied to insure that all

        . pressure boundaries had been identified and isolated.

Table 2-1, SONGS 1 Safe Shutdown Components, summarizes the results of the

 ,        review of the highlighted P8 ids (17). Each component shown on the highlighted P& ids is listed on the table by system.                                   In addition, the component is categorized as required for hot standby, cold shutdown, alternate shutdown, dedicated shutdown, high/ low pressure interface, or as a spurious operator, based on the following definitions:

Hot Standby Equipment - components which are required to operate to achieve or maintain hot standby conditions. Passive mechanical components, i.e., heat exchangers, are included for completeness. Boundary components, which are normally in the position required to achieve or maintain hot standby, are not included here. These components are addressed as high/ low pressure interface or spurious operation equipment. Cold Shutdown Equipment - components which are required to operate to cooldown from hot standby conditions to cold shutdown, or to maintain cold shutdown conditions. Passive mechanical components, i.e., heat

!                  exchangers, are included for completeness. Boundary components, which are normally in the position required to achieve or maintain cold shutdown, are not included here. These components are addressed as spurious operation equipment.

Alternate Shutdown Equipment - components used to provide an alternative means of achieving the safe shutdown function, when the , normal systems / components used for safe shutdown in the event of fire are damaged by a single fire. Dedicated Shutdown Equipment - components composing the dedicated shutdown system, up to and including the interface with the normal shutdown components. High/ Low Pressure Interface - equipment which maintains the integrity of the high/ low pressure interface between the reactor coolant sytem and other plant systems. Failure of high/ low pressure interface components could result in a loss of coolant accident. Spurious Operation Equipment - equipment whose inadvertent operation could adversely affect safe shutdown system operation. ! Safe Shutdown Component - components which are classified as required for hot standby, cold shutdown, alternate shutdown, dedicated shutdown, high/ low pressure interface, or as spurious operation equipment. O Impe11 Corpcration i Report No. 01-0310-1435 2-4 Revision 0

SAN ONOFRE. NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION 2.4 Development of the Minimum Pequired Circuits List The minimum required circuits constitute those circuits which, if damaged, could affect the operation of the safe shutdown components identified above. Circuits which are used for indication only, i.e., pump running status, are not considered as required for safe shutdown, as a single failure is not postulated concurrently with a fire. The required circuits were identified through a review of the station elementary diagrams and station circuit schedules in a three step process.

First, the station circuit schedules were updated using a computerized database manager. Second, the station elementary diagrams were reviewed to determine the circuits which could affect the operation of each safe shutdown component. A block diagram was then developed to illustrate the functional relationships of the circuits for that component. Finally, the circuit schedule was searched to determine the cable identification for each of the circuits on the component's block diagram.

Using the block diagrams, a list of required circuits for each component was developed and input into a computerized database (29). 2.5 Safe Shutdown Circuit Pouting The required circuits for each safe shutdown component were routed by fire area / zone by deterwining, from the raceway layout drawings, the fire area / zone O location of each of the raceways or enclosures through which the circuit was routed. A computerized database of the safe shutdown circuit raceways and enclosures (18) was then used to sort the safe shutdown circuits by fire area / zone. (7-16,18). Field walkdowns were performed for those safe shutdown circuits for which adequate information did not appear in the station circuit schedules or raceway layout drawings (19). 2.6 Common Power Supply Analysis The damage of associated circuits which share a common power supply with components required for hot standby, cold shutdown, or alternate or dedicated shutdown, could result in the loss of power to those safe shutdown components if proper breaker coordination is not provided. The breaker coordination analysis for San Onofre Nuclear Generating Station Unit 1 (20) demonstrates that proper breaker coordination is provided by:

                  -  Buses supplying power to equipment required for hot standby, cold shutdown, or alternate shutdown are properly coordinated.

O I Impell Corporation Report No. 01-0310-1435 2-5 Revision 0

SAN ON0FRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION

          -   Buses which supply power only to boundary components (high/ low pressure interface or spurious operators) need not be properly coordinated, as these components are chosen such that the failure mode of the boundary valve on loss of power is the desired position for safe shutdown.
          -   Intertie breakers between the 480V AC switchgear are properly coordinated.
          -   Train separation between the 4160V AC buses is maintained by racking out the intertie breaker between 4160V buses 1A and 1B.
          -   Equipment required for dedicated shutdown is supplied power from a dedicated diesel generator. There are no associated loads, as the dedicated diesel generator supplies only those loads required for dedicated shutdown.

2.7 Common Enclosure Analysis The damage of associated circuits sharing a comon enclosure with safe shutdown loads could propagate the fire beyond the boundaries defining the fire area / zone. The propagation of the fire could result from either of two causes: the combustion of the cable insulation, or the electrical overheating n of the cable. The comon enclosure evaluation demonstrates that associated circuits due to comon enclosures will not endanger safe shutdown, as:

           -  all circuits at San Onofre Nuclear Generating Station Unit 1 are provided with proper fuse or breaker protection per the applicable industry codes (21);
           -   all cable trays are fire sealed or fire stopped at fire area / zone boundaries (23).

2.8 Circuit Analysis The circuits required for the operation of each safe shutdown component were analyzed to determine how the failure of any of the circuits would affect the operation of the component. The Circuit Analysis (22) postulates each type of fault which could occur in the cable, and using the electrical elementary drawings, determines how the safe shutdown component will operate as a result of the fault. The following circuit failure modes are postulated:

            -  For component sower cables, three types of cable faults are postulated. T1ese are: open circuits, short to ground, and wire to wire short circuit.

Impe11 Corporation Report No. 01-0310-1435 2-6 Revision 0 l

                                                                                             - _ - .     ~_ ._

SAN ONOFPE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION

                     -   For component control cables, open circuits, short circuits to ground, and wire to wire faults are postulated. For clarity, the analysis documents the resulting position of the controlled i                        component, e.g. the spurious position of the flow control valve, not i

the solenoid valve operator.

                     -   For instrumentation, three types of cable failures are evaluated.

These are: open circuit and short circuit failure of the instrument signal loads, and the open circuit failure of the instrument power leads. All cable failures were evaluated for their effect on the instrument indication and/or control circuits. 2.9 Peview of Fire Area / Zone Boundaries Section III.G of 10CFR50, Appendix R sets forth the requirement for fire protection of safe shutdown capability on the basis of fire areas. A fire area is defined (3) as that portion of a building or plant that is separated from other areas by boundary fire barriers (walls, floors, or roofs) with any openings or penetrations protected with seals or closures having a fire resistance rating equal to that of the barrier. The division of the plant into fire area / zones is based on an evaluation of the boundaries of those fire area / zones to withstand the hazards associated with the fire area or zone, and to protect the equipment within the fire

   ,V area / zone from a fire outside the area / zone.

The performance of the 10CFR50, Appendix R, Section III.G Compliance Evaluation on the basis of these fire areas and fire zones requires that an analysis demonstrate that the boundaries of the fire area / zone will limit the consequences of the fire in that area / zone to that area / zone. The Fire Area / Zone Verification (23) establishes the adequacy of these fire area / zone boundaries for preventing the propagation of fire between adjacent fire area / zones. A number of factors were considered in determining the adequacy of a fire area / zone boundary (5, 23). These factors include:

                      -  the construction of the walls, floor, and ceiling of the fire area / zone.
                      -  the size and location of any openings in the walls, floor or ceiling of the fire area / zone.
                      -  the fire loading due to the in situ combustibles in the fire area / zone.
                      -   the protection of the structural steel within the fire area / zone.
                      -  the adequacy of any fire suppression / detection systems in the fire area / zone.

Impe11 Corporation Report No. 01-0310-1435 2-7 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION n -V 2.10 Evaluation of Compliance to 10CFR50, Appendix P, Section III.G Section 4 provides the detailed 10CFR50, Appendix R, Section III.G Com)11ance Evaluation for each fire area / zone. The compliance evaluation for eac1 fire ' area / zone consists of two parts:

  -        Effects of Fire on Safe Shutdown Capability                                                 l This section sumarizes the consequences of the design' basis fire on safe shutdown capability.
  -        III.G Compliance Evaluation This table provides a comarehensive listing of the safe shutdown equipment and cables in tie fire area / zone, and the consequences of fire damage to each component or cable.                                                     l The approach and methods used to develop each of the sections of the III.G compliance evaluation for each fire area / zone are detailed below.

2.10.1 Effects of Fire on Safe Shutdown Capability This section contains a sumary of the consequences of the design basis fire n and the equipment credited for achieving hot standby and cold shutdown. This section is also used to evaluate the worst case spurious actuations for the U fire area / zone. The acceptability of the plant transients resulting from any spurious actuation is analyzed using the results of previous thermal hydraulic and accident analyses as documented in the evaluation of plant transients due to fire (24-28). 2.10.2 10CFR50 Appendix P, Section III.G Compliance Evaluation This table lists the safe shutdown components and cables which are located , within the fire area / zone, the consequences of loss of each of these components / cables, and the action required to mitigate the loss of the component. The table is divided into seven columns: 2.10.2.1 Category This column lists the category of the safe shutdown component. The safe shutdown equipment is discussed in the following order: Hot Standby Equipment Cold Shutdown Equipment High/ Low Pressure Interface Spurious Operation Equipment Alternate Shutdown Equipment Dedicated Shutdown Equipment Impe11 Corporation Report No. 01-0310-1435 2-8 Revision 0

                    --mme SAN ONOFFE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATICN v    2.10.2.2 System This column lists the system which the safe shutdown component serves. The systems required for safe shutdown are discussed in the following order:

4160V AC 480V AC 120Y AC 125V DC Reactor Coolant System (RCS) Chemical and Volume Control System (CVCS) Main Steam System (MSS) Auxiliary Feedwater System (AFW) Component Cooling Water System (CCW) Saltwater Cooling System (SWC) Reactor Cavity Cooling Syster (CVS) Diesel Generator Systems (DGS) Gaseous Nitrogen System (GNI) Residual Heat Removal (PHR) Safety Injection System (SIS) 2.10.2.3 Component This column lists the component which is located within the fire area / zone, or p which is served by the cables which are routed through the fire area / zone. j The components, which are already divided by category and system, are grouped by function as follows: Pumps Fans Valves Instrumentation 2.10.2.4 Circuit-Schedule This column lists the cable identification of the safe shutdown circuit which is routed through the fire area / zone. Note that if the safe shutdown component itself is located within the zone, this column is not applicable and is left blank. 2.10.2.5 Function This column lists the function of the component or circuit which is located within the fire area / zone. O \_/ Impell Corporation Report No. 01-0310-1435 2-9 Revision 0

t - -. , SAN ON0FRE NUCLEAR GENERATING STATION - UNIT 1 , l 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION O 2 .10.2.6 Consequence of Fire Tne consequences of the loss of etch circuit located within tne fire area / zone l are sumarized from the Circuit Analysis. Note that if the safe snutdown l component itself is located within the fire area / zone, the consequence of the fire is assumed to be the loss of the planp. fan or instrument in question.  ! Manual action may be taken to locally control a valve located within the fire . area / zone af ter the fire is extinguished. Passive components, such as tanks, l' are not considered vulnerable to fire. i I 2.10.2.7 Mitigation i The action, if any, which must be taken to mitigate the effects of the fire I damage to the safe shutdown components and circuits is listed in this column. j . These actions may include the use of alternate or dedicated shutdown equipment l or operator action to deenergize and manually operate a valve. r l l O l l O  ; l ! Impell Corporation Report No. 01-0310-1435 2-10 Revision 0

SAN ONOFPE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION i o T/ OLE 2-1 SONGS 1 SAFE SHUTDOWN COWONENTS SYSTEM CATEGORY COWONENT DESCRIPTION 120V HSB 15 KVA XFRMR 480V/120V XFMR, ALT FEED TO Y29, Y30 120V HSB 37.5 KVA XFR m 480V/120V XFMR FEED->Y15, ALT FEED->Y11-14,33 120V HSB 7.5 KVA XFRm 480V/120V FEED TO Y14 120V DSE C-38 DEDICATED SHUTDOWN PANEL 120V HSB Y11 VITAL BUS 1 120V HSB Y11R REGULATED BUS 1 120V HSB Y12 VITAL BUS 2 -

  • 120V HSB Y12R REGULATED BUS 2 120V HSB Y13 VITAL BUS 3 120V HSB Y13R REGULATED BUS 3 120V HSB Y14 VITAL BUS 4 120V HSB Y14R REGULATED BUS 4 120V HSB Y15 UTILITY BUS 120V HSB Y29 VITAL BUS 5 120V HSB Y30 VITAL BUS 6 120V HSB Y33 VITAL BUS 3 A .

120V HSB YV11 INVERTER 1 /O 120V HSB YV12 INVERTER 2 V 120V 120V HSB HSB YV13 YV14 INVERTER 3 INVERTER 4 120V HSB YV29 INVERTER 5 125V HSB 001 DC BUS 1 125V HSB 002 BATTERY OiARGER A 125V HSB 003 BATTERY QiARGER B 125V HSB 004 BATlERY 1 125V HSB 008 DC BUS 2 125V HSB 009 BATTERY OiAFGER C 125V HSB D10 BATTERY OiARGER D 125V HSB D11 BATTERY 2 4160 HSB BUS 1C 4160V BUS 1C 4160 HSB BUS 20 4160V BUS 2C 480V HSB MCC 1 MOTOR CONTROL CENTER 1 480V HSB MCC 1A MOTOR CONTROL CENTER 1A 480V HSB MCC 1B MOTOR CONTROL CENTER 1B 480V HSB MCC 2 MOTOR CONTROL CENTER 2 480V HSB MCC 2A MOTOR CONTROL CENTER 2A 480V HSB MCC 28 MOTOR CONTROL CENTER 2B 480V HSB MCC 3 MOTOR CONTROL CENTER 3 480V HSB SWGR 1 480V SWITQiGEAR 1 480V HSB SWGR 2 480V SWITCHGEAR 2 480V HSB SWGR 3 480V 3tITCHGEAR 3 - ALT POWER FROM BUS 2C 480V HSB XO6 STATION SERVICE XFRMR 1 480V HSB XO7 STATION SERVICE XFRMR 2 480V HSB XO8 STATION SERVICE XFRMR 3 AFW HSB CV-113 AFW TUfEINE STEAM SUPPLY PRESSURE CONTROL AFW HSB CV-3201 AFW TUFBINE STEAM SUPPLY CONTROL V AfW HSB CV-3213 AFW PUW G-10 DISCHARGE (DNTROL VALVE Isrpell Corporation Report No. 01-0310-1435 2-11 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G CCMPLIANCE EVALUATION I LJ TABLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS SYSTEM CATEGORY COWONENT DESCRIPTION AFW HSB D-2A AUXILIARY FEEDWATER STORAGE TANK AFW HSB FCV-2300 AFW FLCM TO SG/A FLOW CONTROL VALVE AFW HSB FCV-2301 AFW FLOW TO SG/B FLOW CONTROL VALVE AFW HSB FCV-3300 AFW FLOW TO SG/C FLOW CONTROL VALVE AFW HSB FCV-3301 AFW FL(M TO SG/B FLOW CONTROL VALVE AFW HSB G-10 AFW PUW G STEAM DRIVEN AFW HSB G-10S AFW PUMP G-10S - MOTOR DRIVEN AFW HSB MOV-1202 AFW PUW G-10S DISCHARGE VALVE AFW SOE MOV-1204 AFW BYPASS ISOLATION AFW HSB SV-3200 AFW 1/2" STEAM SUPPLY BYPASS CONTROL VALVE AFW HSB SV-3 202 AFW 1/2" STEAM LINE DRAIN VALVE AFW HSB SV-3203 AFW 1/2" STEAM LINE DRAIN VALVE AFW HSB SV-3204 AFW 1/2" STEAM LINE DRAIN VALVE AFW HSB SV-3205 SVC WTR INLET TO FUMP G-10 AFW HSB SV-3211 AFW 1/2" STEAM LINE DRAIN VALVE AFW HSB SV-3214 AFW 1/2" STEAM LINE DRAIN VALVE AFW HSB X-1062 STEAM DRIVEN AFW PUMP G-10 TUFBINE CCW HSB C-17 COWONENT COOLING WATER SUFEE TANK CCM HSB CV-722A THERMAL BARRIER (X)IL RETURN CX)NTROL VALVE CCM HSB CV-7228 THERMAL BARRIER COIL RETURN CONTROL VALVE [mC) CCM HSB CV-722C THERMAL BARRIER CX)IL RETURN CONTROL VALVE CW HSB E-20A COMPONENT CX)0 LING WATER W E-21A CW HSB E-20B COWONENT CX)0 LING WATER W E-20B CCW HSB G-15A COMPONENT (X)0 LING WATER PUMP G-15A CCW HSB G-158 COMPONENT COOLING WATER FUMP G-15B CCN HSB G-15C COMPONENT CX)0 LING WATER PUMP G-15C CCM HSB G-964 RCP THERMAL BARRIER PUMP CCW HSB MOV-720A CCM HEAT EXCHANGER E-20A OUTLET CCW HSB MOV-7208 CCW HEAT EXCHANGER E-20B OUTLET CCW CSD TCV-601A CCM FLCN CONTROL TO RHR HX E-21A CCM CSD TCV-601B CCM FLOW CONTROL TO RHR W E-21B CRS SOE CV-114 CONTAINMENT SPRAY CRS SOE CV-82 CONTAINMENT SPRAY CONTROL VALVE CRS SOE CV-92 CONTAINMENT FIRE SPRAY CRS SOE G-27N REFUELING WATER RJMP - NORTH CRS SOE G-27S REFUELING WATER RjMP - SOUTH CVCS HSB C-15 VOLUME CX)NTROL TANK CVCS HSB C-42 RCP SEAL WATER FILTER CVCS HSB C-42S RCP SEAL WATER FILTER CVCS HSB C-952A SEAL SUPPLY FILTER CVCS HSB C-952B SEAL SUPPLY FILTER CVCS HSB C-952C SEAL SUPPLY FILTER CVCS HSB CV-3 04 CHARGING LOOP A CONTROL VALVE CVCS SOE CV-305 PZR AUXILIARY SPRAY CONTROL VALVE CVCS SOE CV-334 BORIC ACID SUPPLY CONTROL VALVE CVCS SOE CV-406A LETDOWN DEMINERALIZER CONTROL VALVE . CV-406B CHEMICAL BLENDING CONTROL VALVE I CVCS SOE ' CVCS SOE CV-525 LETDWON DEMINERALIZER ISOLATION Impe11 Corporation . Report No. 01-0310-1435 2-12 Revision 0 '

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION . 'J TABLE 2-1 SONGS 1 SAFE SHUTDOWN COWONENTS SYSTEM CATEGORY COWONENT DESCRIPTION CVCS SOE CV-S26 LETDOWN DEMINERALIZER ISOLATION CVCS HLP CV-S27 SEAL WATER RETURN ISOLATION PWR MCC1 AT VB CVCS HLP CV-5 28 SEAL WATER RETURN ISOLATION FWR MCC2A AT VB5 CVCS HSB D-1 REFUELING WATER STORNIE TANK - RWST 5' CVCS HSB E-906 LUBE OIL COOLER FOR G-8A, WATER COOLED CVCS HSB E-907 LWE OIL COOLER FOR G-88, WATER COOLED CVCS HSB E-908 LUBE OIL COOLER FOR G-8A, AIR COOLED CVCS HSB E-909 LUBE OIL COOLER FOR G-88, AIR COOLED CVCS SOE FCV-1102A PRIMARY WATER MAKEUP (X)NTROL VALVE CVCS SOE FCV-1102B BORIC ACID PUW DISCHARGE CONTROL VALVE CVCS HSB FCV-1112 CHARGING FLOW CONTROL VALVE CVCS HSB FCV-1115A SEAL INJECTION LOOP A FLOW CONTROL VALVE CVCS HSB FCV-1115B SEAL INJECTION LOOP B FLOW CONTROL VALVE CVCS HSB FCV-1115C SEAL INJECTION LOOP C FLOW CONTROL VALVE CVCS SOE FCV-11150 SEAL WATER SUPPLY VALVE LOOP A CVCS SOE FCV-1115E SEAL WATER SUPPLY VALVE LOOP B CVCS SOE FCV-1115F SEAL WATER SUPFtY V ALVE LOOP C CVCS HSB FT-1112 CHARGING LOOP A. FLOW TRANSMITTER G-42 TEST PU W 7] s "f CVCS CVCS SOE HSB G-8A CHARGING PUMP G-8A, ALSO F0WERED FROM DSD S' CVCS HSB G-8B CHARGING PUMP G-8B CVCS HSB G-942 LWE OIL PUMP FOR G-8A CVCS HSB G-943 LWE OIL PUMP FOR G-8B CVCS HSB G-987 LWE OIL PUMP FOR G-8A CVCS HSB G-988 LWE OIL PUMP FOR G-8B CVCS HSB MG8AF LWE OUL COOLING FAN FOR G-8A CVCS HSB MG8BF LWE OIL COOLING FAN FOR G-8A CVCS HSB MOV-11008 RWST WARGING ISOLATION VALVE CVCS SOE MOV-11000 VOLUME CONTROL TANK ISOLATION VALVE CVCS HSB MOV-11000 RWST WARGING ISOLATION VALVE CVCS HSB MOV-883 RWST ISOLATION RETURN CVCS hSB PC-1115A RCP SEAL FLOW PRESSURE CX)NTROLLER CVCS HSB PC-1115B RCP SEAL FLOW PRESSURE CONTROLLER CVCS HSB PC-1115C RCP SEAL FLOW PRESSURE CX)NTROLLER CYCS HSB PCV-1115A RCP SEAL WATER RETURN CONTROL VALVE CVCS HSB PCV-11158 RCP SEAL WATER RETURN CONTROL VALVE CVCS HSB PCV-1115C RCP SEAL WATER RETURN CONTROL VALVE CVCS HSB PI-1115 A RCP SEAL RETURN FLOW PRESSURE INDICATOR CVCS HSB PI-1115B RCP SEAL RETURN FLOW PRESSURE INDICATOR CVCS HSB PI-1115C RCP SEAL RETURN FLOW PRESSURE INDICATOR CVCS HSB PT-1115 A RCP SEAL FLOf PRESSURE TRANSMITTER CVCS HSB PT-1115B RCP SEAL FLOW PRESSURE TRANSMITTER CVCS HSB PT-1115C RCP SEAL FLOW PRESSURE TRANSMITTER CVS HSB A-9 REACTOR CAVITY COOLING FAN CVS HSB A-95 REACTOR CAVITY COOLING FAN CVS HSB PO-11 REACTOR CAVITY COOLING FAN A-9 CONTROL DAMPi O CVS HSB PO-12 REACTOR CAVITY COOLING FAN A-95 00NTRL DAMP 1 V CVS HSB TS-24 REACTOR CAVITY TEMPERATURE SWITW l Impe11 Corporation Report No. 01-0310-1435 2-13 Revision 0

                   .         .           ~                      .

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION i v TMLE 2-1 SONGS 1 SAFE SHUTDOWN COWONENTS SYSTEM CATEGORY COWONENT DESCRIPTION DG HSB A-13 A DIESEL COOLING WATER HEAT EXCHMGER FAN DG HSB A-13B DIESEL COOLING WATER HEAT EXCHMGER FAN DG HSB A-13C DIESEL COOLING WATER HEAT EXCHANGER FAN DG HSB A-13D DIESEL COOLING WATER EAT EXCHMGER FAN DG HSB A-14A DIESEL COOLING WATER HEAT EXCHMGER FAN DG HSB A-14B DIESEL COOLING WATER HEAT EXCHANGER FAN DG HSB A-14C DIESEL COOLING WATER HEAT EXCHANGER FAN DG HSB A-14D DIESEL COOLING WATER HEAT EXCHMGER FAN DG HSB A-15A CRANKCASE VAQJLM FANS DG HSB A-15B CRANKCASE VAQJLN FANS DG HSB A-16A CRMKCASE VACULM FAN DG HSB A-16B CRANKCASE VAQJLN FAN DG HSB C-13A STARTING AIR STORME TMK DG HSB C-13B STARTING AIR STORM E TANK DG HSB C-14A STARTING AIR STORME TANK DG HSB C-14B STARTING AIR STORAGE TANK DG HSB C-21A DIESEL FUEL OIL FILTER DG HSB C-21B DIESEL FUEL OIL. FILTER , DG HSB C-23 A DIESEL FUEL OIL FILTER ( DG HSB C-23 B DIESEL FUEL OIL FILTER LLBE OIL FILTER DG HSB C-24 A DG HSB C-24B LLBE OIL FILTER DG HSB C-26A LLBE OIL FILTER DG HSB C-26B LLBE OIL FILTER DG HSB C-27 LUBE OIL STRAINER DG HSB C-28 LUBE OIL STRAINER DG HSB C-40 DIESEL LOCAL CONTROL PANEL DG HSB C-48 DIESEL LOCAL CONTROL PANEL DG HSB C-908 INTAKE AIR FILTER DG HSB C-909 INTAKE AIR FILTER DG HSB C-911 AIR INTAKE SILENCER DG HSB C-912 AIR INTAKE SILENCER DG HSB C-924 INTAKE AIR FILTER DG HSB C-925 INTAKE AIR FILTER DG HSB C-926 AIR INTAKE SILENCER DG HSB C-927 AIR INTAKE SILENCER DG HSB D-10 LLBE OIL SUW TMK DG HSB D-14 DIESEL FUEL OIL DAY TANK DG HSB D-19 DIESEL FUEL OIL DAY TANK DG HSB D-23 DIESEL FUEL OIL STORAGE TANK DG HSB D-24 DIESEL FUEL OIL STORME TMK DG HSB D-27 DIESEL CDOLING WATER EXPANSION TANK DG HSB D-28 DIESEL COOLING WATER EXPANSION TMK DG HSB D-5 J ACKET MATER STANDPIPE DG HSB D-6 J ACXET WATER STANDPIPE DG HSB D-9 LLBE OIL SUMP TANK > DG HSB DG 1 DIESEL ENERATOR 1 k DG HSB DG 2 DIESEL ENERATOR 2 Impell Corporation Report No. 01-0310-1435 2-14 Revision 0

SAN ON0FRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION f (3/ TABLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS SYSTEM CATEGORY CO WONENT DESCRIPTION DG HSB E-10 LWE OIL COOLER DG HSB E-16 LWE OIL COOLER DG HSB E-5 DIESEL CX)0 LING WATER HEAT EXmANGER DG HSB E-7 DIESEL COOLING WATER HEAT EXQiMGER DG HSB E-902 AFTERC00LER DG HSB E-903 AFTERC00LER DG HSB E-904 AFTERC00LER DG HSB E-905 AFTERC00LER DG HSB E-910 AFTERC00LER DG HSB E-911 AFTERC00LER DG HSB E-912 AFTERC00LER DG HSB E-913 AFTERC00LER DG HSB E06 EXCITER CABINET DG 1 DG HSB E07 EXCITER CABINET DG 2 DG HSB E08 EXCITER CABINET DG 1 DG HSB E09 EXCITER CABINET DG 2 DG HSB FV-100 STARTING AIR FLOW CONTROL VALVE DG HSB FV-101 STARTING AIR FLOW CONTROL VALVE p DG HSB FV-120 STARTING AIR FLOW CONTROL VALVE] t j DG HSB FV-121 STARTING AIE FLOW CONTROL VALVE V DG HSB G-16 DIESEL COOLING WATER PUMP DG HSB G-18 DIESEL COOLING WATER PUMP DG HSB G-42 DIESEL FUEL OIL PUMP DG HSB G-54 DIESEL FUEL OIL PUMP DG HSB G-62 STMDBY DIESEL FUEL OIL PUMP DG' HSB G-67 DIESEL LWE OIL PUMP DG HSB G-68 DIESEL LWE OIL PUMP DG HSB G-69 STMDBY DIESEL LWE OIL PUMP DG HSB G-70 STMDBY DIESEL LWE OIL PUMP DG HSB G-74 A DIESEL FUEL OIL TRANSFER RJMP G-74A DG HSB G-74B DIESEL FUEL OIL 1RANSFER RNP G-74B DG HSB G-75 A DIESEL FUEL OIL TRANSFER PUMP G-75A DG HSB G-75B DIESEL FUEL OIL TRANSFER RJMP G-758 DG HSB G-76 DIESEL FUEL OIL STANDBY RJMP DG HSB K-902 TU2004ARGER DG HSB K-903 TU20W ARGER DG HSB K-904 TUEODHARGER DG HSB K-905 TURBOWARGER DG HSB K-910 TU20mARGER DG HSB K-911 TURBOWARGER DG HSB K-912 TURBOWARGER DG HSB K-913 TURB0mARGER DG HSB LSWL/LL97A DIESEL FUEL OIL DAY TANK LEVEL SWITCH DG HSB LSWULL97B DIESEL FUEL OIL DAY TANK LEVEL SWITCH DG HSB LSWULL97C DIESEL FUEL OIL DAY TANK LEVEL SWITCH DG HSB LSWULL97D DIESEL FUEL OIL DAY TANK LEVEL SWITW D DG HSB PSL-180 STARTING AIR PRESSURE SWITW I ( s). DG HSB PSL-181 STARTING AIR PRESSURE SWITm Impe11 Corporation Report No. 01-0310-1435 2-15 Revision 0

                                           ~                                          ~                  '~-
                                                                                                             ^^ ~          ~~ ~
                                                                                ~
      ~

i 1 -_ _ _ _ _ . .Z SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION I T/BLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS SYSTEM CATEGORY COWONENT DESCRIPTION DG HSB PSL-215 STARTING AIR PRESSSURE SWITm DG HSB PSL-221 STARTING AIR FRESSURE SWITm DG HSB PSL-308 PRESSURE SWITm -INTERLOCK TO G-76 DG HSB PSL-314 PRESSURE WITW - INTERLOCK TO G-62 DG HSB PV/PY-113 DG1 INTAKE AIR FHEUMATIC (X)NTROL VALVE DG 1:59 PV/PY-114 DG1 INTAKE AIR PNEUMATIC CONTROL VALVE DG HSB PV/PY-115 DG1 INTAKE AIR FNEUMATIC CONTROL VALVE DG HSB PV/PY-116 DG1 INTAKE AIR PNEUMATIC CONTROL VALVE DG HSB PY/PY-153 DG2 INTAKE AIR PNEUMATIC 00NTROL VALVE DG HSB PY/PY-154 DG2 INTAKE AIR PNEUMATIC CONTROL VALVE DG HSB PV/PY-155 DG2 INTAKE AIR PNEUMATIC CONTROL VALVE DG H2 PY/PY-156 DG2 INTAKE AIR PNEUMATIC CONTROL VALVE DG . HSB SV-301 STARTING AIR SOLEN 0ID DG HSB SV-302 STARTING AIR SOLENOID

                   .DG                           HSB         SV-304                      STARTING AIR SOLENOID DG                        - HSB         SV-305                      STARTING AIR SOLENOID DG                          HSB         SV-401                      STARTING AIR SOLENOID VALVE DG                          HSB         SV-402                      STARTING AIR SOLEN 0ID VALVE

, DG HSB SV-404 STARTING AIR SOLENOID VALVE

DG HSB SV-405 STARTING AIR SOLENOID

' DG HSB TCV-1673 DIESEL (X)0 LING WATER TEW CONTROL VALVE DG HSB TCV-1674 DIESEL CX)0 LING WATER TEW 00NTROL VALVE

i DG HSB TCV-1675 DIESEL LWE OIL TEMP (X)NTROL -VALVE l DG HSB TCV-1676 DIESEL LLBE OIL TEMP 00NTROL VALVE FWS ASD A-17A LWE OIL COOLER FOR PUMP G-3A FWS ASD A-17B LtBE OIL COOLER FOR PUMP G-3B FWS ASD CV-36 FEEDWATER TO CONDENSER 2A ISOLATION FWS ASD CV-37 FEEDWATER TO CONDENSER 2A ISOLATION FWS ASD CV-875A FDWTR TO REFUELING WATER STORME ISOLATION
                   . FW S                        ASD         CV-875B                     FDWTR TO REFUELING WATER STORAGE ISOLATION j                      FWS                        HSB         E-17A                       LLEE OIL COOLER FOR PUW G-3 A j                      FWS                        HSB         E-17 B                      LLBE OIL COOLER FOR PUMP G-3B FWS                         SOE         FCV-456                      SG/A FEEDWATER REGULATOR VALVE FWS                        SOE         FCV-457                      SG/B FEEDWATER REGULATOR VALVE FWS                         SOE         FCV-458                      SG/C FEEDWATER PEGULATOR VALVE FWS                         SOE         FT-456                      MAIN FEEDWATER FLOW TRANSMITTER FWS                        SOE         FT-457                       MAIN FEEDWATER FLOW TRMSMITTER FWS                        SOE         FT-458                       MAIN FEEDW ATER FLOW TRMSMITTER FWS                         SOE         FT-460                       MAIN FEEDW ATER FLOW TRMSMITTER              '

FWS SOE FT-461 MAIN FEEDWATER FLOW TRMSMITTER FWS SOE FT-462 MAIN FEEDWATER FLOW TRANSMITTER ' I FWS ASD G-3 A MAIN FEEDWATER PUMP - ALSO ASD FWS ASD G-3B MAIN FEEDWATER RjMP - ALSO ASD FWS ASD G-979 LLEE OIL PUMP FOR PUMP G-3A FW$ ASD G-983 LlBE OIL PUMP FOR PUMP G-3B

,                     FWS                        ASD         HV-852A                     MAIN FEEDW ATER PUMP G-3 A OUTLET ISOLATION FWS                         ASD         HV-852B                     MAIN FEEDWATER PUMP G-3B OUTLET ISOLATION FWS                        ASD         HV-854A                      MAIN FEEDWATER PUMP G-3 A INLET ISOLATION Impe11 Corporation Report No. 01-0310-1435                                      2-16                                   Revision 0

l

 !                                         SAN ON0FRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION

^

                                                                                                                                       \

L TABLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS

}.                 SYSTEM         . CATEGORY      COWONENT                     DESCRIPTION i

3 FWS ASD HV-854B MAIN FEEDWATER PUMP G-3B INLET ISOLATION FWS SOE LT-453 SG/A LEVEL TRANMITTER 4 FWS SOE LT-454 SG/B LEVEL TRMSMITTER FWS SOE LT-455 SG/C LEVEL TRMSMITTER FWS ASD SV-525 SOLEN 0ID CONTROL FOR HV-852A FWS ASD SV-527 SOLENOID CONTROL FOR HV-854A FWS ASD SV-529 SOLENOID CONTROL FOR HV-8528 FW$ ASD SV-531 SOLENOID CONTROL FOR HV-854B i GNI ASD C-1030 FOR TRAIN A-SIS VALVES ' GNI ASD C-1031 FOR TRAIN A SIS VALVES GNI ASD C-1032 FOR TRAIN A SIS VALVES GNI ASD C-1033 FOR TRAIN B SIS VALVES . GNI ASD C-1034 FOR TRAIN B SIS VALVES ,

,                    GNI              ASD          C-1035                      FOR TRAIN B SIS VALVES GNI              HSB          C-1036                      FOR SV-3213, SV-3201 GNI              HSB          C-1037                      FOR SV-3213, SV-3201 GNI              HSB          C-1038                      FOR CV-545, CV-546 -

GNI HSB C-1039 FOR CV-545, CV-546 GNI HSB C-1040 FOR FCV-2300, 2301, 3300, 3301

  • t GNI HSB C-1041 FOR FCV-2300, 2301, 3300, 3301 GNI HSB C-1042 FOR FCV-2300, 2301, 3300, 3301 GNI HSB C-1043 FOR FCV-2300, 2301, 3300, 3301 GNI 'HSB C-1044 FOR FCV-2300, 2301, 3300, 3301 GNI HSB C-1045 FOR FCV-2300, 2301, 3300, 3301 GNI HSB C-1046 FOR FCV-2300, 2301, 3300, 3301 4 GNI HSB C-1047 FOR FCV-2300, 2301, 3300, 3301 GNI HSB C-1173 THROUGH C-1187 FOR EAST STEAM DUMP VALVES GNI HSB C-1188 THROUGH C-1203 FOR WEST STEAM DUMP VALVES i

GNI HSB C-1204 THROUGH C-1213 FOR Of-113 GNI HSB CV-532 CONTROL VALVE PORY NITROGEN SUPPLY , ISA ASD C-1093 HOLDING TMK i ISA ASD C-1094 HOLDING TANK ISA ASD C-1097 HOLDING TANK MS SOE CV-140 TUMINE MAIN STOP VALVE BY PASS MS SOE CV-141 TUEINE MAIN STOP VALVE BY PASS MS SOE CV-3 CONDENSER STEAM DUMP ISOLATION MS SOE CV-4 CONDENSER STEAM DUMP ISOLATION ' MS HSB CV-76 ATESPHERIC STEAM DUMP VALVE MS HSB CV-77 ATMOSPHERIC STEAM DUMP VALVE ,- MS HSB CV-78 ATMOSPHERIC STEAM DUMP VALVE MS HSB CV-79 ATMDSPHERIC STEAM DUMP VALVE

MS HSB LT-2400A SG/A WIDE RANGE LEVEL TRMSMITTER MS HSB LT-24000 SG/B WIDE RANGE LEVEL TRANSMITTER i' MS HSB LT-2400C SG/C WIDE RANGE LEVEL TRANSMITTER
MS HSB LT-3400A SG/A WIDE RANGE LEVEL TRANSMITTER MS HSB LT-34008 SG/B WIDE RANGE LEVEL TRANSMITTER i MS HSB LT-3400C SG/C WIDE RANGE LEVEL TRANSMITTER MS - DSE LT-4500 SG/A LEVEL TRANSMITTER i

4 Impe11 Corporation Report No. 01-0310-1435 2-17 Revision 0

1. ,
   ,-          ,-.J-.-.,-._-..-,.-..----,_--                                          . , - - _ _ _ . . . . . . - .

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFP50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION TABLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS SYSTEM CATEGORY COWONENT DESCRIPTION MS DSE LT-451C SG/B LEVEL TRANSMITTER MS DSE LT-452C SG/C LEVEL TRANSMITTER MS HSB MOV-14 REHEATER ISOLATION VALVE MS HSB MOV-15 REHEATER ISOLATION VALVE MS HSB MOV-16 REHEATER ISOLATION VALVE MS HSB MOV-17 REHEATER ISOLATION VALVE MS HSB PT-459 MAIN STEAM PRESSURE TRANSMITTER MS HSB PV-1611 TUEINE STOP VALVE ACTUATOR MS HSB PV-1612 TUEINE STOP VALVE ACTUATOR MS HSB PV-1650 TUEINE STOP VALVE MS HSB PV-1651 TUEINE STOP VALVE MS HSB RV-1 CODE SAFETY VALVE MS HSB RV-10 CODE SAFETY VALVE MS HSB RV-2 CODE SAFETY VALVE MS HSB RV-3 CODE SAFETY VALVE MS HSB RV-4 CODE SAFETY VALVE MS HSB RV-5 CODE SAFETY VALVE MS HSB RV-6 CODE SAFETY VALVE MS HSB RV-7 CODE SAFETY VALVE MS HSB RV-8 CODE SAFETY VALVE (v MS HSB RV-9 CODE SAFETY VALVE MS SOE SV-119 S.G. SAMPLE ISOLATION MS SOE SV-120 S.G. SAMPLE ISOLATION MS SOE SV-121 S.G. SAMPLE ISOLATION MS SOE SV-122 S.G. SAMPLE ISOLATION MS SOE SV-123 S.G. SAMPLE ISOLATION MS SOE SV-124 S.G. SAMPLE ISOLATION MS HSB SV-175 ALTERNATE STEAM DUMP (I)NTROL AT C-38 MS HSB SV-85 CONTROL SOLEN 0ID FOR CV-76 MS HSB SV-86 CONTROL SOLENOID FOR CV-77 MS HSB SV-87 CONTROL SOLENOID FOR CV-78 MS HSB SV-88 CONTROL SOLENOID FOR CV-79 MS SOE SV-89 CONTROL SOLEN 0ID FOR CV-3 MS SOE SV-90 CONTROL SOLENOID FOR CV-4 MSS ASD FC-1076A ALTERNATE STEAM DUMP AIR CONTROLLER MSS HSB P/418 ATMOSPHERIC STEAM DUMP CONTROLLER MSS HSB PC-418A ATMDSPHERIC STEAM DUMP AIR CONTROLLER RCS HSB C-1 REACTOR VESSEL RCS HSB C-2 PRESSURIZER RCS HSB CV-530 BLOCK VALVE FOR PORY 546 RCS HSB CV-531 BLOCK VALVE FOR PORY 545 RCS HSB CV-545 PORV RCS HSB CV-546 PORV RCS HSB E-1A STEAM GENERATOR 1A RCS HSB E-1B STEAM GENERATOR 1B RCS HSB E-1C STEAM GENERATOR IC O RCS SOE G-2A REACTOR COOL ANT PUMP 2A REACTOR CDOLANT PUMP 2B () RCS SOE G-2B Impell Corporation Report No. 01-0310-1435 2-18 PevfSion 0

SAN ON0FRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION O TABLE 2-1 SONGS 1 SAFE SHUTDOWN COMPONENTS SYSTEM CATEGORY COWONENT DESCRIPTION RCS SOE G-2C REACTOR 000LMT RJMP 2C RCS DSE LT-430A PZR LEVEL TRMSMITTER RCS HSB LT-431 PZR LEVEL TRMSMITTER RCS HSB LT-435 PZR LEVEL TRANSMITTER RCS HSB NE1201 NEUTRON S00RCE RANGE M)NITOR , RCS HSB NE1202 NEUTRON SOURCE RANGE M)NITOR RCS SOE PCV-4300 PAR SPRAY VALVE FROM RCS LOOP B COLD LEG RCS SOE PCV-430H PZR SPRAY VALVE FROM RCS LOOP A COLD LEG RCS HSB PT-425 PZR PRESSURE TRANSMITTER

  • RCS HSB PT-430 PZR PRESSURE TRANSMITTER RCS HSB PT-431 PZR PRESSURE TRANSMITTER RCS HSB PT-432 PZR PRESSURE TRANSNITTER RCS DSE PT-434A PZR PRESSURE TRANSMITTER RCS HSB PZR HEATER GROUP A RCS HSB PZR HEATER GROUP B RCS HSB PZR HEATER GROUP C RCS HSB PZR HEATER GROUP D ALSO POWERED FROM DEDICATED DIESEL

<. RCS HSB REACTOR VESSEL , RCS HSB RPS TRIP CIRCUITS RCS HLP SV-2401 REACTOR VESSEL VENT VALVE 1 RCS HLP SV-2402 REACTOR VESSEL VENT VALVE RCS HLP SV-2403 PZR HIGH POINT VENT VALVE RCS HLP SV-2404 PZR HIGH POINT VENT VALVE RCS HLP SV-3401 REACTOR VESSEL VENT VALVE RCS HLP SV-3402 REACTOR VESSEL VENT VALVE RCS HLP SV-3403 PZR HIGH POINT VENT VALVE RCS HLP SV-3404 PZR HIGH POINT VENT VALVE RCS HSB TE-2401A RCS LOOP A HOT LEG TEMPERATURE RCS HSB TE-2412A RCS LOOP B HOT LEG TEMPERATURE RCS HSB TE-2422A RCS LOOP C HOT LEG TEMPERATURE RCS HSB TE-3402A RCS LOOP A HOT LEG TEWERATURE RCS HSB TE-3411 A RCS LOOP B HOT LEG TEMPERATURE I RCS HSB TE-3421 A RCS LOOP C HOT LEG TEWERATURE RCS ASD TE-400A RCS LOOP A DELTA T l RCS ASD TE-400C RCS LOOP A DELTA T  ! RCS DSE TE-402A RCS LOOP A HOT LEG TEMPERATURE RCS DSE TE-402B RCS LOOP A COLD LEG TEMPERATURE RCS HSB TE-402C RCS LOOP A (X)LD LEG TEMPERATURE RCS ASD TE-410A RCS LOOP B DELTA T RCS HSB TE-411B RCS LOOP B COLD LEG TEWERATURE . RCS DSE TE-412A RCS LOOP A HOT LEG TEWERATURE ! RCS DSE TE-412B RCS LOOP B COLD LEG TEWERATURE RCS ASD TE-412C RCS LOOP B DELTA T RCS ASD TE-420A RCS LOOP C DELTA T RCS ASD TE-420C RCS LOOP C DELTA T RCS DSE TE-422A RCS LOOP A HOT LEG TEMPERATURE DSE TE-4228 RCS LOOP C COLD LEG TEMPERATURE O RCS RCS HSB TE-422C RCS LOOP C COLD LEG TEWERATURE i Impe11 Corporation Report No. 01-0310-1435 2-19 Revision 0

1 1! SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 , 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION O l

}

TABLE 2-1 SONGS 1 SAFE SHUTDOWN G)WONENTS ^ SYSTEM iCATEGORY COWONENT DESCRIPTION

?            ~RCS            ASD            TI-400                         RCS LOOP A DELTA T RCS            ASD            TI-410                         RCS LOOP B DELTA T RCS            ASD            TI-420 -                       RCS LOOP C DELTA T
            'RHR             CSD            E-21A                          RHR HEAT EXCHANGER E-21A RHR            CSD            E-21B                          RHR HEAT EXCHANGER E-21B

{ mR CSD G-14A RHR PUMP G-14A-mR CSD G-14B RHR PUW G-148 i  ; MR RHR CSD CSD HCV-602 MOV-813 RHR FLOW CONTROL VALVE RHR INLET ISOLATION VALVE'- ALSO KP i 'RHR CSD MOV-814 RHR INLET ISQ.ATION VALVE - ALSO KP RHR CSD MOV-822A RHR EAT EXCHANGER E-21A INLET VALVE

}             MR             CSD             MOV-822B                      RHR EAT EXCHANGER E-21B INLET VALVE
RHR CSD MOV-833 RHR DISO4ARGE ISOLATION VALVE - ALSO KP RHR CSD MOV-834 RHR DISOiARGE ISOLATION VALVE - ALOS KP i RHR CSD TC-601A TE W CONTROLLER FOR C0f FLOW CONTROL TCV-601 RHR CSD TC-601B TEMP G)NTROLLER FOR COf FLQt CONTROL TCV-601 i RHR CSD TE-600 RHR INLET TEMPERATURE RHR CSD TE-601A RHR HK E-21A DISCHARGE TEWERATURE O. RHR SIS CSD ASD TE-601B G-50A RHR HX E-21B DISCHARGE TEWERATURE SAFETY INJECTION PUW G-50A -

SIS ASD G-50B SAFETY INJECTION PUMP G-508 SIS ASD HV-851A SAFETY INJECTION RETURN FROM G-3 A SIS ASD HV-851B SAFETY MECTION RETUM FROM G-3B SIS ASD HV-853A SAFETY INJECTION FEED TO G-3 A-

         ,    SIS             ASD            HV-853B                       SAFETY INJECTION FEED TO G-3B                !

SIS SOE MOV-356 SAFETY MECTION RECIRC TO LOOP A SIS SOE MOV-357 SAFETY INJECTION RECIRC TO LOOP B

i. SIS SOE MOV-358 SAFETY INJECTION RECIRC TO LOOP C SIS ASD MOV-850A SAFETY INJECTION LOOP A DISO4MEE SIS ASD MOV-8500 SAFETY INJECTION LOOP'B DISCHARGE

, SIS ASD MOV-850C SAFETEY INJECTION LOOP C DISO4ARGE-i SIS ASD SV-524 SOLENOID CONTROL - FOR W-851A i SIS ASD SV-526 SOLEN 0ID CONTROL FOR HV-853A SIS ASD SV-528 SOLENOID CONTROL FOR HV-851B ' , SIS ASD SV-530 SOLENOID CONTROL FOR HV-853B

SWC HSB G-13A SALTWATER COOLING WATER PUMP G-13A j SWC HSB G-13B SALTWATER G)0 LING WATER RJMP G-13B AUX SWC PUMP - NOT SAFETY'RELATED

~ SWC ASD G-13C i, , 4 O ! Impe11 Corporation ' i Report No. 01-0310-1435 2-20 Revision 0

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 l 10CFR50 APPENDIX R, SECTION III.G COMPLIM'CE EVALUATION ] 3.0 FIRE AREA / ZONE DRAWINGS This section contains the following drawings: Figure 3-1 Containtnent/ Turbine Building Fire Area / Zone Boundaries, E1. 14'-0" Figure 3-2 Containment / Turbine Building Fire Area / Zone Boundaries, El. 35'-6" Figure 3-3 Reactor Auxiliary Building / Intake Structure Fire Area / Zone Boundaries, E1. 20'-0" Figure 3-4 Diesel Generator Building Fire Area / Zone Boundaries, E1. 20'-6" O O Impe11 Corporation Report 01-0310-1435 3-1 Revision 0

i s i l 8' = '~ 4

                                       ,     'jgF ;dh ! 3 jd            4                      l!jhi!!h   jl l                      i:       _L:               a                                                           0  llin
                                )

Il@ I 3,d h[f] vj ~l t  ! t -hhf [ s FN I g r, i,l y (M=3E 3 s i /<A 'i u SI&I_ dd !. c .,de e ![o!,  ; r:: 8r s C 2 s kjiNjdf y -l----h: v i I o*% m-s N !g' 3..f?- _. D, C S .. M !)  ! tj

                                                                                         -:ir- g, je a

r e h:: m.- : - ::Ji: e -g t

.x::q
      \

9 k gf %,. j i _. _ . . . .

                                                                                             .t3 a

g .c __. . . . . . . ig A :I A A St-s iN pl 641,i11 AFl,%e!' 4-r lt9!- 'o i$ 't ti ,I.  :  ! ;4! i gd  ! e U l L_f-  ! !G g h 9x lI ya n _ m - p -..> ,E

                                                                                                                         >n
                                                                                                                       /d -
         .6       1. l E ', '"'"l' $$1'"'"

h lg_j E I Tei M g - J g 1,- t 2 g [.

                    -     %;y,111111111111111111111                       It-                                   r"~1--~~

e.um-. tq [

    ,   4,        q       'hr EID ofEUDEd
                                                                     ,! !! ",    h                              i_- . . _ ! __ . . _

5 h i- E '-{ g4dtr~

                                              /     :                   ;

I N!'4j I b-  ; i ilP j l I !e$l! IMEI).(

n i
                                                                            . c.,-
                                                                                                                       \

r g :: v f: i l , 3 i ,i

                                               --j.         _             .         ..                     .      __._
                                                                                                                        ,            sr
q. g. gr g ,
                      .                                         d 9

s d -

-' 8_ -

e - J i e63 ,/ I

                                                                                                                  ! s , ,.

C) e

                                               !!h v          ju i
                                                                               )'                       !         :!!!!!I'            Y n.
                                      #                                                                                                                                                                                                                                                 I i                               i                                                                       .                                                                                                                                           I
                                                             '                                                                       ?

O l l p _ =_ j

             "!              l                                 _

9 '

                                                                                                                                                                                       "g; '

I l O's 6 .! l I A gj I i/  ! 5

                                                                                                                                                                         '                                                                                        I!

af

                             .         g                            :i :i                                                            g l         -

3 I8 10 7 , h - --- i r g-  ! 'k~ il i i d  !  ! 9 il !

                             !                                   f                                                  f                                                                                                                                         _E d

Nl

                                                    , m       .'-
                                                                                                       < nwwa-.-

O !lEll

                                                                                                                                                                                                                                                              ' l1O r       -llc               .1                  h-                    n l'

tl 4 a f .  ! N l 1  !

                               ------t]aai ts e
                                                                                                                               . r. arj i
                                                                                                                                                              =      p         =        I! p ys                         ,

ln i - ,n , g h __#i g ~ 2

                                                                                               .                                                                                                                   I!             !!

li 1 yi!!!!?! I;I t.; 4,c!. lv - d)+ ,

                                                                                                                                                                                                , E', !:

m 1 m I,'

                                                                                                                                                                                                                                    .y,,l' i

f'!ji' I',l/* l? i t I If,

                                                                                                                                                                                                                       ; j j!

8;--- gi i!! u (lv

                                                                                                                                                                          -       -                                 i                                              ..

1 -i ih !!L l ' . ,:. . . T  :" , . J / / i, l y

                                                                                          /t .iiij-"$ "C# Aq t  I          i
                                                                                                                                                                                                ,,"iii

(; . '; , c 9 e p m l a! b,

                                       .                                  v l      II          y=

m tl . 3 j l<

                                                                                           'j                                                                                              w                                                         '

e l a ri et 33 p4 . "In , ' V  !!c==  ! llb !I

                                ,' ll                                                                                                                 i 'd 'd                li                                  rc..                                "

e

                                                    .r-
                                                                -lkj g

l i! l ll l8 L. X. --- 1

                                                                                                                                                                                                                                           ..   ,j
                                       ,                                        s      -

q) wu pm m

                                                                                                                            ~

, l J!! [ \--

                                                                                                                                                                     ~1]:                                             d! g I ,[

I l l ,3: Ri g;' l l I 5 l l

                                                                                      )[7"'_

sg ,t e Ri I t.

                                                                                                                                                    )
i. - f
                                                                              ,       AA6                          de                      4                                              4                            -
                                          -------- ! (((                                                                             ._3,                                   i         f-_,                             i
                                             =f
                                                                                                                                     .4:.,M fi W1 $'

gl; j _ . .

                                                                                                                                      ,:: u g                ,:: :

I! i  : 1 i3:

Ri i ip 1

[ ni

                                                                                                                    ! if                                             3                                                                           l$
                                                                                                                                    %[y/'s                         (I), 1}3                                                              

N A lt' O / O-

        . , _ _ . . _ , , .       . . ~ . . . . . . . , . _ . . . _ - - . . . . . _ ,                        . - - . _ _ _ _ , . _ _ . . _ _ . . _ _ _ _ _ _ _ , .                             . _ _ _ , . _                             .._

O o  !  !! l;

                                                                                                                                                                                 !i l

O l 3 l ! !.l.

           .o'            x                                                                                                                                                       5. l ll l. "

3 II l 1 3 (O .4i ., gi.mll- -' i, // lgg ll10

E;i t I

i d i

                                                   ,e   !       ,.

s<i .: 61 g ,.

                       ,     O               _

_ _ ___g,3

                                                                                             ,                                    7    m)                   ,

I I

                                 !                        w:             7 sy  "8 g

7 1 s t_ l k b Q g u r I i H5 g A sk l s g- -  :. Ie l

n.  : - n,i ;, k 5

a 'a 6 I a e, h . t

                                                                                      ..         i :-                                                                                           l

( r ' "- r 1 ge k' e e TM t. l

  • 2 1
                                                                                                                                                              ,                                 i g,a6 ~ ~ ~ ,V g               d                                    bao                                                    l 5l 3               g                              }    r                                                                          !                        l l                  (

A

                                     ) 3a+i_-__- pi sa
                                                                                                                                                       ,      )c ;i l    -

i )  ! h k l l l o'.

, . n. .h .

1 . Ii Ol O

             -            h'                                          l' i               sm g.

1 :

                                                                                ~7                                           !      li                    Sf .]'e      i i               k- f :pd]                                                                                          ! jh!t@                                     I!
               ,                                                       !                  A N $

1I g-i s il @ [!! + ti 8 wg.

                    -                        1                                                                                      ,                     ?                  z I

l g Fi

                                                                                                                            =
                                                                                                                                         +

hg 4

                          !-     ::C ii.

1 r, iA 6 8I5 7 /  !' yA 1  : fA $ j , 9_R ' i! j , j ' - J

                                                                                '.                                                       d           hJ h ,b
                    ,v
c. . .

it-

                                                            =

t a O

l s o E - l} l O E3 4 3 'C l'

  • EE l d 16 . il
                                                                                                                                                                                                                                   =

I I; I; i'

                                                                                                                                                                                                                                     ! ?_* *'

yy

                                                                        ,  'r,          /
                                                         ,',)%.
                                                                                                                                                                                                                       !' E ll!O s
                                                                                                                                         . - -. - - -                             .       .              l
                            ,/ ,'
                                   '                                                                                      -l
                                                                                                                          -gl                                                3 i                            n[-
l. .
                  .. .,                                                                            n                                     - - -- .
            ..- '   ** N.                                                                           \                                                                                                     g l. L
         . - /.                :. . . . . . .;
         ***'<d.
              .: . . .' 9 .
                              . . y*.. . .;l l                                      .

L , - +

                                                                                                                                                                                          ,r g               !                                       ;            g

_1, , a =, E;- - i 5

                                        =

f, 4 F I-6 I 0'd

                                       ,a......,                                           g k~
                                                                                                                                                                                                =

l

                                       !....I...,..,                      I i

l bl' i l R , r" 6 lC~ firL l I a,') )I P< g ___g; s 11l lll11 - 1 m e 11l lllll ( 'j ,1 I ~ ~ ' ~ p. I L_bI- "' I Ic[: I  : l?l ,g !D Q .! s

                                      ;..(..,..

i i e ( r n jj 7 g Og m

                                               ,                                                 ' '. e            l
            '~,                        j       =                        ._. N. . I                    &                                                     u              .                    g L. l! '

V' g

                                                                                                                                                                                        ~'5J                           ~
               .: . . . . . . . .! l.

6 , r 1 . /. .3, I

                                                                                                                                                                                        -d                                 '

n '.,'M y . . . . . . . .! . _ _ . _ _ __. __ s g j x ' x r

                                                                                   !n ; a    -

[ _l;g el _ 1 !c- -

                              's ,                                      !. .. ... . .. .
                                                                                                              ..tj                    _

j

                                                                                                                                                                                        ~

s t

                                           's                 .,                                                                                      :                               :                  i N                                s i                          ii                           ii                     i
                                                      's                                 ,

O e __

                                                                    ~
                                                                                                                                                                                                                                          -   y myy                 y   w,       ,r                - - - .                                                              -              -

SAN ONOFRE NUCLEAR GENERATING STATION - UNIT 1 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATICN i 4.0 DETAILED 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATIONS Section III.G Compliance Evaluation for San Onofre Nuclear The Appendix Generating StatR, ion Unit 1 is divided into the following subsections by plant area / building: CO - Containment AB - Reactor Auxiliary Building YD - Yard Areas FH - Fuel Handling Building PB - Power Block TB - Turbine Building DG - Diesel Generator Building VN - Ventilation Equipment Building O 4 Impe11 Corporation Report 01-0310-1435 4-1 Revision 0 1

                  -   ,,,4.-,,m,,_         - - - , _ _ . _ - _ _ _ _ _ , , , _ _ _ , _ _ . , _ _ _ _ , _ . _ _ , . , _ _ _ . _   ,_  .

m .- 10CFR50 APPE W IX R. SECTIL e i!I.G CoprLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 ] Containment Effects of' Fire on Safe Shutdeun Capability 2 A fire in this fire area /rone could result in the loss of the following portions of systems used to achieve hot standby and cold shutdown: , i Reactor Coolant System (RCS)

                                  -     Primary loops
                                 -      Steam generators                                                                             ;
                                  -     Pressurizer Pressurfrer heaters PORVs and associated block valves i                                  -     Primary system temperature instrumentation
                                  -     Pressurizer pressure instrumentation Pressurfrer level instrumentation Source range monttors Associated power, control and instrumentation cabling Chemical and Volume Control System (CVCS)
- Charging loop A control valve f
                                  -     RCP seal water return control valve 4                                  -     RCP seal flow pressure transmitters
                                  -     RCP seal supply filters
                                  -     Associated control and instrumentation cabling

] Main Steam System (MSS) l - Steam generator level transmitters

                                  -     Associated instrumentation cabling j                                  Component Cooling Water System (CCW) 1 1                                  -     Thermal barrier pump

) - Thermal barrier outlet valves j - Associated power and control cabling l i Containment Ventilation System (CVS)

                                  -     Reactor cavfity cooling fans
- Fan discharge control dampers 3

Associated power and control cabling 4 1 i ] Impell Corporation . i Report No. 01-0310-1435 C0-1 Revision 0 4

            ,m                                                                                    ~

l

                 )

10CFR50 APPENDIX R SECTI II.G COWI.!ANCE EVALUATION FIRE AREA / ZONE 1-C0-(-10)-1 Containment Residual Heat Removal System (RHR)

                                -    Residual heat removal pumps
                                -    Residual heat removal heat exchangers RHR inlet isolations valves
                                -    RHR discharge isolation valves
                                -    RHR heat exchanger isolation valves RHR flow control valve
                                -    RHR inlet and discharge temperature transmitters
                                -    Associated power and control cabling The fc11owing poertions of the dedicated shutdown system are located within containment:

Reactor Coolant System (RCS)

                                -    Primary system temperature instruments
                                -    Pressurizer level transmitter
                                -    Pressurizer pressure transmitter
                                -    Cables for the following components:
                                     . Primary system temperature instruments
                                     .      Pressurizer level transmitters
                                     .      Pressurizer pressure transmitters Main Steam System (MSS)
                                -    Steam generator level transmitters
                                -    Cables for the following components:
                                     .       Steam generator level transmitters Cables for the dedicated shutdown system operation of pressurizer heater group D and solenoid operators for operation of the PORYs and block valves from the dedicated shutdown panel will also be located in containment.

The fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendix R, Section III.G.2. The dedicated shutdown system will be used to achieve and maintain cold shutdown in the event of fire. Operator action will be required to deenergize offsite and normal onsite power to prevent and mitigate spurious equipment operation. Operator action will also be required to manually control certain valves located outside the fire area / zone. Cables for the dedicated shutdown system instruments, which are located within the fire area / zone will be protected to i assure the availability of instruments for at least one steam generator / primary coolant loop. R; port No. 01-0310-1435 CO-2 Revision 0

_ _ . . _ s , _ _ _ .___ _ _ _ _. 5 10CFRSO APPENDIX R. SECTI.I f!!.S COW 1.IANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 l Containment 4 Cables and components for indication of pressurizer level and 1 pressurizer pressure at the dedicated shutdoun panel will be protected to assure the availability cf this indication at the dedicated shutdown panel. 1 Cables for dedicated shutdown system operation of tha required i portion of pressurfrer heater group D will be protected. An j exemption will be requested for the existing separation of the pressurizer heater groups at the pressurizer. } Cables and camponents for dedicated shutdeun system operation

of the p0RVs and block valves will be protected to assure the
availability of these components to support dedicated shutdown

] system operation. J Damage to cables for the normal control of the PORVs and their ! associated block valves could cause the PORVs to spuriously { open when the block valves are not available to isolate the ] i lines. The spurious actuation of the valves, untti operator action is taken to deenergire and close the valves, has been 1-analyzed, and will not result in unacceptable consequences (24,25). , Damage to cables for the reactor head vent valves and i pressurizer high point vent valves could cause the two series j high/ low pressure interface valves to spuriously open. The ] spurious actuation of the valves, until operator action is i taken to deenergfre and close the valves, has been analyzed

and will not result in an unacceptable consequences (24, 25I.

1 l Damage to cables for seal injection pressure transmitters 1 PT-1115A, PT-11158, and PT-1115C could cause the seal ] injection flow control valves to sp;;riously close. Damage to i cables for the thermal barrier outlet valves CV-722A, l CV-7228, and CV-722C could cause these valves also to sourtously close, preventing component cooling water flow to the thermal barrier. The interruption of seat injection and i seal cooling to the reactor coolant pumps, untti operator i action is taken to initiate seal injection from the dedicated shutdown panel has been evaluated and determined to be 4 ! acceptable (26l, ( I Damage to cables for auxiliary pressurizer spray isolation ! valve CV-305 could cause the valve to spuriously open. l Charging flow control valve FCV-1112 will remain available to 4 isolate this line until operator action is taken to deepergire j and close CV-305. Impe11 Corporation

pzport No. 01-0310-1435 C0-3 Revision 0 l

1

r o' 10CFR50 APPENDIX R. SECT! p!!!.GCOPPLIANCEEVALUATION o FIRE AREA / ZONE 1-C0-(-10)-1 Contairwent Damage to cables for containment spray isolation valves CV-82, CV-92, and CV-114 could cause the valves to spuriously open. Inadvertent actuation of the residual heat removal room deluge system could be initiated due to gravity flow from the RWST. Operator action will be required to close a manual valve located upstream to isolate this line. Containment spray will not be inadvertently initiated as the refueling water pumps will not be affected by a fire in this fire area / zone. j 1 Impe11 Corporation Rrport No. 01-0310-1435 CO-4 Revision 0

n _.._ g 10CFR50 APPENDIX .9. SECTe.MII.G COWLIANCE EVALUATION O FIRE AREA / ZONE 1-CO-(-10)-1 Containment O Category System Component Circuit-Schedule Function Consequence of Fire Mitigation g Hot RCS CV-530 ---- Block valve for PORY loss of CV-530. Valve will fail Operator action to deenergize 120VAC/480VAC Standby CV-546 open, sources to prevent / mitigate spurious Equipment operation. CV-530 will fail open on loss o of power. Protect cables for the second solenoid operator provided for dedicated shutdown system operation of CV-530. 6 Provide radiant energy shield between the PORY solenoids and their associated block valve solenoids to assure the availability g of at least one PORV to support dedicated shutdown system operation. o 1FY1112C1-KJ Remote valve control Damage to this circuit could , prevent remote operation and/or cause the valve to spuriously 0 oPen or close. . 1FY112C12-KJ Peacte valve control Damage to this circuit could

  ,                                                                                                                          prevent remote operation and/or cause the valve to spuriously open or close.

1FY112C18-KJ Solenoid control power Damage to this circuit could prevent remote operation and/or ( cause the valve to spuriously , open or close. F

'o o

O e j I e Impe11 Corporation

Pzport No. 01-0310-1435 CO-5 Revision 0 d

10CFR50 APPENDIX R, SECTIAII.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 Containment , Category System' Component Circuit-Schedule Function Consequence of Fire Mitigation Hot RCS CV-546 ---- PORY Loss of CV-546. Yalve will Operator action to deenergire 120VAC/4tW)VAC l Staney (contd) fati closed, sources to prevent / mitigate spurious i Equipment operation. CV-546 will fail closed on

 !  (contd)                                                                                                       loss of power. Spurious actuation of the j                                                                                                                  PORY, untti operator action is taken to deepergfre and close the valve, has been
  ,                                                                                                               analyzed and will not result in an l                                                                                                                  unacceptable condition (24,25). Relief j                                                                                                                  valves will remain available to protect 3

against system over-pressure. Protect cables for the second solenoid operator i j provided for dedicated shutdown system j operation of CV-546. Provide a radiant

;                                                                                                                 energy shield between the PORY solenoids j                                                                                                                  and their associated block valve solenoids j                                                                                                                  to assure the availability of at least one PORV to support dedicated shutdown system operation.

1FY111200-KJ Solenoid control power Damage to this circuit could prevent remote operation and/or i cause the valve to spuriously open or close. i 1FY1112C2-KJ Valve position Damage to this circuit could ? fndication prevent remote operation and/or ! cause the valve to spuriously open or close. 1FY112C11-FJ Yalve position indication Damage to this circuit could result in the loss of remote

,                                                                               valve control, and/or cause the                                                   ,

j valve to spuriously close. ' 1FY112C13-KJ Yalve position indication Damage to this circuit could i result in the loss of remote valve control, and/or cause the valve to spuriously close. l IFY112C14-KJ Valve position indication Damage to this circuit could i result in the loss of remote valve control, and/or cause the valve to spuriously close. 1FY112C15-KJ Remote valve control Damage to this circuit could

prevent remote operation and/or cause the valve to spuriously
open or close.

l ! Impe11 Corporation Pzport No. 01-0310-1435 C0-6 Revision 0 l l

(Q) C) 10CFR50 APPENDIX R. SECTIviII.G C(WPLIANCE EVALUATION FIPE AREA /20NE 1-CO-(-10)-1 Containment Category System Cosponent Circuit-Schedule Function , Consequence of Fire Nitigation Hot RCS CV-531 ---- Block valve for PORY Loss of CV-531. Yelve will Operator action to deenergize 120VAC/400VAC Stand'y (contd) CV-545 fail open. sources to prevent / mitigate spurious Equipment operation. CV-531 will fat) open on loss (contd) of power. Protect cables for the second solenoid operator provided for dedicated shutdown system operation of CV-531. 1 Provide a radiant energy shield between

 ;                                                                                                                          the PORV solenoids and their associated block valve solenoids to assure the availability of at least one PORY to a                                                                                                                            support dedicated shutdown system operation.

1GY1215C1-KJ Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1 1GY215C12-KJ Remote valve control Damage to this circuit could prevent remote operation and/or j ' cause the valve to spuriously

;                                                                                           open or close.

1GY215C18-KJ Solenoid control power Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. l l l l 1 I i 1 Impe11 Corporation . RIport No. 01-0310-1435 CO-7 Revision 0 l l

m O O 10CFR50 APPENDIX R. SECTidIII.G C0pFLIANCE EVALUATION O

." FIRE AREA / ZONE 1-CO-(-10)-1 Containment l Category System Component Circuit-Schedule Function Consequence of Fire Mitiestion t G l Not RCS CV-545 -- - PORY Loss of CV-545. Valve will Operator action to deenergize 120VAC/460VAC Standby (contd) fail closed. sources. CV-545 will fati closed on loss Equipment of power. Spurious actuation of the PORV, (contd) untti operator action is taken to deenergize and close the valve, has been

! analyzed and will not result in an unacceptable condition (24,25). Relfef , valves will remain available to protect against system over-pressure. Protect . cables for the second solenoid operator provided for dedicated shutdown system operation of CV-545. Provide a radiant energy shield between the PORV solenoids and their associated block valve solenoids to assure the availabiltty of at least one PORY to support dedicated shutdown system operation. 1GY1215C0-KJ Remote valve control Damage to this circuit could

prevent remote operation and/or cause the valve to spuriously open or close. ,

j 16Y215C11-KJ Yalve position indication Damage to this circuit could i result in the loss of renc.te I valve control, and/or cause the l valve to sportously close, i 16Y215C13-RJ Valve position indication Damage to this circuit could rescit in the loss of remote valve control, and/or cause the valve to spuriously close, j 1GY215C14-KJ Valve position indication Damage to this circuit could result in the loss of remote i valve control, and/or cause the ] valve to spuriously close. l 18Y215C15-KJ Remote valve control Damage to this circuit could prevent remote operation and/or

cause the valve to spuriously 1

open or close. 1GY1215C2-KJ Remote valve control / Damage to this circuit could position indication prevent remote operation and/or j cause the valve to spuriously ( open or close. Impe11 Corporation j RIport No. 01-0310-1435 C0-8 Revision 0 4 i

m 10CFR50 APPENDIX R, SECT. s 'III.G COW LIANCE EVALUATION FIRE APEA/ ZONE 1-CO-(-10)-1 Containment C'tesory System Component Cfrcutt-Schedule Function Consequence of Ffre Mitfgotion Hot PCS Par ---- Pressurfrer heater Loss of pressurfrer heater None. Dedicated shutdown system Standby (contd) Heater group A group A. operation of pressurfrer heater group D Equipment Group A will remain available. (contd) 1FBil5P4A-KA Power Demoge to this circuit could cause the loss of power to at least one of the heaters in the l pressurfrer heater group. 1FB115P4B-KA Power Damage to this circuit could cause the loss of power to at least one of the heaters in the pressurfrer heater group. ? Par - Pressurfrer heater Loss of pressurfrer heater None. Dedicated shutdown system Heater group B. operation of pressurfrer heater group D i Group B will renain available. 1GB215P4A-KA Power Damage to this circuit could cause the loss of power to at 4 least one of the heaters in the pressurfrer heater group.

1GB215P48-KA Power Damage to this circuit could 4

cause the loss of power to at least one of the heaters in the pressurfrer heater group. 1 I l l I i l l I I i . Impe11 Corporation l PIport No. 01-0310-1435 C0-9 pevision 0

f ( 10CFR$0 APPEIBIX R, SECTa -i!I G CtpFLIANCE EVALUATION 4 FIRE AREA /ZOIE 1-CO-(-10)-1 Contalment , C-tegory System Campement Cfreutt-Schedule Functfen , Consequence of Fire Itttfeation i Hot PCS Pzr -- Presserfrer heater loss of pressurizer heater llone. Dedicated shutdown system operation 1 Standby (contd) Heater group C group C. of pressurfrer heater group D will remain ] Equfpaent Group C available. 1 (contd) l IFB109P01-KA Power Damage to this circuit could cause the loss of power to at i least one of the heaters in the l presserfrer heater group.  ; l IF8109P02-KA Power Damage to this circuit could , a cause the loss of power to at j least one of the heaters in the i pressurfrer heater group. j IF8109P03-KA Power Damage to this circuit could ] cause the loss of power to at least one of the heaters in the  ; pressurfrer heater group. l 1FB109P4A-KA Power Damage to this circuit could a cause the loss of power to at l 1 east one of the heaters in the j presserfrer heater group. l 1F8109P5A-KA Power Damage to this circuit could i cause the loss of power to at least one of the heaters in the , pressurfrer heater group. i I r 4 I i i i i Impe11 Corporation i

R port No. 01-0310-1435 C0-10 Revision 0

(b > 10CFR50 APPENDIX R, SECLWi!!.G COWI.IANCE EVALUATION p 0 FIPE AREA / ZONE 1-CO-(-10)-1 Containment Crtegory System Component Cfreutt-Schedule Function Consequence of Fire Mitigation Hot PCS Pzr ---- Pressurizer heater Loss of pressurizer heater Protect cables for the required portion Staney (contd) Heater group D group D. of pressurfrer heater proup D with a Equipment Group D noncombustible radiant energy shield or a (contd) 1-hour rated barrier. Exemption for existing separation of the pressurizer i heater groups. 1GB209P4A-KA Power Damage to this circuit could

  • cause the loss of power to at 1 east one of the heaters in the pressurizer heater group.

1G8209P48-KA Power Damage to this circuit could cause the loss of power to at least one of the heaters in the pressurfrer heater group. 1GB209P5A-KA Power Damage to this circuit could i cause the loss of power to at least one of the heaters in the pressurizer heater group. 1GB209P58-KA Power Damage to this circuit could cause the loss of power to at j least one of the heaters in the pressurfrer heater group. ^ 1GB209P5C-KA Power Damage to this circuit could cause the loss of power to at least one of the heaters in the i pressurfrer heater group. . l I i .i i I Impe11 Corporat1on Report No. 01-0310-1435 CO-11 Revision 0

                                                                         .n 10CFR50 APPEWIX R. SECTIMII.G COWLIANCE EVALUATION FIRE APEA/ZO K 1-CO-(-10)-1 Containment Category System Camponent Circuit-Schedule Function                       Conseguence of Fire                  Mitigation Hot         RCS     NE-1201   ---           Source range monitor      loss of NE-1201.              None. During operation of the dedicated Staney      (contd)                                                                                 shutdown system, shutdown margin will be J

Equipment determined by sampling primary system (contd) boron concentration. 1GQ102106-KA Indication signal Damage to this circuit could result in low off-scale or

erroneous indication.

) 1GQ102107-KA Indication signal Damage to this circuit could result in low off-scale or erroneous indication. NE-1202 ----- Source range monitor loss of K-1202. None. During operation of the dedicated 3 shutdown system, shutdown margin will be determined by sampling primary system boron concentration. { 1FQ102091-KA Indication signal Dame to this circuit could i resu in low off-scale or erroneous indication. l 1F0102092-KA Indication signal Damage to this circuit could l result in low off-scale or erroneous indication.

1FQ102097-KA Power Damage to this circuit could 1 cause a loss of power to NE-1202.

a LT-431 --- Presseriter wide range Loss of LT-431. None. LT-430A will remain available j level transmitter at the dedicated shutdown panel. 1GQ104090-KA Sensor signal Damage to this circuit could result in high off-scale, low a off-scale, or erroneous 4 indication. J I i Impe11 Corporation R port No. 01-0310-1435 C0-12 Revision 0 1

m - 10CFR90 APPDWII R, SECTI m t!.G CS FLIANCE EVALUATION l FIRE AREA / ZONE 1-CO-(-10)-1 Contaisement C-tegory System Componeet Circuit-Schedule Function , Conseguance of Fire Mitigation Not RCS LT-435 ---- Pressurizer wide range Loss of LT-435. None. LT-430A will recein available , Standby (contd) level transmitter at the dedicated shutdoun panel. 3 Eguipsent ! (contd) IWQ104093-KA Sensor signal Damage to this circuit could ! result in high off-scale, low . off-scale, or erroneous indication. PT-425 ----- Pressurizer pressure Loss of PT-425. None. PT-434A will rescin available at the dedicated shutdoun panel. i IFQ108II-KJ 5ensor signal / interlock Damage to this circuit could I to RHR valves MOV-813, result in high off-scale, low MOV-834 off-scale or erroneous i indication. This could remove l the high RCS pressure interlock J for RHR valves MOV-813 and i MOV-834 i f* PT-430 - Pressurizer pressure Loss of PT-430. Pressurizer pressure indication will transmitter remain available at the dedicated , shutdoun panel. Operator action to deenergize pressurizer heater groups

  • A and B. Spurious operation of PCV-430C

' and PCV-430H will not affect safe shutdoun, l as the reactor coolant pumps are tripped. j Pressurizer code safety valves will be j available for over-pressure protection. 1FQ104II-KJ Sensor signal / input to Damage to this circuit could pressurizer heater result in high off-scale, low control off-scale or erroneous indication. This could cause spurious operation of pressurizer heater s A and B and PCV-4 and PCV-430H. I 1 i i 1

 !  Impe11 Corporation .

] Rrport No. 01-0310-1435 C0-13 Revision 0 l,

O b l 10CFR50 APPENDIX R SECTI A II.G COWLIANCE EVALUATION e V FIRE AREA / ZONE 1-CO-(-10)-1 Conta1noent j Category System Component Circult-Schedule Function Consequence of Fire Mitigation Hot RCS PT-431 IFC104I2-KJ Pressurfrer pressure Damage to this cfrcuit could Operator action to deenergize 120VAC/480VAC Staney (contd) transitter cause a high off-scale, low sources to prevent / mitigate spurious Equipment off-scale, or erroneous operation. CV-546 will fail closed on (contd) indication. This will loss of power. Spurious actuation e i cause PC-4318 to spuriously of the PORY untti operator action is . open or close CV-546 taken to deenergfre and close the valve has been analyzed and will not result in any unacceptable condition (24,25). Relief valves will remain available to protect against system over-pressure. 4 TE-2401A ---- RCS loop A het leg Loss of TE-2401A. None. Instrumentation for at least temperature element one loop of dedicated shutdown panel j instruments will remain available. 3 1 IFY3309IA-KJ Sensor signal Damese to this circuit could result in high off-scale, low off-scale, or erroneous ] fndication. i IFY330916-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous

indication.

TE-2412A ---- RCS loop B hot leg Loss of TE-2412A. None. Instrumentation for at least temperature element one loop of dedicated shutdown panel fnstruments will remain available. 1FY3309IB-KJ Sensor signal Damage to this circuit could result in high off-scale, low 4 off-scale, or erroneous indication. 1 1FY33091H-KJ Sensor signal Damage to this circuit could i result in high off-scale, low ] off-scale, or erroneous ', indication. 4 i 1 ~ Impe11 Corporation i RIport No. 01-0310-1435 00-14 Revision 0

L O O 10CFR50 APPENDIX R. SECTivf!I.S CopFLIANCE EVALUATION O j FIpE AREA / ZONE 1-CO-(-10)-1 j Contaitument Category System Component Circuit-Schedule Function Consequence of Fire 9Htisetton i Not - RCS TE-2422A - -- RCS loop C hot leg Loss of TE-2422A. None. Instrumentation for at least St ney (contd) temperature element one loop of dedicated shutdown panel Equipment instruments will remain available. ! 1FY33091C-KJ Sensor signal Demoge to this circuit could result in high off-scale, low 1 off-scale, or erroneous indication. I IFY3309II-KJ Sensor signal Demoge to this circuit could I result in high off-scale, low off-scale, or erroneous

;                                                                                                indication.

1 TE-3402A - - - - RCS loop A het leg Loss of TE-3402A. None. Instrumentation for at lee: t l temperature element one loop of dedicated shutdown panel ! instruments will remain available. 16Y29041A-KJ Sensor signal Damage to this cirtuf t could j i result in high off-scale, low 4 off-scale, or erroneous j indication. { 1GY290416-KJ Sensor signal Damsge to this circuit could ,j result in high off-scale, low

off-scale, or erroneous j indication.

4 i TE-3411A ----- RCS loop B hot leg Loss of TE-3411A. None. Instrumentation for at least

temperature element one loop of dedicated shutdown panel instruments will remain available.

1GY29041B-KJ Sensor signal Damese to this circuit could ! result in high off-scale, low i off-scale, or erroneous ! fadication, f 16Y29041H-KJ Sensor signal Damage to this circuit could )I result in high off-scale, low

off-scale, or erroneous indication.

l l r

Impe11 Corporation i Report No. 01-0310-1435 C0-15 Revision 0 i

f.. .-...... - .. -. ..... . . . . . . . i

m 10CFR50 APPENDIX R. SECTidIII.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-C0-(-101-1 Containment . Category System Component Circuit-Schedule Function , Consequence of Fire Mitigation Hot RCS TE-3421A ----- RCS loop C het leg Loss of TE-3421A. None. Instrumentation for at least Standby (contd) temperature element one loop of dedicated shutdown panel Equipment instruments will remain ave 11able. (contd) 1GT2504IC-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. 16Y290411-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. TE-402C ----- RCS loop A cold leg Loss of TE-402C. None. Instrumentation for at least temperature element one loop of dedicated shutdown canel instruments will remain available, i j 1F0103I43-KA Sensor signal Damage to this circuit could

~

result in high off-scale, low off-scale, or erroneous indication. i TE-411B 1XQ103I48-KA Sensor signal Damage to this circuit could None. Instrumentation for at least i result in high off-scale, low one loop of dedicated shutdown panel off-scale, or erroneous instruments will remain available, indication. TE-422C ----- RCS loop C cold leg Loss of TE-422C. None. Instrumentation for at least

temperature element one loop of dedicated shutdown panel l instruments will remain available, 1HQ103161-KA Sensor signal Damage to this circuit could I result in high off-scale, low

! off-scale, or erroneous i indication. i I l 1 i l Impe11 Corporation Rzport No. 01-0310-1435 C0-16 Revision 0

s . . . - - _ - 4 , 10CFR50 APPENDIX R. SECTI J i!I.G C(BWLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 Containment C:tegory System Component Cf revit-Schedule Function Consequence of Fire Mitigation Hot RCS C-1 - - - - Reactor vessel None. None. Staney (contd)

Equipment j (contd) C-2 ---

Pressurizer None. None. E-1A ---- Steam generator E-1A None. None. i j E-18 - - - - Steam generator E-18 None. None. j E-1C ----- Steam generator E-1C None. None. CVS A-9 - pesctor cavity cooling Loss of A-9. None. The reactor cavity cooling fans are fan required only to support operation of NE-1201 and NE-1202. j IN8109 PIA-KA Power Loss of power to A-9. INB109C3A-KA TS-24 interlock Damage to this circuit could spuriously start or stop the fan and/or prevent remote ] operation of the fan. I P0-11 --- A-9 discharge control Loss of PO-11. None. The reactor cavity cooling fans are { damper required only to support operation of j NE-1201 and NE-1202. i j INB109C2A-KA Damper control Damage to this circuit could j spuriously close the damper. A-95 - - - - Reactor cavity cooling Loss of A-95. None. The reactor cavity cooling fans are fan required only to support operation of NE-1201 and NE-1202. 9 j IXB209 PIA-KA Power Loss of power to A-95. 3 1XB209 CIA-KA TS-24 interlock Damage to this circuit could spuriously start or stop the fan, and/or prevent remote 1 operation of the fan. j Operation of the fan with the i handswitch in the " Bypass" position would not be affected. l Impe11 Corporation 1 Report No. 01-0310-1435 CO-17 4 Revision 0 1 . ___ .. 4

n - n 10CFR50 APPENDIX R. SECT 1 6 41.C C0prLIANCE EVALUATION O' < FIpE AREA / ZONE 1-CO-(-10)-1 Contaffusent Category System - Cesponent Circuit-Schedule Function gsequenceofFire Mitigation Hot CVS PO-12 --- A-95 discherpe control Loss of PO-12. None. The reactor cavity cooling fans are Staney (contd) dampe required only to support operation of Equipment NE-1201 and NE-1202 (contd) 1X8209C2A-KA Damper control Damage to this circuit could spuriously close the damper. TS-24 ----- Reactor cavity Damage to the temperature switch None. The reactor cavity cooling fans are temperature switch could spuriously start or stop required only to support operation of fans A-9 and A-95. Operation NE-1201 and NE-1202. of fan A-95 with the handswitch in the bypass position would not be affected. CVCS CV-304 ---- Charging loop A control Loss of CV-304. Valve will fail FCV-1112 will remain available to isolate valve closed. this line untti operator action is taken to deenergize 120VAC/480VAC power. Operator action will then be required to close FCV-1112 from the dedicated shutdown panel if isolation of this line is required. CV-304 will open on ressure differential if charging throug loop A is required. 1FQ107118-KA Scienoid control power Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. PCV-1115A ---- Sea 1 water return control Loss of PCV-1115A. Valve will Operator action to deenergfre 120VAC/480VAC valve fail open. power sources to prevent / mitigate spurious operation. Valve will fail open. 1WQ107112-KA Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control, and/or cause the valve to spuriously close. PCV-11158 ---- Sea 1 water return control Loss of PCV-11158. Valve Operator action to deenergize 120VAC/480VAC valve will fail open. power sources to prevent / mitigate spurious operation. Valve will fail open. 1WQ107131-KA Remote valve control / Damage to this circuit could ' position indication result in the loss of remote valve control, and/or cause the valve to spuriously close. R1 port No. 01-0310-1435 CO-18 Revision 0

O 10CFR50 APPENDIX R. SECTi s tII.G C(BFLIANCE EVALUATION FIRE AREA / ZONE 1-CC-(-10)-1 Containment C-tegory System Component Cirtutt-Schedule Function , Consequence of Fire Mitigation j Hot CVCS PCV-1115C ---- Sea 1 water return control Loss of PCV-1115C. Valve will Operator action to deenergire 120VAC/480VAC Standby (contd) valve fail open. power sources to prevent / mitigate spurious Equipment operation. Valve will fati open. (contd)  ! i IWQ107132-KA Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control, and/or cause the j valve to spuriously close. PT-1115A ----- G-2A seal flow p.wssure Loss of PT-1115A. Operator action to deenergire 120VAC/480VAC l transmitter power sources to prevent / mitigate spurious operation. Operator action required to

 ,                                                                                                          f ail FCV-1115A open b
air at the doghouse, verify y isolating instrument FCV-1115D
closed, and to control seal injection flow

, using manual valve located upstream. 1WQ107134-KA Sensor signal Damage to this circuit could i result in high off-scale, low off-scale or erroneous

indication. This could cause flow controller FC-1115A to spuriously open or close FCV-1115A and FCV-11150 PT-11158 -----

G-2B seal flow pressure Loss of PT-11158. Operator action to deenergire 120VAC/480VAC

;                                                transmitter                                                power sources to revent/ mitigate spurious operation. Operator action required to i

fail FCV-11158 open by isolating instru- , ment air at the dogMuse, verify FCV-1115D 1 closed, and to control seal injection flow using manual valve located upstream. IXQ107126-KA Sensor signal Damage to this circuit could result in high off-scale, low

off-scale or erroneous
indication. This could cause

, the flow controller FC-11158 ! to spuriously open or close FCV-11155 or FCV-1115E. I i i , Impe11 Corporation-RIport No. 01-0310-1435 C0-19 Revision 0 l l l

                                                              -.                                              - -      -              -            .          ~       -    -              - -       . -

n O cl 10CFR50 APPEWIX R SECT 4 #111.8 CCWLIANCE EVALUATION l FIRE APEA/ ZONE 1-CO-(-10)-1 Containment Category System Camponent Circuit-Schedule Function Consequence of Fire Mitigation l Mot CVCS PT-1115C - G-2C seal flow pressure Loss of PT-1115C. Operator action to deenergize 1200C/480VAC l Stan ey (contd) transmitter power sources to prevent / mitigate spurious a Equipment operation. Operator action required to I (contd) fail FCV-1115C open by isolating instru-ment air at the doghouse, verify FCV-1115F i closed, and to control seal fdjection flow using manual valve located upstream. 1XQ107127-KA Sensor signal Damage to this circuit could result in high off-scale, low i off-scale, or erroneous indication. This could cause flew controller FC-1115C to spur 1ously open or close FCV-1115C or FCV-1115F. 4 I' C-952A ---- RCP seal flow supply None. None. filter

C-9525 -----

pCP seal flow supply None. None. , filter i C-952C ----- RCP seal flow supply None. None. filter l i 1 MSS LT-2400A --- Steam generator A wide Loss of LT-2400A. None. At least one loop of dedicated J range level transmitter shutdown panel instruments will remain available. 1FY331514-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous j indication. 1 LT-24008 --- Steam generator B wide Loss of LT-24008. None. At least one loop of dedicated l range level transmitter shutdown panel instruments will remain available. 1FY3315IS-KJ Sensor signal Damage to this circuit could result in high off-scale, low

,                                                                                                                                                             off-scale, or erroneous indication.

Impe11 Corporation Peport No. 01-0310-1435 C0-20 Revision 0 t

I

                 -                                    10CFR50 APPDmIX P. SECTuaII.G CtWLIANCE EVAltJATION

! FIRE AREA / ZONE 1-CD-(-10)-1 Containment Category System Cn: : .t Circuit-Schedule Function Consequence of Fire Mitigation Hot MSS LT-2400C - - - - Steam generator C wide Loss of LT-2400C. None. At least one Icop of dedicated Standby (contd) range level transmitter shutdown panel instruments will remain

Equipment available.

(contd) 1FY331516-KJ Sensor signal Camage to this circuit could result in high off-scale, low off-scale, or erroneous indication. I LT-3400A ---- Steam generator A wide Loss of LT-3400A. None. At least one loop of dedicated range level transattter shutdown panel instruments will remain available. 16Y29011A-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. l LT-34008 ---- Steam generator B wide Loss of LT-34008. None. At least one loop of dedicated a range level transmitter shutdown panel instruments wf11 remain j available. ) 1GY290118-KJ Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous ] indication. LT-3400C --- Steam generator C wide Loss of LT-3400C. None. At least one loop of dedicated

!                                                     range fevel transaftter                                   shutdown panel instruments will remain

't

 ;                                                                                                              available.

l 16Y2901IC-KJ Sensor signal Damage to this circuit could j result in high off-scale, low

;                                                                                 off-scale, or erroneous
indication.

I l l I.

  !     Impe11 Corporation F port No. 01-0310-1435                                                    C0-21                                                          Revision 0 A

n 10CFR50 APPENDIX R, SECTIl< II.C COWLIANCE EVALUATION O 1 FIpE AREA / ZONE 1-CO-(-10)-1

!                                                                     Containment 1

Category System temronent Circuit-Schedule Function Consequence of Fire Nitigation Hot CCW G-964 - - - - RCP thermal barrier p o p Loss of G-964 Operator action to start G-964 at 125V DC 1 Standby Bus 1. Component cooling water is not J Eeufpment required to support dedicated shutdown I (contd) system operation. Interruption of seal cooling and seal injection to the reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable

;                                                                                                          (26).

1WD120C7A-KA power Damage to this circuit could spuriously start or stop the pump, or prevent p e p start. l IWD120C8A-KA power Damage to this circuit could spuriously start or stop the

pump, or prevent pump start.

CV-722A --- G-2A thermal barrier Loss of CV-722A, Valve will Operator action to deenergize 120VAC/480VAC outlet valve fail open, power to prevent spurious operation. valve will fati open to support operation of the thermal barrier pump as required.

;                                 IWQ106029-KA Solenoid control power      Damage to this circuit could

. prevent remote operation and/or d cause the valve to spuriously j open or close. ) CV-7228 ---- G-28 thermal barrier Loss of CV-7228. Valve will Operator action to deenergize 120VAC/480VAC i outlet valve fail open, power to prevent spurious operation.

Valve will fail open to support operation

! of the thermal barrier pump as required, l

lWQ106030-KA Solenoid control power Damage to this circuit could 1

prevent remote operation and/or

cause the valve to spuriously j open or close.

i i I l I Impell Corporation Peport No. 01-0310-1435 C0-22 Pevision 0 ] i

6 8 10CFR50 APPENDIX R SECTI -ws!.G COMPLIANCE FVALUATION O FIRE AREA / ZONE 1-CO-(-10)-1 Containment C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Not CCW CV-722C ---- G-2C thermal barrier loss of CV-722C. Yelve will Operator action to deenergize 120VAC/480VAC Standby (contd) outlet valve fail open. power to prevent spurious operation. Equipment Valve will fall open-to support operation (contd) of the thermal barrier pump as required. 1WQ106031-KA Solenoid control power Darege to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. Csid PHR G-14A --- RHR pump Loss of G-14A. None. The dedicated auxilf ary feedwater Shutdown pump will remain available for single Equiprent phase ccoldown. 1F85122P2-KJ Power Loss of power to G-14A. 1F85122P3-KJ Power Loss of power to G-14A. G-148 ---- RHR pump Loss of G-148. None. The dedicated auxfitary feedwater pump will remain available for single phase cooldown. IG85222P2-KJ Power Loss of power to G-148. 1G85222P3-KJ Power Loss of power to G-148. HCV-602 ----- RHR flow control valve None None. This valve is not required to support single phase cooldown. 1FC106165-KA Remote valve control Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open, Impe11 Corporation Rsport No. 01-0310-1435 C0-23 Pevision 0

m 10CFR50 APPE W IX R. SECTI M II.G C(BFLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 Containment j Cetesory Systen Component Cfresit-Schedule Funct1on Consequence of Ffre Mitigotion

!     Cold       RHR      MOV-813     ---            RHR falet isolation         Less of MOV-813.              None. This valve is not required to l     Shutdown   (contd)                             valve                                                     support single phase cocidown.

l Equipment (contd) IFB169 PIA-KA Power loss of power to MOV-813. 1FB169C3A-KA Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will

;                                                                                fall as is, normally closed.

i MOV-814 ---- RHR fnlet isolation Loss of P0"d18 None. This valve is not required to I support single phase cooldown. valve 1G8271 PIA-KA Power Loss of power to MOV-814 l 1GB271C2A-KA Position switch / torque Damage to this circuit could switch fecesck result in the loss of remote valve control. The valve will fall as is, nornelly closed. 4 i MOV-822A ----- RHR heat exchanger E-21A Loss of MOV-822A. None. This valve is not required to l inlet control valve support single phase cocidown. 1FB164P1A-KA Power Loss of power to MOV-822A. 1 IFB164C2A-KA Position switch / torque Damage to this circuit could switch feedback result in the loss of remote ]. valve control. The valve will fail as is. i j i 1 j 1 1 Impe11 Corporation R port No. 01-0310-1435 CO-24 l Revisfon 0 I____________ _

                      ^
                                                                                                                                                         ^
                                                                                         .+

, 10CFR50 APPENDIX R, SECTas1II.S COMPLIANCE EVALUATION FIRE ASEA / ZONE 1-CO-(-10)-1 Containment Crtogory . System Camponent Circutt-Sche &ie Function , Conseguence of Fire Mftigetton Cold RNR MOV-8225 ----- RNR heat exchanger E-21B Loss of MOV-8228. None. This valve is not required to Sh:tdown (contd) inlet control valve support single phase cooldown. Equipment (contd) 1G8266 PIA 4A Power Loss of power to MOV-8226. 1G8266C2A4A Position switch / torque Damage to this circuit could switch feeeack result in the loss of remote j talve control. The valve will fail as 1:. l I MOV-833 ---- RNR discharge isolation Loss of MOV-833. None. This valve is not required to } valve support single phase cooldown. 5 ] 1F8170 PIA 4A Pouer Loss of power to MOV-833. 4 i IFB170C2A4A Position switch / torque Demoge to this circuit could i switch feedback result in the loss of remote

valve control. The valve will j fail as is, norselly closed.

!} MOV-834 ---- RHR discharge isolation Loss of MOV-834. None. This valve is not required to j valve scpport single phase cooldown, d 1G8272P1A4A Power Loss of power to MOV-834. 1 1G8272C3A4A Position switch / torque Damage to this circuit could j switch feedback result in the loss of remote j valve control. The valve will j fail as is, norselly closed. i l l i i i 1 Impe11 Corporation. PIport No. 01-0310-1435 C0-25 Revision 0 i

f% (M

                                                                                              /

t 10CFR50 APPEWIX R SECTi.a)II.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 Containment C'tegory System Component Circult-Schedule Function Consequence of Fire Mitigation C Id PHR TE-600 ---- RHR inlet temperature Loss of TE-600. None. Thfe instrument is not required for Shutdown (contd) single phase cooldewn. Equipuent ~ (contd) INQ106036-KA Sensor signal Dasage to thfs circutt could result in high off-scale, low I off-sc61e, or erroneous indication. t TE-601A ---- RHR heat exchanger E-21A Loss of TE-601A. None. This instrument is not required for discharge temperature single phase cooldown. 1FQ106162-KA Sensor signal / input to Damage to this circuit could TCV-601A controller result in high off-scale, low

;                                                                                              off-scale, or erroneous indication. This could cause the flow controller to spuriously open or close TCV-601A.

I TE-6018 --- ~4# ha v exchanger E-21G Loss of TE-6018. None. This instrument is not required for sc+ sa'e e' temperature single phase cocidown. , 1GQ106163-KA Sensor sf pal / input to Damage to this circuit could TCV-60lb controller result in high off-scale, low off-scale, or erroneous indication. This could cause the ficw controller to i spuriously open or close TCV-6018. E-21A ----- RHR heat exchanger E-21A None. None. E-218 ---- RHR heat exchanger E-218 None. None, l Impe11 Corporation Rzport No. 01-0310-1435 C0-26 Revision 0

o n 10CFR50 APPEN0IX R. SECTI v ill.G CL9FLIANCE EVALUATION O FIpE AREA / ZONE 1-CO-(-10)-1 Containment Category System Cesponent Circuit-Schedule Function -Consequence of Fire Nitigation High/ Low RCS SV-2401 ----- Reactor vessel vent Loss of SV-2401. Valve will fail Operator action to denergire 120VAC/480VAC pr2ssure valve closed.' power to prevent / mitigate spurious Interface operation. Valve will fall closed on loss

of power. Spurious actuation of the vent valves untti operator action is taken to

! deepergize and close the valves has been l analyzed and will not result in an ! unacceptable condition (24,25). 1FY3312CA-KJ Solenoid control power Damage to this circuit could result in the loss of remote valve control, and/or cause the

valve to spuriously open.

SV-2402 ----- Reactor vessel vent Loss of SV-2402. Valve will fail Operator action to denergire 120VAC/480VAC i valve closed. power to prevent / mitigate spurious operation. Valve will fail closed on loss

of power. Spurious actuation of the vent valves until operator action is taken to deenergire and close the valves has been analyzed and will not result in an I unacceptable condition (24,25).

1 1FY3312CB-KJ Solenoid control power Damage to this circuit could result in the loss of remote

valve control, and/or cause the valve to spurtously open.

) SV-2403 ----- Pressurizer high point Loss of SV-2403. Yalve will fall Operator action to deenergize 120VAC/480VAC j vent valve closed. power to prevent / mitigate spurious operation. Valve will fati closed on loss of power. Spurious actuation of the vent } valves untti operator action is taken to j deenergfre and close the valves has been

analyzed and will not result in an

, unacceptable condition'(24,25). I 1FY3312CC-KJ Solenoid control power Damage to this circuit could result in the loss of remote valve control, and/or cause the j valve to spuriously open. i ) 1 i

Impe11 Corporation Rrport No. 01-0310-1435 C0-27 pevision 0

m ( n 10CFR50 APPENDIX R. SECTIsdI.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-CO-(-10)-1 Containment ! Category System Component Circuit-Schedule Function , Consequence of Fire Nitigation High/ Low RCS SV-2404 ---- Pressurfrer high point loss of SV-2404 Valve will fall Operator action to doenergfre 120VAC/480VAC Pr:ssure (contd) vent valve closed. power to prevent / mitigate spurious Int:rface operation. Yelve will fati closed on loss j (contd) of power. Spurious actuation of the vent valves untti operator action is taken to deepergize and close the valves has been analyzed and will not result in an

,                                                                                                                             unacceptable condition (24,25).

1

IFY3312CD-KJ Solenoid control power Damage to this cfrcuit could result in the loss of remote valve control, and/or cause the valve to spuriously open.
SV-3401 ----- peactor vessel vent Loss of SV-3401. Valve will fail Operator action to deenergfre 120VAC/480VAC j valve closed, power to prevent / mitigate spurious operation. Valve will fati closed on loss of power. Spurious actuation of the vent valves untti operator action is taken to deenergize and close the valves has been analyzed and will not result in an unacceptable condition (24,25).
1GY3005CA-KJ Solenoid control power Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open.

i i 1 I j i ) i 4 Impe11 Corporation j Report No. 01-0310-1435 C0-28 Revision 0 l 1 } - _ - _ __-_ - - _ -. - _ _ .- . ._ _ _ __ _ - _ . . ____ .__

?' ( 10CFp50 APPENDIX R SECTt. M II.S CCIFLIANCE EVALUATION FIRE AREA /2tWE 1-CO-(-10)-1 Containment j Cctegory System Component Ciremit-Schedule Function Consequence of Fire lettigation High/ Low RCS SV-3402 --- Reactor vessel vent Loss of SV-3402. Valve will fail Operator action to doenergire 120VAC/483VAC ! Pr:ssure (contd) valve closed. power to prevent /mitisate spurious 17.terface operation. Valve will fail closed on loss i (contd) of power. Spurious actuation of the vent

valves until operator action is taken to

, deepergize and close the valves has been analyzed and will not result in an j unacceptable condition (24,25). ' 16Y3005CB-KJ Solenoid control power Damage to this circuit could result in the loss of remote j valve control, and/or cause the valve to spuriously open. l j SV-3403 ---- Presserfrer high point Loss of SV-3403. Valve will fati operator action to deenergfre 120VAC/480VAC 1 vent valve closed. power to prevent / mitigate spurious

operation. Valve will fail closed on loss of power. Spurious actuation of the vent
valves untti operator action is taken to deepergize and close the valves has been

. analyzed and will not result in an i unacceptable condition (24,25). 1GY3005CC-FJ Solenoid control power Damage to this circuit could result in the loss of remote valve control, and/or cause the

,                                                                            valve to spuriously open.

I i t SV-3404 ---- Presserfrer high point Loss of SV-3404 Valve will fail Operator action to deepergize 120VAC/480VAC i vent valve closed. power to prevent / mitigate spurious 4 operation. Valve will fait closed on loss 1 of power. Spurious actuation of the vent l valves until operator action is taken to j deenergize and close the valves has been

analyzed and will not result in an
unacceptable condition (24,25).

2 ] IGY3005CD-KJ Solenoid control power Damage to this circuit could i result in the loss of remote i valve control, and/or cause the j valve to spuriously open. i i I Iepell Corporation Prport No. 01-0310-1435 00-29 Revision 0 i

t O O 10CFR50 APPEWIX R. SECU III.G CCBW1.!ANCE EVALUATION O 1 FIRE ABEA/ ZONE 1-CO-(-10)-1 Containment I C-tegory System Cn n- .t Circuit-Schedule Function Consequence of Fire Mitigation High/ Low CVCS CV-527/ IFM1111C4-KJ pemote valve control / Damage to this circuit could CV-528 and CV-526 will remain available

Pressure CV-525 position indication result in the loss of remote to isolate seal return t.nd letdown II.terface valve control, and/or cause the flow until operator action is taken (contd) valve to spuriously close, to deenergize 120VAC/480VAC power to prevent / mitigate spurious operation.
)                                                                                                                            Spurious actuation of the seal return and letdown valves untti operator action is j                                                                                                                            taken to deenergize and close the valves,   '

has been analyzed and determined to be acceptable (24, 25). 1FY121P09-KJ Remote valve control. Damage to this circuit could prevent remote operation and/or

cause the valve to spuriously open or close.

1 CV-527 - Sea 1 water return Loss of CV-527. Valve will CV-526 will remain available to isolate 3 isolation valve fail closed. seal return flow until operator action { is taken to deenergize 120VAC/480VAC power i to prevent / mitigate spurious operation. Spurious actuation of the seal return ] valves untti operator action is taken to 1 deenergize and close the valves has been l analyzed and determined to be acceptable j (24,25). 1 1FM111106-FJ Remote valve control / Damage to this circuit could j position indication result in the loss of remote j valve control, and/or cause the 4 valve to spuriously close.

 ,                                     1FY121P05-KJ           Pesote valve control           Damage te this circuit could l          ,                                                                                 prevent remote operation and/or i                                                                                            cause the valve to spuriously j                                                                                            open or close.

1FY121P10-KJ Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. I i i l t Impe11 Corporation ! Report No. 01-0310-1435 CO-30 Revision 0 J a

10CFR50 APPENDIX R. SECT v ill.G COMPLIANCE EVALUATION FIRE AREA /2ONE 1-CO-(-10)-1 Contalment C-tegory Systo Component Cf rest t-Schedule Functfon , Consequence of Ff re Mitigetion Spurious PCS G-2A - Reactor coolant Loss of G-2A. None. Turbine trip will deenergize the i Operation pump pump.

;           Equipment l

1NA1A03P3-KA Power Loss of power to G-2A. INA1A03P4-KA Power Loss of power to G-2A. l INA1A0X5-KA 011 lift pressure Damage to this circuit could ] fnterlock spuriously start the pump and/or j prevent remote operation, damage i could also bypass the lube oil pressure faterlock and allow starting the pop on a low cil i pressure condition. 4 G-28 Reactor coolant Loss of G-28. None. Turbine trip will deenergize the j pump pump. 1NA1903P3-KA Power Loss of power to G-29. INA1803P4-KA Power Loss of power to G-28. 1 IIA 1803C6-KA 011 Ifft pressure Damese to this circuit could j interlock spuriously start the pump and/or , prevent remote operation, dmage

could also bypass the lobe oil 4 pressure interlock and allow starting the pump on a low oil pressure condition.

G-2C - Peactor coolant loss of G-2C. None. Turbine trip will deenergize the pump pump. INA1A01P3-FA Power Loss of power to G-2C. - ) INA1A01P4-KA Power Loss of power to G-2C. l 1XAIA01C4-KA 011 Ifft pressure Damage to this circuit could interlock spuriously start the pump and/or i prevent remote operation, damage i could also bypass the lobe oil i pressure interlock and allow i starting the pump on a low oil j pressure condition. ) l. Impe11 Corperation. Report No. 01-0310-1435 C0-31 Revision 0 4 l

                                                                            ,~

O n 10CFR50 APPENDIX R. SECTI#aII.G COOFLIANCE EVALUATICM O FIRE AREA / ZONE 1-C0-(-10)-1 Containment C tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious RCS PCV-430C Pressurizer spray valve Loss of PCV-430C. None, as reactor coolant pumps are tripted. Cperation (contd) from PCS loop 8 cold leg Equipment

.   (contd)                       1FQ108133-KA  Positioner signal          Damage to this circuit could I                                                                          result in the loss of remote i                                                                           valve control, and/or cause the
!                                                                          valve to spuriously close.

l IXQ108131-RA Valve posttion indication Damege to this circuit could t result in the loss of remote

 ,                                                                         valve control and/or
erroneous indication at panel C09.
 !                       PCV-430H  - --         Pressurizer spray valve Loss of PCV-430H.                  None, as reactor coolant pumps are tripped.

from RCS loop A cold leg l IG0108I34-KA Positioner signal Damage to this circuit could i i result in the loss of remote valve control, and/or cause the valve to spuriously close.

)                                 1XQ108133-FA  Yelve position indication Damage to this circuit could result in the loss of rewote i                                                                         valve control, and/or erroneous indication at panel C09 CVCS CV-305     -- -        Pressurizer auxilfary      Loss of CV-305. Valve will fatl FCV-1112 will remain available to isolate 4

spray control valve closed, this ifne until operator action is taken j to deenergize 120VAC/480VAC power sources j to prevent / mitigate spurious operation. 4 CV-305 will fait closed on loss i of power. Spurious actuation of this valve, until operator action is taken to deenergize and close the valve, has been

;                                                                                                          analyzed and t*.etermined to be acceptable (24,25).

i IWQ107119-KA Solenoid control power Damage to this circuit could prevent remote operation and/or l cause the valve to spuriously

 ;                                                                         open or close.
l 1

i j Impell Corporetion

RIport No. 01-0310-1435 C0-32 Revision 0 l
  \

l i o c9 10CFR50 APPENDIX R, SECTI m j!.S Ct3 M IANCE EVALUATION 0 <

,                                                                                         FIDE AREA / ZONE 1-CO-(-10)-1 l                                                                                                Containment
                                                                                                                                                                                     ~

Cateeory System Component Circuit-Schedule Function Consequence of Fire Nitigation

!                    Spurious CVCS        CV-525   ----

Letdown domineralfrer Loss of CV-525. Valve will CV-526 will remain available to isolate + Operation (contd) isolation fail closed. this line until operator action is taken to l Equipment deenergize 120VAC/480VAC power to prevent / (contd) mitigate spurious operation. CV-525 will fail closed on loss of power. Spurious 1 actuation of this valve to deepergire and close the valve, until operator action is taken has been analyzed and determined to l l be acceptable (24,25). } 1FN1111C5-KJ Remote valve control / Damage to this circuit could { position indication result in the loss of rePote valve control, and/or cause the valve to spuriously close. 1FY121P03-KJ Remote valve control Damage to this circuit could prevent remote operation and/or <! cause the valve to spuriously

open or close.
SIS McV-356 --- Safety injection loop A Loss of MOV-356 Yelve will fall None. Dedicated shutdown system operation

) recirculation isolation as is, normally closed. of charging pump G-8A will remain valve available. Valve fails closed as required for charging system operation. 1F8158P1A-KA Power Loss of power to MOV-356 i IF8158C2A-KA Position switch / torque Damage to this circuit could I switch feedback result in the loss of remote l valve control. The valve will 1 fail as is, normally closed. i MOV-357 ---- Safety injection loop 8 Loss of MOV-357. Valve will None. Dedicated shutdown system operation , recirculation isolation fail as is, normally closed. of charging pump G-8A will remain

valve available. Valve fails closed as required

' for charging system operation. 168243P1A-KA Power Loss of power to MOV-357. , 1G8243C2A-KA Position switch / torque Damage to this circuit could I switch feceack result in the loss of remote ! valve control. The valve will ' fall as is, normally closed. ? i i l c Impe11 Corporation l PIport No. 01-0310-1435 3 CO-33 Revision 0 }

n 10CFR50 APptISIX R. SECTImII.C CopTLIANCE FVALUATION O ' FIRE AREA /70ut 1-CO-(-10)-1 Contalmeent Category System Caeponent Circuit-Schedule Function , Consequence of Fire pHtisetten Spurfeus SIS NOV-358 ---- Safety injectfan loop C Loss of MOV-358. - Valve will fall None. Dedicated shutdous system operation Operation (contd) recirculation isolation as is, normally closed. of charging pump G-8A will remain Equipment valve available. Valve fails closed as required (contd) for charging system operation. 1HB305 PIA 4A Pouer Loss of pouer to MOV-350. 1HB385C2A4A Position switch / torque Demoge to this circuit could switch feeeock result in the loss of remote valve control. The valve will fall as is, noruelly closed. CRS CV-114 ---- Containment spray Loss of CV-114. The valve Operator action to close manual valve isolation valve

  • will fall open. located upstream. Refuelfeg water pumps will not be affected by the fire.

19t1214C04J Control peuer and Demoge to thfs circutt could position indication prevent remote operation and/or cause the valve to spuriously open or close. 1Ep1214CE4J Pouer Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1EN1214CF4J Position indication Damage to this cfremit could cause erroneous valve position fadication. IGM 1214CG4J Position fadication Damage to this circuit could cause erroneous valve posf tion indication. Impe11 Corporation Riport No. 01-0310-1435 CO-34 Revision 0

d (~ \

                                                                             \

1 10CFR50 APPENDIX R SECtadIII.G Cowf.IANCE EVAltlATION (J FIRE AREA / ZONE 1-CD-(-10)-1 Containment ) C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation ) Spurious CR$ CV-8" ---- Containment spray Loss of CV-82. The valve will Operator action to close manual valve Operation (contd) control valve fail open. located upstream. Refueling water pumps Equipment will not be affected by fire. ) (contd) IFM1111CE-KJ Control power / Damage to this circuit could position indication prevent remote operation and/or ) cause the valve to spurfously open or close. ) 1FM1111CF-KJ Control power Damage to this circuit could prevent remote operation and/or cause the valve to spuriously ) open or close. 1FM1111CG-KJ Position indication Damage to this circuit could ) cause erroneous valve position indication. ) 1FM1111CH-KJ Position indication Damage to this circuit could cause erroneous valve position indication. 3 CV-92 ---- Containment spray Loss of CV-92. The valve will Operator action to close manual valve ) control valve fail open. located upstream. Refueling water pumps will be be affected by fire. 3 FWS FT-460 1F0112I66-KA Sensor signal Damge to this circuit could None. Main feeduater pumps are tripped, result in a high or low steam 2 flow indication, causing FCV-456 to spuriously open or close, and/ or cause a reactor scram. 3 1FYR1005A-KA Power Damage to this circuit could cause a loss of power to FT-460, 2 causing FCV-456 to spuriously close, and/or cause a reactor scram. J J 9 a Impe11 Corporation pIport No. 01-0310-1435 C0-35 Revision 0

o o m a 10CFR50 APPENDIX p SECT.JIII.G CtprLIANCE EVALUATION FIRE ApEA/ ZONE 1-CO-(-10)-1 Containment Category System Ceaponent Circutt-Schedule Function Conseguence of Fire Mitigation Spurfous FWS FT-461 1GQ112051-KA Sensor sfgnal Damage to this circuit could None. Main feeduster pumps are trfpped. Operation (contd) result in high or low steam Equfpment flow fndication, causing FCV-457 (contd) to spurious 1 open or close, and/ or cause a reactor scram. 1GQ112167-KA Sensor signal Damage to this circuit could 4 result in high or low steam flow fndication, causing FCV-457

.,                                                                            to spuriously open or clo;e and/

cause a reactor scram.

  ,                                   1GYR1006A-KA  Power                     Damage to this cfreult could d

cause a loss of power to FT-461, I causing FCV-457 to spurfously j, close, and/or cause a reactor scram. 1 j, 1GYR1007A-KA Power Damage to this circuit could j cause a loss or power to FT-461, i causfng FCV-457 to spuriously i, close, and/or cause a reactor scram. I* FT-462 1HQ112I68-KA Sensor signal Damage to this circuit could None. Naf n feeduster pumps are tripped.

result in high or low steam
!                                                                             flow fndicetfon, causino FCV-458 l,                                                                            to spuriously open or close, and/
or cause a reactor scram.

a' 1HYR1001A-KA Power Damage to this circuit could I cause a loss of power to FT-462, , j* causing FCV-458 to spuriously ' close, and/or cause a reactor ] scram. l l' l 1 i Impe11 Corporation 1 peport No. 01-0310-1435 CO-36 pevision 0 4,

    . .  . . . ..-.e--   ...        .

f3')

                                                                                $)

( 10CFR50 APPENDIX R, SECTQJI.G CiprLIANCE EVALUATION Oq ' FIDE AREA /2ONE 1-C0-(-10)-1 Contalment Category Syste Campenent Cf rcut t-Schedule Function , Consequence of Ff re Mitigetion Spurfees FWS LT-453 IWC1120474A Sensor signal Demoge to this cfreaf t could None. Main feeduster pesups are trfpped. Operetton (contd) cause FCV-456 to spuriously close Equipment and/or cause a reactor scre. (contd) 1WYR1000A4A power Demoge to this circuit could I cause a loss of power to LT-453, j causing FCV-456 to close, and causing a reactor scram. } LT-454 1WQ1120484A Sensor s1gnal Demoge ta thfs c1rcutt could None. Ma1n feedueter pumps are tripped. cause FCV-457 to spurlessly close

and/or cause a reactor scram.

I IWYR1009A4A power Damage to this circuit could cause a loss of power to LT-454, 1 causteg FCV-457 to close, and causing a reactor scram.

!    .                       LT-455 1XQ1120414A        Sensor signal              Damage to this circuit could            None. Main feedwater pumps are tripped.

] cause FCY-458 to spuriously close 1 and/or cause a reactor scrap. I power Demoge to this circuit could IWYR1004A4A .l cause a loss of power to LT-455, 1 causing FCV-458 to close, and ] causing a reactor scram. i l

 ?

} i i I i i ) i i j Impe11 Corporation - Report No. 01-0310-1435 CO-37 Revision 0 i. l______ . f

m n 10tFR50 APPEWII R. SECTdI!!.S CIBWLIARCE EVALilATION 0 FIRE AREA /2EEE 1-CO-(-10)-1

Containment Category System Campement Circuit-Schedule Function r
n . _+ of Fire pitigation
   ,       Alternete SIS         Mov-8504                     SafetyinhectionloopA        Loss of MOV-850A. Valve will fail home. Dedicated shutdemn system operation Shutdeun                                           discharge                   as is, normally closed.           of charging pump G-8A will ressin

{ Equipment available. IE30274P1-KA Pouer Loss of power to IWV-8504 1

, ISOO274C5-KA Position switch /torgue Demoge to this circuit could suitch fecesck result in the loss of remote i

valve centrol. The valve will

   ,                                                                                      fail as is, noruelly closed.

} 2 MOV-8505 Safety injection loop B Loss of MOV-8508. Valve will Bone. Dedicated shutdoun system operation i, discharge fail as is, norselly closed. of charging pump G-8A will remain j available. 1 A 1EB180 PIA-KA Peuer Loss of peuer to MOV-8508. 4, ISB180C94-KA Positten switch / torque Demese to this circuit could

switch fecesck result in the loss o' remote valve control. The velve will
, fail as 1
, normally closed.

I f MOV-850C Safety injection loop C Loss of MOV-850C. Valve will None. Dedicated shutdeun system operation

 /                                                            discherge                   fail as is, noruelly closed.      of charging pump G-8A will recein
ave 11able.

ilWO391P2-KA Peuer Loss of peuer to MR-850C. 1Hp0391C7-KA Positten switch / torque Demoge to this circuit could switch fec e ack result in the loss of remote valve control. The valve will

, fail as is, noruelly closed.

1 l 4, ) i, i' l 4 j Impe11 Corporation peport No. 01-0310-1435 CO-38 pevision 0 {e t

O N 10CFR50 APPEND!I p. SECTUII.E Cl39L!ANCE EVALUATION O FIDE AptA/20K 1-CO-(-10)-1 Containment Category System Campenent Circutt-Schedule Function Conseguence of Fire Mittention Dedicated KS LT-430A Presserf aer level Loss of LT-430A. Protect pressurfrer level transmitter and Shutdown transmitter instrument cables to assure pressurfrer Equipment level indication will remain available at

  ,                             1GC300002-RA    Sensor sfgnal             Damage to this circuit could  the dedicated shutdown panel.

result in high off-scale, low l off-scale, or erroneous fr.dtcation.

  ,                     PT-434A                 Pressertzer pressere      Loss of PT-434A.              Replace transmitter with wide range transmitter                                             transaf tter. Protect pressurfrer pressure transmitter and instrument cables to assure pressurfrer pressure indication will remain available at the l                                                                                                       dedicated shutdown panel.

1GC300001-KA Sensor signal Damese to this circuit could { result in high off-scale, low 1

  ,                                                                       off-scale, or erroneous indication.

} t TE-402A pCS Loop A hot leg Loss of TE-402A. Protect instrument / cables to assure one

,                                               temperature element                                     loop of dedicated shutdown panel

'l indication will remain available or protect all dedicated shutdown paiiel instrument cables, and request exemption for instruent separation due to intervening corbustibles.

!                               IW103115-KJ     Sensor signal             Damage to this cfrtuft could
!                                                                         result in high off-scale, low
;                                                                         off-scale, or erroneous

[ fndication. l IWQ103115-KJ Sensor signal Damage to this cfremit could I, result in high off-scale, low off-scale, or erroneous ] fndication. l l 4 i. Impe11 Corporation "l, Report No. 01-0310-1435 CC-39 Revision 0 t

o 10CFP50 APPEWII R. SECT 1tN !!!.s CarLIABCE EVALMTION [ FIPE AREA /205E 1-CO-(-101-1 Contaissent [ Category Systen Campement Cf resit-Schedule Functfen , Consequence of Ffre Pitisetfen 3 Dedicated RCS TE-412A RCS loop B hot leg Loss of TE-412A. Protect instrement/ cables to assure one , Shetdoun (contd) temperature element loop of dedicated shutdown panel ' fosfreent indication will remain available or o (contd) protect all dedicated shutdown paliel instrument cables, and request exemption t for instrument separation due to . o intervening ceu6ustibles. l l 1XQ103197-EJ Sensor signal Damage to this circuit could  !

, result in high off-scale. Iow q off-scale, or erroneous '

j, fedication. F IIC103097-EJ Sensor signal Damage to this circuit could j result in high off-scale, low l 0 off-scale, or m s  ; indication. 1 i f TE-422A RCS loop C het leg Loss of TE-422A. Protect instrisent/ cables to assure one j temperature element loop of dedicated shutdoun panel 4 fadication will reosin available or protect all dedicated shutdown paliel j f astrument cables, and request exemption i t for instrasent separation due to 4 intervening cou6ustibles. .l ' IIC103I96-EJ Sensor signal Demoge to this efrcuit could 1 result in high off-scale. Iow { off-scale, or erroneous l, fadication. 1

;                                         IIC103098-EJ   Sensor signal              Damage to this efrcuit could 1,                                                                                  result in high off-scale. Iow t

off-scale, or erroneous I 1 fadfcation. jo ) ] o e l ? i a e ] Impe11 Corporetion l Report No. 01-0310-1435 CO-40 Revision 0 I' i -.

f^s\ fh t V f)

                                                                             \

10CFR50 APPDWII R. SECTi M II.G COIP.!ANCE EVALUATICU G' FIK AREA /20K 1-CO-(-10)-1 Contefament Category System e n- .t Circutt-Schedule Functfan Consequence of Fire Nftigation Dedicated RCS TE-402B RCS loop A cold leg Loss of TE-4029. Protect instrument / cables to assure one Shutdown (contd) temperature element loop of dedicated shutdown panel 1 Equipment fndication will reeaf n available or 1 (contd) protect all dedicated shutdown paw 1 instrument cables, and request exemption for instrument separation due to intervening combustibles. 1 1 1G030016g-KA Sensor signal Damage to this circuf t could 4 result in high off-scale, low  : i off-scale, or erroneous 1 indication. TE-4125 RCS loop B cold leg Loss of TE-4129. Protect instrument / cables to assure one i temperature element loop of dedicated shutdown panel fndication will reeafn available or protect all dedicated shutdown palEl instrument cables, and request exemption

 !                                                                                                            for instrument separation due to j                                                                                                              intervening coa 6ustibles, i                                   1GQ300I70-KA      Sensor sfgnal             Damage to thf a cfrcutt could result in high off-scale, low

] off-scale, or erroneous

 ;                                                                             indication.

] TE-4229 RCS loop C cold leg Loss of TE-4229. Protect instrument / cables to assure one i temperature element loop of dedicated shutdown panel indication will reeafn available or protect all dedicated shutdown paliel instrument cables, and request exemption for instrument separation due to I intervening coa 6ustibles. 1 1G0300171-KA Sensor signal Damage to this circuit could I result in high off-scale, low off-scale, or erroneous fndication. I j l

 ,  Impe11 Corporation i  Report No. 01-0310-1435                                                    C0-41                                                            Pevision 0 i

1 O O C 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE APEA/2ONE 1-CO-(-10)-1 Containment Crtegory System Cagement Circuit-Schedule Function Consequence of Fire Mitigation Dedicated PS$ LT-450C Steam generator A Loss of LT-450C. Protect instrument / cables to assure one

Shutdoun level transmitter loop of dedicated shutdown panel l Equipment indication will rossin available or (contd) protect all dedicated shutdoun panel ,

instrument cables, and request exemption  ! for instrument separation due to intervening coubestibles. IG0300003-KA Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. i LT-451C Steam generator B Loss of LT-451C. Protect instrument / cables to assure one level transmitter loop of dedicated shutdown panel indication will reonin available or c protect all dedicated shutdown paliel , instrument cables, and request exemption  ! for instrument separation due to intervening coubustibles. 160300004-KA Sensor sfonal Damage to this circuit could result in high off-scale, low off-scale, or erroneous ' indication. t i LT-452C --- Steam generator C Loss of LT-452C. Protect instrument / cables to assure one > level transmitter loop of dedicated shutdown panel indication will remain available or protect all dedicated shutdown paliel j instrument cables, and request exemption for instrument separation due to intervening coe ustibles. 1GC300005-KA Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. i h Impe11 Corporation Report No. 01-0310-1435 CO-42 Revision 0

[ ,/'T p..

           \                                           d                                    V            ,

ICCFP50 APPENDIX R. SECTICN !!I.C C(PPLIANCE EVALUATICN i FIPE APFA/7CNE 1-AB-(-3)-2A Peacter Acziliary Puilding Lcwer Level l Effects of Fire on Safe $butdown Capability A fire in this fire area /rene could result in the loss of the followine portions of systems used to achieve bot standby and cold sketecwn: CPemical aed volume Control System (CVCS)

                                  -    Charging purys and associated support equipment
                                  -    Charging PWST isolation valves Cables for the following components:
                                       . Charging pump and associated support equipment
                                       . Charging PWST isolation valves Fssential Electric Systems -
                                  -    Motor control center 2A
                                  -    Cabling for the following components:
                                       -     Motor control center 2A The fire protection features provided for the protection of the charging system do not rett the requirements of 10CFR50, Appendiz R. Section III.G.2. The safety injection system will be used as an alternate to the charging system for a fire in this fire area /rone, per III.G.3. Fire detection and an automatic fire suppression system will be installed for coverage of the charging pump room. An esemption for area-wide suppression / detection reevirements of III.G.3 will be reevested.        ,

Damage to cables for the test pump could cause the pump to spuriously start. Operator action will be required to deepergize the pump by deepergizing motor control center 2A. Darage to cables for primary plant water makeup control valve FCV-1102A could cause the valve to spuriously open allowing primary plant water to be supplied directly to the charging pump suction. Operator action will be required to close a manual valve located downstream of FCV-1102A to isolate this line. Spurious actuation of this valve will not affect safety injection system operation. Irre11 Corporatien Pevision 0 Prport No. 01-0310-1435 AB-1

n U Og. J - 10CFP50 APPEPDIF P SECTION III.G CCPPLIAPCE TVALUATICW FIPE APEA/7CNE 1-AB-(-3)-PA Peactor Auxiliary Building Lower Level Damage to cables for boric acid supply valves FCV-1102A, . CV-334, CV-406A and CV-406B could cause these valves to spuriously open, allowing concentrated boric acid to be supplied to the charging pump suction. Operator action will be required to close manual valves to isolate these lines. Spurious actuation of these valves will not affect safety injection system operation. Camage to cables for volume control tank isolation valve POV-1100C could cause the valve to spuriously open, l preventing suction flew to tre charging purps free the i PWST. If the charging pumps remain in operation, operator action would be reevired to Panually close the valves to prevent cavitation of the purps when the volume control tank l erpties. Spurious actuation of this valve will not affect safety injecticn syster operation. l l l l l l l l 1 l Irrell Corporatien Fevision 0 Report Fo. 01-0310-1435 AB-?

n ,-

                                                                                                                                              \

10CFP50 APPENDIX P, SECTION III.G C WPLIANCE EVALUATION FIPE APFA/20WE 1-AP-(-31-2A Peactor Auxiliary Building Lower Level C.ctecory Systee reeponent Circuit-Schedule Function Consecuence of Fire Mitigation Het 4eCV KC-2A --- Motor centrol center 2A Loss of MCC-2A pone. The couiprent powered from this Standby rotor control center is only required to Foufreent support charging system operation. 1YPS223P2-KB Power Loss of power to MCC-2A will cause the loss nf power to the folicwing components recuired for norwal/ alternate stutdown: PG8AF G*a2 MGBPF CVCS G-SA Charging pump G-SA Loss of G-8A. Cperator action to deepergize cParging pumps G-SA and G-88. Use the safety injection system es an alternate shutdown system to the charging system; and install suppression / detection for coverage of the charging pump room per the requirements of Section III.G 3; and request an exerption for partial supressTon/detecticn coverage. 1GA2C07P1-FB Power Loss of power to G-BA G-EP ---- Charging pump G-8B Less of G-PB Operator action to deepergize charging pumps G-BA and G-88. 1FA1007P1-FB Power loss of power to G-PB r . Irpell Corporation Feport Fo. 01-C310-1435 AB-3 Pevision 0

            ,g                                                          c3                                                            p l                                                                                                                                                     (

10fFP50 APPENCIY P, SFrTICF III.G COPPLIPWCE EVALUATION FIPF APEA/ZCWF 1-AF-(-3)-2A Peactor Auxiliary Puilding Lower Level 4 Crtegery Syster rogocent Circuit-Sche <8vle Function Consecuence of Fire Mitigation Wot CVCS G-942 ---- Lube oli pump for G-BA Loss of G-942 Wone. Loss of G-942 has no effect on Standby safety injection system operation. Equipment (centd) 1XF2A16PI-KB Power Loss cf power to G-942 IXB2A16Cl-KB Interlock to G-2A Damace to this circuit could l prevent autostart of pwp 6942 when G-8A is started, or i spuriously start G942 when G-8A is not running. l lyB2A16C2-EB Local purp control Damage to this circuit could cause a loss of remote control and/or prevent local eenval start of the purp or spuriously start the purp. 1FP2A16C3-FB Low bearing oil pressure Darape to this circuit could interlock cause a loss of remote pump control, prevent autostart of the pump or spuriously start tre pupp. G 043 Lube oil pupp for G-PB Loss of G-943 None. Loss of G-943 has no effect on safety injection system operation. 1FB012?PI-EC Power Loss of power to G-943 IFB0129C3-KC Local pump control Damage to this circuit could prevent local renual start of the pump, or spuriously start tre pump, 1WB0129C4-EC Low bearing oil Damage to this circuit could pressure interlock prevent auto start of the pupp , or spuriously start the pump. G eP7 Shaft triven lobe oil Wone. None. purp for G-BA Shaft driven lube oil None. Wone, G-9P8 - pump for G-88 Impell Corporation AP-4 Revisien 0 Percrt be. 01-0310-1435

r-

             ,m

(~x em

s. N y 10CFP50 APPENDIX P, SECTION III.G CCPPLIANCL EVALUATICW c

FIPE APEA/ZCNE 1-AB-(-31-2A Peactor Auxiliary Building Lower Level 4 Cr:+ecory Systear Compocent Circuit-Schedule Function Consequence of Fire Pitfoetion , Het CVCS MG8pF - Lube oil coolfog fan loss of MG8AF None. Loss of MG8AF has no effect on , Standby (contd) safety injection systee operation. Eouippent for G-PA (contd) s IXF2A14P1-KB Power Loss of power to MGPAF l 1XB2A14C1-KB Fan Control Damace to this circuit could I spuriously start the fan, or l prevent auto start of the fan,

                              .1XB2A14C2-FB      Local fan test control     Depage to this circuit could prevent local manual start of I

the fan, or spuriously start the fan. MG8BF ---- Lube oil coolfeg fan Loss of MG8BF None. Loss of MG88F has no effect on safety injection system operation, for G-88 1XB2A15P1-F8 Power Loss of power to MGB8F 1WB2A15C1-KB Fan control Damage to this circuit could prevent autostart of the fan, or spuriously start the fan. 1XB2A15C2-KB Local fan test control Parage to this circuit could speriously start the fan, or prevent auto start of the fan. s Irpell Corporation i Frpert F3. 01-C310-1435 AE-5 Pevision 0 1

r 10CFP50 APPFPtIN P. SFCTIcu III.G CopFLIANCE EVALUSTION

                                                                                                                                                      -4 i                                                              FIPE APFA/70WF 1-88-(-3)-FA Wesctor Amm111ery Building Lower Level ft:segory Systeer Componeet Circuit-Schedule Function                       r _      .__e of Fire                 Pitigation Not          CTC5    - ptv-11005              PW5T cherping isolation Loss of MtV-1100R                 Operator action to deenergize and verify      ,

Stoney valve closed MOV-11000. Eguipseet. {cc-te ' (contd) IF90147P143 Power Loss of power to POV-11008. ~ 1F90147C148 Position switch /tergue Danese to this circuit could switch fee eack prevent remote operation and/or cause the valve to spuriously l open or close. l IF90147C243 McV-1100C open interlock Desese to this circuit could result in the loss of remote valve control, and/or cause tha valve to spuriously close. PCV-11000 PWST charging isolatten Loss of POV-11000 - Operator action to deenergize and verify valve closed POV-11000. IMOc378P143 Power' Loss of power to MOV-11C30. IN0379C148 peV-1100C open interlock Damese to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. 1NB0378C243 Position suiter/torgue Damage to this circuit could switch feeeach prevent resete eperation and/or cause the valve to spuriously open or close. E-906 Lebe oil cooler for Mone. None. G-8A, water cceled E 807 Lebe off cooler for None. None. G-88, water cooled F *08 Lube oil cooler for pone. None. < G-8A, air cooled E-?0* Luke oil cooler for pone. None. E-8F, air cooled i l irrell Corporation Fevisice 0 ! Perert Po. 01-0310-1435 AF-6 1

i l

                                                                                                                                                          ,r3                                                                                   (-

l ! 10CFRSC APPEFCII P. SECTION III.G CCWLIANCE EVAttiATICW L l *. IPE AptA/2011E 1-At-(-3)-2A l ReaC*r tumiliary Building Lower Level Categery System Carpenent Circuit-Schedule Function Consemence of Fire Mitigation l Celd None l Statdown Eguipeent l f High/Lew CVCS CV-52F/ 1GT2A3fP14C Power Darace to this circuit could None. CV-527 and CV-525 will reesin Pressere CV-526 result in the loss of repete available to isolate seal water return Interface valve control, and/or reuse the and letdown. valve to spuriously close. l Speriees CVCS G-42 Charging systeer test Loss of G-42 Operator action to teenergize the Cyeratten pump pump by deenergiring MCC-2A, ! E pippent THF2AICP14F Power Less of power to G-42 1H92A10C145 Pepote pupp control and Papage to this circuit could indication spuriously start the peep and/ or prevent remote pump l operation. 1HB2A10C248 Local peep control Damage to tPis circuit could spuriously start the peep and/ or prevent remote or local peep operation. CV-334 Beric acid supply Less of CV-334 Valve will Operator action to close manual valve control valve fail open. located upstream. Spurious actuation of this valve will have no effect on safety injection system operation. 1FC1070334B Selenoid control pcwer Capece to this circuit could prevent rerote operation and/or cause the valve to spuriously open or close. s Impe11 Corperatien Frycrt Po. C1-0310-1435 AB-7 Revision 0

p ym (} < 100FR50 APPEWOIF P. SFCTION III.G CtpFLIArtT FVALUATION FIPE APEA/7CPE 1-AB-(-3)-2A Peacter Ausfliary Putiding Lower Level e Cateeory Syste= Costonent Ciremit-Schedule Function Censecuence of Fire Mittoation Sperices CVCS CV a0fA Leteewn deeineralfrer Loss of CV a0fA. The valve Operator action to close manual valve Operation (centd) contrel valve will fail open. located downstress of FCV-1102A. Spurious Ecefprest actuation of this valve will have no effect en safety injection syster fccetd) operation. CV-4068 Cheetcal blendino Loss ef CV-4068. Operator action to close maeval valve centrol valve. located downstream of FCV-1102A. Spurious actuation of this valve will have no effect on safety injection system operation. FtY-1102A Prirary water makeup Less of FCV-1102A. The valve Operator action to close manual valve centrol valve will fail closed. located downstream to prevent boron dilution. Spurious actuation of the valve, untti operator action is taken to close the downstream manual valve has been analyzed and determined to be acceptable (27). 1WCIC7007-rB Scienoid control power Carace to this circuit could prevent remote operation and/or cause tre valve to spuriously open or close. l FCY-11028 Poric acid pump discharge Loss of FCV-11028. The valve Operator action to close manual valve control valve will fati open. located downstream of FCV-1102A. I IWC107009-RB Solenoid contrel pcwer Daeage to this circuit could j prevent remote operation and/or cause the valve te spuriously open or close. l l Irre11 Correretire Pevision 0 Pepert Fo. 01-0310-1435 AF-8 l

I V V d 10CFP50 APPENDIN P. SECTICW III.G COPPLIAPCE EVALUATICW FIPE APEA/ZCFE 1-AF-(-31-2A Peactor Aus111ery Building Lower Level C-tecory System Component Circuit-Schedule Function Consequence of Fire Mitfoetion Spurious CVCS MCV-1100C IGB2A76P145 Power Loss of power to MCV-1100C. None. Spurious actuation of this valve Operatica (contd) will have no effect on safety injection Equiprent system operation. ! (contd) l ICPC187CS4B MCV-11005 oren interlock Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1G82A7EC148 Position switch / torque Damage to this circuit could switch fecesck result in the loss of remote valve control. 1GB2A76C2-FB Perete valve control Darece to this circuit could prevent repete operation and/or cause the valve to spuriously open or close. 1GP2A76C348 Volume control tank low Damese to this circuit could level interlock prevent remote operation and/or cause the valve to spuriously open or close. 1G82A76C4-tB McV-11000 open interlock Darage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1GB2A76C6-tB POV-11000 interlock This circuit is entirely contained within the fire area / zone. The circuit and its termination points are assured destroyed. 1GP2A76C7-r8 POV-11008 interlock This circuit is entirely contained within the fire area / zone. The circuit and its terirination points are assumed destroyed. 4 Irpell Correration Pepert No. C1-0310-1435 AB-9 Pevision 0

10CFR50 APPEPe!X p, SECTI N III.G Cl*PLIANCE EVALUATION FIPE APEA/70FE 1-A8-(-3)- A Peactcr Auxiliary Building Lower Level Cetecory Syster Camponent Circuit-Schedule Function Consequence of Fire Mitigation Alternate pone

 $butdown Equipment redicated   -                                                                                                Equipment / cable identifiers for dedicated Shutdown                                                                                                     shutdown equipeent will be added when Equipment                                                                                                    as-built information is available.

120V C-38 1GY2A30P1-FB Power Damage to this circuit could result No effect on normal safe shutdown systems. in loss of power to auxiliary shutdown papel instrupents, and prevent transfer of steam dump control through SV-175 to ti.e auxiliary shutdown panel C-38. W Irpell Corporation Pepert No. 01-C310-1435 AP-10 Pevision 0

                                                                                  ._._.     --. - - . . .   . - . . - .         .   ..~ _ ~ . _

( . O ' 10CFP50 APPEFDIX P. SECTICW III.6 C(WPLIANCE EVALUATIDW FIPE APEA/ ZONE 1-A8-20-2C. , Solid Waste Baling Roca 3 - Effects of Fire on Safe Shutdown Capability The esign basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area /rone. i 1 v w n e Impe11 Corporation  ! Pepert No. 01-0310-1435 AB-11 Revision 0

O O O . 10CFP50 APPENDIX R, SECTICE III.G CCFPLIAPCE EVALUATION FIRE APEA/7CNE 1-AB-20-2C Selid Neste Paling Reen

                                                                                                                             ~

Cetecory Fyster Component Cirevit-Schedule Function Consequence of Fire Mitigation Not None . Stan4y Equipment Cold None Shutdown Ecufpment High/ Low None Pressure Interface Spurious None Operation Equipment Alttrnate None Shutdown Equipment Dedicated None $butdown Eculpment Irpell Corporation Peport Po. 01-0310-1435 AB-12 Pevision 0

                                                                                                                          \

10CFP50 APPENDIX P. SECTICN III.G COWLIAPCE FVALUATICN FIPE APEA/7ONE 1-AB-20-FD ' ideste Gas Cryogenic Treatment Room Fffects of Fire on Safe Shutdown Capability-The design t' asis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone. P Iepell Corporation pevision 0 Peport No. 01-0310-1435 - AB-13

w

                    \

l i

                                                    -10CFRSC APPENDIX R. SECTICN III.G COWLIANCE EVALUATION FIRE AREA /20NE 1-A8-20-2D
 .                                                             Weste Gas Cryogenic Treatment Poor Catigory    Systen Component' Circuit-Schedule Function                     Consequence of Fire        Mitication Pot         None StIndty Equipment Cold        None Shutdown
   - Equipment High/ Low None Pressure Inttrface Spurious None Operation Equipment Alternate None Shutdown Equipment Dedicated None Shutdown Equipment P

Irpell Corporation Report IJo. 01-0310-1435 AP-14 Revision 0

N 10CFP50 APPENDIF P SECTION III.G C(WPLIAKE EVALUATICW

                                                                                             's FIPE APEA/20ME 1-AB-20-2F High Level Solid Waste Storage Fffects of Fire on Safe Shutdown Capability The design basis fire will Pot affect the capability to achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone.

Impe11 Corporation Peport No. 01-0310-1435 AP-15 Pevision 0 L

   - -            -   .    . - . .       -   . . = - . ~ . . . . -
                                                                                         -                                   "N 10CFR50 APPENDIX R SECTION III.G C(WPLIANCE EVALUATICW 4

FIPE AREA /70NE 1-A8-20-2F Hioh Level Solid Waste Storage 1 -

'       Category     System ' Component Circuit-Schedule Function                      . Consequence of Fire      Mitigation Hot         None                                                                                                                .

.. Standby l Equipment i Celd . Nona 9 . Shutdown Equipment l j High/ Low None t Pressure-Interface Spurious None Operation Equipment i 4 Alternate None , Shutdown Equipment

Dtdicated None Stutdown Eculpeent 1

i 1 } i ? f 1 [ - i ? I' 4 Irpell Corporation Peport No. 01-0310-1435 AB-1E Pevision 0 , i 1  ! 1

     . . _ . . , ... _ .     . . _-   = . _ _ _ _. . . _. .. .        . _ _    .               ._. .      ..  . _ . . . . . ,. . . _ _ _ . _ . - . . . _ . . _ . . . .m. _ m _ .
                                                                                                                                                                                      +

10CFR50 APPENDIX P. SECTICW III.G CCPPLIANCE EVALUATICW

                                                                                                   .                                                                                -i FIPE APEA/70NE 1-AP-20-?G '

Pesin Slurry Tank Poce ,

                                                                                                                                                                                    -l
;                                                                 Effects of Fire on Safe Shutdown Capability'                                                                      -i 1

The design basis fire will not affect the capability te I achieve and paintain cold shutdown, as there are no safe stutdown cosponents or cables within the fire area / zone. i

  • 4 1

I t i , a i i, , 1 i t 1 I j . l I i a ? 1 F I t

 !                                                                                                                                                                                   I i                                                                                                                                                                                     4
  ',                                                                                                                                                                                 f 4

1  !

 ,                                                                                                                                                                                   t i                                                                                                                                                                                     l Irpell Corporation                                                                                                                                                  [

Peport Po. 01-0310-1435 AB-17 Revision 0 , A

10CFR50 APPEPDIX P. SECTION III.G CC9FLIANCE EVALUATION

                                                                                                                                                          ~

FIPE APEA/ ZONE 1-A8-20-?G Pesin Slurry Tank Poom Category System Component Circuit-Schedule Function- Consecuence of Fire Mitigation Hot .None Standt'y Equipment Cold None Shutdown Ecufpeent High/ Low None Pressure Interface Spurious None Operation Equipment 1 Alternate None Shutdown Equipeent Dadicated None Shutdown Equiprent F P w Irpell Corporation pevision 0 peport l'o, 01-0310-1435 AB-18

O 10CFP50 APPENDIY R, SECTION III.G COMPLIANCE EVALUATIDW FIRE APEA/70NE 1-AB-20-2H Protective Clothino Storage Fffects of Fire en Safe Shutdown Capability The design basis fire will not affect the capability to - achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone. l Irnpe11 Corporation Peport No. 01-0310-1835 A B-19 Revision 0

O . 10CFR50 APPENDIX P. SECTIOF !!I.G C(PPLIANCE EVALUATION FIPE AREA / ZONE l-AB-20-2H Protective Clothing Storage Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot None

                                 ' St:mey Fquipment Cold            None Shutdown Ecufpment High/ Low None Pressure Interface Spurious        None Operation Equipment Alternate None Shutdown Equipment Dedicated None Shutdown Equipment P

P Irpell Corporation Report No. 01-0310-1435 AB-20 Pevision 0

      --    .      . .      ~ . --       .
                                   ' ICCFR50 APPENCIX P, SECTION III.G CCMPLIANCE EVALL'ATION FIPE AREA /ZCNE 1-AP-20-2I Boron Concentration Measuring Room i

Effects of Fire on Safe Shutdown Capability The design t' asis fire will not affect the capability to 1 achieve and reintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone, i l i i a 4 1 i l i + i i i i i i ] i i 4 4 Impe11 Corporation Peport No. 01-0310-1435 AB-21 Pevision 0 j

< b  : Q w). e l 10CFP50 APPENDIF P $ECTICW III.G COPPLIANCE EVALUATION - s FIPE # PEA / ZONE 1-AF-20 Boron Concentration Measurine Poom Cat.qory Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Het None , Standby-Equipment Cold None Shutdown Eq'Jipment Higb/ Low None Pressure Inttrface I Spurious None Operation Eoutpoent l i Altzrnate None Shutdown j Equipeent i Dedicated None ! Shutdown i Equipment 1 ) 1 4 i i I j i l Irpell Corporation Peport No. 01-0310-1435 AE-22 Fevision 0

[ N 10CFR50 APPENDIX P, SECTICW III.G CC99LIANCE EVALUATION

                                               . FIRE AREA /ZCNE 1-AB-70-?L tecentamination Room Effects of Fire on Safe Shutdown Capability The design basis fire will not affect the capability to achieve and pointain cold shutdown, as there are no safe shutdown components or cables within the fire area /zore, r

P Irpell Corporation Peport Po. 01-0310-1435 AB-23 . Pevision 0

10CFP50 APPENDIF P. SFCTICW III.G COPPLIANCE EVALUATICW .. FIPE APFA/ICWE 1-AF-PO-PL Decontamination Poop Catecery- System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot None St:ndby Equipment Cold- None Shutdown Equipment High/ Low None Pressure Inttrface Spurious None Operation Fquipment Alttrnate None Shutdown Equipment Dedicated None Shutdown Equipment Impe11 Corporation Pepcrt No. 01-0310-1435 AB-24 Pevisien 0

j h O rh (V L) U 10CFR50 APPEFDIY P, SECTION III.G COMPLIANCE EVALUATICN FIPE APEA/7CNE 1-AP-20-2N Peactor C~:1:::t filter Esclosures Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of - the following portions of systems used to achieve hot standby and cold shutdown: Cherical and Volume control Syster (CVCS)

                               -    Cables for the following components:
                                     -     Charging RWST isolation valves Damace to cables for volume control tank isolation valve MOV-1100C and charging isolation valves MOV-1100P and MOV-11000 could cause MOV-1100C to remain open, and prevent repote operation of MOV-1100G or MOV-11000, thus preventing chargine suction from the PWST. Operator action vill be required to deenergize and manually close PCV-11000, to prevent cavitation of the charging pumps when the volume control tank empties. Operator actica may also be reqvf red to deenergize and rianually open MOV-1100B or MOV-1100D to provide charging flow from the RWST.

Irpell Corporation Peport No. 01-0310-1435 AR-25 Revision 0

q fw ,

                                                                                                                                              ,          J 10CFP50 APPEFCIY P, SECTICN III.G COPPLIANCE EVALL'ATICW FIPE APEA/70NC 1-AP-20-?N Peacter Coolant Filter Enclosures Category System Corponent      Circuit-Schedule Function                       Ccnsecuence of Fire                    Mittoation Hot         CVCS     MOV-11008 1FP0147C?-KB      MCV-1100C open interlock Darspe to this circuit could      Operator action to verify MOV-11009 or Standy                                                                      prevent remote operation and/or MOV-1100D open.

Ecufprent' cause the valve to spuriously cloa. MOV-1100D 1HP0378Cl-rB MOV-liOOC open interlock Damage to this circuit could Operator action to verify MOV-11008 or result in the loss of rerote McV-11000 open. valve control, and/or cause the valve to spuriously close. Cold None Shutdown Equiprent High/ Low None Pressure Interface Spurious CYCS MCV-1100C ---- Volume control tank Loss of MOV-1100C. Operator action to manually close Operation valve MOV-1100C. Equipment 1GP2A76P1-KB Power Loss of power to MOV-11000. 1GB2A76C1-kB Position switch /toroue Darare to this circuit could switch feedback result in the loss of remote valve control. Alternate None Shutdown Equiprent Dedicated None Shutdown Equipment Impe11 Corporation Peport Po. 01-0310-1435 AB-26 Pevision 0

10CFP50 APPEPOIX P. SECTION III.G f(VPl.IANCE EVALUATICW FIPE APEA/ ZONE 1-AB-20-2P. Boric Acid Mixing Room Effects of Fire on Safe Shutdown Capability The design basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone. Impe11 Corporation Peport No. 01-0310-1435 AE-27 Pevision 0

10CFF50 APPEPCIN R, SECTICN III.G CCtFLIANCE EVALUAT109' FIPE APEA/7CNE l-AE-20-?P Peric Acid Mixine Poes Cateoory . System Component Circuit-Schedule Functica Consequence of Fire Mitigation Hot . None Standby Equipment Cold None

 $butdown Eouipment High/ Low None Pressure Interface Spurious None Operation Equipment Alternate None
 !butdown Eouipment Dedicated None Frutdown Equipment Irpell Corporation Peport Po, 01-0310-1435                                                    AP-28                                 Pevision 0

10CFP50 APPEPDIX P, SECTINr III.G C(9PLIANCE FVALUATION FIPF APEA/Z0hF 1-AB-20-3 Voluye Control Tank poem Effects of Fire on Safe Shutdown Capability The design basis fire will not affect the capability to

                                  . achieve and maintain cold shutdown, as there are no safe shutdown couponents within the fire area / zone.which could be adversely affected by a fire.

Impe11 Corporation Peport No. 01-0310-1435 AB-29 Revision 0

O (:1; 10CFP50 APPENDIX R, SECTICW III.G CopFLIANCE EVALUATION FIPE APEA/ ZONE 1-A8-20-3 Volume Control Tank Room Cateocry System Cosponent' ' Circuit-Schedule Function Ccnsequence of Fire Mitigation Hot CVCS C-15 ---- Volure contro tank None. None. , Stardby Equipment Cold None Shutdown Foufprent Higb/ Low None Pressure laterface Spurious None Operation Eq2ippent Altsrnate None Shutdows Equiprwnt Dedicated Mone Shutdown Fquipment 3 Impe11 Corporation Peport No. 01-0310-1435 AB-30 Revision 0

m n ,~ i 10CFR50 APFENDIX R, !ECTICE III.G CCPPLIANCE EVALL'ATiet! W FIRF AREA /ZOWE 1-AB-11-34 Pipe Tunnel Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the followir.g porticut of systems used to achieve hot standby and cold sfiutdown: Chemirai and Volume Control System (CVCS) ]

                                   -     Cables for the following components:
- Charging pumps
                                         . Charging pump lobe oil pump i
                                         . Chargir.g pump lube oil cooling fan
                                         . Charging PWST isolation valve
                                         . Seal injection flow control valves
                                         . Charging loop A flow control valve
                                         . Charging loop A flow transmitter Component Cooling Water System (CCW) 1
                                   -     Cables for the following components:
                                         . CCW to PHR heat exchanger flow control valves Essential Electric Systems
                                   -     Cables for the following components:
                                         . Motor control center 2A Cables for the train 1 charging purp and associated support equipment will be rerouted outside the fire area / zone to meet the separation requirements of 10CFR50 Appendix R, Section III.G.2. Operator actions will be taken to locally control the charging RWST isolation valves, the seal injection and charging loop A flow control valves, and the CCW to PHR heat exchanger flow control valves. An exemp-tion will be requested for the lack of area-wide suppression /

detection per the raquirements of Section III.G.3. Damage to cables for primary plant makeup water control valve FCV-1102A could cause the valve to spuriously open, allowing primary plant makeup water to be supplied directly to the charging pump suction. Operator action will be required to close a manual valve located downstream of FCV-1102A to isolate this line. Spurious actuation of the valve, until operator action is taken to close the downstream manual valve, has been analyzed, and deterritned to be acceptable (27). l Impell Corporation Peport No. 01-0310-1435 AB-31 Pevision 0 j

                                                                                                )

ICCFP50 APPEN0!X R, SECTICN III.G COMPLIANCE EVALUATION e FIRE APEA/ ZONE 1-AB-11-34 Pipe Tunnel e Camage to cables for boric acid supply valves FCV-1102B and Cd-334, could cause these valves to spuriously open, , allowing concantrated beric acid to be supplied to the charging pump sucticn. Operstor action will be required to close menval valves to isolste these lines. Spurious , actuation cf these valves will not affect safe shutdown capability. Damage to cables for volume control tank isolation valve POV-1100C could esute this valve to remain open, thus preventing charging pump suction from the PWST. Operator action will be recuired to verify open MOV-11008 or MOV-1100D to provide flow to the charging pumps from the PWST and to deenergize and manually close MOV-11000 to prevent cavitation of the charging pumps when the volume contrcl tank empties. i P Impe11 Corporation Report Po. 01-0310-1435 AB-32 Revision 0

O (" % - d U V < 10CFPSC APPEk?IX P SECTICN I!!.G COPPLIANCE EVALUATION FIPF APFA/ZOWE 1-AP-11-34 Pipe Tunnel Catecory System Coeponent Circuit-Schedule Function Consequence of Fire Mitigation ~ Pot 4POV MCC-2A lyPS223P2-KB Power Loss of power to PCC2A will cause None. Pedundant lube oil heat exchangers 5t:ndty the loss of power to the following (cooled by CCW) will remain available. Equipment components required for normal / Peterminate the lube oil cooling fan for alternate shutdown: charging pump G-8B at a train 1 motor MG-8AF G-942 control center. Cabling for the new power PG-8BF supply should be routed outside the fire area / zone. CVCS G-8A IGA 2007P1-KB Power loss of power to charging pump None. G-8B will remain available. G-8A. G-8B 1FA1C07P1-KB Power Loss of power to charging pump Reroute cable from fire area / zones 8,9A, G-8B. 4B, 4D, 34, 2A to fire area / zone 8,9A, 48, 4C, 35, 2A. G-942 1XB2A16C1-KB Inte; lock to GBA recape to this circuit could None. Charging pump G-8B and associated prevent autostart of pump G-942 support equipment will remain available. when G-8A is started, or spuriously start pump G-942 when G-8A is not running. G-943 IFB0129C3-KC Local pump control Damage to this circuit could cause Peroute cables for this pump from fire a spurious start of the pump or area / zones 8, 9A, 48, 4D, 34, 2A to fire prevent pump start. area / zones 8. SA, 48, 4C, 35, 2A. 1FB0129PI-KC Power loss of this circuit will result in loss of power to the pump. 1WB0129C4-KC Low bearing oil pressure Damage to this circuit could cause interlock a spurious start of the pump or prevent pump start. MGEAF 1XB2A14Cl-KB Fan control Damage to this circuit could None. Charging pump G-6B and associated

                                                                            <puriously start the fan or prevent support equipment will remain avaliable, auto start of the fan.

PG8BF 1WB2A15Cl-KB Fan control Damace to this circuit could Reterminate MG8AF at a train 1 motor spuriously start the fan or prevent control center. Cabling for the new power auto start of the fan. supply should be routed through fire area / zones 8, 9A, 4B, 4C, 35, 2A. Impe11 Corporation Peport No. 01-0310-1435 AB-33 Pevision 0

O O O . 10CFE50 APPENDIX P SECTICN III.G COPPLIANCE EVALUATICN - FIPE APEA/70WE 1-AR-11-34 ripe Tunnel Cet? gory System Component Circuit-Schedule Functica Consequence of Fire Mitioation Hot CVCS MOV-11008 1FB0147C2-KB MOV-1100C open interlock Damage to this circuit could Operator action to deenergize and manually Standby (contd) result in the loss of rerote open either MOV-11008 or MOV-11000. Eoutpoent valve control, and/or cause the (contd) valve to spuriously close. M0Y-1100D 1HB037BP1-KB Power Loss of power to POV-11000. Operator action to deepergize and manually open either MOV-11008 or MCV-11000. 1HB0378C1-KB M0Y-1100C open interlock Darage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. 1HP0378C2-KB Position switch /toroue Damage to this circuit could switch feedback prevent remote operation and/or cause the valve to spuriously open or close. FCV-1112 IFC107011-KB Positioner control Damage to this circuit could Operator action to close manual valves signal cause a loss of remote control located upstream will be required if and spuriously open the valve. charging through the seal injection Operation of the valve through flowpath. For higher makeup flow rates sequencer 1 and 2 initiation through charging loop A, operator action would not be affected. will be required to manually override and open the flow control valve. 1FC107037-KB SV-1112 positioner Damace to this circuit could override solenoid result in the loss of valve control power control through SV-1112 and cause the valve to spuriously open. FT-1112 1F0107103-KB Sensor signal ramage to this circuit could Operator action to close manual valves result in erroneous indication located upstream will be required if of charging flow rate and charging through the seal injection cause spurious operation of flowpath. For hiaher rakeup flow rates FCV-1112. through charging loep A, operator action will be required to manually override and open the flow control valve. Irpell Corporation Peport Po. 01-0310-1435 AB-34 Pevision 0

O O O . ICCFR50 APPENDIX R. SECTICN III.G COPPLIAPCE EVALUATION FIPE APEA/70pE 1-AB-11-34 Pipe Tunnel e Cateoory Systes Component Circuit-Schedule Function Consecuence of Fire Mitigation' Het OYCS FCV-1115A 1FC10707E-FB Control signal Damace to t>fs circuit could Operator action to fail FCV-1115A open by ,, Standby (contd) cause a loss of positioner isolating instrument air at the doghouse. Equipment control, causing FCV-1115A verify FCV-11:50 closed, and control seal (contd) and FCV-1115D to close or injection flow using manual valve located result in a loss of upstream. instrument air causing FCV-1115A to fati open. FCV-1115B 1G0107077-KB Control signal Damage to this' circuit could Operator action to fail FCV-11158 open by cause a loss of positioner isolating instrument air at the doghouse control, causing FCV-11158 verify FCV-1115E closed, and control seaI and FCV-1115E to close or injection flow using manual valve located result in a loss of upstream. instrument air causing FCV-11158 to fail open. FCV-1115C 1HC107078-KB Control signal Damage to this circuit could Operator action to fail FCV-1115C open by cause a loss of positioner isolating instrument air at the doghouse, control, causing FCb1115C verify FCV-1115F closed, and control seal and FCV-1115F to close or injection flow using ranual valve located result in a loss of upstream. instrueent air causing FCV-1115C to fail open. Cold CCW TCV-601A 1FQ106010-KB Velve position feedback Daeage to this circuit could Valve will fail open as required for safe Shutdown result in the loss of shutdown. If required, flow control may Eoutpeent valve position Indication. be achieved using manual valve located downstream. 1FQ106011-r8 Control signal Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open. TCV-6018 1GQ106012-KB Valve position feedback Damage to this circuit could Valve will fail open as required for safe result in the loss of valve shutdown. If required, flow control may position indication, be achieved using manual valve located downstream. 1GQ106013-FB Control signal Damace to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open. Irpell Corporation Peport Fo. 01-0310-1435 AB-35 Revision 0

             -g                                                              g                                                               cs
                                                                               )                                                            (    )
                )                                                          %J                                                               G' 10CFP50 APPENDIX P SECTION III.G CCM LIANCE EVALUATION                                                    .

FIPE APEA/7CFF 1-AB-11-34 Ffpe Tennel , C-tTgery System Cosiponey Circuit-Schedule Fer.ction Consequence of Fire Mitigation High/ Low hone Pressure Interface Spurious CVCS G-42 1HP2A10Cl-KB Perote pump control / Damage to this circuit could Cperator action to deenergize the pump. Operation position indication spuriously start the pump, and/or Etzigeent prevent remote operation. 1HB2A10C2-KB Local pump control Camage to this circuit could spuriously start the pump and/or prevent remote or local pump operation. FCV-1102A 1WC107007-KB Solenoid control power Darage to this circuit could Operator action to close manual valve prevent remote operation and/or located downstream to prevent bcron cause the valve to spuriously dilution. Spurious actuation of the open or close, valve entil operator action is taken to close the downstream ranual valve, has been analyzed and determined to be acceptable (27). FCV-1102B 1WC107009-KB Solenoid control power Damage to this circuit could Operator action to close manual valve prevent remote operation and/or located downstream of FCV-1102A. cause the valve to spuriously open or close. CV-334 1F0107033-KB Solenoid control power Darage to this circuit could Operator action to close manual valve prevent remete operation and/or upstream, cause the valve to touriously open or close. Irpell Corporation Peport No. 01-0310-1435 AB-36 Revision 0

O O O 10CFP50 APPEPDIX R. SECTION III.G CCPPLIANCE EVALUATION FIPE APEA/ZCFE 1-AB-11-34 -- Pipe Tunnel a Cateoory System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS POV-1100C 1GB0147C9-FF Interlock to PCV-11008 Damage to this circuit could Operator action to deenergize and manually

 ' Operation (contd)                                                         prevent remote operation and/or      close the valve.

Equipment cause the valve to spuriously (contd) open or close. 1GB2A76C2-KB Penote valve cortrol Daraoe to this circuit could prevent remote eperation and/or , cause the valve to spuriously open or close. 1G82A76C3-KB Volice control tank low Papage to this circuit could level interlock prevent rerote operation and/or cause the valve to spuriously open or close. 1G82A76C4-KB MCV-11000 open interlock Daeage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. Alt:rnate None Shutdown Foutpment Dedicated 120V C-38 1GY2A30PI-FB Power Damage to this circuit could result No effect on poreal safe shutdown systems. Shutdown in loss of power to auxiliary This circuit will be rerouted as part of Eaufpeent shutdown panel instruments, and dedicated shutdown system design. prevent transfer of steam dump control through SV-175 to the auxiliary shutdown panel C-38 Irpell Corporation Peport No. 01-0310-1435 AB-37 Pevision 0

                                                                                        \-

s). ..

                                                                                                  .A 10CFP50 APPENDIX P SECTION III.G COMPLIANCE EVALUATIDW
                                                                                                     ^

FIPE APEA/70NE 1-AB-14-35 North Pipe Tunnel d Effects of Fire on Safe Shutdown Capability The design basis fire will not affect the capability to . achieve and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone. Equiprent/ cable identifiers for the dedicated shutdown equipment which is to be routed through this fire area / zone will be added wean as-built information is available, s Impe11 Corporation Report No. 01-0310-1435 AB-38 Revision 0

A

  ~

U U,A . 10CFR50 APPENDIX R. SECTICN III.G COMPLIANCE EVALUATION FIDE APEA/70NE 1-AB-14-35 North Pipe Tunnel i Cateocry System' Component Circuit-Schedule Function Consecuence of Fire Mitigation Hot None . Standby Feufprent Cold None Shutdown E(ufpment High/ Low None Pressure Irterface 1 3 Spurious None Cpiration Equipment I Alternate None. Shutdown Equipment Dtdicated None Equipment / cable identifiers for dedicated 1-Shutdown shutdown equipment will be added when Equiprent as-built information is available, i I. l l I l. Impe11 Corporation Peport No. 01-0310-1435 AB-39 Revision 0 i

       ,                                          - y                                                                 ~.

L) ) J i 10CFP50 AP*ENDIX R SECTION III.G CCM LIANCE EVALUATICN I FIRE APEA/ZCWE 1-YD-20 4A East Penetration Area Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the following portions of systees used to achieve bot standby and cold shutdown: Peactor Coolant System (PCS)

                             -     Cables for the following comporents:
                                   -     PORVs
                                   -     Block valves
                                   -     Pressurizer heaters
                                   -     Source range monitors
                                   -     Pressurizer level transmitters
                                   -     Pressurizer pressure transmitters
                                   -     Primary system temperature trcnsmitters Chemical and Volume Control (CVCS)
                             -     Cables for the following components:
                                   -     Charging loop A control valve
                                   -     Reactor coolant pump seal flow pressure transmitters Main Steam System (MSS)
                             -     Atmospheric steam dump valves
                             -     Cables for the following components:
                                    -    Atmospheric steam dump valves
                                   -     Steam generator level transmitters Auxiliary Feedwater System (AFW)
                             -     Cables for the following components:
                                    -    Motor driven auxiliary feedwater pump
                                   -     Steam driven auxiliary feedwater pump
                                   -     Flcw control valves Component Cooling Water (CCW)
                              -    Cables for the following components:
                                    -    Thermal barrier peep
                                    -    Thermal barrier outlet valves Impell Corporatten Peport No. 01-0310-1435                             YD-1                                                               Revision 0

O 'O O 10CFR50 APPENDIX P. SECTIDW -III.G COMPLIAWCE EVALUATI(* FIPE APEA/70WE 1-YD-20-4A East Penetration Area i Containment Ventilation System (CVS)

                                -     Cables for the following components:
                                      -     Reactor cavity cooling fan and associated damper Residual Heat Removal (RHR)
                                -     Cables for the following components

! . Pesidual heat removal pump

                                      -     Pesidual beat removal inlet isolation valve j
                                       -    Pesidual Feat removal discharge isolation valve j
                                       -    RHR heat exchanger isolation valve Essential Electrical Systems i
                                -     Cables for the following components:
                                       . Station service transformer 1
                                       . 480V switchgear
                                       . 120V vital buses The fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendix R, Section III.G.2. The dedicated shutdown system will be used to achieve and maintain cold shutdown in the event of a fire in the fire area / zone. Operator action will be taken to locally control certain valves required for hot standby.

1 Operator action will also be taken to deenergize offsite and i nomal onsite power sources to prevent and mitigate spurious i equipment operation. An exemption request for lack of

area-wide suppression / detection, per the requirements of

! Section III.G.3 will be provided. ! The interruption of seal injection and seal cooling to the < reactor coolant pumps, for the period required to initiate . seal injection from the dedicated shutdown system, has been _ i evaluated and determined to be acceptable (26). 1 i I i I 1

Imp 211 Corporation Report Fo. 01-0310-1435 YD-2 Pevision 0

A

                         '10CFP50 APPENCIX R, SECTION III.G COMPLIANCE EVALUATION
                                                                                                          -~

FIRE AREA /7CWE 1-YD-20-4A

                                              . East Penetration Area                                         ,

The lo'ss of auxiliary feedwater flow, for the period required -

                         . to initiate auxiliary feedwater flow from the dedicated                         ,

shutdown system, has been evaluated and determined to be acceptable (24,25).

                                                                                                           ^

Damage to cables for POPV and its associated block valve could cause the spurious actuation of the PCRV when the block valve is not available to isolate the line. Spurious actuation of ', the PCRY, until operation action is taken to deenergize and close the valve, has been analyzed, and will not result in unacceptable consequences (24,25). , Darage to cables for atmospheric steam dupp valves CV-76 and CV-78 could cause the valves to spuriously open. Spurious actuation of the steam dump valves, until operator action is taken to deenergize and close the. valves, has been analyzed and will not result in unacceptable consequences (24,25). The redundant steam dump valves CV-77 and CV-79 are located ~ outside the fire area / zone and will remain available for dedicated shutdown system operation. Damage to cables for the reactor vessel head vent valves and pressurizer high point vent valves could cause the spurious actuation of the two series high/ low pressure interface valves in each line. Spurious actuation of these valves, until operator actioil is taken to deenergize and close the valves, has been analyzed, and will not result in unacceptable consequences (24,25). Damage to cables for auxiliary pressurizer spray control valve CV-305 could cause this valve to spuriously open. FCV-1112 will remain available to isolate this line until operator , action is taken to deenergize and close this valve. Damage to cables for containment spray isolation valve CV-82 could cause the valve to spuriously open. Containment spray - will not be inadvertently initiated as the refueling water purps will not be affected by a fire in this fire area / zone. ( w

                                                                                                           ~

Iepell Corporation Report No. 01-0310-1435 YD-3 Revision 0

O A e^s b 10CFP50 APPEPDIX P, SECTION III.G CCtsPLIANCE EVALUATION FIPE APEA/70NE 1-YD-20-4A East Penetration Area Catteory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160 Bus 1C, IFA1C10P1-KB Power to station service loss of power to 480V switchoear 1 None. Dedicated shutdown system will Standby Brkr 10 transformer 1 from station service transforwer 1. remain available. Pequest exemption for lack of area-wide suppression / detection per III.G.3. 480V Swgr #1 1FBS102P2-r.B Power feed from station Loss of power to 480V switchgear 1 None. Dedicated shutdown system will Brkr 02 service transforwer i from station service transformer 1. remain available. 1FES102P3-KB Power feed from station Loss of power to 480V switchgear 1 service transforwer 1 from station service transformer 1. 1FBS102P4-KB Power feed from station Loss of power to 4POV switchgear 1 . service transforwer 1 from station service transformer 1. 1FBS102PS-KB Power feed from station Loss of power to 480Y switchgear 1 service transformer 1 from station service transformer 1. Swgr #3 1YBS303C1-KC Perote breaker position Damage to this circuit could None. Dedicated shutdown system will Brkr 03 indication prevent remote operation of the remain available, breaker. 120V Y-29 1GYV29P2-KC Power Loss of power to vital bus 5 could Dedicated shutdown system will remain cause the loss of power to the available. Operator action to manually following components required for position FCV-3300 and FCV-3301 will be normal / alternate shutdown: required. LT-3400A TE-3402A FCV-3300 LT-34008 TE-3411A FCV-3301 LT-3400C TE-3421A CV-3201 SV-3200 SV-3204 SV-3202 SV-3205 SV-3214 SV-3203 SV-3211 CV-3213 YY-29/ 1GD0217D1-KC Power Loss of 125V DC power to Dedicated shutdown system will remain Inverter 5 inverter 5. available. Operator action to manually position FCV-3300 and FCV-3301 will be required. Irre11 Corporation Piport No. 01-0310-1435 YD-4 Fevision 0

r [x p /7 l l O) t t G' 4 10CFR50 APPEPPIX R, SECTION III.G COMPLIANCE EVALUATION (J s

                                                                                                                                                                                                     ^

FIPE APEA/ ZONE 1-YD-20-4A l East Penetration Area

                                                                                                                                                                                                    ~

Ca t? gory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot PCS CV-530 1FY1112Cl-KC Pemote valve control Damage to this circuit could Operator action to deenergize 120VAC/400VAC Sttndby (contd) result in the loss of remote power to prevent / mitigate spurious Eculpment valve control, and/or cause the operation. CV-530 will fail open on loss (contd) valve to spuriously close, or of power. . open. CV-546 1FY1112CO-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. CV-546 will fail closed on open or close. loss of power. Spurious actuation of the PORV, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25).

                                                                                                                                                                                                     ~

IFY1112C2-KC Valve position Damage to this circuit could indication prevent remote operation and/or cause the valve to spuriously open or close. CV-531 IGY1215Cl-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. CV-531 will f ail open on loss valve to spuriously close, or of power. open. CV-545 1GY1215C2-KC pemote valve control / Darage to this circuit could Operator action to deenergize 120VAC/480VAC position indication prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. CV-545 will fail closed on open or close, loss of power. Spurious operation of the PORV, untti operator action is taken to deenergize and close the valve, has been analyzed, and will not result in an unacceptable condition (24,25). 1GY1215CO-KC Pemote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously - open or close. m v w I pell Corporation Report No. 01-0310-1435 YC-5 Pevision 0

(~s { 10CFR50 APPENDIY R. SECTICW III.G COMPLIANCE EVALUATION FIPE APEA/ ZONE 1-VD-20-4A Fast Penetration Area Catcoory System Copponent Circuit-Schedule Function Consequence of Fire Mittoation Hot PCS Pzr 1FBS115P4-KB Power Loss of power to pressurizer None. Cables for dedicated shutdown 4 Standby (contd) Heater heater group A. system operation of pressurizer heater Equipeent Group A group D are routed outside the fire zone (contd) and will reeain available. Pzr IFBS109P4-KB Power Loss of power to pressurizer None. Cables for dedicated shutdown Heater heater group C system operation of pressurizer heater 1 Group C group D are routed outside the fire zone and will remain available. IFBS109PS-KB Power Loss of power to pressurizer heater group C. NE-1202 1F0102059-FB Power Damage to this circuit could None. During operation of the dedicated result in loss of source range shutdown system, shutdown margin will be

indication or erroneous source determined by sampling primary system range indication, boron concentration.

1 IFQ102049-KB Indication Parage to this circuit could result in low off-scale or 3 erroneous indication. 1FQ102050-KB Indication DaraPe to this circuit could result in low off-scale or I erroneous indication. l LT-431 1GQ104078-KB Sensor signal Damace to this circuit could None. LT-430A will reeaf n available at result in high off-scale, low the dedicated shutdown panel. off-scale, or erroneous indication. PT-425 1FQ108I2-KC Sensor signal Damage to this circuit could None. PT-434A will retain available at result in high off-scale, low the dedicated shutdown panel. off-scale, or erroneous indication, and/or remove the PCS pressure interlock to RHR i valves MOV-813 and MOV-834 PT-430 1FQ104Il-KC Sensor signal Damage to this circuit could Operator action to deenergize 120VAC/460VAC result in high off-scale, low power to prevent / mitigate spurious off-scale, or erroneous operation. Spurious operation of the t indication. This could cause spray valves PCV-430C and PCV-430H will l spurious operation of the not affect safe shutdown as the reactor

pressurizer heater groups A coolant pumps are tripped. Pressurizer -

and B and/or pressurizer spray - code safety valves will be avaliable for valves PCV-430C, PCV-430H. over-pressure protection. PCRV's will be available for syster pressure control ,_ after dedicated shutdown system operation is initiated. Impell Ccrporation i RZport No. 01-C310-1435 YD-6 Pevision 0

                                                                                                                                         -~

U b V 10CFR50 APPENDIX P SECTION III.G COMPLIANCE EVALUATION FIRE ARFA/ ZONE 1-YD-20-4A East Penetration Area Crtigory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot PCS PT-431 IFC104I2-KC Pressurizer transmitter Damage to this circuit could Cperator action to deenergize 120VAC/480VAC , Standby (contd) signal cause a high off-scale, low power to prevent / mitigate spurious Equipeent off-scale or erroneous indi- operation. (contd) cation This could cause CV-546 to spuriously open or close. TF-2401A 1FY33091D-KC Sensor sfonal Damaoe to this circuit could None. TE-402A will remain available on 1 result in high off-scale, low the dedicated shutdown panel. off-scale, or erroneous indication. TE-2412A 1FY33091E-KC Sensor signal Camage to this circuit could None. TE-412A will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. TE-2422A 1FY3309IF-KC Sensor signal Damage to this circuit could None. TE-422A will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. TE-3402A 1GY2904ID-KC Sensor signal Damage to this circuit could None. TE-402A will remain available at result in high off-scale, low the dedicated shutdown panel. off-scale, or erronecus indication. TE-3411A IGY2904IE-KC Sensor signal Damage to this circuit could None. TE-412A will remain available at result in high off-scale, low the dedicated shutdown panel, off-scale, or erreneous indication. L v e Impe11 Corporation Rtport No. 01-0310-1435 YD-7 Revision 0

(" r n 10CFR50 APPENDIX P. SECTICW III.G COPPLIANCE EVALUATION FIRE APEA/70PE l-YD-20-4A East Penetration Area

                                                                                                                                                       ~

Cr:t'. gory System Component Circuit-Schedule Function Consecuence of Fire Mitigation Hot PCS TE-3421A IGY29041F-KC Sensor sional

                                                         ~

Daeage to this circuit could None. ' TE-422A will remain available at Standby (contd) result in high off-scale, low the dedicated shutdown panel. Equipment off-scale, or erroneoes (contd) indication. , TE-402C IFQ103087-KB Sensor signal Damage to this circuit could None. TE-402B will remain available at _ result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. TE-411B IXQ103063-KB Sensor signal Damage to this circuit could None. TE-4128 will remain available at result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. TE-422C IHQ104071-KB Sensor signal Dacage to this circuit could None. TE-4228 will remain available at result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. CYCS CV-304 1FC107071-KB Solenoid control power Damage to this circuit could Operator action to close FCV-1112 from prevent remote operation and/or the dedicated shutdown panel if the cause the valve to spuriously isolation of this line is required. open or close. CV-304 will open on pressure differential if charging through loop A is required. Irpell Corporation Peport No. 01-0310-1435 YD-8 Pevision 0

                                             '10CFR50 APPENDIX P, SECTION III.G COMPLIANCE EVALUATICW                          ,

FIPE APEA/70pE 1-YD-20-4A

                                                              . East Penetration Area d

Category System Cosponent Circuit-Schedule -Function ' Consequence of Fire Mitigation Hot CVCS .- PT-11158 1XI)107096-KB Sensor signal Damage to this circuit could Operator action to fail open FCV-11158 c Standby .(contd) result in high off-scale, low by isciating instrument air at the Equipeent off-scale, or erroneous doghouse, verify FCV-1115E closed, and (contd) indication. This could cause control seal injection flow using manual , controller FC-11158 to valve located upstream. Interruption of spurforsly open or close seal. injection and seal cooling to the - FCV-11158 and FCV-1115E and/ reactor coolant pump seals for the period , or cause controller PC-I1158 required to initiate seal injection from to spuriously close PCV-11158. the dedicated shutdown system has been evaluated and determined to be acceptable , (26). PT-1115C 1WC107097-KB Sensor signal Pamaae to this circuit could Operator action to fail open FCV-1115C result.in high off-scale, low by isolating instrument air at the off-scale, or erroneous doghouse, verify FCV-1115F closed, and , indication. This could cause control seal injection flow using manual controller FC-1115C to valve located upstream. Interruption of

                                                                        . spuriously open or close            seal injection and seal cooling to the
                                                                       'FCV-1115C and FCV-1115F, and/         reactor coolant pump seals for the period or cause controller PC-1115C         required to initiate seal injection from to spuriously close PCV-1115C.       the dedicated shutdown system has been evaluated and determined to be acceptable (26).

MSS SV-85/ IFW10319-KB Remote valve control Damage to this circuit could Operator action to deenergize 125VPC and CV-76 transfer valve control to the 120VAC/480VAC power to prevent / mitigate main steam pressure transmitter spurious operation. Spurious operation PT-459 (via YM-418A), or cause of the steam dump valves until operator the valve to spuriously open. action is taken to deepergize and close the valves has been analyzed and will not result in an unacceptable condition (24,25). SV-87/ 1FW10320-KB Remote valve control Damage to this circuit could Operator action to deenergize 125VDC and CV-78 transfer valve control to the 120VAC/480VAC power to prevent / mitigate - Pain steam pressure transmitter spurious operation. Spurious operation PT-459 (via YM-418A), or cause of the steam dump valves until operator the valve to spuriously open, action is taken to deenergize and close , the valves has been analyzed and will not result in an unacceptable condition (24,25). w 4 m Impell Corporation Report No. 01-0310-1435 YD-9 Revis,fon 0

I ( ) (,

                                                                         \d                                                                (

10CFP50 APPENDIX P, SECTION III.G COMPLIANCE EVALUATION FIRE APEA/70NE 1-YD-20-4A East Penetration Area Cateocry System Component Circuit-Schedule Function Consecuence of Fire Mitigation Het PSS SV-85/87 1FW10307-FB Solenoid control power Damage to this circuit could Operator action to deeperpize 125VDC and Standby (contd) CV-76 transfer valve control to the 120VAC/480VAC power to prevent / mitigate Equipment main steam pressure transmitter spurious operation. Spurious operation (contd) PT-459 (via YM-418A), or cause of the steam dump valves until operator the valve to spuriously open. action is taken to deenergize and close the valves has been analyzed and will not result in an unacceptable condition _ (24,25). LT-2400A 1FY3315I4-KC Sensor signal Damage to this circuit could None. LT-450C will remain available on result in high cff-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. LT-24006 1FY331515-KC Sensor signal Damage to this circuit could None. LT-451C will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. LT-2400C 1FY3315I6-KC Sensor signal Daraoe to this circuit could None. LT-452C will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. LT-3400A IGY290lIA-KC Sensor signal Damage to this circuit could None. LT-450C will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. LT-3400B 1GY29011B-rc Sensor signal Damage to this circuit could None. LT-451C will remain available on result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication. Irpell Corporation \ Report Ko. 01-0310-1435 YD-10 Revision 0

                                                                    ,r \                                                           ,,g f'%
                                                                                                                                                 -a 10CFR50 APPE8011 R SECTION III.G COMPLIANCE EVALUATION FIRE AxEA/10hE 1-YD-20-4A East Penetration Area                                                                a Category Systen Coseonent Circuit-Schedule Function                       Consequence of Fire                  Mitigation Hot         MSS      LT-3400C 1GY29011C-KC  Sensor signal             Damage to tnis circuit could   None. LT-452C will remain availaole on        -

result in high off-scale, low the dedicated shutdown panel. Standey (contd) Eq:1pment off-scale, or erroneous (contd) indication. Pouer Loss of power to G-10S Mone. Dedicated auxiliary feceater pump AFW G-105 1F85125P1-KC will remain available. Loss of auxiliary fee &ater flow, untti operator action is taken to initiate auxiliary feedwater flow < from the dedicated shutdown system, has been evaluated and detemined to be acceptable (24,25). 1FBS125C8-KC MOV1202 Interlock Damage to this circuit could prevent remote operation of - G-105 and MOV-1202. G-105/ IF85125C9-KC 125VUC Power Renote Damage to this circuit could None. Dedicated auxiliary feedwater pump Control & Indication result in the loss of remote' will remain available. Loss of auxiliary McV-1202 pump control and/or cause feedwater flow, until operator action is spurious operation of G-105 taten to initiate auxiliary feeowater flow and MOV-1202, from tne cedicated snutoown system, has been evaluated and determineo to be acceptacle (24,2b). s Impell Corporation Report No. 01-0310-1435 YD-11 Revision 0

10CFR50 APPENDIX R, SECTION III.G CCMPLIANCE EVALUATICW FIRE ApEA/20NE 1-YD-20-4A East Penetration Area C-tegory System Component Circutt-Schedule Funetion Consequenee of Fire Mitigation Hot AFW CV-3201/ 1GY2906CH-KC Position switch Darage to this circuit could None. Dedicated auxiliary feedwater purp . feedback prevent SV3205 free being opened will remain available. Loss of auxiliary Standby (contd) SV-3205 Equipment when CV3201 opens, or allow feedwater flow, until operator action is (contd) CY3201 and CV-3205 to open taken to initiate auxiliary feedwater flow , simultaneously. Damace to from the dedicated shutdown syster, has this circuit could also result been evaluated and deterwined to be in the loss of remote valve acceptable (24,25). ,, control and/or cause valve CV-3201 to spuriously close and cause valves SV-3200, 02, 03, . 04, 05,11,14. and CV-3213 to spuriously open. SV-3201, 1GY2906C5-KC Valve position Damage to this circuit could None. Dedicated auxiliary feedwater pump 02,03,04 indication result in the loss of remote will res.ain available. Loss of auxiliary .. valve control. This could feedwater flow, until operator action is cause SV-3200, 02, 03, 04, 05, taken to initiate auxiliary feedwater flow 11,14, CV-3213 to open and from the dedicated shutdown system, has CV-3201 to close, been evaluated and deterwined to be acceptable (24,25). SV-3200-05,1GY2906CC-KC Solenoid control power Damage to this circuit could None. Dedicated auxiliary feedwater pump 11,13,14 spuriously open CV-3201 and will remain available. Loss of auxiliary close SV-3202,03,04.11,13,14, feedwater flow, until operator action is or close CV-3201 and open taken to initiate auxiliary feedwater flow SV-3200, 02, 03, 04, 05, 11 from the dedicated shutdown system, has 14 and CV-3213 Remote operation been evaluated and determined to be of the valves could also be acceptable (24,25). prevented. 1GY2o06C6-KC Valve position Damage to this circuit could indication result in erroneous valve position indicaticn, but would not affect valve operation. L I pell Corporation Feport ro. 01-0310-1435 YD-12 Revision 0

i l rs Q  ?" 10CFR50 APPEPDIX R. SFCTION III.G COMPLIANCE EVALUATION FIPE APFA/ZOWE 1-YD-20-4A East Penetration Area

                                                                                                                                                      ~

C"tegcry System Component Circuit-Schedule Function Consequence of Fire Mitfoetion Hot AFW FCV-2300 IFY3315!8-KC Positioner control Damage to this circuit ceuld Operator action to isolate instrument air . Standty (contd) result in the loss of remote and manually control FCV-2300. l valve control, and/or cause the l Equipment (contd) valve to spuriously open. ,, FCV-2301 1FY331519-KC Positioner control Damage to this circuit could Operator action to isolate instrument air , result in the loss of remote and manually control FCV-2301. l valve control, and/or cause the valve to spuriously open. , l l FCV-3300 1GY29061G-KC Positioner control Damage to this circuit could Operator action to isolate instrument air , I result in the loss of remote and manually control FCV-3300 valve control, and/or cause the j valve to spuriously open. ,. l i FCV-3301 IGY2906IH-KC Positioner control Damage to this circuit could Operator action to isolate instrument air l result in the loss of remote and manually control FCV-3301 l valve control, and/or cause the ! valve to spuriously open. CCW G-964 IFD012002-KB Power Camage to this circuit could None. Component cooling water is not i spuriously start the pump, or required for dedicated shutdown system -

!                                                                        prevent purp cperation.         operation. Interruption of seal cooling and seal injection to the reactor coolant pump and seals for the period required to l

initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). - l 1FD012003-KB Power Damage to this circuit could spuriously start the pump, or prevent pump operation. i 1FD012004-KC Power Damage to'this circuit could - spuriously start the pump, or prevent pump operation. l ~ w Impell Corporation Report Wo. 01-0310-1435 YD-13 Pevision 0

p n

                                                                        \

10CFR50 APPENDIX R, SECTION III.G CCMPLIANCE EVALUATION FIPE AREA /20WE 1-YD-20-4A East Penetration Area C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CCW CV-7228 IWC106015-KB Solenoid control power Damage to this circuit could None. Interruption of seal cooling and , Standby prevent resote operation and/or seal injection to the reactor coolant pump Equiprent cause the valve to spuriously and seals for the period required to (contd) open or close. initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). 1 CV-722C IWC106016-FB Solenoid control power Damage to this circuit could None. Interruption of seal cooling and prevent reeote operation and/or seal injection to the reactor coolant pump cause the valve to spuriously and seals for the period required to open or close. initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). CVS A-9S 1XB0209PI-KB Power Loss of power to A-95. None. The reactor cavity cooling fans are required only to support operation of the source range monitors. lye 0209C1-FB Interlock to reactor I'amage to this circuit could cavity temperature spuriously start or stop the fan switch TS-24 and/or prevent operation of the fan. PO-12 IXP0209C2-KB Damper control Damage to this circuit could cause None. The reactor cavity cooling fans are the damper to spuriously close required only to support operation of and/or prevent remote operation. the source range monitors. Cold PHP G-14A 1FBS122P2-KC Power Loss of power to G-14A. None. Dedicated auxiliary feedwater pump Shutdown will remain available for single phase Equipment cooldown. MOV-813 IFP0169P1-KB Power Loss of power to MOV-813. Valve None. This valve is not required for fails as is, normally closed, single phase cooldown. , 1FB0169C3-FP Position switch /toroue Damaoe to this circuit could switch feedback resuit in the loss of remote valve control. x t Impe11 Corporation Report No. 01-0310-1435 YD-14 Revision 0

f f3  % i 's )  !

            %                                                             v                 .

w./ < 10CFR50 APPENDII P, SECTION III.G CopFLIANCE EVALUATION FIPE APEA/ICNE 1-YD-20-4A East Penetration Area Cntegory Systen Component Circuit-Schedule Function Consecuence of Fire Mitigation C:lld PHR PCV-P22A 1FBC164P1-FB Power loss of power to M0Y-P22A. None. This valve is not required for , Shutdown (centd) single pnase cooldown. Equipment (contd) 1FB0164C2-KB Position switch / tort;ue Darage to this circuit will result , switch feedback in the loss of remote valve control. The valve will fail as is. MCV-833 1FB0170P1-KB Power Loss of power to P0Y-833. None. This valve is not required for single phase cooldown. 1FB0170C2-FB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. High/ Low PCS SV-2401 1FY3312CA-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC Pressure result in the loss of rerote power to prevent / mitigate spurious Int:rface valve control, and/or cause the operation. Vent valves will fail closed valve to spuriously open. on loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). SV-2402 1FY3312CB-KC Solenoid control power Darage to this circuit could Operator action to deenergize 120VAC/480VAC i result in the loss of remote power to prevent / mitigate spurious l valve control, and/or cause the operation. Vent valves will fail closed l valve to spuriously open. on loss of power. Spurious actuation of the vent valves, until operator action is I ' taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). k c Impe11 Corporation

R port Fo. 01-0310-1435 YD-15 Revision 0

_ . _ , __ -_ .. . . _ . . _ s. ..- . , _ . _ - . . _ . . . , . _ . ._ _. . . - - _ . _ ._ _ . m V-10CFR50 AppfutIX p. SECTION III.E CCuplIANCE EVALUATION . FIDE ApfA/ ZONE 1-YD-20-4A East penetration Area Category System Camponent Circuit-Schedule Function Consequence of Fire Nitigation High/ Low RCS SV-2403 .1FY3312CC-KC Solenoid control power. Damage to this circuit could . Operator action to doenergize 120VAC/480VAC pressure (contd) result in the. loss of remote power to prevent /sitigste spurious  ; IIterface valve control, and/or cause the operation. Vent valves will fail closed

         .(contd)                                                                               valve to spuriously open,                     on loss of power. Spurious actuation of the vent valves, untti operator action is
                                                                                                                                             -taken to doenergize and close the valves,               ;

has been analyzed, and will not result in an unacceptable condition (24,25). SV-2404 1FY3312CD-FC - Solenoid control power Damage to this circuit could Operator action to doenergize 120VAC/400VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. Vent valves will fail closed , valve to spuriously open, on loss of power. Spurious actuation of :I the vent valves, until operator action is  ; i taken to doenergire and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). SV-3401/02 16Y3005CI-KC' Solenoid control power Panage to this circuit could Operator action to deenergize 120VAC/480VAC , result in the loss of remote power to prevent /mitigste spurious ' valve control. operation. Vent valves will fail closed  ; on loss of power. Spurious actuation of the vent valves, until operator action is i taken to deenergize and close the valves,

                          '                                                                                                                   has been analyzed, and will not result in l                                                                                                                                              an unneceptable condition (24,25).

i 16Y3005CJ-KC Solenoid control power Damage to this circuit could prevent remote operation and/or . I cause the valve to spuriously  ; open or close. l l i i i t r I i Irpell Corporation , Report No. 01-0310-1435 YD-16 Pevision 0 l r __ ., ,_ _ _ , _, - - _ _ . . - , _ ..__,r

W U Q () . 10CFP50 APPENDIX P SECTION III.G CCMPLIANCE EVALUATICN FIPE AREA /20K 1-YD-20-4A East Penetration Area C'teoory System Component Circuit-Schedule Function Consequence of Fire Mitigation Cigh/ Low PCS SV-3403/04 1GY3005CK-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC , Pressure (contd) result in the loss of remote power to prevent / mitigate spurious Interface valve control. operation. Vent valves will fail closed (contd) on loss of power. Spurious actuation of , the vent valves, until operator action is taken to deeneroire and close the valves, has been analyzed, and will not result in , an unacceptable condition (24,25). 16Y3005CL-KC Solenoid control power Damage to this circuit could prevent revete operation and/or l cause the valve to spuriously open or close. CVCS CV-527/ 1FM1111C3-KC pemote valve control / Damage to this circuit could Aone. CV-528 and CV-526 will remain ' CV-525 position indication result in the loss of remote available to isolate the seal return l valve control, and/or cause the and letdown lines, valve to spuriously close. 1FY121P09-KC pemote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. CV-527 1FY121PO4-KC Resete valve control Damage to this circuit could None. CV-528 will remain available to prevent remote operation and/or isolate the seal return line. l cause the valve to spuriously close. x Irpell Corporation Peport Po. 01-0310-1435 YP-17 Fevision 0

m ,~ ., 10CFP50 APPENDIX R, SECTICW III.G CCWLIAM EVALUATICW FIPE APEA/ZCNE l-YD-20-4A East Penetration Area - Category System Ccaponent Circuit-Schedule Function Consequen.e of Fire , Mitigation Spurious RCS G-28 IWAlB03PI-KB Power Loss of power to G-28. None. Turbine trip will deenergize the Operation pump. Eeulpment lWAlBC3P2-KB Power Loss of power to G-28. . 1WA1203C6-KB Cil lift pressure Damage to this circuit could interlock spuriously start the pump and/or ' prevent its remote operation. G-2C IWA1A01PI-KB Power Loss of power to G-2C. None. Turbine trip will deepergize the pump. lWA1A0lP2-KB Power Loss of power to G-2C. i j IWA1A01C4-KB 011 lift pressure Damage to this circuit could i interlock spuriously start the pump and/or prevent its remote operation. l! j CYCS CV-525 1FY121P02-KC Pesote valve control Damage to this circuit could None. CV-526 will remain available to prevent remote operation and/or isolate the letdown line. cause the valve to spuriously open or close. i i 1FY121P07-KC Pemote valve control Damage to this circuit could i prevent reecte operation and/or cause the valve to spuriously open or close. l i j CV-305 lWQ107070-KB Solenoid control power Damage to this circuit could None. FCV-Ill2 will remain available to , prevent remote operation and/or isolate this line until operator action i cause the valve to spuriously is taken to deenergize and close this i j open or close. valve. I i i i 1 1 i , i. Iepell Corporation Revision 0 Peport Fo. 01-0310-1435 YC-18 1

d b 10CFR50 APPENDIX R, SECTICel III.G COMPLIAlfCE EVALUATIC81 b-s e i FIRE APEA/ ZONE l-YD-20-4A East Penetration Area Crtegory Syster Component Circuit-Schedule Function Consecuence of Fire Mitigation Spurious SIS PCV-358 lHB0385P1-KB Power Loss of power to MOV-358. Ilone. y cperation 4 Eculpment IPB0385C2-KB Position switch / torque Damage to this circuit could j (contd) switch feedback result in the loss of remote ., valve control. The valve will fail as is, nome 11y closed. i l CRS CV-82 IFP1111CD-KC Control power / Damage to this circuit could Operator action to close manual valve i position indication prevent remote operation and/or located upstream. Pefueling water pumps , l cause the valve to spuriously will not be affected by the fire. 4 open or close. i j FWS FT-462 lHQ112030-KB Sensor signal Darage to this circuit could None. Main feedwater pumps are tripped, j cause the main feedwater flow , 1 control valve to close and/or 4 cause a reactor scram. a lHYP10-KB Power Damage to this circuit could cause a loss of power to FT-462, causing FCV-458 to close and/or f cause a reactor scram. LT-455 1WO112023-KB Sensor signal Damage to this circuit could None. Main feedwater pumps are tripped, i cause FCV-458 to close and the plant to scram. 1WYR1004-KB Power Damace to this circuit could cause a loss of power to

l. LT-455, causing FCV-458 to -

j close and the plant to scram.

                                                                                                                                                                       ~

l b 6 i i 6 1 j i i Irpell Corporation

!        P: port Fo. 01-0310-1435                                                    YD-19                                                               Pevision 0 l

I y ~. (,n . s( \ ( ( 10CFR50 APPFWDD seh .II.G C(W LIANCE EVALUATION

                                                                                                                                                                                  ~

FIRE AREA /ZCFE 1-YD-20-4A East Penetratfor Area C-tegory System Canponent Circuit-Schedule Function Consequence of Fire Nitigation Alternate RCS TE-400C 1FQ103085-KB Sensor signal Damage to this circuit could None. Shutdown cause erreneous loop A delta Equipment temperature indication. TE-410A 1GC103074-KB Sensor signal Damage to this circuit could None. cause erroneous loop B delta teeperature indication. TE-412C 1GC104068-KB Sensor signal Darage to this circuit could None. cause erroneous loop B delta temperature indication. TE-420A Sensor signal Damage to this circuit could None, 1H0103076-KB cause erroneous loop C delta temperature indication. TE-420C Sensor signal Dacace to this circuit could None, 1HC104069-KB cause erroneous loop C delta temperature indication. SIS MOV-850C IHB0391P2-KB Power Loss of power to MOV-850C. Valve None. will fall as is, normally closed. 1HB0391C7-FB Position switch / torque Darage to this circuit could switch feedback result in the loss of remote valve control. The valve will fail as is, normally closed. Deticated PCS TE-412A IXQ103080-KC Sensor signal Darage to this circuit could This circuit is to be spared as part Sh:tdown result in high off-scale, low of the dedicated shutdown system Eculpment off-scale, or erroneous modi fications. indication. TE-422A IXC103073-KC Sensor signal Damage to this circuit could This circuit is to be spared as < result in high off-scale, low part of the dedicated shutdown systes off-scale, or erroneous modifications. indication. Impe11 Corporation P: port No. 01-0310-1435 YD-20 Revision 0

p (~m ( s. < 10CFR50 APPEICII R. SECTION III.G COW 1.IANCE EVALUATION FIRE AREA / ZONE 1-YD-20-4B tiest Penetration Area a Effects of Fire on Safe Shutdown capabtlity a A fire in this fire rea/rone could result in the loss of the following portions of systems used to achieve hot standby and cold shutdown: . Reactor Coolant System (RCS)

                                 -     Cables for the following components
                                       -     POWS                                                                ,
                                       . Block valves
                                       -     Pressurizer neaters
                                       -     Source range monitors                                               <
  • Pressurizer level transmitters
                                       -     Prissy systen temperature transmitters Chemical ed Volume Control (CVCS)
                                 -     Cables for the following components:
  • Chrging pumps and associated support equipment
                                       -     Cheging loop A control valves
                                       . Chrging loop A flow transmitter j                 ,
                                       . Reactor coolant pump seal flow pressure transmitters
                                       . Chrging IWST isolation valves
                                       . Seal injection flow control valves Main Steam System (MSS)
                                 -     Atmospheric steam den valves
                                 -     Cables for the following components:
                                       . Atmospheric steam dap valves
                                       -      Steam generator level transmitters Auxiliary Feeesater System (AFW)
                                 -     Caoles for the following components:
                                       -      Motor driven auxiliry feedwater pump
                                       *    . Steam driven aux 111ry feedwater pump
                                        -     Flow control valves I

Impell Corporation l Report No. 01-0310-1435 YD-21 Revision 0

Nx _.s] ] ( ,I 10CFR50 APPENDIX R SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-48 West Penetration Area l Component Cooling water (CCw) l

                             -    Caoles for the following components:
  • Component cooling water pamp
                                  -    CCW heat excnange isolation valve
                                  -    Thermal barrier outlet valves
                                  -    CCW RHR heat exhanger flow control valves Containment Ventilation System (CVS)
                             -    Cables for the following components:
                                  -    Reactor cavity cooling fan and associated damper Gaseous Nitrogen System (GNI)
                             -    Cables for the following components:
                                  -    PORY nitrogen control valve Residual Heat Removal (RHR)
                             -    Cables for the following components
                                  -    Nesidual heat removal pump
                                  -    Residual heat removal inlet isolation valve
                                  -    Residual heat removal aischarge isolation valve
                                  -    RHK heat excnanger isolation valve
  • KHR inlet and discharge tenperature transmitters
                                  -    RHR flow control valve Essential Electrical Systems Station service transformer 3
                             -    Cables for the following components:
                                  -    480V switchgear
                                  -    120V vital buses lapell Corporation Report No. 01-0310-1435                         Yu-22                                    Revision 0
                .                                             c                                   ,
                   \                                        (     )

v' u ./ \ j; 10CFR50 APPENDIX R, SECTION III.G CCffLIAEE EVALUATION FIRE AREA / ZONE 1-YD-20-48 Vest Penetration Area The following portions of the dedicated shutdown system are located within the west penetration area: Reactor Coolant System

                                      -     Cables for the following components:
                                            . primary system temperature transmitters
                                            . pressurizer pressure transmitter
                                            -     pressurizer level transmitter Main Steam System (M55) 1
                                      -     Cables for tne following components:                               .
                                            . stema generator level transmitters Caoles for the cedicated snutdown system operation of pressurizer heater group D and tne PORVs and their associated cloct valves will also be routed tnrough tnis tire area / zone.

The fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendia R, Section III.G.2. The dedicated snutdown system will ne used to achieve and maintain cold shutdown in the event of a fire I l in the fire area / zone. Operator action will be taken to l locally control certain valves required for hot standby. l Operator action will also be taken to deenergize offsite and normal onsite power sources to prevent and mitigate spurious l equipment operation. An exemption request for the lack of i area-wide suppression / detection per the requirements of Sections III.G.3 will be provided. Cables and equipment for the dedicated shutdown system which are routed through this fire area / zone will be protected by a 3-hour rated fire barrier. The interruption of seal injection and seal cooling to the reactor coolant pumps, for the period required to initiate seal injection from the cedicated snutdown system, nas Deen evaluated and determined to be acceptacle (26). Tne loss of auxiliary fee &sater flow, for the pertoo required to initiate auxiliary feedwater flow from tne dedicated shutdown system, has Deen evaluated and determined to De l ! acceptable (24,25). Impe11 Corporation Revision 0 Report No. 01-0310-1435 YD-23

                                                                                                                 ,m (M                                             b,rm                                   ( -[

u. 10CFR50 APPENDIE R, SECTION III.G COW LIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Damage to caoles for PuMV and its associated clock valve could cause tne spurious actuation of tne PORW wnen the bloca valve - is not availaole to isolate tne line. :eurious actuation of the PORV, until operation action is tasen to deenergize and close tne valve, nas seen analyzed, and will not result in unacceptaole consequences (24,25). Damage to the caoles for atmospneric steam dap valves CV-77 and CV-79 coulo cause the valves to spuriously open. Spurious actuation of the valves, untti operator action is tacen to deenergize and close the valves, has been analyzed, and will not result in unacceptable consequences (24,25). The redundant steam dump valves CV-76 and CV-78 will remain available for dedicated shutdown system operation. Damage to cables for the reactor vessel head vent valves and pressurizer high point vent valves could cause the spurious actuation of the two redundant high/ low pressure interface valves in each line. Spurious actuation of these valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable consequences (24,25). Damage to cable for primary plant makeup water control valve FCV-Il02A could cause the valve to spuriously actuate, allowing primary plant water to be supplied directly to the charging pump suction. Spurious actuation of this valve, until operator action is tasen to deenergize and close tne valve, has oeen analyzed and determined to ne acceptaole (27). Damage to cables for boric acid supply valves FCV-11028 and CV-334 coulo cause tnese valves to spuriously open, allowing concentrated Doric acto to De supplied to the cnarging pop suction. Operator action will be required to close manual valves to isolate these lines. Damage to cables for the containment spray control valve CV-114 could cause this valve to spuriously open. Containeet spray will not be inadvertently initiated, as the refueling water pumps will not be spuriously actuated by a fire in this fire area / zone. Impe11 Corporation Nevistos 0 Report No. 01-0310-1435 YD-24

( u

                 )

a

                                                                                )                                                               +..

10CFR50 APPEhDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area e Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus IC, IWAIC11P1-KB Power to station service Loss of power to 480V switchgear 3 None. Dedicated shutdown system will , Standby Brt* 11 transformer 3 from station service transformer 3 remain available. Request exemption for lack of area-wide suppression / detection per III.G.3. _ 120V Y-29 1GYY29P2-KC Power loss of power to vital bus 5 Operator action to manually position could cause the loss of power FCV-3300 and FCV-3301 will be required. to the following components Dedicated shutdown system will remain required for normal / alternate available. shutdown: LT-3400A TE-3402A FCV-3300 LT-3400d TE-3411A FCV-3301 LT-3400C TE-3421A CV-3201 SV-3200 SV-3204 SV-3214 5V-3202 SV-320s CV-3213 SV-3203 $W-3211 YV-29/ ItiD021701-KC Power Loss of 125V DC power to Operater action to manually position Inverter 5 Inverter 5. FCV-3300 and FCV-3301 will ne requireo. Dedicated shutoown system will remain ava11aale. RCS CV-531 1GY1215Cl- d Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. CV-531 will f ail open on loss of valve to spuriously close, or power, open. C0 545 1GY1215CO-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. CV-545 will fall closed on loss open or close, of power. Spurious operation of the PORV, until operator action is taken to deenergize and close the valve, has Deen analyzed, and will not result in an unacceptable condition (24,25). 1GYl215C2-KC Remote valve control / Damage to tnis circuit could position indication result in tne loss of remote m valve control, and/or cause the valve to spuriously open, or close. l Impe11 Corporation Report No. 01-0310-1435 YD-25 Revision 0

m. cf . a 10CFR50 APPENDIX R. SECTION III.G COIPLIAICE EVALU4TI0ll FIRE AREA / ZONE 1-YD-20-44 tiest Penetration Area Category System Campenet Circuit-Schedule Function . Consequence of Fire Nitigation Not RCS Pzr 1GSS215P4-K8 Power Damage to tais circuit could leone. ~ Celes for dedicated snutdown Staney (contd) Heater cause the loss of power to at systen operation of pressurizer heater Equipment Group s least one of the neaters in the group D util remain avatiante. (contd) _ pressurizer heater group. Pzr 1G8209P4-Es Pouer Damage to this circuit could operator action to transfer control of tne Heater cause the loss of power to at required portion of pressurizer heater Group G 1 east one of the heaters in the group D to tne deoicated snutdown panel, pressurizer heater group. Protect celes for dedicated snutdoom system operation of pressurizer heater group D with a 3-hour rated barrier. 1GBS20W 5-K8 Power Damage to this circuit could cause the loss of power to at least one of the heaters in the ' pressurizer heater group.

                     - IE-1201  1GQ102074-KB  Sensor signal               Damage to this circuit could          llone. During operation of the dedicated result in low off-scale or            shutdown system, shutdown margin will be erroneous source range indication. determined by sampling primary system baron concentration.

l 1GQ102075-KB Sensor signal Damage to this circuit could l result in low off-scale or erroneous source range indication. 1GQ102003-Ks Instrument power Damage to this circuit could result ' in low off-scale or erroneous i source range indication. I l LT-435 1mQ104081-Es Sensor signal Damage to tnis circuit coula 36cne. LT-430A will remain avall ele at result in high off-scale, low the dedicated shutdown panel.

                                                                         .off-scale, or erroneous indication.

TE-3402A IGY2904ID-KC Sensor signal Damage to this circuit could leone. TE-402A will remain availmie at result in high off-scale, iow the dedicated shutdown panel, off-scale, or erroneous indication. Impe11 Corporation Report No. 01-0310-1435 YD-26 Revision 0 L

O O O . 10CFR50 APPENDIX k, SECTION III.6 CuWLIANCE EVALUAT104 FINE ANEA/ ZONE 1-YD-20-4s west Penetration Area

                                                                                                                                                    .a Consequence of Fire                     Mitigation Category System Component Circuit-Schedule Function 1GY2904IE-KC  Sensor signal              Damage to this circuit could     None. TE-412A will remain availaole at      y

( Hot RCS TE-3411A result in high off-scale, low the dedicated shutdown panel. ! Staney (contd) off-scale, or erroneous Equipment ! (contd) indication. - TE-3421A 16Y2904IF-KC Sensor signal Damage to this circuit could None. TE-422A will remain available at , result in high off-scale, low the dedicated shutdown panel. off-scale,or erroneous indication, TE-402C 1FQ103087-K8 Sensor signal Damage to this circuit could None. TE-4028 will remain available. _ t I result in high off-scale, low off-scale,or erroneous indication. l l l CVCS G-as 1FA1C07PI-K8 Power Loss of power to G-Ikl. None. Caoles for dedicated shutoown l systen operation of 6-dA will remain ! avail aole. t l G-942 IX82A16C1-Kd Interlock to G-8A Damage to this circuit could hone. Caoles for dedicated snutdown prevent autostart of the pump system operation of 6-8A and associated when G-8A is started, or support equipment will remain available. spuriously start the pump isien G-8A is not running. G-943 IF80129PI-KC Power Loss of power to G-943. None. Cables for dedicated shutdown system operation of G-8A and associated support equipment will remain available. 1F80129C3-KC Local pump control Damage to this circuit could prevent local manual start of the pump, or spuriously start _ 1W80129C4-KC Low bearing oil Damage to this circuit could pressure interlock prevent auto start of the pump, or spuriously start the pump. 4 Impell Corporation Revision 0 Report No. 01-0310-1435 Yo-27

       ,/~ ~                                                          ,, ~m                                                            ,,
                                                                                                                                            ~

k. 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Category Systen Component Circuit-Sche @ e Function Consequence of Fire . Mitigation Hot CVCS MG8AF IIB 2A14C1-KS Initiated fan control Damage to this circuit could None. Cables for dedicated shutdown , Standby (contd) spuriously start the fan or system operation of G-8A and associated Eqxipment prevent autostart of the fan. support equipment will remain available. g (contd) M688F 1W82A15C1-K8 Initiated fan control Damage to tnis circuit could None. Caoles for dedicated shutoown spuriously start the fan or system operation of G-dA and associated , prevent autostart of tne fan. support equipment will remain availaole. MOV-1100B Ifu0147PI-K8 Power Loss of power to MOV-11008. Operator action to verify n0V-1100s or MOV-11000 open to initiate charging pump G-8A operation from tne dedicated snutoown systen. 1FB0147C1-K8 Position switch / torque Damage to this circuit could . switch feedback prevent remote operation and/or cause the valve to spuriously open or close. 1FB0147C2-K8 MOV-1100C open interlock Damage to this circuit could prevent remote operation and/or tause the valve to spuriously close. Impe11 Corpcration Report No. 01-0310-1435 YD-28 Revision 0

y 10CFA50 APPENDIX R. SECTION III.6 CupFLIANCE EVAtuAT!081

                                                                                                                                                                    ?

Flaf ANEA/ZumE l-Yu-31-4s west Penetration Area - C-tegory System Component Circuit-Schedule Function Conseeuence of Fire mittention CVCS .. FCV-1112 IFyl07011-Ks Positioner Damage to this circuit could operator action to position FCV-1112 - Het .from the dedicated shuteoun panel, as Stauany ' (contd)- control signal cause a loss of remote control Equipment and spuriously open the valve. required. (contd) Operation of the valve through sequener 1 and 2 initiation would not be affected. 1FQ107037-K8 SV-1112 positioner Damage to this circuit could override solenoid result in the loss of valve control power control through SV-1112 and - cause the valve to spuriously open or Close. FT-1112 Sensor signal Damage to this circuit could Operator action to position FCV-1112 from 1FQ107103-K8 the dedicated shutdown panel as required. result in erroneous indication _ of charging flow rate and cause spurious operation of FCV-1112. FCV-1115A 1FQ107076-K8 Control signal Damage to this circuit could Operator action to f all FCV-1815A open cause a loss of positioner by isolating instrument air at tne control causing FCV-1115A dognouse, verify FCV-11150 closed, and and FCV-11150 to close or control seal injection flow using manual result in a loss of valve located upstream. Interruption of instrumentation, causing seal injection and seal cooling to tne FCV-Il15A to fail open. reactor coolant pump seals for tne period requirM to initiate seal injection from the dedicated shutdoun systen has Deen evaluated and determined to oe acceptable (26). FCV-11158 IGQ107077-K8 Control signal Damage to this circuit could Operator action to fall FCV-11158 open cause a loss of positioner by isolating instrument air at the control, causing FCV-11158 doghouse, verify FCV-1115E closed, and and FCV-1115E to close or control seal injection using manual result in a loss of valve located upstream. Interruption of ~ instrumentation, causing seal injection and seal cooling to the FCV-11158 to fall open, reactor coolant pump seals for the period required to initiate seal injection from - the dedicated shutdoun systen has been evaluated and determined to De acceptable (26). . Irpell Corporation Report No. 01-0310-1435 YD-29 Nevision 0

3

          ~b O                                                            O                                                                     N 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION
                                                                                                                                                           ~

FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Category - System Component Circuit-Schedule Function Consequence of Fire Mitigation FCV-Il15C Control signal Damage to this circuit could Operator action to fall FCV-1115C open _ Hot CVCS IHQ107078-K8 5tandby (contd) cause a loss of positioner by isolating instrument air at the Equipment control, causing FCV-1115C doghouse, verify FCV-Ill5F closed, and and FCV-Ill5F to close or control seal injection flow using manual - (contd) valve located upstream. Interruption of result in a loss of instrumentation, causing seal injection and seti cooling to the FCV-1115C to fail open. reactor coolant pump seals, for the period , required to initiate seal injection from the cedicated shutoown system, has oeen evaluated and determined to De acceptacle _, (26). PT-il15A Sensor signal Damage to this circuit could Operator action to f ail FCV-1115A opten 1WQ107108-Kts result in high off-scale, low by isolation instrument air at the off-scale, or erroneous indica- dognouse, verify FCV-1115D closed, and , tion. This could cause controller control seal injection flow using manual FC-1115A to spuriously open or valve located upstream. Interruption of close FCV-1115A and FCV-11150, seal injection and seal cooling to the and/or cause controller PC-1115A reactor coolant pump seals, for the period to spuriously close PCV-1115A. required to initiate seal injection from the dedicated shutdown system, has been evaluated and determined to De acceptable (26). PT-1115C IWQ107097-KB Sensor signal Damage to this circuit could Operator action to fall FCV-1115C open result in high off-scale, low by isolation instrument air at the off-scale, or erroneous indica- doghouse, verify FCV-Ill5F closed, and tion. This could cause controller control seal injection flow using manual FC-Ill5C to spuriously open or valve located upstream. Interruption of close FCV-1115C and FCV-1115DF seal injection and seal cooling to the and/or cause controller PC-1115C reactor coolant pump seals, for the period to spuriously close PCV-lll5C. required to initiate seal injection from the dedicated snutdown systese, has been evaluated and determined to De acceptacle (26). - MSS SV-86/ IGW10317-KB Solenoid control power Damage to tnis circuit could operator action to oeenergtze 12bvuC and CV-77 spuriously open the valve or 120VAC/480VAC power to prevent / mitigate - transfer valve control to steam spurious operation. Spurious operation of pressure transmitter PT-459 the steam dusp valves until operator (via YM-418A). action is tamen to deenergize and close - the valves has been analyzed and will not result in an unacceptable condition (24,25). Irpell Corporation Revision 0 Report No. 01-0310-1435 YD *J

p U b b - 10CFR50 APPENDIX R. SECTION III.G C0ffLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-48 West Penetration Area Category Systen Component Circuit-Senedule Function Consequence of Fire Mitigation

   ' Hot         M55      SV-88/ 1GW10318-K8      Solenoid control power     Uamage to this circuit could     operator action to oeenergize 12dvuC and     .

St:ndoy spuriously open tne valve or 120VAC/4dOVAC power to prevent / mitigate (contd) CV-79 spurious operattun. Spurious operation of Equipment transfer valve control to steam pressure transmitter PT-459 the steam dump valves until operator - (conto) action is taKen to deenergize and close (via YM-418A). the valves has Deen analyzed and will not result in an unacceptaole condition (24,25). SV-86/ 1GW10306-KB SV-86/SV-88 Control Damage to this circuit could Operator action to deenergize 125VDC and SV-88 spuriously open the valve or 120VAC/480VAC power to prevent / mitigate transfer valve control to steam spurious operation. Spurious operation of pressure transmitter PT-459 the steam dump valves until operator (via YM-418A). action is taken to deenergize and close the valves has been analyzed and will not result in an unacceptable condition (24,25). SV-175 IGY2A30Cl-KB Solenoid control power Damage to this circuit could Relocated SV-175 and associated cables cause a loss of power to SV-175, outside all fire areas where dedicated preventing transfer of steam shutdown system operation of the dump control to C-38. atmospheric steam dump valves is required. Irpell Corporation Report No. 01-0310-1435 Yu-31 Kevision 0

m .,m q

                                                                                                       /                                                                             ,

l 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUAfl0N FIRE AREA / ZONE 1-YD-20-4B West Penetration Area Category System Component Circult-Schedule Function Consequence of Fire Mitigation Hot MSS LT-3400A' 1GY29011A-KC Sensor signal Damage to this circuit could None. LT-450C will remain available. Standby (contd) result in high off-scale, low I Equipment off-scale, or erroneous (contd) indication. LT-34008 1GY290118-KC Sensor signal Damage to this circuit could None. LT-451C will remain available. result in high off-scale, low off-scale, or erroneous indication. LT-3400C 1GY29011C-KC Sensor signal Damage to this circuit could None. LT-4b2C will remain availaole. result in hign off-scale, low off-scale, or erroneous indication. AFW G-105 1FBS125PI-KC Power Loss of power to auxiliary feed- None. Dedicated auxiliary feedwater pump water planp G-105. will remain availaole. Loss of auxiliary feedwater flow, until operator action is taken to initiate auxiliary feedwater flow from the dedicated shutdown system, has been evaluated and determined to be acceptable (24,25). 1FBS125C8-KC MOV-1202 interlock Damage to this circuit could prevent operation of G-105 and MOV-1202 from panel C-71. Operation of G-105 via I handswitch at panel C-38

                         <                                                                           would not be affected.

G-10S/ 1FBS125C9-KC Remote pump / valve Damage to this circuit could None. Dedicated auxiliary feedwater MOV-1202 control spuriously start the pump and/or pump will remain availaole. Loss of cause MOV-1202 to spuriously open. auxiliary feemvater flow, until operator Operation of the pump at panel action is taken to initiate auxiliary C-38 would be prevented. feedwater flow from the dedicated shutdown system, nas oeen evaluated and determined to be acceptaole (24,25). l 1 Impe11 Corporation Report No. 01-0310-1435 YD-32 Revision 0

O f

                                                                                                     '-u-
                                                                                                                                                'd i

10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION I FIRE AREA / ZONE 1-YD-20-48 e West Penetration Area Category System- Component Circuit-Schedule Function Consequence of Fire Witigation MOV-1202 IFu0137PI-KC Power loss of power to nuV-1202. . None. Dedicated auxiliary feewater Hot AFw Standny (contd) pump will remain availaole. Loss of Equipment auxiliary feedwater flow, until operator action is taxun to initiate auxiliary (contd) feemater flow from the dedicated snutdown system, has Deen evaluated ano determined .' to oe acceptacle (24,25). , IFB0137C1-KC Position switch / torque Damage to this circuit could 'None. Dedicated auxiliary feeWater i switch feedback result in the loss of remote pump will remain available. Loss of valve control. The valve will auxiliary feeWater flow, until operator f all as is, normally closed. action is taken to initiate auxiliary feedwater flow frem the dedicated shutdown ' system, has been evaluated and determined i to be acceptable (24,25). i i Switch position Damage to this circuit could None. Dedicated auxiliary fee &ater

CV-3201/ IGY2906CH-KC SV-3205 feedback result in the loss of remote pump will remain available. Loss of 4 valve control and/or cause auxiliary fee &ater flow, until operator valve CV-3201 to spuriously action is taken to initiate auxiliary close and cause valves feedwater flow from the dedicated shutdown i

SV-3200, 02, 03, 04, 05, system, has been evaluated and determined i 11,14 and CV-3213 to to be acceptable (24,25). spuriously open. Damage [ a to this circuit could also a allow CV-3201 and CV-3205 to oe opened simultaneously ) or prevent $V-3205 from i Deing opened unen CV-3201 opens. i SV-3201, 1GY2906C5-KC Valve position Damage to this circuit could None. Dedicated auxiliary fee mater 02.03,04 indication result in the loss of remote pump will remain availaole. Loss of

auxiliary feemater flow, until operator i valve control. This could cause SV-3200, 02 03 04, action is taken to initiate auxiliary L 05,11,14andCV'321$to feedwater flow from the dedicated shutdown open and CV-320) to close. system, has been evaluated and determined to be acceptable (24,25).

7 i i i i b Impe11 Corporation l Report No. 01-0310-1435 YD-33 Revision 0 1

fN, ,

             %s)                                                               J(aC)                                                             \a/

10CFR50 APPENDIX R, SECTION III.G COMPLIANCE E/ALUATION FIRE AREA / ZONE l-YD-20-48 West Penetration Area Category System' Component Circult-Schedule Function Consequence of Fire Mitigation Hot AFW SV-3200-05, 1GY2906C6-KC Valve position Damage to this circuit could None. Dedicateji auxiliary feedwater Standby (contd) 11,13.14 indication result in erroneous valve pump will remain available. Loss of Equipment position indication, but would auxiliary feedwater flow, until operator (contd) not affect valve operation. action is taken to initiate auxiliary 4 feecheater flow from the dedicated shutdown a system, has been evaluated and determined I to be acceptable (24,25). 1GY2906CC-KC Solenoid control power Damage to this circuit could spuriously open CV-3201 and close SV-3202,03,04,05,11,13, 14, or close CV-3201 and open SV-3200, 02, 03, 04, 05, 11, 14, and CV-3213. Remote operation of the valves 1 could also oe prevented. i e SV-3200 1GY2906CE-KC solenoid control power Damage to this circuit could None. Dedicated auxiliary feeuwater result in the loss of remote pump will remain availaole. Loss of a valve control, and/or auxiliary feecheater flow, until operator spuriously open SV-3200, 02, action is taKen to initiate auxiliary

 !                                                                                  03, 04, 05,11,14 CV-3213         feedwater flow from the dedicated snutdown l                                                                                   and spuriously close CV-3201. system, has oeen evaluated and determined i

a tobeacceptaole(24,25), i 1 i i i 1 i Impe11 Corporation Report No. 01-0310-1435 YD-34 Revision 0

es., f~s n V 10CFR50 APPENDIX R. SECTION !!I.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot AFW FCV-2300 IFY331518-KC Positioner control Damage to this circuit could Operator action to isolate instrument air Standby (contd) cause tne valve to spuriously and manually contrt,1 FCV-2300. Equipment open, and/or prevent remote (contd) valve control. ) FCV-2301 IFY331bl9-KC Positioner control Damage to this circuit coula operator action to isolate instrument air cause tne valve to spuriously and manually control FCV-2301. open, and/or prevent remote < valve control. FCV-3300 1GY29061G-KC Positioner control Damage to this circuit could Operator action to isolate instrument air cause the valve to spuriously and manually control FCV-3300. open, and/or prevent remote valve control. FCV-3301 IGY2906IH-KC Positioner control Damage to this circuit could Operator action to isolate instrtment air a cause the valve to spuriously . and manually conrol FCV-3301. open, and/or prevent remote valve control. CCW G-15A 1FBS121P2-KB Pcwer Loss of power to G-15A. None. Component cooling water is not required for dedicated shutdown system opration. Interruption of seal cooling and seal injection to the reactor coolant plap seals, for tne period required to initiate seal injection from tne I dedicated shutdown systea, has oeen evaluated and determined to be acceptaole 4 (26). MOV-7208 1FB0187PI-KB Power Loss of power to MOV-7208. None. ) 1FB0187C1-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote i valve control. The valve will f ail as is. 1 CV-722A 1WQ106019-KB Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC spuriously open or close the power to prevent / mitigate spurious valve or prevent remote operation if required to support operation operation, of the thermal barrier pump. t Impe11 Corporation Report No. 01-0310-1435 YD-35 Revision 0

       .(

V (^) V ' V' 10CfR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA / LONE l-YD-20-48 West Penetration Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation A-9 IWB0109PI-KB Power Loss of power to A-9. None. The reactor cavity cooling fans are Hot CVS Standby required only to support operation of Equipment the source range monitors. (contd) Damage to this circuit could IWB0109C3-KB Interlock to TS-24 spuriously start or stop the fan and/or prevent remote operation of the fan. PO-11 IWB0109C2-KB Damper control Damage to this circuit could None. The reactor cavity cooling fans are cause the damper to spuriously required only to support operation of close. the source range monitors. GNI CV-532 1GD0220C4-KC Remote valve control / Damage to this circuit could Operator action to open manual pypass for position indication prevent remote operation and/or CV-532 to supply nitrogen for operation cause the valve to spuriously of the PURVs and Diocu valves from the open or close. dedicated shutdown panel. IGU0220Cti-KC Remote valve control Damage to this circuit could prevent renote operation and/or cause the valve to spuriously open or close. Cold RHR G-14B IGBS222P2-KC Power Loss of power to G-148 None. The dedicated auxiliary feedwater Shutdown pump will remain available for single Equipment . phase cooldown. MOV-814 1GB0271PI-KB Power Loss of power to MOV-814 The None. This valve is not required for valve will fall as is, normally single phase cooldown. closed. 1GB0271C2-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will fail as is, normally closed. f Irpell Corporation Report No. 01-0310-1435 YD-36 Revision 0

(~N f G ' 10CFR50 APPENDIX R SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-4B West Penetration Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation 1 Cold RHR MOV-8228 1GR0266P1-K8 Power Lc 5 of power to MOV-8228. None. This valve is not required for Shutdown (contd) single phase cooldown. Equipment (contd) 1GB0266C2-K8 Position switch / torque Damage to this circuit could switch feedoacK result in tne loss of remote valve control. Tne valve will f ail as is. MOV-834 1Gu0272PI-KB Power Loss of power to MOV-834. None. Tnis valve is not requirea for single phase cooldown. IG80272C3-KB Position switch / torque Damage to this circuit could 2 4 switch feedback result in the loss of remote valve control. The valve will fail as is, normally closed. TE-600 IWQ106026-KB Sensor signal Damage to this circuit could None.This instrument is not required for result in high off-scale, low single phase cooldown. off-scale, or erroneous indication. i TE-601A 1FQ106024-KB Sensor signal Damage to this circuit could None. This equipment is not required for cause high off-scale, low off- single phase cooldown. scale or erroneous indication. This could cause flow con-troller TC-601A to spuriously open or close TCV-601A. 4 TE-6018 1GQ106025-K8 Sensor signal Damage to this circuit could None. Tnis equipment is not required for cause hign off-scale, low single pnase cooldown. off-scale or' erroneous inoication. This could cause flow controller TC-60lu to I spuriously open or close TCV-6018. 4 i HCV-602 IFQ106018-K8 Remote valve control Damage to this circuit could None. This equipment is not required for . result in the loss of remote single pnase cooldown. j valve control, and/or cause the valve to spuriously open. i 4 Impell Corporation Report No. 01-0310-1435 YD-37 Revision 0 l

        %j                                                                            L.)                                                                                                              ()

10CFR50 APPEhDIX R, SECTION !!!.G COW LIAhCE LVALUATION

                                                                                                                                                                                                                     ~

FIRE AREA / ZONE l-YU-20-45 west Penetration Area Category System Component Circuit-Scnedule Function Consequence of Fire Mitigation Valve position feedback Damage to this circuit could None. Tne component cooling water system < C21d CCW TCV-601A 1FQ106010-KB result in the loss of valve is not required to support dedicated Shutdown . shutdown system operation. Equipment position indication, s (contd) Damage to this circuit could IFQ106011-KB Control signal result in the loss of remote valve control, and/or cause the , valve to spuriously open. Valve position feedback Damage to this circuit could None. The component cooling water system TCV-601B 1GQ106012d3 result in the loss of valve is not required to support dedicated position indication. shutdown system operation. j 1GQ106013-KB Control signal Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open. Hign/ Low RCS SV-3401 1GY3005CA-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC l Pressure result in tne loss of remote power to prevent /mttigate spurious j Interface valve control, and/or cause the operation. Vens valves will fall closed ' valve to spuriously open, on loss of power. Spurious actuation of tne vent valves, until operator action is tamen to deenergize and close tne valves, nas Deen analyzed, and will not result in an unacceptaole condition (24,25). Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC SV-3401/02 1GY3005CI-KC power to prevent / mitigate spurious result in the loss of remote valve control, operation. Vent valves will f all closed on loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). 1GY3005CJ-KC Solenoid control power Damage to this circuit could result in the loss of remote valve control, and/or cause the vaive to spuriously open. Impell Corporation Revision 0 Report No. 01-0310-1435 YD-38

m p ,m G L) U , 10CFR50 APPEN0lX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA /10NE l-Y0-20-48 West Penetration Area a Category System Component Circuit-Schedule Function @v,ance of Fire Mitigation High/ Low RCS $V-3402 1GY3005CB-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC < Pressure (contd) result in the loss of remote power to prevent / mitigate spurious Interface valve control, and/or cause the operation. Vent valves will f all closed valve to spuriously open. on loss of power. Spurious actuation of 4 (contd) the vent vsives, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in . an unacceptable condition (24,25). SV-3403 1GY3005CC-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. Vent valves will fall closed , valve to spuriously open. on loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). SV-3403/04 IGY3005CK-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in tne loss of remote power to prevent / mitigate spurious valve control. operation. Vent valves will fall closed on loss of power. Spurious actuation of tne vent valves, until operator action is taKen to oeenergize and close the valves, nas oeen analyzed, and will not result in an unacceptable condition (24,25). 1GY3005CL-KC Solenoid control power Damage to this circuit could result in the loss of remote valve cc,ntrol, and/or cause the valve to spuriously open. SV-3404 IGY3005CD-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. Vent valves will fail closed valve to spuriously open. on loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, J has been analyzed, and will not result in an unacceptaole condition (24,25). w t Impell Corporation Report No. 01-0310-1435 YD-39 Revision 0

                                                                     .v                                                             v 10CFR50 APPENDIX R, SECTION III.G C0FFLIANCE EVALUATION 1

FIRE AREA / ZONE'l-YD-20-48 West Penetration Area Category System Component Circult-Schedule Function Consequence of Fire Mitigation High/ Low CVCS CV-528/ 1GY2909C5-KC Remote valve control / Damage to this circuit could None. CV-527 and CV-525 will remain , Pressure CV-526 position indication cause the valves to spuriously available to isolate the seal water Interface open or close, and/or prevent return and letdown lines. (contd) the valves from being closed. CV-528 1GY2A36P4-KC Remote valve control Damage to this circuit could None. CV-527 will remain available to prevent remote operation ano/or isolate the seal water return line. cause the valve to spuriously Close. 1GY2909C7-KC Remote valve control Damage to tnis circuit could result in tne loss of remote valyt control, and/or cause the valve to spuriously close. Spurious RCS G-2A lWA1A03C4-KB 011 lift pressure Damage to this circuit could None. Turoine trip will deenergize the Operation interlock spuriously start the pump, and/ pump. Equipment or prevent remote p op operation. IXA1A03Pl-KB Power Loss of power to G-2A IXA1A03P2-KB Power Loss of power to G-2A PCV-430C 1FQ108005-KB Positioner signal Damage to this circuit could None, as reactor coolant p ops are result in the loss of remote tri pped. valve control, and/or cause the valve to spuriously close. PCV-430H IGQ100006-K8 Positioner signal Damage to this circuit could None, as reactor coolant pumps are result in tne loss of remote tri pped . valve control, and/or cause the valve to spuriously close. Impell Corporation Report No. 01-0310-1435 YD-40 Revision 0

O /' N s

                                                                                                                                           \.

10CFR50 APPENDIX R, SECTION Ill.G C0pFLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-46 west Penetration Area Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS G-42 lHH2A10Cl-Ks Remote pump control Damage to this circuit could Operator action to trip offsite/ diesel < Operation '

                                             'and indication             spuriously start tne pump, or       generator power will deenergize Equipment                                                                 prevent remote operation.           tnis pump.

(contd) . FCV-1102A IWQ107007-KB Solenoid control power Damage to this circuit could . Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. FCV-1102A will fail closed on.

                                                                        . open or close.                     loss of power. Spurious actuation of this valve, until operator action is taken to deenergize and close the valve, has been analyzed and detemined to be acceptable (27).

FCV-Il028 lWQ107009-KB Solenoid control power Damage to this circuit could Operator action to close manual valve prevent remote operation and/or located downstream of FCV-1102A. cause the valve to spuriously open or clo,.e. CV-334 IFQ107033-K8 Solenoid control power Damage to this circuit could Operator action to close manual valve prevent remote operation and/or located upstream of CV-334.

  • cause the valve to spuriously open or close.

3 Icpell Corporation Report No. 01-0310-1435 YD-41 Revision U

m im ' (p). ( N,j) I i w/ G - 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area - . Category System Component Circuit-Schedule Function Consequence of Fire Mitigation 1 Spurious CVCS FCV-Ill50 1G00205DA-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC Operation (contd) prevent cor. trol of FCV-Ill5D power to prevent / mitigate spurious Equipment via the nitrogen supply system operation. FCV-1115D will fail closed on (contd) or the normal plant instrument on loss of power. - air system. 1GD0205DB-KC Remote valve control- Damage to this circuit could prevent coritrol of FCV-11150 via the nitrogen supply system. Control via tne normal plant instrument air system could still be availaole. FCV-1115E IGD 0205EA-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevant control of FCV-1115E power to prevent / mitigate spurious via the nitrogen supply system operation. FCV-1115E will fail closed on or the normal plant instrument on loss of power. air system. 1GD0205EB-KC Remote valve control Damage to this circuit could prevent control of FCV-1115E via the nitrogen supply system. Control via the normal plant instrument air system would still be available. i FCV-1115F 1G00205FA-KC Renote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent control of FCV-ll15F power to prevent / mitigate spurious via the nitrogen supply system operation. FCV-1115F will fail closed on or the normal plant instrument on loss of power. air system. 1GD0205FB-KC Remote valve control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via tne normal plant instrument air system would still oe availaole. Impell Corporation Revision 0 Report No. 01-0310-1435 YD-42

b L U \s! 10CFR50 APPENDIX R. SECTION III.G COPPLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Category Systen Component Circult-Schedule Function Consequence of Fire Mitigation Spurious CVCS CV-526 IGY2A36PS-KC Remote valve control Damage to tnis circuit could None. CV-525 will remain availaole to Operation (contd) prevent remote operation and/or isolate the letdown line. Equipment cause the valve to spuriously 4 (contd) close. IGY2909C6-KC Remote valve control Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. AFW MOV-1204 IF80127PI-KC Power Loss of power to MOV-1204. None. Dedicated auxiliary feedwater pump will remain available. 1F80127Cl-KC Position switch /tortiue Damage to this circ' sit could , switch feedback result in the loss of remote valve control. The valve will fall as is, normally closed. CRS G-27N IF8S119P2-K8 Power Loss of power to G-27N. None. i. I CV-114 1GM1214CC-KC Control power and Damage to this circuit could Operator action to close manual valve position indication prevent remote operation and/or located upstream. cause the valve to spuriously open of Close. J SIS MuV-356 IFt50158PI-K8 Power Loss of power to MOV-356. None. 1F80158C2-K8 Position switen/ torque Damage to tnis circuit could switch feedoacK result in tne loss of remote valve control. The valve will i fail as is, normally closed. MOV-357 IGB0243P1-K8 Power Loss of power to MOV-357. None. 1GB0243C2-K8 Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f ail as is, normally closed. l IKpell Corporation Report No. 01-0310-1435 YD-43 Revision 0

                                                                                  ,,a i                                                                 S                                                                                m s

4 10CFR50 APPENDIX R, SECTION III.G C(#FLIANCE EVALUATION [ FIRE AREA /lJNE l-YD-20-46 West Penetration Area . Category System Component' ' Circuit-Schedule Function Consequence of Fire Mitigation Sourious FWS FT-460 IFQll2034-KB Sensor signal Damage to this circuit could None. Main fee &ater ptmps are tripped.

Operation spuriously close the main Equipment fee &ater control valve and/or t (contd) cause a reactor scram.

IFYR10-KB Power Damage to this circuit could l cause a loss of power to FT-460, + causing FCV-456 to close and/or cause a reactor scram. e FT-461 IGQll2O35-K8 Sensor signal Damage to this circuit could None. Main fee &ater ptsps are tripped. spuriously close the main  ;

!                                                                                feedwater control valve and/or i                                                                                 cause a reactor scram.

4 j IGYR10-Kis Power Damage to this circuit could

;                                                                                cause a loss of power to FT-461, causing FCV-457 to close and/or cause a reactor scram.

2 4 LT-453 IFQ112028-K8 Sensor signal Damage to this circuit could None. Main fee &ater pumps are tripped. I cause FCV-456 to close and

}                                                                                the plant to scram.                                                                           1 j                                    IWYR1008-KB       Power                     Damage to this circuit could
 '                                                                               cause a loss of power to LT-453,
  • causing FCV-456 to close and I the plant to scram.

1

 ;                           LT-454  1WQ112029-KB      Sensor signal             Damage to this d ccult could           None. Main fee &ater pumps are tripped.

1 cause FCV-457 to close and the plant to scram. , i 1 k - i { m I o 4 (

  ,      Impell Corporation Report No. 01-0310-1435                                               YD-44                                                                                Revision 0 j
                                                              ~r j       .

en a p i J t 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-48 West Penetration Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Alternate RCS TE-400A 1FQ103081-K8 Sensor signal Damage to this circuit could None. Shutdown cause erroneous loop A delta Equipment temperature indication. TE-400C 1FQ103085-K8 Sensor signal Damage to this circuit could None, cause erroneous loop A delta temperature indication. SIS G-508 1FAIC05PI-K8 Power Loss of power to G-50s. Operator action to trip offsite/ diesel generator power will deenergize this pump. MOV-850A IGB0274PI-K8 Power Loss of power to MOV-850A. None. 1G80274C5-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will fall as is, normally closed. MOV-8508 1GB0180P1-K8 Power Loss of power to MOV-8508. None. 1GB0180C9-K8 Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f ail as is, normally closed. Dedicated RCS LT-430A 1GQ300002-K8 Sensor signal Damage to this circuit could Protect caoles for dedicated shutdown Shutdown result in hign off-scale, low system with a 3-nour rated barrier. Equipment off-scale, or erroneous indication. PT-434A 1GQ300001-KB Sensor signal Damage to this circuit could Protect caoles for dedicated shutdown result in high off-scale, low system with a 3-hour rated barrier. off-scale, or erroneous indication. TE-402A 1WQ103083-KB Sensor signal Damage to this circuit could Protect cables for dedicated shutdown result in high off-scale, low system with a 3-hour rated barrier. off-scale, or erroneous indication. Impe11 Corporation Raprt No. 01-031@-14N> _ _ _ . YD-45 ._ _ n- f e ina m

O O O 10CFR50 APPENDIX k, SECTION III.G COMPLIANCE EVALUATIUM FIRE AREA / ZONE 1-YD-20 liest Penetration Area _. C'tegory System Component Circult-Schedule Function Consequence of Fire Mitigation Dedicated RCS TE-4028 IGQ300006-KB Sensor signal Dama to this circuit could Protect cables for dedicated shutdown - i Shutdown ~(contd) resu t in high off-scale, low system with a 3-hour rated b rrier.

Equipment off-scale, or erroneous (contd) indication. -

TE-412B IGQ300007-KB Sensor signal Damage to this circuit could Protect cables for dedicated shutdown , result in high off-scale, low system with a 3-hour rated barrier. off-scale, or erroneous indication. 4 TE-422B IGQ300008-KB Sensor signal Damage to this circuit could Protect cables for dedicated shutdown result in high off-scale, low system with a 3-hour rated barrier. off-scale, or erroneous indication. i MS$ LT-450C 1GQ300003-K8 Sensor signal Damage to this circuit could Protect cables for dedicated snutdown result in nign off-scale, low system with a 3-hour rated Darrier. off-scale, or erroneous indication. LT-451C IGQ300004-K8 Sensor signal Damage to this circuit could Protect cables for dedicated snutdown

result in nigh off-scale, low system with a 3-hour rated barrier.

' off-scale, or erroneous 4 indication. ' LT-452C IGQ300005-KB Sensor signal Damage to this circuit could Protect cables for dedicated shutdown result in high off-scale, low system with a 3-hour rated barrier. off-scale, or erroneous i .,' indication. 4 1 l 4 Impell Corporation Report No. 01-0310-1435 YD-46 Revision 0

j. O wl () 10CFR50 APPENDIX R SECTION III.G C0fFLIANCE EVALUATION . FIpE AREA / ZONE 1-YD-20-4C Doghouse r Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the following portions of systems used to achieve hot standby and cold shutdown: 3 Chemical and Volume Control (CVCS)

                                                -      Charging flow control valve
                                                -     Seal injection flow control valves
                                                -      Cables for the following components:
                                                       . Charging flow control valve
                                                       . Seal injection flow control valves GaseousNitrogenSystem(GNil
                                                -      PORV/ block valve nitregen centrol valve
                                                -    ' Cables for the following conponents:

, i

  • PORY/ block valve nitrogen control valve The fire protection features provided for the protection and separation of safe shutdown systems withir. the fire area /zons ,

do not raet the se9aration requirements of 10CFR50, j Appendix R, Section III.G.2. Operator action will be taken to locally control the seal injection and charging flow control valves located within the fire area / zone. Component cooling ! water thermal barrier cooling to the reactor coolant punp 4 seals will (maain availaole until operator action is taken to ! locally contrO seal injection flow. Charging flow will 4 remain availaole, as caoles for tr.e charging pumps will not oe i affected oy a fire in this area / zone. An exemption request for lack of area-wide suppression / detection, per tne requirements of section III.G.3, will be provioed. 1 I i l Impell Corporation i Report No. 01-0310-1435 YD-47 Revision 0 i

( 0 LJ f)\ Q 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-4C Dognouse , Category System Component Ercuit-Schedule Function Consequence of Fire ' Mitigation Hot CVCS FCV-1112 ----- Charging flow control Loss of FCV-1112. Valve will fall Operator action to close manual valves - Standby valve open. located upstream of FCV-1112 f f charging Equipment through the seal injection flowpath. To achieve higher makeup flow rates through a charging loop A, operator action will De required to manually override and open the flow control valve. 4 1FQ1070ll-KB FY-1112 positioner Damage to this circuit could control signal cause a loss of remote control and spuriously open the valve. Operation of the valve through sequencer initiation would not be affected. IFQ107037-KB SV-1112 positioner Damage to this circuit could override solenoid result in the loss of valve control power. control through SV-1112 and cause the valve to spuriously open. FCV-1115A ----- Seal injection Loop A Loss of FCV-1115A. Valve will Operator action to fall FCV-1115A open Oy flow control valve fall closed on loss of power, Isolating tastrument air at tne dognouse.

  • out will fail open on loss of air. verify FCV-Illbu closed, and control seal injection flow using manual valve located wstream.

IFQ107001-KB Remote valve control Damage to this circuit could cause a loss of positioner control, causing FCV-Ill5A and FCV-11150 to close, or result in a loss of instrument air causing FCV-Ill5A to fall open. 1FQ107076-KB Control signal Damage to this circuit could - cause a loss of positioner control, causing FCV-1115A and FCV-11150 to close, or result in a loss of instrument air causing FCV-1115A to f all open. Irpell Corporation Neport No. 01-0310-1435 Yu-48 Revision 0

A O O a 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YO-20-4C Doghouse Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS FCV-11158 ----- Seal injection Loop 8 Loss of FCV-11158. Valve will Operator action to f ail FCV-1115B open by Standby (contd) flow control valve fail closed on loss of power, isolating instrument air at the doghouse, Equipment but will f ail open on loss of air, verify FCV-1115E closed, and control seal (contd) injection flow using manual valve located upstream. 1FQ107002-KB Remote valve control Damage to this circuit could cause a loss of positioner control, causing FCV-11158 and FCV-1115E to close or result in a loss of instrument air causing FCV-11158 to open. IGQ107077-KB Control signal Damage to this circuit could cause a loss of positioner control, causing FCV-11158 and FCV-1115E to close or result in a loss of instrument air causing FCV-11158 to open. FCV-1115C ----- Seal injection Loop C Loss of FCV-1115C. Valve will Operator action to fail FCV-1115C open by flow control valve fall closed on loss of power, isolating instrument air at the doghouse, but will fati open on loss of air. verify FCV-1115F closed, and control seal injection flow using manual valve located testream. 1FQ107003-KB Remote valve control Damage to this circuit could cause a loss of positioner control, causing FCV-1115C and FCV-1115F to close or result in a loss of instrument air causing FCV-1115C to open. 1HQ107078-KB Control signal Damage to this circuit could cause a loss of positioner control, causing FCV-1115C and FCV-1115F to close or result in a loss of instrument air causing FCV-1115C to open. GNI CV-532 ----- PORV nitrogen supply Loss of CV-532. Valve will Operator action to open manual oypass control valve fail closed. valve to provide nitrogen if P0HV or Diock valve operation is required. 1GD0220C5-KC Remote valve control Damage to this circuit could prevent remote operatien and/or cause the valve to spuriously open or close. Impell Corporation Report No. 01-0310-1435 YD-49 Revision 0

e g

                                                                     %J                                                                ,

10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATIGN FIRE AREA / ZONE l-YD-20-4C Dognouse Category System Component Circuit-Senedule Function Consequence of Fire Mitigation Ccid None Shutdown Equipment High/ Low CVCS CV-528 ----- Seal Water Return Loss of CV-528. Valve will fail None. CV-527 will remain available to Prsssure Isolation Valve closed, isolate seal water return. Interface 1GY2A36P4-KC Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously close. 1GY2909C7-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control, and/or cause the valve to spuriously close. Spurious CVCS CV-526 ----- Letdown Demineralizer Loss of CV526. Valve will f all None. CV-525 will remain available to Operation Isolation closed. 1solate letdown. Equipment 1GY2A36PS-KC Renote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously close. 1GY2909C6-KC Remote valve control Damage to tnis circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. s Impell Corporation Report No. 01-0310-1435 YD-50 Revision 0

             . . -      - ~ .           .       . ._           - - .                  . - .     ~.       . . -       ~              .    -.-                   .

4 O O O 10CFR50 APPENDIX R. SECTION"III.6 C0fFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-20-4C Doghouse Category- System' Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS FCV-1115D - - - - Seal Water Supply Valve Loss of FCV-11150. Valve will Operator action to verify FCV-1115D closed. - Operation (contd) -Loop A fati closed on loss of air, but - and verify FCV-1115A open. Equipment will fall open on loss of power. (contd) Damage to this circuit could i 1FQ107004-KB Remote valve control cause a loss of positioner i i control, causing FCV-1115A and ] FCV-1115D to close, or result  ; in loss of instument air causing FCV-11150 to fail closed. . t IG002050A-KC Remote valve control Damage to this circuit could prevent control of FCV-111bu I via the nitrogen supply ! system or the normal plant I instrument air system. 4 IGD 020508-KC Remote valve control Damage to this circuit could

prevent control of FCV-111bD , '

via the nitrogen supply system. i Control via the normal plant i O instrument air system would still be available. i 1G00205DC-KC Remote valve control Damage to this circuit could prevent control of FCV-11150 $ via the nitrogen supply 4 system or the normal plant instrument air system. 1 1GD020500-KC Remote valve control Damage to this circuit could {) prevent control of FCV-11150 via the nitrogen supply system. 1 Control via the normal plant ] instrument air system would ] I still oe available. t - 1G00205DE-KC Remote valve control Damage to this circuit could prevent control of FCV-11150 e via tne nitrogen supply system. -

'                                                                                Control via tne normal plant instrument air system would 1
                                                                               ' still oe availaole.                                                             -

j 1GD02050F-KC Remote valve control Damage to this circuit could prevent control of FCV-1115D

 '                                                                                via the nitrogen supply system.

Control via the normal plant instrument air system would 1 I still be available. Impell Corporation Report No. 01-0310-1435 YD-51 Revision 0 }

                                                                                                                                                         ,-l rx
           .U                                                           Q,-                                                                 (D.

10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA /2ONE 1-YD-20-4C - Doghouse ' Category System. Component Circuit-Schedule Function Consequence of Fire Nitiention Spurious CVCS FCV-1115E ----- Seal water supply Loss of FCV-1115E. . Valve will Operator action to verify FCV-111R closed. - Operation (contd) valve Loop 8 fait closed on loss of air, but . and verify FCV-11158 open. Equipment n will f ail open on loss of power. . (contd) . IFQ107005-K8 Remote valve contml Damage to tnis circuit could cause a loss of positioner control causing FCV-11158 , and FCV-1115E to close, or result in a loss of instrument air causing FCV-1115E to f ail - closed. 1G00205EA-KC Remote valve control Damage to this circuit could ,. prevent control of FCV-1115E via the nitrogen supply system or the normal plant instrument air system. 1G00205EB-KC Remote valve control Damage to this circuit could prevent control of FCV-1115E via the nitrogen supply system. Control via the normal plant instrument air system would still be available. IG00205EC-KC Remote valve control Damage to this circuit could prevent control of FCV-1115E via the nitrogen supply system or tne normal plant instrument air system. 1GUO205ED-KC Remote valve control Damage to this circuit could prevent control of FCV-1115E via the nitrogen supply system. ~ Control via the normal plant instrument air system would still be available. _ t_ L Impe11 Corporation Rtport No. 01-0310-1435 YD-52 Revision 0

O O O 10CFR50 APPENDIX R. SECTION lil.G CUWLIANCE EVALUATION - FIRE AREA / ZONE 1-YD-20-4C Doghouse Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS FCV-Ill5E IG00205EE-KC Remote valve control Damage to this circuit could - Operation.(contd) (contd) prevent control of FCV-1115E Equipment via the nitrogen supply system. Control via the normal plant - (contd) instrument air system would 2 still be available. IG00205EF-KC Remote valve control Damage to this circuit could prevent control of FCV-1115E via the nitrogen supply system. Control via the normal plant i instrument air system would 1 still be available. . FCV-1115F ----- Seal water supply Loss of FCV-1115F. Valve will Operator action to verify FCV-1115F closeo, valve Loop C f ati closed on loss of air, out and verify FCV-IllSC open. will fail open on loss of power. IFQ107006-K3 Remote valve control Damage to this circuit could

'                                                                         cause a loss of positioner control causing FCV-1115C and FCV-1115E to close, or result in a loss of instrument air causing FCV-1115F to fail closed.

l 1G00205FA-KC Remote valve control Damage to this circuit could prevent control of FCV-lll5F via the nitrogen supply system or the nonnal plant instrument air system. IG00205FB-KC Remote valve control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via the normal plant instrument air system would i still be available. i 4 M 1 1 i Impell Corporation Report No. 01-0310-1435 YD-53 Revision 0 l

O G (D1 m/ 10CFR50 APPEN0!X R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE l-YD-20-4C Doghouse C*tegrry System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS FCV-1115F 1G00205FC-KC ~ Remote valve control Damage to this circuit could Operation (contd) (centd) prevent control of FCV-lil5F Equipment via the nitrogen supply (contd) systee or the normal plant instrument air system. IGD 0205FD-KC Remote valve control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via the normal plant instrument air system would still oe available. 1GD0205FE-KC Remote valse control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via the normal plant instrument air system would still be available. 1GD0205FF-KC Remote valve control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via the normal plant instrument air system would still be available. Alternate None Shutdown Equipment Dedicated None Equipment /caole identifiers for dedicated Shutdown shutoown equipment will oe added unen as Equipment builts are availaole. Impe11 Corporation Report No. 01-0310-1435 YD-54 Revision 0

     .-                           - . .   .  . ..                   -       -                 .     .   . . . ~ -                     . . .     -      .-

10CFR50 APPENDIX R. SECTION 111.6 CurFLIANCE EWALUATION FIRE AREA / ZONE 1-YD-14-40 Yard Area Effects of Fire on Safe Shutdown Capapility A fire in this fire area / zone could result in the loss of the following portions of systems used to acnieve hot standby and , cold shutdown: 4 Reactor Coolant System (RCS)

                                                       -     Cables for the following components l

3

                                                             .        Pressurizer heaters Chemical and Voline Control-(CVCS) 5                                                       -     RWST isolation valve
                                                      --     Charging loop A flow transmitter
                                                        -    Reactor coolant ptsap seal water filter
                                                        -    Refueling water storage tann

! - Cables for the following components: I - RWST isolation valve l

  • Charging pumps and associated support equipment j
                                                             -        Charging RWST isolation valves
  • Charging loop A control valve

- - Seal injection flow control valves. l 4 Auxiliary Feedsater System (AFW)

                                                        -    Flow control valves i

4

                                                        -    Cables for the following components:

i - Motor driven auxiliary feedwater pump i

                                                             -        Steam driven auxiliary feedwater pump
                                                             -        Flow control valves i

Main Steam System (MSS) " - Cables for the following components:

                                                              -       Steam dump transfer control valve 1

{ 1 i Impe11 Corporation Report No. 01-0310-1435 YD-55 Revision 0 1

O td v LJ 10CFR50 APPENDIX R. SECTION III.G COPPLIANCE EVALUATION FIRE AREA / ZONE l-Y0-14-40 Yard Area i Component Cooling Water (CCW) j

                               -    . Component cooling water pumps
                               -     Component cooling water heat exchangers i
                               -     CCW heat excnanger isolation valves
                               -     CCh/RHR heat exchange flow control valves
                               -     CCW surge tans I                               -     Cables for the following components:
                                      -     Component cooling water pumps v
                                      -     CCW heat exchanger isolation valves
                                      -     CCW/RHR heat exchanger flow control valves               -

Saltwater Cooling System (SWC)

                               -     Cables for the following components:

i

                                      -    . Saltwater cooling pumps Gaseous Nitrogen System (GNI) 1                                                                                                     <

~

                               -     Nitrogen bottles i                               Essential Electrical Systess
                               -     Station Service Transformers 1

1

                               -      Cables for the following components:

i

- Station service transformers
                                      -      480V switchgear

' - 120V vital ouses j Tne dedicated shutdown system diesel generator, dedicated j shutdown panel, dedicated auxiliary feedwater pump and " associated equipment will be located in the northwest section of the yard area. a 4 Impell Corporation Report No. 01-0310-1435 Y D-56 Revision 0 m

          ,                                         p_                                       ,

j  ! e J G  % s/  % j' 10CFR50 APPEh0lX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA /Z0hE l-YD-14-40 Yard Area Tne fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet tne separation requirements of 10CFR50 Appendix R, Section III.G.2, in that area-wide suppression and detection systems are not provided. The substantial physical separation will allow the train 1480V electrical distribution system to remain available when the train 2 and train 3 station service transformers are damaged by fire. The train 2 and train 3 480V electrical distribution system will remain available when the train I station service transformer is damaged by fire. Operator action may be required to intertie the 480V switchgear to provide power to components on the redundant switchgear. The intertie cables are routed outside the fire area / zone. Operator action will be required to locally control certain valves required for hot standby located within the fire zone and outside of the fire zone. Damage to cables for charging ptmps G-8A and G-88 and their associated support equipment coulo result in the loss of redundant charing pungs. Cables for charging pep G-86 and its associated support equipment will be rerouted outside the fire area / zone, i Damage to caoles fur RWST isolation valve MuV-883 could cause the valve to spuriously close. Operator action will oe required to deenergize and manually open the valve, which is located within tne fire area / zone, to provide RWhT flow to tne charging pumps, after the fire has been extinguished. Damage to cables for charging RWST flow control valves MOV-11008 and MOV-11000 and volume control tank isolation i valve MOV-1100C could prevent flow to the charging pumps from 1 the RWST. Operator action will be required to deenergize and manually close MOV-1100C and open MOV-11008 or MOV-11000 to provide charging flow from the RWST and prevent cavitation of the charging pap when the volme control tank empties. Damage to cables for the seal injection flow control valves 1 could cause the valves to spuriously close. The interruption of seal injection, until operator action is taken to manually control the seal injection valves and provide charging flow

!                         from the RWST, has been analyzed and detennined to be 1                          acceptable (24,25).

i Damage to caoles for motor driven auxiliary feedwater pump G-105 and its associated disenarge control valve MOV-1202 could prevent tne remote operation of this equipment. Operator action will be required to manually start the pep at 480V switchgear 1, and to manually open or verify open MUV-1202. Impell Corporation Report No. 01-0310-1435 Yu-57 Revision 0

q q N) O. O 10CFR50 APPENDIX R SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D

                                                      . Yard Area Damage to cables for the auxiliary feedwater flow control valves, which are located within the fire area / zone, could cause the loss of remote valve control or cause the valves to fall open. Operator action will be required to manually control auxiliary feedwater flow using the manual valve

' located upstream or using the flow control valves after extinguishment of the fire. Damage to caoles for the component cooling water pumps could result in tne loss of the tnree redundant pungs. For a fire in this zone, the cnarging pumps will remain available. Therefore tne compoamt cooling water system will be required only to support reswual heat removal system operation. Cables for pianp G-15A will De wrapped and suppression / detection installed over tne component cooling water pumps. Snould a fire disable all component cooling water pumps, the

  • motor driven auxiliary feedwater pump G-10S (located outside the fire area / zone) may oe used for single-phase cooldown.

Damage to cables for redundant saltwater cooling pumps G-13A and G-138 may result from a fire in fire area / zone. Cables for the auxiliary saltwater cooling pump G-13C are routed in ent>edded conduit through this fire area / zone. The auxiliary saltwater cooling pump will remain available to support component cooling water system operation. The saltwater cooling system is not required to support single phase cooldown. Damage to cables for the temperature control valves for component cooling water flow to the residual heat removal heat exchangers could cause the loss of remote valve control or cause the valves to f all open. Operator action will be taken to locally control component cooling water flow if the residual heat removal system is used to achieve cold shutdown. Damage to cables for the reactor vessel head vent valves and pressurizer high point vent valves, which are routed tnrough this fire area / zone, could cause tne spurious actuation of the two redundant high/ low pressure interface valves in eacn line. Operator action will be required to operate disconnect 2 switches in the penetration area to deenergize and close valves to isolate these lines. Spurious actuation of tnese valves, until operator action is taken, has oeen analyzed, and will not result in unacceptable conditions (24, 25). l Impell Corporation Revision 0 Report No. 01-0310-1435 YD-58

CN r"N' m

                                                        \

10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION

                                              . FIRE AREA / ZONE 1-YD-14-40 Yard Area Damage to caoles for primary plant maxeup water control valve FCV-1102A could cae3e the valve to spuriously open, allowing
                  -            primary plant water to De supplied to the charging pump suction. Operator action will be required to close a manual valve located downstream, to isolate tnis line. Spurious actuation of the valve, until operator action is taken to close the downstream manual valve, has been evaluated, and detennined to be acceptable (27).

Damage to cables for boric acid supply control valves FCV-11028 and CV-334 could cause the valves to spurious 1.y open, allowing concentrated boric acid to be supplied to the charging pump suction. Operator action will be required to close manual valves to isolate these lines. Damage to cables for the charging safety injection isolation valves MOV-358 could cause the valve to spuriously open. Spurious actuation of this valve will divert flow from the seal injection flowpath to the charging safety injection flowpath. The effects of the spurious actuation have been analyzed. The analysis demonstrates that adequate flow will remain availaole for seal injection (28). An exemption request for the lack of area-wide suppression and detection systems will be provided per the requirements of Sections III.G.2 and III.G.3. Impe11 Corporation Report No. 01-0310-1435 YD-69 Revision 0

                                                                                                                                                                                               ,,m bp b,m                                                                      U
                                                                                           - 10CFR50 APPENDIX R SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D -

Yard Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus IC, IFA1C10P1-KB Power feed to station Loss of power to 480V The existing separation will allow the Standby Brkr 10 service transformer 1 switchgear 1 from station service train 1 480V electrical distribution to be Equipment (XO6) transformer 1 availaole when train 2 and train 3 elec-trical distribution systems are lost. The train 2 and train 3 480V electrical dis-tribution systems will be availaole when train 1 480V electrical distribution system is lost. Operator action may be required to intertie the 480V switchgear to provide power to components on the redundant train. The intertie caoles are routed outside the fire zone. Exemption for lacx of area-wide suppression / detection per III.G.2. Bus IC, 1WA1C11PI-K8 Power feed to station Loss of power to station service None. Train 1 or train 2 and 3 electrical Brkr 11 service transformer 3 transformer 3 and 480V distrioution systems will remain availaole. (XO8) switchgear 3. Bus 2C, 1GA2C10P1-KB Power feed to station Loss of power to station service None. Train 1 or train 2 and 3 electrical Brkr 10 service transformer 2 transformer 2 and 480V distribution systems will remain available. (XO7) switchgear 2 Bus 2C, 1GA2C15C1-KC Interlock to Breaker RY1 Damage to this circuit could Ncne. Train 1 or train 2 and 3 electrical Brkr 15 cause loss of remote breaker distribution systems will remain available, control and/or cause breakers 1A2C15 and RY1 to spuriously operate. IGA 2C1501-KC DC control power Loss of control power to RY1. 1XARY1C01-KC Power circuit breaner Damage to this circuit could trip mechanism cause loss of remote breaker i control and/or cause breaxers 1A2C15 and RY1 to spuriously l operate. 480V Station ----- Station service trans- Loss of station service trans- None. Train 1 or train 2 and 3 electrical Service former I former 1. distrioution systems will remain availaole. i trans-l former 1 Impe11 Corporation Report No. 01-0310-1435 YD-60 Revision 0

A o

           \_

10CFR50 APPENDIX R, SECTION III.G CO@LIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Cctegory Systen Component Circuit-Schedule . Function Consequence of Fire Mitigation Hot 480V Station ----- Station service trans- Loss of station service trans-- None. Train 1 or train 2 and 3 electrical former 2 former 2. distrioution systems will remain availaole. Standby (contd) Service Equipment Trans-(contd) former 2 Station ----- Station service trans- Loss of station service trans- None. Train 1 or train 2 and 3 electrical 4 Service former 3 former 3. distrioution systems will remain availaole. Trans-former 3 Swgr #1 1F BS102P2-KB Power feed from station Loss of power to 480V Swgr 1 None. Train 1 or train 2 and 3 electrical Brkr 02 service transformer 1 from station service trans- distribution systems will remain available. former 1. IFBS102P3-KB Power feed from station Loss of power to 480V Swgr 1 service transformer 1 from station service trans-fonner 1. < 1FBS102P4-KB Power feed from station Loss of power to 480V Swgr 1 1 service transforner i from station service trans-former 1. I 1FBS102PS-K8 Power feed from station Loss of power to 480V Swgr 1 service transformer I from station service trans-former 1.

  • Swgr #2 IG85202P2-KB Power feed from station Loss of power to 480V Swgr 2. None. Train I or train 2 and 3 electrical Brkr 02 service transformer 2 distrioution systems will remain availaole.

I IGBS202P3-K8 Power feed from station Loss of power to 480V Swgr 2. ' service transformer 2 1GBS202P4-KB Power feed from station Loss of power to 480V Swgr 2. . service transformer 2 1GBS202PS-KB Power feed from station Loss of power to 480V Swgr 2. service transformer 2 f Impe11 Corporation Report No. 01-0310-1435 YD-61 Revision 0

f t'} G V () 10CFR50 APPENDIX R, SECTION Ill.G COWLIANCE EVALUATich - FIRE AREA / ZONE l-YD-14-4D Yard Area Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 480V Swgr #3 IHBS303P6-KB Power feed from station Loss of power to 480V Swgr 3. None. Train 1 or train 2 and 3 electrical Standby (contd) Brkr 03 service transformer 3 distribution systems will remain available. Equipment j (contd) 1HBS305P7-KB Power feed from station Loss of power to 480V Swgr 3. service transformer 3 i lHBS303P8-KB Power feed from station Loss of power to 480V Swgr 3. service transformer 3 lHBS303P9-KB Power feed from station Loss of power to 480V swgr 3. service 'ransformer 3 MCC-2A 1XBS223P2-K8 Power Loss of power to MCC-2A will Ncne. Train 1 or train 2 and 3 electrical cause the loss of power tn the distrioution systems will remain availaole. following components required for g normal / alternate snutdown: MGBAF G-942 MG8uF MCC-3 1GBS314P2-Kb Power Loss of power to MCC-3 will None. Train 1 or train 2 and 3 electrical , cause the loss of power to distribution systems will remain availaole. the following components required for normal / alternate shutdown: MOV-883 MOV-850C a MOV-1100D

!                                                                                                                 Operator action to manually position f

120V Y29 IGYV29P2-KC Power Damage to this circuit could

'                                                                                cause the loss of power to       FCV-3300 and FCV-3301 will be required.

the following components Redi.ndant hot leg and stea.s generator required for normal / alternate level instrumentation will remain shutdown: available. LT-3400A TE-3402A FCV-3300 LT-34008 TE-3411A FCV-3301 LT-3400C TE-3421A CV-3201 SV-3200 SV-3204 SV-3203 SV-3205 SV-3214 SV-3202 SV-3211 CV-3213 YY-29/ 1GD021701-KC Power Loss of 125V DC power to Operator action to manually position inverter 5 Inverter b. FCV-3300 and FCV-3301 will be required. - Redundant not leg and steam generator i level instrumentation will remain availaole. t Impell Corporation Report No. 01-0310-1435 Y D-62 Revision 0

l

                         ~

10CFR50 APPENDIX R, SECTION III.G C0fFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Category System Component Circult-Schedule Function Consequence of Fire Mitigation IG85215P4-KB Power Damage to this circuit could None. Pressurizer heater group A or C will Hot RCS Pzr Standoy Heater cause the loss of power to at remain availaole. Equipment Group B least one of the neaters in the (contd) pressurizer heater group. Pzr 1GBS209P4-Ku Power Damage to this circuit coulo None. Pressurizer neater group A or C will Heater cause tne loss of power to at remain availaole. Group D least one of the heaters in the pressurizer heater group. IG85209PS-K8 Power. Damage to this circuit could cause the loss of power to at least one of the heaters in the pressurizer heater group. CYCS G-8A IGA 2C07Pl-XB Pcwer Loss of power to G-8A. None. G-88 will remain available. Cables for G-88 which are routed through the area are to be rerouted. G-88 1FAlC07P1-KB Power Loss of pow?r to G-88. Reroute cable for G-88 from fire area / zones 8, 9A, 4B, 40, 34, 2A to 8, 9A, 48, 4C, 35, 2A to resolve circuit routing concerns in fire area / zones 40 and 34. IXB2A16Cl-KB G-8A interlock Damage to this circuit could None. Cnarging pump G-88 and associated G-942 spuriously start the pump support equipment will remain availaole. when G-8A is not running, or prevent auto start of the punp wnen G-8A is started. 1XB2A14Cl-KB Fan control Damage to this circuit coula None. Charging pump G-88 and associated MG-8AF spuriously start tne fan or prevent support equipment will remain availaole. auto start of the fan. MG-8BF IWB2A15Cl-KB Fan control Damage to this circuit could Reterminate fan fG-8F at train 1 MCC. spuriously start the fan or prevent Route cable for new power supply in auto start of the f an, fire area / zones 8, 9A, 48, 4C, 35, 2A. MOV-11008 IF80147C2-KB MOV-Il00C open interlock Damage to this circuit could Operator action to deenergize and manually result in the loss of remote open MOV-11008 or MOV-11000. valve control, and/or cause the valve to spuriously close. Impell Corporation Revision 0 Report No. 01-0310-1435 YD-63

                                                                                                                                      ]'

n r~ ,. x 10CFR50 APPENDIX R, SECTION III.G COMPLIAhCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yaro Area Category System Component Circult-Schedule Function Consequence of Fire Mitigation Hot CVCS MOV-11000 lHB0378Pl-K8 Power Loss of power to MOV-11000. Operator action to deenergize and manually open MOV-11008 or MOV-Il000. Standby (contd) Equipment (contd) IHB0378Cl-KB -MOV-1100C open interlock Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously clou. lHB0378C2-KB Position switch / torque Damage to this circuit could switch feedback prevent remote operation and/or cause the valve to spuriously open er close. lHB0378C7-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. lHB0378C8-K8 Volume control tank Damage to this circuit could level interlock result in the loss of remote valve control, and/or cause the valve to spuriously close. MOV-883 ----- Reactor water storage Loss of MOV-883. Operator action to deenergize and manually tant isolation valve open MOV-883. lHB0390PI-KC Power Loss of power to MOV-883. lHB0390C2-KC Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control, and/or cause the valve to spuriously close. 1HB0390C5-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control. The valve will fall as is, normally open. lHB0390C8-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control. The valve will fail as is, normally open. Impell Corporation Report No. 01-0310-1435 YD-64 Revision 0

('O p (. N.- 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE l-YD-14-40 Yard Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation FCV-1112 SV-1112 positioner Damage to this circuit could Operator action to close manual valves Hot CVCS IFQ107037-KB override solanoid result in the loss of valve located upstre.?ra of FCV-1112 if charging Standby (contd) Equipment control por control through SV-lll2 and through the~ seal injection flowpath. For cause tne valve to spuriously higher makeup flow rates through charging (contd) loop A, operator action will ne required open. ' to manually override and open FCV-1112. FT-1112 ----- Charging loop A flow Loss of FT-1112. Operator action to close manual valves transmitter located upstream of FCV-1112 if charging 1 througn tne seal injection flowpatn. For higner makeup flow rates through cnarging loop A, operator action will be required to manually override and open FCV-1112. 1FQ107103-KB Sensor signal Damage to this circuit could result in erroneous indication of charging flow rate and cause spurious }' operation of FCV-1112. 7 FCV-Ill5A IFQ107076-KB Control signal Damage to this circuit could cause Operator action to fall open FCV-Ill5A by a loss of positioner control, isolating instrument air at the doghouse, causing FCV-1115A and FCV-11150 to verify FCV-11150 closed, and control seal j close or resu't in a loss of injection flow using manual valve located instrument ali, causing FCV-Ill5A upstream.

'                                                                                to f all open.

1 i FCV-1115B IGQ107077-KB Control signal Damage to this circuit could cause Operator action to fail open FCV-II158 by a loss of positioner control, isolating instrument air at the dognouse, causing FCV-11158 and FCV-1115E to verify FCV-1115E closed, and control seal close or result in a loss of injection flow using manual valve located instrument air, causing FCV-11158 upstream. to f ail open. FCV-1115C IHQ107078-KB Control signal Damage to this circuit could cause Operator action to fail open FCV-1115C Dy a loss of positioner control, isolating instrument air at the dognouse, causing FCV-1115C and FCV-1115F to verify FCV-1115F closed, and control :::! close or result in a loss of injection flow using manual valve located instrument air, causing FCV-1115A upstream.

'                                                                                 to f all open.

i Impell Corporation Report No. 01-0310-1435 YD-65 Revision 0

n O r3 10CFR50 APPENDIX R, SECTION III.G C0ffLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Cetegory System Component Circuit-Schedule Function Consequence of Fire Mitigation C-42 ----- Pr..ctor coolant pump None. None. Hot CVCS Standby (contd) seal water filter i Equipment (contd) Reactor coolant pump None. C-425 ----- None. seal water filter D-1 - - - - Refueling water storage None. Kone. i tank SV-175 control Damage to this circuit could No effect on norma' control of steam dump , MSS SV-175 1GY2A30C1-KB cause a loss of powr to SV-175, valves.

'                                                                              preventing transfer of steam dump 1

control to C-38. i AFW G-105 1FBS125C8-KC MOV-1202 interlock Damage to this circuit could Operator action to manually start pump prevent operation of G-105 and G-10S at 480V switengear 1. 1 MUV-1202 from panel C-71. Operation of G-105 via handswiten at panel ' C-38 would not oe affected. G-10S/ IFBS125C9-KC 125VDC power, remote Damage to tnis circuit could Operator action to manually start pump i MOV-1202 control, and indication spuriously start the pump and/or G-10S at 480V switchgear I and verify j MOV-1202 open. Loss of auxiliary cause MOV-1202 to spuriously open. i Operation of the pump at panel feedwater flow, until the operator action l

 '                                                                             C-38 would be prevented.              is performed, has been analyzed and determined to be acceptaDie (24,25).

j MOV-1202 1 M 137PI-KC Power Loss of power to MOV-1202. Operator action to manually open MOV-1202. Loss of auxiliary feedwater

   '                                                                                                                 flow, until the operator action is performed, has been analyzed and 4

determined to be acceptable (24,25). I i 1FB0137C1-KC Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. i i Impell Corporation Revision 0 Report No. 01-0310-1435 Yu-66

h. ^\

{ LJ . 10CFR50 APPENDIX R SECTION III.G C0fFLIANCE EVALUATION ' FIRE AREA / ZONE 1-YD-14-4D Yard Area Categnry System Component Circuit-Schedule Func tion Contequence of Fire Mitigation Hot AFW CV-3201/ 1GY2906CH-KC Position switch Damage to this circuit could None. G-105 will remain available. Staney (contd) SV-3205 feedback prevent SV-3205 from being opened Equipment when CV-3201 opens, or allow CV-3205 and CV-3205 to open l (contJ) simultaneously. Damage to this 4 circuit could result in the loss of remote valve control and/or cause valve CV-3201 to I spuriously close and cause valves SV-3200, 02, 03, 04, 05,11, 14, ' and CV-3213 to spuriously open. 4 SV-3200-05, IGY2906C6-KC Valve position Damage to this circuit could Mone. G-105 will remain availaole. 11, 13, 14 indication result in erroneous of valve i position indication, out would not affect valve operation. 1GY2906CC-KC Solenoid control power Damage to this circuit could prevent remote operation and/or spuriously open CV-3201 and I close SV-3200, 02, 03, 04, 05, t 11,14. and CV-3213, or close CV-3201 and open SV-3200, 02, 03, 04, 05,11,14 and CV-3213. SV-3201, 1G12906C5-KC Valve position Damage to this circuit could None. G-105 wtII remain available. 02, 03, 04 indication result in the loss of remote valve control and/or cause SV-3200, 02, 03, 04, 05,11,

14. and CV3213 to open and
CV3201 to close.

1 J FCV-2300 Auxiliary feedwater to Loss of FCV-2300. Valve will Operator action to manually control auxili-steam generator A flow f ail open. ary feedwater flow using FCV-2300 or manual i

;                                                  contrnt valve                                                 valve located upstream.

IFY3315IS-KC Positioner control Damage to this circuit could I result in the loss of renote l valve control, and/or cause tne valve to spuriously open. i Impe11 Corporation Report No. 01-0310-1435 YD-67 Revision 0

a

                                                                                                                                                      )

10CFR50 APPENDIX R SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-40 Yara Area Category System Component Circuit-Schedule Function Consequence of Fire nitigation Hot AFW FCV-2301 ---- Auxiliary feedvater to Loss of FCV-2301. Valve will Operator action to manually control aux 111-Standby (contd) steam generator t$ flow fail open, ary feeowater flow using FCV-2301 or manual Equipment control valve valve located upstreas. (contd) ' IFY331519-KC Positioner control Damage to this circuit could result in the loss of remote 4 valve control, and/or cause the valve to spuriously open. FCV-3300 ----- Auxiliary feedwater to _ Loss of FCV-3300. Valve will fail Operator action to manually control aux 111-steam generator C flow open. ary feedvater flow using FCV-3300 or manual control valve valve located upstream. 1 1GY29061G-KC Positioner control Damage to this circuit could

'                                                                             result in the loss of remote valve control, and/or cause the i                                                                              valve to spuriously open.
FCV-3301 ----- Auxiliary feedwater to Loss of FCV-3301. Valve will fail Operator action to manually control auxili-steam generator 8 flow open. ary feeevater flow using FCV-3301 or manual i valve located upstream.

control valve i;! 1 1GY29061H-KC Positioner control Damage to this circuit could i result in tne loss of remote 1 valve control, and/or cause the I valve to spuriously open. j CCW G-15A ---- Component cooling water For a fire in tnis zone, seal injection pump flow will remain availaole. Therefore, j CCW will only oe required to support RHR j system operation. Wrap power cables to G-15A and install suppression / detection I locally 5ver the CCW pumps and redundant cabling and request exemption for lack of area-Wiue suppression / detection and pump f separation. Alternately, auxiliary feedwater pump G-105 may be used for j and request single phase exemption forcooldown, lack of aTe'a-wide 4 suppression / detection per III.G.3. j 1F85121P2-KB Power Loss of power to G-15A. i i 1 i

 )

l Impe11 Corporation Report No. 01-0310-1435 YD-68 Revision 0 I

                                                                          \%                                                        Tj,.

10CFR50 APPENDIX R, SECTION !!!.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-40 Yard Area Consequence of Fire Mitigation Cxtegory System Component Circuit-Schedule ' Function Component cooling water See G-15A above. Hot CCW G-158 ---- pump Staney (contd) Equipment 1GBS221P2-K8 Power Loss of power to G-158. (contd) Component cooling water See G-15A above. G-15C . pump 1HB0305P2-K8 Power Loss of power to G-15C. , Component cooling water None. MOV-720A or MOV-720s is maintained MOV-720A - - - - normally open. heat exchanger E-20A outlet isolation valve 1GU028BPl-K3 Power Less of power to MOV-720A. P IGB0288Cl-Ku Position switch /to que Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f all as is. MOV-7208 ----- Component cooling water None. MOV-720A or MOV-7208 is maintained heat exchanger E-208 nonnally open. outlet isolation valve 1FB0187PI-KB Power Loss of power to MOV-7208. 1FB0187Cl-KB Position switch / toque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f ail as is. None, C-17 ----- Component cooling water None. surge tank Impell Corporation Revision 0 Report No. 01-0310-1435 YD-69

i A ,A ex

                                                                                                                                                              =
                                             -10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Consequence of Fire                                              Mitigation Category System Component Circuit-Schedule Function Component cooling water           None.                         None.

Hot CCW E-20A ----- Standby (contd) heat exchanger E-20A Equipment ts~r'd) Component cooling water None. None. E-208 ----- heat exchanger E-206 1F85114P2-K8 Power Loss of power to G-13A. None. Auxiliary saltwater cooling pump SWC G-13A G-13C will remain availaole to support component cooling water system operation. The saltwater cooling system is not required to support single phase cooldown. 1F8Sil4C4-KB Discharge header low Damage to this circuit pressure interlock could prevent remote operationof the pump, or spuriously stop G-13A or spuriously start G-138. IGBS214P2-K8 Power Loss of power to G-138 None. Auxiliary saltwater cooling pump G-138 G-13C will remain available to support ' component cooling water system operation. l' The saltwater cooling system is not required to support single phase cooloown. 1GBS214C4-Ku Discharge header low Damage to tnis circuit could pressure interlock prevent remote operation of the planp, or spuriously stop G-138 or spuriously start G-13A. Impell Corporatien Revision 0 Report No. 01-0310-1435 YD-70

O O O 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION rIRE AREA / ZONE l-YD-14-4D Yard Area Category System Component Circuit-Schedule Function Consequence of Fire Mittention C-1036 Nitrogen bottle for None. None. Hot GNI ---- Standby SV-3213, SV-3101 Equipment (contd) None. C-1037 --- Nitrogen bottle for None. SV-3213, SV-3101 C-1038 ---- Nitrogen bottle for None. None. CV-545, CV-546 C-1039 --- Nitrogen bottle None. None. for CV-545, CV-546 C-1040 ---- Nitrogen bottle for None. None. FCV-2300, 2301, 3300, 3301 C-1041 Nitrogen bottle for None. None. FCV-2300, 2301, 3300, 3301 C-1042 ---- - Nitroge bottle for None. None. FCV-2300, 2301, 3300, 3301 C-1043 ---- Nitrogen bottle for Mone. None. FCV-2300, 2301, 3300, 3301 Impell Corporation Report No. 01-0310-1435 YD-71 Revision 0

       %                                                            x                                                                 q) 10CFR50 APPENDIX R. SECTION III.G CapFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Crtegory System Component Circult-Schedule Function                         Consequence of Fire                    Mitt ention C-1044                 Nitrogen bottle for          Mone.                           None.

Hot GN! ---- Standby (contd) FCV-2300, 2301, 3300, Equipment 3301 (contd)

  • C-1045 Nitrogen bottle for Mone. None.

FCV-2300, 2307, J300, 3301 C-1046 ---- Nitrogen bottle for None. None. FCV-2300, 2301, 3300, 3301 C-1047 -- - Nitrogen bottle for None. None. FCV-2300, 2301, 3300, 3301 C-1234 - - - - Nitrogen supply for None. None. thru CV-113 C-1213 Cold CCW TCV-601A Control valve for CCW Loss of TCV-601A. Valve will If required, operator action to verify Shutdown flow to Rift heat f all open. valve position and control flow Equipment excnanger E-21A using manual valve located downstream. 1FQ106010-KB Valve position feedback Damage to this circuit could result in the loss of valve position indication. 1FQ106011-K8 Control signal Damage to tnis circuit could result in tne loss of remote valve control, and/or cause the valve to spuriously open. Impe11 Corporation Revision 0 Report No. 01-0310-1435 YD-72

                                           ~            _       ._.    . .               .             ..

(~ im _ 10CFn50 APPEh0lX N, SECTION III.6 COMPLIANCE EVALUATION ' FIRE AREA / lone 1-Yo-14-4D Yaro Area Consequence of Fire Mitigation i Crtegory System Component Circult-Schedule Function 4 TCV-6018 Control valve for CCW Loss of TCV-6018. Valve will If required, operator action to verify Cold CCW - - - - valve position and control flow Shutdown (contd) flow to RHR heat fail open. exchanger E-218 using manual valve located downstream. Equipment (contd)

  • Valve position feedback Damage to this circuit could IGQ106012-KB result in the loss of valve position indication.

1GQ106013-KB Control signal Damage to this circuit could [ ' result in the loss of remote valve control, and/or cause the ' valve to spuriously open, i Solenoid control power Damage to this circuit could Operator action to close SV-3402 will High/ Low RCS SV-3401 1GY3005CA-KC Pressure result in the loss of remote isolate this line. Interface valve control, and/or cause the valve to spuriously open. 1 1 SV-3401/ IGY3005CI-KC solenoid control power Dsaage to this circuit could Install disconnect switen for sv 3402 SV-3402 result in the loss of remote at tne penetration area. Spurious valve control, actuation of tne vent valves, until j operator action is taKen to deenergize Solenoid control power Damage to this circuit could and close SV-3402, has oeen analyzed and IGY3005CJ-KC will not result in an unacceptaole prevent remote operation and/or cause the valve to spuriously condition (24, 25). open or close. ) i SV-3402 1GY3005CB-KC Solenoid control power Damage to this circuit could Install disconnect switch for SV-3402 , result in the loss of remote at the penetration area. Spurious i valve control, and/or cause the actuation of the vent valves, until valve to spuriously open. operator action is taken to deenergize i and close SV-3402, has been analyzed and will not result in an unacceptable ' condition (24, 25). l l i i i _ l j Impe11 Corporation Revision 0 Report No. 01-0310-1435 Y0-13 i '

m ,m em 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4D Yard Area Category System Component- Circuit-Schedule Function Consequence of Fire Mitigation High/ Low RCS SV-3403 1GY3005CC-KC Solenoid control power' Damage to this circuit could Operator action to close SV-3404 will Pressure (contd) result in the loss of remote isolate this line. Ixterface valve control, and/or cause the (contd) valve to spuriously open. SV-3403/ IGY3005CK-KC Solenoid control power Damage to this circuit could Install disconnect switen for SV-3404 SV-3404 result in the loss of remote in tne penetration area. Spurious valve control. actuation of tne vent valves, until operator action is tanen to deenergize 1GY30050.-KC Solenoid control power Damage to this circuit could and close SV-3404, has oeen analyzed, prevent remote operation and/or and will not result in an unacceptacle cause the valve to spuriously condition (24, 25). open or close. SV-3404 1GY3005CD-KC Solenoid control power Damage to this circuit could Install disconnect switch for SV-3404 result in the loss of remote in the penetration area. Spurious valve control, and/or cause the actuation of the vent valves, until valve to spuriously open. operator action is taken to deenergize and close SV-3404, has been analyzed, and will not result in an unacceptable condition (24, 25). CVCS CV-528/ 1GY2A36P1-KC Power Damage to this circuit could None. CV-527 and CV-525 will remain CV-526 result in the loss of remote available to isolate seal water and valve control, and/or cause letdown flow. the valves to spuriously Close. Impe11 Corporation Report No. 01-0310-1435 YD-74 Revision 0

(" m

       &                                                              \

v h 5v). 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-Y0-14-40 Yard Area Category Systen Component Circuit-Seneoule Function Consequence of Fire Mitigation Spurious CVCS G-42 1He2A10Cl-K8 Remote pop control Damage to this circuit could Operator action to deenergize the pop. Operation (contd) and indication spuriously start the pump and/or. Equipment prevent remote operation. 1HB2A10C2-KB ' Local pump control Damage to this circuit could spuriously start the pap and/or prevent remote or local operation. CV-334 1FQ107033-KB Solenoid control power Damage to this circuit could Operator action to close manual valve prevent remote operation and/or located upstream, cause the valve to spuriously open or close. FCV-1102A 1WQ107007-KB Solenoid control power Damage to this circuit could Operator action to close manual valve prevent remote operation and/or located downstream of FCV-1102A. Spurious cause the valve to spuriously actuation of the valve, until operator upen or close, action is taken to close tne manual valve downstream, nas oeen evaluated and detenained to De acceptaole (27). i FCV-1102b swQ107009-KB Solenoid control power Damage to tnis circuit could Operator action to close manual valve prevent remote operation and/or located downstream of FCV-1102A. cause the valve to spuriously open or close. Impe11 Corporation Report No. 01-0310-1435 Yu-75 Revision 0

n U 'J 10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE l-YD-14-40 Yard Area Crtegory Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS MOV-1100C 1G80147C9-K8 MOV-11008 open interlock Damage to this circuit could Operator action to deenergize and manually Operation (contd) prevent remote operation and/or close MOV-Il00C. Equipment cause the valve to spuriously (contd)

                                 #                                      open or close.

1GB2A76C2-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. IGu2A76C3-KB Volume control tant Damage to tnis circuit could level interlock prevent remote operation and/or cause the valve to spuriously open or close. 1GB2A76C4-KB MOV-11000 open interlock Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. AFW MOV-1204 IFB0127PI-KC Pwer Loss of power to MOV-1204 None. IF80127Cl-KC Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f all as is, normally closed. CRS G-27N Refueling water ptsep - Loss of G-27N. None. north IFBS119P2-K8 Power Loss of power to G-27N. Refueling water pump - Loss of G-275. None, G-27S soutn IGBS219P2-Ks Power Loss of power to G-275. SIS MOV-357 IG80243Pl-K8 Power Loss of power to MOV-357. None. IG80243C2-K8 Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will fall as is, normally closed. Impell Corporation Revision 0 Report No. 01-0310-1435 YD-76

() V \,s 10CFR50 APPENDIX R SECTION III.G COW LIAhCE EVALUATION FIRE AREA / ZONE 1-YD-14-40 Yard Area C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation . Spurious SIS MOV-358 1Hu0385P1-K8 Power Loss of power to MOV-358. None. Spurious actuation of this valve will divert flow from the seal injection Operation (contd) Equipment flowpatn to the charging safety in,)ection flowpath. The effects of the spurious (contd) actuation have Deen analyzed. Tne analysis demonstrates that adequate flow will remain availaole for seal injection (28). 1HB03850-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open, iHB0385C2-K8 Positinn switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f ail as is, normally closed. Alternate SWC G-13C INBS313P1-K8 Power Loss of power to G-13C Mone. Cables for G-13C are routed in Shutoown escedded conduit throughout the fire Equipment area / zone. G-13C will remain availaole. INBS313C3-K8 Priming syste.n control Damage to this circuit coulo prevent remote operation of the pianp. IN85313C4-K8 Priming system control Damage to this circuit could prevent remote operation of the pianp, or cause the puno to spuriously stop. SIS G-50A - - - - Safety injection pump Loss of G-50A. None. Charging system will remain available. 1GA2C05PI-K8 Power Loss of power to G-50A. G-508 ----- Safety injection pump Loss of G-508. None. Charging systen will remain available. IFAIC05P1-KB Power Loss of power to G-508. Impe11 Corporation Report No U1-0310-1435 YD-77 Revision 0

d(~ bM .Cm ,

                                           .10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE l-YD-14-4D Yard Area Cttegory System Component Circuit-Schedule Function                          Consequence of Fire                      Mitigation Alternate SIS        MOV-0508 1G80180Pl-K8   Power                       Loss of power to Mot-8508.        None. ' Charging system will remain-Shutdown    (contd)                                                                                        available.

Equipment (contd) 1G80180C9-K8 Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f ail as is, normally closed. GNI C.1030 - - - - Nitrogen supply for None. None.' Charging system will remain thru Train A SIS valves availaole. C-1032 C-1033 ---- Nitrogen supply for None. None. Charging system will remain tnru Train 8 SIS valves available. C-1035 Dedicated 120V C-38 IGY2A30PI-K8 Power D mage to this circuit could No effect on normal shutdown systems. Shutdown cause loss of power to auxiliary Equipment shutdown panel instruments and prevent transfer of steam dump control through SV-175 to the auxiliary shutdown panel C-38. RCS LT-430A IGQ300002-K8 Sensor signal Damage to this circuit could None. Control room instrumentation will result in high off-scale, low remain available. off-scale, or erroneous indication. PT-434A 1GQ300001-K8 Sensor signal Damage to this circuit could None. Control room instrumentation will result in high off-scale, low remain available. off-scale, or erroneous indication. TE-402u IGQ300006-Ku Sensor signal Damage to this circuit could None. Control room instrumentation will result in nign off-scale, low remain availaole, off-scale, or erroneous indication. Impell Corporation Revision 0 Report No. 01-0310-1435 YD-78

m m e

                                                                                                                                 /-.

10CFR50 APPENDIX R SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-40 Yard Area Consequence of Fire Mitigation Category System Component Circuit-Schedule Function Dedicated RCS TE-4125 1GQ300007-K8 Sensor signal Damage to tnis circuit could None. Control room instrumentation will $nutdown (contd) result in hign off-scale, low remain availaole. Equipment off-scale, or erroneous (contd) indication. TE-4228 IGQ30000B-K8 Sensor signal Damage to this circuit could None. Control room instrumentation will result in high off-scale, low ~ remain available, off-scale, or erroneous indication. MSS LT-450C 1GQ300003-KB Sensor signal Damage to this circuit could None. Control room instrumentation will result in high off-scale, low remain available. off-scale,or erroneous indication. LT-451C 1GQ300004-KB Sensor signal Damage to this circuit could None. Control room instrimentation will result in high off-scale, low remain available, off-scale,or erroneous indication. LT-452C 1GQ300005-K8 Sensor signal Damage to this circuit could None. Control room instrumentation will result in nign off-scale, low remain availaole, off-scale,or erroneous indication. Impell Corporation Report No. 01-0310-1435 YD-79 Revision 0

O O C~%) f~d1 10CFR50 APPEhDIX R, SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-(-7)-4E Circulating Water Pump Well Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the - following portions of systems used to achieve hot standby and cold shutdown: Saltwater Cooling System (SWC)

                                            -    Saltwater cooling pimps
                                            -    Cables for the following components:
                                                  -     Saltwater cooling pumps The fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendix k.

Section III.G.2. Tne auxiltary saltwater cooling pump, which is located outside the fire area / zone, will oe used as an  ; alternate for saltwater cooling system operation per Section III.G.3. An exemption request for the lack of area-wide suppression and detection systems, per tne requirements of Section III.G.3, will be provided. 1 l i l i i i e l t I , I i l Impe11 Corporation Report No. 01-0310-1435 YD-80 Revision 0 i ___ _ _ ._

(m Y  %) 10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-(-7)-4E Circulating Water Pap Well Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot SWC G13A ----- Saltwater Cooling Puep Loss of G-13A. None. Auxiliary saltwater pump G-13C will Standby remain avallanle. Exemption required Equipment for lact of area wide suppression / detection. 1F85114P2-Kn Power Loss of power to G-13A. 1FuS114C7-KB Service water control Damage to tnis circuit could valve interlock cause loss of control power to SV-81, tne service water control valve. 1FBS114C4-KB Discharge header Damage to this circuit could pressure interlock prevent remote operation of of the pump, or spuriously stop G-13A or spuriously start G-138. G138 - -- Saltwater Cooling Pump Loss of G-13B. None. Auxiliary saltwater pump G-13C will remain available. 1GBS214P2-KB Power Loss of power to G-138. 1GBS214C7-K8 Service water control Damage to this circuit could valve interlock cause a loss of control power to SV-82, the service water control valve. 1GBS214C4-KB Discharge header low Damage to this circuit could pressure interlock prevent remote operation of the pump, or spuriously stop G-13d or spuriously start G-13A. Cold None Shutdown Equipment High/ Low None Pressure Interface Impe11 Corporation Report No. 01-0310-1435 YD-81 Revision 0

    ..-.. - . - - .. - - ..                       . - - . - .. . . . . . .-. .~. - . . - .        _ . . . .-._.-_ _....-.       , , ~ . ..  - - - .,, .-        . ..

T i $ 10CFk50 APPENDIX R. SECTION III.S CUWLIANCE EVALUATION I FIRE AREA /20hE l-YD-(-7)-4E j Circulating Water Pesep Well i i Category- System Component Circuit-Schedule Function Consequence of Fire Mittention k

 !                       Spurious None Operation I'                       Equipment                                                                                                                                                   -

I t Alternate None f Shutdown Equipment Dedicated None ) Shutdown Equipment I u u I 1 i t I i i I t p i i i Impe11 Corporation Nevision 0 - Report No. 01-0310-1435 YD-82 j  ; 'I . - -. - - m _. . - - - - . - -

("% sq ,., 10CFR50 APPENDIX R. SECTION III.G C0fFLIANCE EVALUATION FIRE AREA / ZONE l-YD-(14)-4F Condensate Storage Tank Area Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the following portions of systems used to achieve hot standby and cold shutdown: Chemical and Volume Control (CVCS)

                                -     Caoles for tne following components:
  • RWST cnarging isolation valve Essential Electric Systems
                                -     Cables for the following components:
                                      -     4160V buses
  • Motor control center 3 The fire protection features provided for the protection and separation of safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendix R.

Section III.G.2. Damage to control cables for offsite power to 4160V buses 1C and 2C could prevent remote control of the offsite power breakers. Operator action may be required tc manually trip the offsite power supply breakers in the 4160V switchgear room, and close the diesel generator bus supply breakers, if required to energize the 4160V buses from the diesel generator. Damage to cables for voltme control tank isolation valve MOV-1100C could cause tne valve to remain open, preventing flow to the charging pimps from the RWST. Operator action will be required to manually clo,e MOV-1100C to prevent charging pump cavitation as tne volume control tanz empties. An exemption request for tne lack of area-wide suppression / .i detection per tne requirements of Section III.G.3 will oe provided, l 1 1 4 l Impell Corporation Revision 0 Report No. 01-0310-1435 YD-83 l 1

t' (O [m,' C')

                                                                             \

V 10CFR50 APPENDIX R, SECTION III.G C0FFLIANCE EVA:. CAT!0N FIRE AREA / ZONE l-Y0-14-4F Condensate Storage Tant Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus IC, llARX1C01-KC Control circuit PCB Damage to tnis circuit could Operator action to manually trip breater Standby Brkr 14 trip mechanism cause a loss of remote breaker RXI and close breaker llc 14, if required to Equipment control, and spuriously trip the energize 4160V dus IC from diesel breaker. generator 1. 1FAIC14Cl-KC Breaker lAIC14 and RX1 Damage to this c'rcuit could 1 interlock cause loss of remote breaker 1 control, or could trip bypass

                                                                         ' breaker RXI or close breaker 11C14.

IFAICl4DI-KC DC control power RXI Damage to this circuit could bypass breaker trip. result in the loss of ability to trip the breaker. Eus 2C, IXARYlC01-KC Control circuit PC8 Damage to this circuit could Operator action to manually trip breater Brkr 15 trip mechanism cause a loss of remote breaker RY1 and close breaker 12C15, if required to ] ' control, or spuriously trip energize 4160V Bus 2C from diesel bypast RY1 or close breaker generator 2. i 12C15. t l IGA 2C15Cl-KC Auxiliary transformer Damage to this circuit could

interlock cause a loss of remote
breamer control', and/or cause one or Doth of the breakers

' to spuriously close.

IGA 2C1501-KC Remote breaker control Loss of control power to RYl.

l 480V MCC #3 1GBS314P2-K8 Pc,wer Loss of power to MCC-3 will None. Valves fall on loss of power to the result in the loss of power to position required for safe shutdown. the following components required for normal / alternate shutdown: I MOV-Il00D MOV-850C MOV-883. l i i Impell Corporation Report No. 01-0310-1435 YD-84 Revision 0

                                                                               /m                                                               /~.

k. 10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4F f' Condensate Storage Tank Area Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS MOV-11000 1H80378P1-K8 Power Loss of power to MOV-11000. None. MOV-11008 will remain available. Staney Eqxiprent 1H80378C1-K8 MOV-1100C open interlock Loss of power to MOV-11000. (contd) Damage to this circuit could .; result in the loss of remote valve control, and/or cause the 4 valve to spuriously close.

IH00378C2-K8 Position switch / torque Damage to this circuit could switch feedback prevent remote operation and/or -

cause the valve to spuriously open or close. 1H80378C7-K8 Remote valve control Damage to this circuit could prevent remote operation and/or ' cause the valve to spuriously open or close. 1H80378C8-KB Volume control tank Damage to this circuit could level interlock result in the loss of remote

  • valve control, and/or cause the
valve to spuriously close.

i Cold None Shutdown Equipment ] l High/ Low None . Pressure ~ Interface 3 i { -- 1 1 I l, Itpell Corooration Report No. 01-0310-1435 YD-85 Revision 0

b d d 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-14-4F

  1. Condensate Storage Tank Area Category System Component Circuit-Schertule Function Consequence of Fire Mitigation 2

Spurious CVC5 MOV-1100C 1Gd2A76C4-K8 MOV-11000 open interloct Damage to tnis circuit coulo Operator action to oeenergize and manually Operation prevent remote operation and/or close MuV-1100C. Equipment cause the valve to spuriously open or close. 1 SIS M0V358 IH90385PI-K8 Power Loss of power to MOV-358. None. Cnarging system will remain available. 1H00385C1-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open. 1H90385C2-Kel Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will f all as is, nomally closed. Alternate None Shutdown Equipment Dedicated None Snutdown Equipment l 1 i l 4 i Impell Corporation Revision 0 Report No. 01-0310-1435 YD-86

1 :-

l. 10CFR50 APPENDIX R. SECTIull III.6 COMPLIANCE EVALUATIch l FIRE ANEA/ ZONE 1-YD-7-21 '

Pass Process Cow artment i  ! Effects of Fire on Safe Shutdown Capability  ! ' The design basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe j shutdown components or cables in the fire area / zone. . I 1 i I i l l }

I i

i i i I 1 1 I ,i i } I i I 1 4 i i t 1 i Impe11 Corporation Report No. 01-0310-1435 YD-87 , Revision 0 ]

a 10CFR50 APPENDIX R SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-YD-7-27 Pass Process Compartment Category System Component Circuit-Schedule Function Consequence of Fire Mitigation ) , Hot None Standby j Equipment i i l . Cold None i i Shutdown 1 Equipment ! High/ Low None a Pressure 4 Interface i 1, '. Spurious None i j Operation l Equipment Alternate None i Shutdown j Equipment 1 j Dedicated None I t Shutdown Equipment j i p i i !~ i l  ! s j Impe11 Corporation Report No. 01-0310-1435 YD-88 Revision 0 l I _ __ .- . . -. .- _ _ . - .

_ . . _ . . .. . _ . . _ . . . . . . _m. . . . 10CFR50 APPEhDIX R, SECTION til.G C0ffLIANCE EVALUATION . i FIRE AREA /20hE l-YD-7-28 ' Pass Control Compartment , i i 1 Effects of Fire on Safe Shutdown Capao111ty i The design basis fire will not affect the capability to 4 achieve and maintain cold shutdown, as there are no safe 1 shutdown components or cables in the fire area / zone. 1 l 4 i i ! t i i l I 4 e 4 l t i i } 1 g i l 1 l 1 l

  • I l 3

j-i f l 4

}  Impell Corporation                                                                                            Nevision 0 Report No. 01-0310-1435                                               Yu-89 j

l

                                                                                                                                          't 4

10CFR50 APPENDIX R. SECTION III.G C0FFLIANCE EVALUATION FIRE AREA / ZONE 1-YD-7-28 ' ,

                                                             . Pass Control Compartment
Category System Component Circult-Schedule Function- Consequence of Fire Mitigation L Hot None Staney .

Eculpme'it 5 ^ Cold None

Shutdown l Equipment 9,
High/ Low None Pressure j

i Interface g I g Spurious None Operation j Equipment J i

Alternate None
. Shutdown                                                                                                                                  ,

Equipment '.i l Dedicated None Shutdown Equipment l  ! l ( i i 1 l , i i 1 1 i j

s 3 i 1

i Impell Corporation Report No. 01-0310-1435 YD-90 Revision 0

s A

                                                              )

10CFR50 APPENDIX R. SECTIL-dI.G CtWLIAKE EVALUATION FIK ASEA /70NE 1-FN-2-5 Spent Fuel Storage Room  ; i Effects of Fire on Safe Shutdown capability The design basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe

shutdown components or cables within the fire area / zone.

-l i 1 i r 4 4 9 i a 1 4 i I l 1 4 i i I .l i }. i l 1 i Impe11 Corporation .

 ]   Peport No. 01-0310-1435                      FH-1                                     Revis1on 0 t

i

(" 10CFR50 APPENDIX R. SECiasTII.C CiWFLIANCE EVALUATION FIDE AREA / ZONE 1-FN-2-5 Spent Fuel Storage Room C.tegory System Caponent Circuit-Schedule Function ~ Consequence of Fire Mitigetton Hot None Standby Equipment Cs1d None Shutdown Etvipment High/ Low None Pressure Interface Spurious None Operation Equipment Alternate None Shutdown Equipment Dedicated None Shutdown Eculpment Impe11 Corporation Report No. 01-0310-1435 FH-2 Revision 0 _ _ - - _ _ _ _ = _ _ _ _ _ _ _

                                                          .m                                 -

n 10CFR50 APPDWIX R. SEchd!!!.S CopFLIANCE EVALUATION

                        .                         FIRE AREA / ZONE 1-FN-42-6 New Fuel Storage Room Effects of Fire on Safe Shutdown capabf11ty 4

The design basis fire will not affect the capabflity to j achfeve and meintain cold shutdown, as there are. no safe i shutdown components or cables within the fire area / zone. i i t ). l i I i i I l. i i 1 i t i } l I i ! Impe11 Corporation Piport No. 01-0310-1435 FH-3 Pevision 0 l 1 l

                ^                                                                                                                        -

7 5

               )s                                                       (

10CFR50 APPENDIX R SECTk II.G C00FLIANCE EVALUATION FIRE AREA / ZONE 1-FH-42-6 New Fuel Storage Rsom I Category System Component Circuit-Schedule Function Consequence of Fire Mitigation i Hot None Standby

;   Equipment I

! Ceid None Shutteown

  • i Equipment
  • High/ Low None l Pressure Interface Spirious None Operation Eq11prent
)

i Alternate None Shutdown j Equipment 'l Dedicated None ! Shutdown } Egufprent l l l i l i 4 i I t Impe11 Corporation

 . Riport No. 01-0310-1435                                        FH-4                                                                    Pevision 0 i

s

          .(O)
           %d t

A)

                                                       %j                                   G
                                                                                               )
                          -10CFP50 APPElfDIX P SECTION III.G COPPLIANCE EVALUATION FIPE APEA/70PE 1-FH-14-7 4POV Switchgear Room Effects of Fire on Safe Shutdown Capability A fire in this fire area / zone could result in the loss of the following portions of systems used to achieve hot standby and cold stutdown:

Reactor Coolant System (RCS)

                                -      Cables for the following components:
                                       -    Pressurizer heaters Chemical and Volume Control System (CVCS) i
                                 -     Cables for the following components:

4

                                       -    Charging pump
                                       -    RWST isolation valve
                                       -    Charging isolation valve 1

Component Cooling Water System (CCW)

                                 -     Cables for the following components:
  • Component cooling water pumps
                                       .-   CCW heat exchanger isolation valve Saltwater Coolino System (SWC)
                                 -     Cables for the following components:
                                       -    Saltwater cooling pumps Containment Ventilation System (CVS) 4
                                 -     Cables for the following corronents:
  • Peactor cavity cooling f&re and associated discharge control damper Residual Heat Pemoval System (RHP)

, - Cables for the following components: i

                                        -   Residual heat removal purp i                                        -   Pesidual beat reroval inlet isolation valve j                                        -   Residual hcat removal discharge isolation valve
                                        . RHR heat exchanger isolation valve i

t Irpell Corporation

i. Peport No. 01-0310-1435 FH-5 Revision 0

c - g' ( , { 10CFR50 APPEleIX R. SECTL/III.G CG88LIANCE EVALUATION - FIRE AREA /20NE 1-FN-14-7 480V Switchgear Room

                                                                                         ' EsseAtal Electric Systems j                                                                                          -    480V Switchgear 2 4                                                                                           -

480V Switchoear 3 l - Motor control center 2 i - Utility bus 4 - Vital bus 6 Inverter 5

                                                                                           -    Cables for the following components:
                                                                                                . 480V switchgear j

Motor control centers

                                                                                                . Vital buses
                                                                                                . Battery charger B j                                                                                    Damage to cables for vital bus 5 could cause auxiliary feeduster 1

flow control valves FCV-3300 and FCV-3301 to fail open. Operator ] action will be taken to reneally position the auxiliary feedwater j flow control valves. d Damage to cables for component cooling water pump G-15A could result in the loss of remote pump control. Operator action will be required to manually start the pump at 480V switchgear 1. I Damage to cables for residual heat removal isolation valves MOV-814 and MOV-834 could cause the valves to spuriously open or cause the loss of remote valve control. Redundant isolation valves MOV-813 , and MOV-833 will remain available to isolate these lines. Operator i action may be required to manually open the valves to initiate restNel heat removal. One train of all other systems required for hot standby and cold shutdown will remain free of fire damage.

Damepe to cables for the reactor vessel head vent valves and pressurfrer high point vent valves, which are routed through 4

this fire area /rone, could cause the spurious actuation of , the two redundant high/ low pressure interface valves in each line. Operator action will be required to operate disconnect switches in the penetration area to deenergire and close these

valves to. isolate these lines. Spurious actuation of these valves.

l until operator action is taken, has been analyzed, and will not , result in unacceptable conditions (24, 25), i Damage to cables for MOV-1100C could cause the volue control l tank isolation valve to remain open, thus preventing suction flow to the charging pumps from the RWST. Operator action will be required to manually close this valve to prevent cavitation of the charging pump when the volume control tank empties. l 1 1 Impe11 Corporation i Report No. 01-0310-1435 FH-6 Revision 0 i

                                                       ,@                                    s

( 10CFR50 APPENDIX R. SECT 1-aII.G CC9M.IANCE EVALUATION M FIRE ARFA/?CNE 1-FN-14-7 480V Switchgear Room Damage to cables for MOV-357 and MOV-358 could cause these wavles to spuriously open. Spurious actuation of these valves could divert flow from the seal infection flowpath to the charging safety injection flowpath. The effects of the spurious actuation have been analyzed. The analysis i demonstrates that adequate flow will remain available for

seal injection flow (28).

j Damage to cables for the refueling water pump G-275 could spuriously start this pump. The containment spray i isolation valves will remain available to prevent

;                            inadvertent containment spray, and depletion of RWST fnventory.

4 t ) a l i ] I i. 1 . l t i

  <  Impe11 Corporat1on i  RIport No. 01-0310-1435                      FH-7                                       Revision 0

10CFR50 APPEWIX p, SECTIs,4I.G C(WLIANCE EVALUATION FIRE AREA / ZONE 1-FN-14-7 480V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus 2C, 1GA2C10P1-KB Power feed to station Loss of power to station service None. Train 1 480V electrical St:ney Brkr 10 service transformer 2 transformer 2 and 480V distritution system will remain available. Equipment (X07) switchgear 2. 480V Swgr #1, 1WBS103P2-KB Power feed to 480V Loss of power to 480V None. Train 1 480V electrical Brkr 03 Switchgear 3 Switchgear 3. distribution system will remain available. 1WBS103P3-KB Power feed to 480V Loss of power to 480V Switchgear 3 Switchgear 3. 1WBS103P4-KB Power feed to 480V Loss of power to 480V Switchgear 3 Switchgear 3. 1WBS103PS-KB Power feed to 480V Loss of power to 480V Switchgear 3' Switchgear 3. 1WBS103C4-KB Interlock, Swgr 1/3 Damage to this circuit could and Swgr 2/3 tie prevent remote control of the breakers tie breaker from the control room, but it could still be closed at the 480V switch-gear 804, or the interlock could be bypassed and allow the breaker to close when the switchgear 2-3 tie breaker is closed. 1WBS103C9-KB Interlock, Swgr 1/3 Damage to this circuit could and X08/Swgr 3 breakers prevent remote control of the tie breaker from the control room, but it could still be closed at the 480V switch-gear B04, or the interlock could be bypassed and allow the breaker to close when the switchgear 3-3 tie breaker is closed. _ Swgr #2 ---- 480V Switchgear 2 Loss of 480V Switchgear 2 None. Train 1 480V' electrical distribution system will remain available. Impe11 Corporation. Peport No. 01-0310-1435 FH-8 Pevision 0

                       -                                                          q.                                                              s
                                                                                       )

10CFR50 APPEWIX R SECTUII.G CCWLIANCE EVALUATION 4 FIPE AREA / ZONE 1-FN-14-7

480V Switchgear Poem 1

Cctegory System Component Circuit-Schedule Function Consequence of Fire

 ~
                                                                                                                              , Mitigation
Not 480V Swgr #2, 1685202P2-K8 Power from' station Loss of power to 480V None. Trafn 1 480V electrical i Standby (contd) Brkr 02 service transformer 2 Switchgear 2. distribution system will remain available.

l ' Equipment (contd) IG85202P3-KB Power from station Loss of power to 480V service transformer 2 Switchgear 2 4 1GBS202P4-KB Power free station Loss of power to 480V j service transformer 2 Switchgear 2 1GBS202PS-KB Power from station Loss of power to 480V

 ,                                                     service transformer 2      Switchoear 2.

l 1XBS202C3-KB Remote breaker control Damage to this circuit could I cause a loss of remote breaker

 ;                                                                                control, and spuriously close or

, trip the breaker. The

 !                                                                                breaker could be closed via i                                                                                  push button at 480V switch-
gear 805.

?

                              $wgr #2,  1XBS20367-KB   Remote breaker control     Damege to this circuit could     None. Train 1 480V electrical distribution 3                             Brkr 03                                             cause a loss of remote breaker   system will remain available.

1 control, and spuriously close , j or trip the breaker. The  ! breeker could be closed via 3 push button at 480V switch-j gear 905. !i 1WBS203C4-KB Bus tfe 2-3 and 2-1 Damage to this circuit could breaker interlock prevent remote control of the j tie breaker from the control j room, but it could still be I closed at the 480V switch-

gear P05 or the interlock j could be bypassed and allow the breaker to close when the switchgear 2-1 tie breaker is closed.

i IX8S203C5-KB Remote breaker control Damage to this circuit could i cause a loss of remote i breaker control, and/or l remove the interlock and allow j the breaker to close. f-4 1 4 Impe11 Corporation l Piport Fo. 01-0310-1435 FH-9 Revision 0

                                                             .10CFR$0 APPENDIX R. SECTw'III.G CONPLIANCE EVALUATION L

FIRE AREA /FONE 1-FM-14-7 480V Switchgear Room C'tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 480V Swgr #3 --- 480V Switchgear 3 Loss of 480V Switchgear 3. None. Train 1 480Y electrical distribution Standby (contd) system will remain available. Equipment (contd) i Swgr #3 1HBS303P4-K8 Power from station Loss of power to 480V None. Train 1 480V electrical distribution system will remain available. ' j Brkr 03 service transformer 3 Switchgear 3. 3 1HBS303PS-KB Power from station Loss of power to 480V service transformer 3 Switchgear 3. 1HFS303P6-KB Power from station Loss of power to 480V

service transformer 3 Switchgear 3.

I 1HBS303P7-KB Power from station Loss of power to 480V service transformer 3 Switchgear 3. 1HBS303P8-KB Power from station Loss of power to 400V service transfo w r 3 Switchgear 3. 4 1HBS303P9-FB Power from XOB Loss of power to 46Cf Switchgear 3. 1WBS303C1-KB Interlock Swgr #3/f1 Damage to this circuit could ! breakers prevent remote control of the tie breaker from the control

.                                                                                       room, but it could still be
!                                                                                       closed at the 480V switch-
gear 806 or the interlock j could be bypassed and allow

, the breaker to close when the switchgear 3-1 tie breaker is closed. 4 1 IXBS30X2-KB Interlock Sugr #3/f1 Damage to this circuit could breakers remove the interlock and allow j the breaker to close. 1YBS30X3-KB Remote breaker control Damage to this circuit could cause a loss of remote breaker r control, and spuriously close or j trip the breaker. The breaker i could be closed via push button at 480V switchgear 806 ] 1

!     Impe11 Corporation i      R port No. 01-0310-1435                                                    FH-10                                                                   Pevision 0 l

r

                                                                                                     )                                                                                                           ).

l 10CFR$0* APPENDIX R. SECTh u 21.G COMPLIANCE EVALUATION d FIRE AREA / ZONE 1-FH-14-7 - 480V Switchgear Room , Category System Component Circuit-Schedule Function Consequence of Fire Nitigation Hot 480V MCC-2 ----- Motor Control Center 2 Loss of MCC-2 Mone. Trafn 1 480V electrical distribution Standby (contd) system will remain available. Equipment (contd) 1685218P2-K8 Power Loss of power to MCC-2 will result in the loss of power to the following components required for normal shutdown: A-9S MOV-814 G-979 PC-12 MOV-8228 MOV-850A G-942 McV-834 MOV-720A A-17A l MCC-2A IX85223P2-KB Power Loss of power to MCC-2A will Wone. Train 1480V electrical distribution result in the loss of power to system will remain available.

the following components required for normal shutdown:

l MG-8AF MG-88F i

MCC-28 IG85229PI-KC Power loss of power to MCC-28 will None. Train 1 480V electrical distribution i result in the loss of power system will remain available.

i to the following components required for norzel/ alternate i shutdown: 1 D-10 A-14A LSH/L/LL97C 4 G-75A A-148 iSH/L/LL97D } G-758 A-14C 1 G-70 A-140 , IG8S229P2-KC Power loss of power to ICC-28 will 4 result in the loss of power j to the following components ' required for normal / alternate i shutdown:

!                                                                                                D-10     A-14A LSH/L/LL97C 4                                                                                                 G-75A A-148 LSH/L/LL97D G-758 A-14C G-70 A-14D 1

1G85229P3-KC Power Loss of power to MCC-28 will result in the loss of power to the following corponents I required for norme1/ alternate shutdown: l D-10 A-14A LSH/L/LL97C G-75A A-148 LSH/L/LL97D a G-75B A-14C G-70 A-14D Impe11 Corporation R: port No. 01-0310-1435 FH-11 Revision 0 _m- ___.____ __m _____ _ _ _ _ _ _ ___ _ _ . _ _ _ _ _ _ _ _ _ _ . _ _ _ _

                                                         ~~

q. s/

                                                              )                                                       (Q) 10CFR50 APPENDIX R. SEC7u'111.6 COMPLIANCE EVALUATION FIPE APEA/ ZONE 1-FH-14-7 480V Switchgear Room Citegory System Component Circuit-Schedule Function ,                         Consequence of Fire                               Mitigation Hot           480V    MCC-3      1GBS314P2-KB   Power                     loss of power to MCC-3 will                pone. Train 1 480V electrical distribution Standby       (contd)                                                     result in the loss of power to             system will remain available.

Equipment 4 the following components required (centd) for normal / alternate shutdown: MOV-883 MOV-11000 MOV-850C 120V 37.5/7.5 1GB0238-KB Power Loss of power to the 37.5/7.5 None. Train 1 electrical distribution kVA Xfur kVA transformers will result system will remain available, in loss of power to vital bus 4, and alternate power feed to vital buses 1,2,3,3A and 4 Y15 ----- Utility bus Loss of utility bus CV-304 will open on pressure differential if operation of the valve is required. I 1WL101C3-KB Power Loss of power to utility bus will result in loss of power to the following components required for normal / alternate shutdown: CV-304

V29 1GYY29P2-KC Power Loss of power to vital bus 5 Operator action to manually position could cause the loss of power FCV-3300 and FCV-3301. Train 1 electrical to the following components distribution system will remain i

required for normal / alternate available. Power for redundant shutdown: instruments / valves w111 remain available. 4 LT-3400A TE-3402A FCV-3300 LT-34008 TE-3411A FCV-3301 LT-3400C TE-3421A CV-3201 SV-3200 SV-3204 SV-3202 SV-3205 SV-3214 CV-3213 , SV-3211 SV-3203 I i c Impe11 Corporation R port No. 01-0310-1435 FH-12 Revision 0

4

                   }                                                                                                                                                                             }

U 10CFR50 APPENDIX R. SECTI jf.G Ct2FLIANCE EVALUATION V FIRE AREA / ZONE 1-FM-14-7 480V Switchgear Room Category Systeur Camponent Circuit-Schedule Function Consequence of Fire Nitigati e Hot 120f VV29 ----- Inverter 5 Loss of Inverter 5. Operator action to manually position Standby (contd) Inverter 5 FCV-3300 and FCV-3301. Train 1 electrical Equipment distribution system k'11 remain available. . l (contd) Power to redundant instruments / valves will l IG80268P1-FC Power Damage to this circuit would remain available. , result in the loss of power to Inverter 5. 1GB0268P2-FC Power Damage to this circuit could j cause a loss of power from transformer X41 to Inverter 5. 1GD0217DI-KC Power Loss of 125V DC power to

Inverter 5.

i Y30 ---- Vital bus 6 Loss of vital bus 6. None. I 1GYV29PI-KC Power Loss of power to vital bus 6 1 will not cause the loss of power any components required for

normal /al% w te shutdown.

125V D03 168S210P1-KB Power Loss of power to battery charger B. None. Redundant power to 125VDC switch-gear 1 from battery I will remain

;                                                                                                                     available.

l 1XBS210C2-KB Remote breaker control Damage to this cfrtutt cos,1d cause a loss of remote britaker

,                                                                           control, and spuriously close or j                                                                            trip the breaker.

I j i j I

  , Impe11 Corporation Rioort No. 01-0310-1435                                         FH-13                                                                                                              Revision 0

i 10CFR50 APPENDIX R. SECTa-i!!.G Ct3FLIANCE EVALUATION

FIRE AREA / ZONE 1-FN-14-7 i 480V Switchgear Room
Category System Camponent Circuit-Schedale Function Consequence of Fire Mitigation f Hot RCS Par 1CBS215P2-KB Power This cir uf t is entirely Operator action to deepergire pressurfrer l Standby Heater contained within the fire heater group B. Pressurfrer heater group A Equipment Group 8 area /rone. The circuit and vill remain available, c (contd) its termination points are assumed destroyed.

1GBS215P3-KB Power This circuit is entirely , contained within the fire i area /rone. The circuit and its terminatirA points are l assumed dest".cyed.

.                                                                                1GBS215P4-KB Power                     Damage te this circuit could I

cause '.ne loss of power to at leas',one of the heaters in the pressurfrer heater group. 1GBS215PS-KB Power Damage to this circuit ret1d cause the loss of r'Aser to at , least one of the heaters in the i ' pressurfrer heater group. i 1GBS215C3-KB Remote breaker control Darece to this circuit could i result in the loss of mmote j heater control, and/or l spuriously energize or trip l the heaters. 1GBS215C4-KB Presserfrer level Damage to this circuit could j interlock cause a loss of remote breaker t control and/or spuriously j energfre or trip the heaters. } l 1GBS215C5-KB Pressuriter level Damage to this circuit could j interlock result in the loss of remote i heater control, and/or j spuriously trip the heaters.

}                                                                                1GQ104077-KB Control signal            Damage to this circuit could i

I prevent operation of pressurfrer heater group B, although ) group A would operate correctly. I Par 1FBS109C6-KB Interlock to pressurfrer Damage to this circuit could Operator action to deenergize pressurfrer Heater heater group D result in the loss of remote heater group C. Pressurfrer heater

 ,                                                            Group C                                                   automatic / manual heater control                    group A will remain available.

{ and/or spuriously trip the heaters

]

Impe11 Corporation.

 ,            Report No. 01-0310-1435                                                                            FH-14                                                                                        Revision 0 i

j

                                                                         ,~

1

10CFR50 APPENDIX R. SECTi s ill.G CO WLIANCE EVALUATION FIRE APEA/ ZONE 1-FN-14-7 480V Switchgear Poem Category System Component Circuit-Schedule Function , Consequence of Fire Mitigation

! Hot Par Damage to this circuit could RCS 1GBS209P2-KB Power Operator action to deenergire pressurizer j Staney (contd) Heater cause the loss of power to at heater group D. Pressurfrer heater , Equipment Group D least one of the heaters in the group A will remain available. (contd) pressurizer heater group. j 1GBS209P3-KB Power Damage to this circuit could i cause the loss of power to at least one of the heaters in the

pressurfrer heater group.

1GBS209P4-KB Power Damage to this circuit could cause the loss of power to at least one of the heaters in the j pressurfrer heater group. 1GBS209P5-KB Power Damage to this circuit could cause the loss of power to at i least one of the heaters in the pressurfrer heater group.

.                                  1GBS209C3-KB Interlock to pressurfrer Damage to this circuit could

! heater group C result in the loss of remote 1 control, and/or spuriously j trip the heaters. 2 1GBS209C4-KB Remote breaker control Damage to this circuit could result in the loss of remote control, and/or spuriously energize or trip the heaters. i 1GBS209C5-KB Pressurizer level Damage to this cirtvit could interlock result in the loss of remote 1 control, and/or spuriously { trip the heaters. j 1GBS209C6-KB Remote breaker control Damage to this ,;frcuit co;1d i result in the loss of rest,te control, and/or spuriously i trip the heaters. l 1 i ,i Impe11 Corporation z RIport No. 01-0310-1435 FH-15 Revision 0

O, (Ce) 10CFR50 APPENDIX R. SECTi s s!I.G CO M UANCE EVALUATION

                                                                                                                                                                                                      ,o FIDE AREA / ZONE 1-FN-14-7 480V Switchgear Room Category System Component Circuit-Schedule Function                                                      Consequence of Fire                               Nitigation Hot          CVCS     G-8A                         1GA2007PI-KB           Power                       Loss of power to G-8A           Ncne. G-8B will remain available.

Standby Equipment MDV-1100D 1HB0378P1-KB Power Loss of power to MOV-11000 F.one. MOV-11008 will remain available. (contd) IHB0378C1-KB MOV-1100C open interlock Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. 1HB0378C2-KB Posftion softch/ torque Damage to thfs cfreuf t could switch feedback prevent remote operation and/or cause the valve to spuriously open or close. 1H80378C7-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1HB0378C8-KB Volume Control tank Damace to this efetuf t could level interlock result in the loss of remote valve control, and/or cause the valve to spuriously close. MOV-883 1HB0390C5-KC Remote valve control / Damage to this circuit could None. Valve will fail open as required position indication result in the loss of remote for safe shutdown. valve control. Yelve will fail as is, normally open. Impe11 Corporation P: port No. 01-0310-1435 FH-16 Pevision 0

               .,                                                                                                                         .~

w 10CFR50 APPENDIX R. SECTS s t!!.G Coppt!ANCE EVALUATION FIpE AREA / ZONE 1-FN-14-7 480V Suitchgear Room i Category System Camponent Circuit-Schedule Function Consequence of Fire Nitigation l Hot CCW G-15A 1FBS121C3-KB Interlock to G-158 recoge to this circuit could Operator action to verify start or Stoney spuriously start the pump and/or manually start G-15A at the breaker.

~

Equipment prevent remote operation.

(contd) 1FBS121C4-KB Interlock to G-15C Damage to this circuit could j

spuriously start the pump and/or prevent remote operation. 1FBS121C7-KB Interlock to G-158 Damage to this circuit could j prevent remote operation of the j pump. I 1FBS12108-KB Interlock to G-15C Damage to this circuit could 2 prevent remote operation of the 4 pump. I G-158 1GBS221p2-KB Power Loss of power to G-158 None. G-15A will remain available. f ) 1GBS221C2-KB Interlock to G-15A Damage to this circuit could

spuriously start the pump and/or prevent remote operation.
!                             1GBS221C4-KB    Interlock to G-15C          Damage to this circuit could i                                                                          spuriously start the pump and/or prevent remote operation.

j i 1GBS221C5-KB Remote pump control Damage to this circuit could l* spuriously start the pump and/or j prevent remote operation. I 1GBS221C7-KB Interlock to G-15C Damage to this circuit could prevent autostart the pump, however, handswitch control from the control room is still available. 1ABPND269-KB Remote pump control Damage to this circuit could prevent auto start or remote operation of the pump, l i l ) i i ! Impe11 Corporation j Report No. 01-0310-1435 FN-17 Revision 0 l

3 O- n 10CFR50 APPENDIX R. SECTi m II.G COWLIANCE EVALUATION FIRE APEA/ ZONE 1-FH-14-7 o . 3 480V Switchgear Room Category System Component Circuit-Schedule Function , Consequence of Fire Mitigation Hot CCW G-15C 1HB030$P2-KB Power Loss of power to G-15C None. G-15A will remain ave 11able. Standby (contd) . Equipment 1HBS305C2-K8 Interlock to G-158 Damage to this circuit could ' (contd) spuriously start the pump and/or

prevent remote operation.

1HBS305C4-KB Interlock to G-15A Papage to this circuit could ' spuriously start the pump and/or prevent remote operatica. I 1HBS305C5-KB Interlock to G-158 Damage to this circuit could 3 prevent remote operation of the pump. l 1H80305C6-Ka Remote pump control Damage to this circuit could spuriously start or stop the pump and/or prevent remote ' j operation. 1A80ND268-K8 Remote pump control Damage to this circuit could prevent auto start or resete - operation of the pump. M0Y-720A 'G80288PI-KB Power loss of power to MOV-720A None. MOV-720A or MOV-7208 is maintained ] normally open. MOV-7208 will remain i - available. i-l 1 1GB0288C1-KB Position switch / torque Damage to this circuit could i switch fecesck result in the loss of remote valve control. The valve will l fall as is. ! 1G80288C2-KB Interlock to G-138 This circuit is entirely j contained within the fire area /rone. The circuit and its termination points are assumed destroyed. 1GB0288C3-KB Remote valve control

 !                                                                           DameN resu     in the to this loss circuit         could of remote j                                                                             valve control, and/or cause the valve to spuriously operate.

1 f Impe11 Corporation j Riport No. 01-0310-1435 FH-18 Revision 0

C4 k i 10CFR50 APPENDIX R SECT W,I.G CtWLIANCE EVALUATION FIRE APEA/ ZONE 1-FN-14-7 480V Switchgear Room

   - Category System' Component Circuit-Schedule Function                                 Consequence of Fire                     Ritigation

, Hot SWC G-13A 1FBS114P2-KB Power Loss of power to G-13A Reroute cables for G-13A from fire areas / Standy zones 8, 9A, 7, 40, 4E to 8, 9A, 40 Equipment 1FBS114C4-KB Low discharge pressure Damage to this circuit.could (es6edded), 4E. (contd) interlock prevent remote operation of the pump, or spuriously 3 i stop G-13A or spurir' aly , start G-138. l G-138 1GBS214P2-KB Power Loss of power to G-138. None. G-13A will remain available. 1GBS214C3-KB Penote control / Damage to this cirtuf t could indication spuriously start or stop the pump and/or prevent remote operation. 1 GPS 214C4-KB Low discharge pressure Damage to this circuit could interlock prevent remote operation of the pump, or spuriously stop G-13B or spuriously

start G-13A.

I CVS A-9s IXB0209P1-KB Power Loss of power to A-95 None. A-9 and its associated control damper will remain available. 3

,                                         IX80209C1-KB     Interlock to reactor        Damage to this circuit could

! cavity teaperature spuriously start or stop the fan j switch TS-24 and/or prevent remote operation of the fan. l P0-12 IX80209C2-KB Damper control signal Damage to this circuit could None. A-9 and its associated control

spuriously close the damper damper will remain available.
;                                                                                      and/or prevent remote operation.

1 Cald RHR G-148 1GBS222P1-KC Power Loss of power to G-148 None. G-14A will remain available. Shitdown I' Equipment j 1GBS222C1-KB Remote pump control Damage to this circuit could ! spuriously start or stop the , pump and/or prevent remote 1 operation. l IGBS222C2-KC Remote pump control Damage to this circuit could { spuriously stop the pump, i i Impe11 Corporation j P port No. 01-0310-1435 FH-19 Revision 0 i

i ( ) 10CFR50 APPEWOIX R. SECTLedII.G COpFLIANCE EVALUATION i FIRE AREA / ZONE 1-FN-14-7 ] 480V Switchgear Room 1 Category System. Component Circuit-Schedule Function Consequence of Fire Mitigation Csid pHR MOV-814 1GB0271P1-KB Power Loss of power to MOV-814. The Operator action to deenergfre and manually Shutdown (contd) valve will fail as is, open POV-814 to initiate PHR system Equipment normally closed. operation. MOV-813 will remain available. (contd) 1GB0271C1-KB Remote valve control Damage to this circuit could result in the loss of remote

valve control, and/or cause the i

valve to spuriously open. i 1GB02710248 Position switch / torque Damage to this circuit could . switch feedback result in the loss of remote j valve control. The valve will fall as is, normally closed, i ! MOV-8228 IGB0266PI-KB Power Loss of power to MOV-8228 None. McV-822A or MOV-8228 is maintained j normally open. MOV-822A will remain ^ available. l

  • 1GB0266Cl-KB Remote valve control Damage to this circuit could j result in the loss of remote
valve control, and/or cause the valve to spuriously operate.

1GB0266C2-KB Position switch / torque Damage to this circuit could switch feedoack result in the loss of remote

valve control. The valve will j fail as is.

MOV-834 1GB0272P1-KB Power Loss of power to McV-834 Operator action to deenergfre and manually I open MOV-834 to initiate PHR system { operation. POV-833 will remain availabic. 1GB0272C1-KB Remote valve control Damage to this circuit could prevent remote valve control and/or l cause the valve to spuriously open, i 1GB0272C2-KB Low reactor coolant Damage to this circuit could pressure interlock remove the RCS high pressure j interlock. 1 j 1GB0272C3-KB Position switch / torque Damage to this circuit could 1 switch feedback result in the loss of remote 1 valve control. The valve will ! fail as is, normally closed. ! Impe11 Corporatton. 1 Peport No. 01-0310-1435 FH-20 Revision 0 1

j O n 10CFR50 APPENDIX p. SECTI M II.G Ct3FLIANCE EVAltfATION o i FIDE AREA / ZONE 1-FN-14-7 480V Switchgear poem Cateeory System Component Circuit-Schedule Function Consequence of Fire Nitigetton l High/ Low RCS SV-3401, IGY3005p1-KC Solenoid control power Demoge to this circuit could None. prsssure 02,03,04 result in the loss of remote

Ixt
rface- valve control.

SV-3401 1GY3005CA-KC Solenoid control power Deunge to this circuit could Operator action to close SV-3402 will < result in the loss of remote isolate this line. ) valve control eno/or cause 4 the valve to spuriously open. 4 l SV-3401/ IGY3005CI-KC Solenoid con vol power Damage to this circuit could Install disconnect switch for SV-3402 at 4 SV-3402 result in the loss of twoote . the penetration area. Spurious actuation valve control. of the vent valves, untti operator action is taken to deenergire SV-3402, has been , analyzed, and will not result in unaccept- ! able conditions (24,25). i l 16Y3005CJ-KC Solenoid control power Damage to this circuit could result in the loss of remote j valve control, and/or cause the valve to spuriously open or close. SV-3402 16Y3005C84C Solenoid control power Dessee to this circuit could Install disconnect switch for SV-3402 at result in the loss of remote the penetration area. Spurious actuation valve control, and/or cause the of the vent valves, untf1 operator action l valve to spuriously open. is taken to deenergize SV-3407, has been 4 analyzed, and will not result in unaccept-able conditions (24,25). l ! SV-3403 1GY3005CC-KC Solenoid control power Damage te this circuit could Operator action to close SV-3404 will ] result in the loss of remote isolate this 11pe. I valve coctrol, and/or cause the j valve to spuriously open. l j SV-3403/ 16Y3005CK-KC Solenoid control power Damage to this circuit could Install disconnect switch for SV-3404 at j SV-3404 result in the loss of remote the penetration area. rious actuation

 <                                                                           valve control,                      of the vent valves, unti operator action    '

I  ; is tsken to deenergire SV-3404, has been sulyzed, and will not result in unaccept-

]                                                                            Damage to this circuit could        able conditions (24,25).

l 16Y3005CL-KC Solenoid control power s result in the loss of remote I

  • valve control, and/or cause the

{ valve to spuriously open or j close, f Impe11 Corporation

]   PIport Po. 01-0310-1435                    3                       FH-21                                                                      Revision 0 4              _.                                                                     . s --     _     _

A (9 ) 10CFR50 APPENDIX R. SECTfUI.G CopFLIANCE EVALUATION

                                                                                                                                           /

(/ ) FIRE AREA / ZONE 1-FH-14-7 480V Switchgear Room

                                                                        ~

Category System Ceaponent Circuit-Schedule Function Consequence of Fire Mitigation High/ Low RCS $V-3404 1GY3005CD-KC Solenoid control power Damage to'this circuit could Install disconnect switch for SV-3404 at

Pressure (contd) result in the loss of remote the penetration area. Spurious actuation i Int'.rface valve control, and/or cause the of the vent valves, untti operator action (contd) valve to spuriously open. is taken to deenergize SV-3404 has been analyzed, and will not result In unaccept-able conditions (24,25).

CVCS CV-528/ 1GY2A36P1-KC Power Damage to this circuit could None. CV-526 result in the If,ss of remote valt'e control, and/or cause the + 4 val' e to spuriously close. l Spurious pCS G-2A 1NA1A03C1-KB Lube oil pump Damage to this circuit could Operator action to deenergize

Cperation interlock srt:riously start the pump and/or the pump.

Equiteent prevent remote operation. ! G-2B 1XA1B03C3-KB Lube oil pump camage to this circuit could Operator action to deenergize j inter 1cck spuriously start the pump and/or the pianp. prevent remote operation, i CVCS G-42 1HB2A10C2-KB Local pump control Damage to this circuit could Operator action to deenergize l spuriously start the pump and/or the pump. j prevent remote or local operation. I I i i i 1 t j l Impe11 Corporation RIport No. 01-0310-1435 FH-22 Revision 0 l

                           \                                                       10CFR50 APPENDIX p. SECTIw-wil.G C019LIANCE EVALUATION FIDE AREA /FONE 1-FN-14-7 480V Switchgear poem Category System Component- Cfreutt-Schedule Function                                                            Consequence of Fire                       Mittgetton Sportous CVCS                                          FCV-11150, 1600205D2-KC    power                     Demoge to this circuit could       None.

Operation (contd) E,F prevent the control of FCV-11150 Equipment E.F via the nitrogen supply (contd) system. Control via the norsel plant fastrument air system would still be avellable. 1GD0205D4-KC power Damege to this circuit could None.

                                                                                                           - prevent the control of FCV-1115D, E.F via the nitrogen supply system. Control via the normal plant instrument afr system would stt11 be available.

1GD020506-KC pouer Damage to this efrtvit could None, prevent the control of FCV-1115D, E,F via the nitrogen supply - system. Control via the normal plant instrument air system would still be available. MOV-1100C 1GB0147C9-KB MOV-11008 open interlock Damage to this cfremit could Operator action to deenergfre and manually prevent twote operation and/or close MOV-1100C. cause the valve to spuriously open or close. 1682A76C2-KB pemote valve control Damage to this cfremit could prevent remote operation and/or cause the valve to spuriously open or close. 1682A76C3-KB Volume control tank Damage to this circuit could level interlock prevent remote operation and/or cause the valve to spuriously open or close, l i 1G82A76C4-K8 MOV-11000 open interlock Damage to this circuit could prevent remote operation and/or cause the volve to sportously open or close. Impe11 Corporation RIport No. 01-0310-1a35 FH-23 Revision 0

g' r. s k 10CFR50 APPENDIX P SECTi _ ,2i!.G COMPLIANCE FVALUATION FIDE AREA / ZONE 1-FN-14-7 480V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CRS G-27S 1GBS219P2-KB Power Loss of power to G-275. Operator action to deenergize the pump. Operation Equipment 4GBS219C9-KC Remote pump control Damage to this circuit could (contd) spuriously start the pump and/or prevent remote operation. 1GBS219CC-KC Undervoltage lockout - Damage to this circuit could spurlously stop the pump, and/or prevent remote operation of the

pWWp*

1 i SIS MOV-357 1GB0243P1-KB Power Loss of power to MOV-357. None. Spurious actuation of this valve

will divert flow from the seal injection flowpath to the charging safety injection j flowpath. The effects of the spurious actuation have been analyred. The analysis demonstrates that adequate flow l will remain available for seal injection j (28).

1GB0243Cl-KB Remote valve control Damage to this circuit could j prevent remote operation and/or i cause the valve to spuriously

open.

i 1GB0243C2-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will

!                                                                            fall as is, normally closed.

1 1, i 1 1 4 Impe11 Corporation RIport No. 01-0310-1435 FH-24 Revision 0 4

r"N r3 10CFR50 APPENDIX R, SECTltWIII.G CMFLIANCE EVALUATION FIRE APEA/ ZONE 1-FH-14-7 480Y Switchgear Poem Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious SIS MOV-358 1HB0385P1-FB Power Less of power to MOV-358. None. Spurious actuation of this valve Operation (contd) will divert flow from the seal injecticn Equipment flowpath to the charging safety injection (contd) flowpath. The effects of the spurious actuation have been analyzed. The analysis demonstrates that adequate flow will remain available for seal injection (28). 1HB0385C1-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open. 1HB0385C2-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will fail as is, normally closed. Alternate SIS G-50A 1GA2005P1-KB Power Loss of power to G-50A None. Charging syst a will remain Shitdown available. Equipment M0Y-850A 1GB0274P1-KC Power Loss of power to MOV-850A. None. Charging system will remain available. 1GB0274C2-KC Recete valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open. 1C80274C5-KC Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. The valve will 2 fail as is, normally closed. l i 4 I Impe11 Corporation Peport No. 01-0310-1435 FH-25 Revision 0 i

10CFR50 APPEuplX R. SECTI s t!I.C COMPLIANCE EVALUATION FIRE AREA / ZONE 1-FN-14-7 480V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Nitigetton Alt:rnate SIS MOV-8508 1680180P1-K8 Power Loss of power to MOV-8508. None. Charging system will recein

   $bitdown    (contd)                                                                                         available.

Equipment (certd) 1G80180C9-KB Position switch / torque Demoge to this circuit could switch feedback result in the loss of nuote valve control. The valve will fail as is, normally closed. FWS CV-37/ 1FA1004C2-K8 CV-37 control / Damage to this efftuit could Operator action to trip main feeduster CV-8758 SV-8758 indication cause a loss of remote pump s to prevent feedwater flow to the operation and/or prevent through SV-8758. Spurious actuation closure of CV-37. of this valve, untti operator action is taken to trip the , has been evaluated and determined to acceptable (27). Charging system will remain available. CV-37 1FA1C04C8-F8 CV-37 control Damage to this circuit could Operator action to trip main feedwater cause a loss of remote pump pumps. control, and/or cause CV-37 to spuriously close, or disable the open or close interlocks for valve CV-37. CV-8758 IFA1004C9-KB SV-8758 control Damage to this circuit could Operator action to trip sein feedwater cause a loss of remote pumps. control of G38 and SV-8758, and/or cause SV-8758 to spuriously open or close. A-17A IG80282PI-KC Power loss of power to A-17A. Operator action to trip mein feeduster pumps. . 1G80282C4-KC Automatic control Dasege to this circuit could spuriously. start or stop the fan and/or prevent remote operation of the fan. P Impe11 Corporation-Rrport No. 01-0310-1435 FH-26 Revision 0

[V 3 [ 10CFR50 APPENDIX R. SECLstII.G CWm.!ANCE EVALUATIDH FIRE AREA /2ONE 1-FN-14

  • 480V Switchgear Room Category System Component Circuit-Schedule Function , Consequence of Fire Nitigation Alternate SNC G-13C INBS313P148 Power Loss of power to G-I X. pone. Saltwater coolfeg pump G-13A Shutdown will remain available.

Equipment 'INBS31X1-R8 Remote pump control Damege to this cfrevit could (contd) prevent remote operation of the 4 pump, and/or cause the pump to

,                                                                                                                      spuriously start or stop.                                                    ,

i i INBS31X3-rB Priming system control Damage to this circuit could { prevent remote operation of the t pump. I

;                                                                           INBS31X44B     Priming system control      Damage to this cfremit could i                                                                                                                       prevent remote operation of the 1

pump, or cause the pump to j spuriously stop. l l Dedicated -- Equipment / cable identiffers for dedicated j Shutdown shutdown equipment will be added when as ] Equipment builts are available. 1 i I i } l \ Impe11 Corporation Rrport No. 01-0310-1435 FH-27 Revision 0 t l

10CFRSO APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14 . 4160V Switchgear Room Effects of Fire on Safe Shutoown Capao111ty A fire in this fire area / zone could result in the loss of the following portions of systems used to achieve hot sta9dby and cold shutdown: , Reactor Coolant System (RCS)  ;

                               -    Reactor protection system trip circuits
                               -    Cables for the following components:
  • PORVs
                                    -      Block valves                    c                      ,
  • Pressurizer heaters
                                     . Source range monitors

' - Pressurizer level transmitters

                       *
  • Pressurizer pressure transmitters
                                     . Primary system temperature transmitters Chemical and Voline Control System (CVCS)
                               -    Cables for the following components:
                                     -     Charging pumps and associated support equipment
  • Charging RwST isolation valve
                                     . RWST isolation valve
                                     . Charging loop A control valves
  • Charging loop A flow transmitter
                                     . Seal injectio't flow control valves
  • Reactor conlant pump seal flow pressure transmitters Main Steam System (MSS)
                               -    Cables for the following components:
                                     -     Atmospheric steam dump valves
                                     -     Steam generator level transmitters
                                     . Main steam header pressure transmitter
                                     . Turbine stop valves
                                     . Reneater isolation valves Irpell Corporation Report No. 01-0310-1435                                 PB-1                                            Revision 0
                                                                                                     ' r,

7" f- [v yl

              \                                           I
                                                           \
                                                                                                                                 \

s 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PS-14-8 ' 4160V Switchgear Room Auxiliary Feedvater System (AFW)

                                   -     Cables for the following components:
                                         . Motor driven auxiliary feedwater pump and associated discharge control valve Component Cooling Water System (CCW)
                                   -     Cables f r the following components:

i

                                         . Component cooling water pumps
                                         .      CCW heat exchanger isolation valve
                                         .      Thermal barrier pump
                                         .      Thermal barrier outlet valves
                                         .      CCW to RHR heat exchanger flow control valves Saltwater Cooling System (SWC)
                                   -     Cables for the following components:
. Saltwater cooling pumps Containment Ventilation System (CVS)
                                   -     Caoles for the following components:
                                         .    . Reactor cavity cooling fans and associated damper I

a Residual Heat Removal System (RM) ! - Cables for the following components:

                                         .      Residual heat removal pumps
                                         .      Residual heat removal inlet isolation valve;
                                         .      Residual heat removal discharge isolation valves
  • RHR heat exchanger isolation valves
                                         .      Residual neat removal inlet / discharge temperature transmitters
                                         .      Residual heat removal flow control valve I                                   Diesel Generator Systems (UG)
 ?

1 - Cables for the following components: i

                                         -      Olesel generators and associated support equipment Gaseous Nitrogen System (GNI) j                                    . Cables for the following components:
                                         .      PORV/ block valve nitrogen supply control valve Impell Corporation Reoort No. 01-0310-1435                                P8-2                                                                                Revision 0
]

O O 10CFR50 APPENDIX R SECTION III.G COMPLIANCE EVALUATICN O q

                                                                                                                                                           'd FIRE AREA /ZOPE 1-P8-14-8 4160V Switchgear Poem
<                                                                                                                                                            t Essential Electric Systems 4160V buses
                                  -     480V switchgear 480V motor control centers -
                                  -     Cables for the following components:                                                                                 j l
                                        . 4160V buses
                                        . 480V switchgear
                                        . 480V motor control centers
                                        . 120V vital buses
                                        . 125VDC switchgear The fire protection features provided for the protection and separation of the safe shutdown systems within the fire area / zone do not meet the separation requirements of 10CFR50 Appendix R. Section III.G.2 The dedicated shutdown system will be used to achieve cold shutdown in the event of fire.
                          - Operator action will also be taken to deenergize offsite and normal onsite power sources to prevent and mitigate spurious equipment operation. Operator action will also be taken to locally control certain valves used for hot standby.

The interruption of seal cooling and seal injection to the reactor coolant pumps, for the period required to initiate seal injection from the dedicated shutdown system, has been

                          . evaluated and determined to be acceptable (26).

The loss of auxiliary feedwater flow, for the period required to initiate auxiliary feedwater flow from the dedicated shutdown system, has been evaluated and determined to be acceptable (24,25). Peactor scram breaker trip is postulated for a fire in this fire area /rone, due to the multiple diverse failures required to prevent breaker trip (30). Damage to cables for the PCRVs and their associated block valves could cause the PORVs to spuriously actuate when the block valves are not available to isolate the lines. Spurious actuation of the PCRV, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). Iepell Corporation Report No. 01-0310-1435 PE-3 Pevision 0 l

    . . _    ,._       _. _ _ _ _ m , _ _ ___. _ _    .             .._. .         . _ - . -        .       _ _ . < __ _ _         .  ,
                    #~T 1                                                         [
                         ,l 10CFR50 APPENDIY P, SECTICN III.G COMPLIANCE EVALL9 TION                     .-

FIPE AREA / ZONE 1-PB-14-8 4160V Switchoear poem b j Damace to the cables for PWST flow control valves MOV-11008 and MOV-11000, and volume control tank isolation valve i MOV-1100C could prevent suction flow to the charging pumps j - from the RWST. Operator action will be required to manually 1 close MOV-1100C and open MOV 11008 or MOV-11000, to provide charging flow from the pWST and prevent cavitation of the - charging pump when the volume control tank empties. The time ' available for operator action to prevent damage to the charging pumps is currently under evaluation. , I ' f' Damage to cables for the turbine stop valves could cause the valves to remain open, preventing turbine trip. Operator action will be required to manually trip the turbine at the . i - turbine stand. Spurious actuation of the valves, until

operator action is taken to manually trip the turbine, has i' been analyzed, and will not result in an unacceptable condftfon (24,25).

Damage to cables for the atmospheric steam dump valves and condenser dump valves could cause these valves to spuriously open. Spurious actuation of these valves, until operator i action is taken to deenergize and close the valves, has been , i j analyzed and will not result in an unacceptable condition - 1 (24,25), i

,                                                   Damage to cables for the reheater isolation valves could cause j                                                    the valves to remain open. Operator action will be required j                                                    to manually close the valves. Spurious actuation of the i                                                    valves, until operator action is taken to close the valves, i

has been analyzed and will not result in an unacceptable condition (24,25). 3 L j Damace to cables for the residual heat removal "nlet isolation valves MOV-813 and MOV-814, could cause the two series isolation valves to spuriously open. Spurious actuation of MOV-813 will be prevented by locking out power to the valve - i during power operation. I I d Damage to cables for the residual heat removal discharge } isolation valves MOV-833 and MOV-834 could cause the two i series valves to spuriously open. Spurious actuation of t } MOV-834 will be prevented by locking out power to the valve - $ during power operation.  ; ) 1 l 4 i t

!         Impe11 Corporation j  .

Peport No. 01-0310-1435 PB-4 Revision 0 w

         /m                                                 .

C. d C,.m 10CFR50 APPEN9IX R SECTION III.G COMPLIANCE EVALUATION

                                         ,.i AREA / ZONE 1-P6-14-8 4160V Switchgear Room Damage to cables for the reactor head went valves and pressurizer head vent valves could cause the two series high/ low pressure interface valves to spuriously open. The spurious actuation of these valves until operator action is taen to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25).

Damage to cables for the seal return and letdown isolation valves could cause the two series valves in each line to remain open. The spurious actuation of these valves, until operator action is taken to deenergize and close the valves, has been analyzed, and determined to be acceptable (24,25). Damage to cables for auxiliary :,mssurizer spray isolation valve CV-305 could cause the valve to spuriously open. Spurious actuation of the valve, until operator action is taken to deenergize and close the valve, has been analyzed and detemined to be acceptable (24,25). Damage to cables for primary plant ameup water control valve FCV-1102A could cause the valve to spuriously actuate, allowing primary plant makeup water to be supplied directly to the cnarging pump suction. Spurious actuation of this valve, untti operator action is taken to deenergize and close the valve, has been analyzed and detemined to be acceptable (27). Damage to cables for the Doric acid supply valves FCV-11926 and CV-334 could cause these valves to spuriously open, allowing concentrated Doric acid to be supplied to tne charging pump suction. Operator action will be required to close manual valves to isolate these lines. Damage to caoles for the refueling water pumps could cause these pups to spuriously start. Containment spray could De inadvertently initiated as the cables for the containment spray isolation valves could also De affected by a fire in this fire area / zone. Operator action to trip offsite power and close a manual valve located at the refueling water puos, will deenergize the pump, and prevent depletion of the RWST inventory (31). Irpell Corporation Report No. 01-0310-1435 P u-5 Revision 0

n /m .,s m 10CFR50 APTEPDIX R, SECTION III.G COMPLIANCE EVALUATION

                                                                                                    ~

FIPE AREA /ZOWE 1-PB-14-8 4160V Switchgear poem Damage to circuits for charging safety injection isolation valves POV-356, POV-357 and POV-358 could cause these valves to spuriously open. . Spurious actuation of these valves will divert charging flow from the seal injection flowpath to the charging safety injection flowpath. The effects of the spurious actuation have been analyzed. The analysis indicates that adequate flow will remain available for seal injection (28). Damage to circuits for alternate shutdown system components will not affect safe shutdown as these systems are not credited for a fire in this fire area / zone. Spurious actuation of the safety injection and main feedwater system components will not affect safe shutdown as the safety injection and main feedwater pumps are tripped by operator action to trip offsite power. Impe11 Corporation Peport Po. 01-0310-1435 PB-6 Pevision 0

s m f- s 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA /70NE 1-PB-14-8 4160V Switchgear Room Cattgory System Component Circuit-Schedule Function Consequence of Fire Mitigation Fot 4160V Bus 1A IXA1A02C1-KB Remote breaker Damage to this circuit could Maintain this breaker racked out to prevent Staidby Brkr 02 control cause a loss of remote breaker Bus lA and IB intertie. Equipment control, and spuriously close or trip the breaker. Bus 1C ----- 4160V Bus 1C. Loss of Bus IC None. Dedicated shutdown system will , remain available. Bus IC, IFAlC01C1-KC Sequencer 502 trip and Damage to this circuit could Operator action to trip offsite power Brkr 01 lockout trip the breaker, prevent closing prior to exiting the control room. of the breaker, or prevent a trip en sequencer initiation. 1WAlC01Al-KB Sensor signal Damage to this circuit could cause a loss of overcurrent protection or could cause the j breaker to trip on overcurrent. lWA1001C1-KB Bus 1A, breaker 04 This circuit is entirely contained interlock within the fire area / zone. The circuit and its termination points are assumed destroyed. lWAIC01C2-KB Remote trip and close Damage to this circuit could i bus IC to 1A tie breaker cause a loss of remote breaker { control, and spuriously close or trip the breaker. I Bus 1C. 1WAlCO2C2-KB Differential and sudden Damage to this circuit could Operator action to trip offsite power i Brkr 02 pressure relay trip cause a loss of remote breaker prior to exiting the control room. ! interlock control, and spuriously trip t or prevent tripping of the breaker, l e 1 i i 4 i. Irpell Corporation i Report No. 01-0310-1435 PB-7 Revision 0

f' J 1 v v 10CFR50 APPENDIX R SECTION III.G COMPLIANCE EVALUATION FIRE AREA /20NE l-PB-14-8 i 4160V Switchoear Poce C-ticory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus IC, IFAIC10Pl-KB -Power to station service Loss of power to 480V None. Dedicated shutdown system will St:ndby (contd) Brkr 10 transformer 1 switchgear 1 from station remain available, i Equipment (XO6) service transforwer 1 1 (cratd) , lWAIC10Al-KB Amoeter circuit Parage to this circuit could remove overcurrent protection or cause the breaker to trip on overcurrent. 1WAIC10Cl-KC Pemote breaker control Damage to this circuit could cause a loss of remote breaker

control, and spuriously trip the i breaker, or prevent closing or tripping the breaker. ,

lWAIC10Cl-KB Remote breaker trip and Damage to this circuit could 1 close indication cause the loss of remote breaker

circuit, requiring mechanical j tripping or closing of the i breaker, i

i s } i , t .\ 1 1 Irpell Corporation f Peport No. 01-0310-1435 PB-8 Revision 0 l 1

s k 10CFP50 APPENDIX P, SECTION III.G CCPPLIANCE EVALUATION FIPE APEA/ ZONE 1-PB-14-8 4160V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus 1C. 1WAIC11P1-FB Power to station service Loss of power from station None.' Dedicated shutdown system will Stradby (contd) Brkr 11 -transformer 3 service transformer 3. remain available. Equipment (XO8) (contd) 1WAIC11Al-KB Asceter circuit Damage to this circuit could recove overcurrent protection or trip the breaker on overcurrent. l 1WAIC1101-KB , Breaker 1AIC11 and Damage to this circuit could 1A1C11 interlocks cause a loss of remote breaker , control, and spuriously close or. l trip the breaker, or disable the i auto tripping of breaker 1AIC11 on the racking of breaker 1A2C11 to the test position, or

prohibit electrical tripping or -

l closing of the breaker. l 1WA1C11Cl-KC Pesote breaker position Damage to this circuit could l indication cause the loss of remote ! breaker control and/or result in a loss of breaker position indication at panel C41, 1WA1C11C2-KB Pemote breaker control Damage to this circuit could cause a loss of remote breaker control, and spuriously c1)se er trip the breaker. 1WAIC11C3-KC Remote breaker position This circuit is entirely centained indication within the fire area / zone. The circuit and its termination points are assumed destroyed. l l I Impe11 Corporation Peport No. 01-0310-1435 PB-9 Revision 0

t J v. 10CFR50 APPENDIX R, SECTICN III.G CCMPLIANCE EVALUATION FIPE APEA/ ZONE 1-PB-14-8 4160V Switchgear Room Cateoory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot -4160V Bus IC, IFA1C14PS-KC Power from diesel Loss of power to 4160V bus IC Wone. Dedicated shutdown system will Standby (contd) Brkr 14 generator 1 to bus 1C from diesel generator 1. remain available. Equipment (contd) IFA1C14P6-KC Power fren diesel Loss of power to 4160V bus 1C <

                                            . generator 1 to bus 1C       from diesel generator 1.

1FAIC14P7-KC Power from diesel Loss of power to 4160V bus 1C , generator 1 to bus 1C from diesel generator 1. 1FA1C14P8-KC Power from diesel Loss of power to 4160V bus 1C generator 1 to bus 1C from diesel generator 1. 1FA1C14Cl-KC Preaker 1A1C14 and Damage to this circuit could RXI interlock cause loss of remote breaker control, and spuriously close one or both breakers. , IFAIC14C4-KC Generator potential Damage to this circuit could to synchronizer cause the generator output breaker to trip. If the diesel generator is sequencer started, then the output breaker protective function is disconnected. 1FA1C14C9-KC Engine run signal to Damage to this circuit could breaker trip prevent the diesel generator from being loaded onto the 4160V bus, or prevent manual testing of the diesel. t t N Impe11 Corporation j Peport No. 01-0310-1435 PB-10 Revision 0 i

O O 1CCFP50 APPENDIX R. SECTION III.G COPPLIANCE EVAll'ATICW O FIRE AREA /7CNE 1-PB-14-8 4160V Switchgear Poem Category System Component Circuit-Schedule Function Consecuence of Fire - Mitigation Hot 4160V Bus IC IFAIC14CE-KC -Generator stator Damace to this could cause the Standby (contd) Brkr 14 generator output treaker to trip. Equipment (contd) (c:ntd) 1FAICl4CF-KC Phase current Daeage to this could cause the transfomer circuit for generator output breaker to trip. differential current 1FA1C14CG-KC Generator stator Damage to this circuit could ground point sensor trip the generator or trip the circuit generator's c.:tput breaker. If the diesel is sequencer started, the generator output breaker protective function is disconnected. 1FAlC14CH-KC Generator metering and Damage to this circuit could protective relays cause the generator output breaker to open on "Peserve Power,"

                                                                      " Negative Phase Sequence," or
                                                                      " Voltage Controlled overcurrent."

If the diesel generator is sequencer started, then the output breaker protective function is disconnected. 1FAlC14CJ-KC Generative metering Damage to this circuit could and protective relays causethecenerator'soutgut breakers to be opened on Negative Phase Sequence" or " Voltage Controlled Overcurrent." If the diesel generator is sequencer started, then the output breaker p;otectivefunctionisdisconnected. 1FAIC14Cr-KC Bus 1C potential Damage to this circuit could to synchronizer cause Bus 1C to trip and isolate itself from diesel generator 1 and offsite power. If the diesel is sequencer started, then the output breaker protective function is disconnected. IFAlC14CP-KC 1AIC14 breaker trip Damage to this circuit could acknowledge to sequencer cause the sequencer to spuriously 502 stop loading the bus or signal the sequencer that the output breaker was closed and that Bus 1C was ready for loading. Impell Corporation Paport No. 01-0310-1435 Pit-11 Pevision 0

r ( ( t k \,s Y - 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION

                                                                                                                                       ~

FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room C*tegory System Component # Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus 1C 1FAIC14CR-KC Remote breaker control Damage to this circuit could , Standby (contd) Prkr 14 cause a loss of remote breaker Equipment (contd) control, and spuriously trip the (contd) breaker, disconnecting diesel . generator 1 from bus 1C. 1FA1C14CS-KC Sequence 502 tr y ?.d Damaje to this circuit could - close signals cause a loss of remote breaker control, and spuriously trip the breaker or prevent tripping of the breaker, although it could still be controlled at AIC. 1FA1C14CT-KC Sequence 502 trip and Damage to this circuit could close signals cause a loss of remote breaker control, and spuriously trip the breaker, or prevent sequentfal control of the breaker. 1FA1C14CZ-KC Engine lockoff and Damage to this circuit could run signal for breaker cause the diesel generator close circuit alignment output breaker to close even if it was shut down for maintenance or ready for loading,-or prohibit manual or automatic remote closure of the diesel generator output breaker, lWA1C14C1-KC Remote breaker This circuit is entirely contained position indication within the fire area / zone. The circuit and its terwination points are assumed cestroyed. 1WARX1C01-KC Control ciret;?t PCB Damage to this circuit could trip mechanism cause a loss of remote breaker control, or could trip bypass breaker RX1 or close breaker . 11C14 1FA1C1401-KC DC control power Damage to this circuit could - PX1 bypass trip circuit result in the Icss of ability to trip the breaker. Impell Corporation Peport No. 01-0310-1435 PB-12 Revision 0

m r3 r% 10CFR50 APPEPDIX R WCTICW III.G CC*tPLIANCE EVALUATION i  % F'PE AREA /ZOWE 1-PB-14-8 4160V Switcbgear Poor C-tegory System C e nent Circuit-Schedule Function Consequence of Fire

  • Pitigation Hot 4160V Bus 2C 4160V Bus 2C Loss of Rus 2C. None. Dedicated shutdown system will Standby (contd) remain available.

Equipment (contd) Bus 2C, IXA2001Al-KB Current ammeter circuit Damage to this circuit could Cperator action to trip effsite power pr or Brkr 01 remove overcurrent protection or to exiting control room. spuriously trip the breaker. 1XA2001C1-KB Station loss of voltaga Damage to this circuit could auto transfer interlock cause loss of remote breaker control, and prevent closing of the breaker. The breaker could still be tripped or closed via panel C12. Damage could also cause the breaker to close if both breakers 12C02 and , j 12C15 are open. 1GA2001Cl-KC' Sequencer 503 trip Damage to this circuit could and lockout cause a loss of rmte breaker control, and spuriously trip l or prevent tripping of the breaker. 1XA2001C2-KB Remote breaker control Damage to this circuit could cause a less of remote breaker control, and spuriously close or trip the breaker. Pus 2C, 1XA2002C2-KB Differential and sudden Damage to this circuit ceuld Operator action to trip offsite power prior Brkr 02 pressure relay trip cause a loss of remote breaker to exiting control room. interlock control, and spuriously trip the breaker and/or prevent or disable the trip. 1XA2002C4-KB Remote breaker control / Damage to this circuit could feeder from auxiliary cause a loss of remote breaker transformer C. control, and spuriously close or trip the breaker. Impell Corporation Peport Po. 01-0310-1a35 PB-13 Fevision 0

            %                                                                                                                   f%

10CFR50 APPFNDIX R. SECTION III.G COMPLIANCE EVALUATIch FIRE AREA /ZOWE 1-PB-14-8 l 4160V Switchgear Poes  ! l Category System Compenent. Circult-Schedule Function Consequence of Fire Mitigation l Not 4160 . Bus 2C, 1GA2C10P1-KB Power to station service : Loss of power from station None. Dedicated shutdown system will .j St:ndby (contd) Brkr 1C transformer 2 service transformer. remain available. ' Equipment (XO7) (centd) 1XA2C10Al-KB Sensor signal Damage to this circuit could i remove overturrent protection or spuriously trip the breaker. j l 1XA2C10Cl-KB Pesote breaker control Damage to this circuit could l cause a loss of remote breaker

                                                                                                                                - control, and spuriously close ur trip the breaker.

1XA2C1001-KC Remote breaker trip and Damage to this circuit could close indication cause the loss of remote breaker circuit, reoutring mechanical tripping or closing of the breaker. Bus 2C, 1XA2C11P1-FB Power to station service Loss of pouer to station service None. Dedicated shutdown system will Brkr 11 transformer 3 transformer 3 and 480V remain available. (XOB) switchgear 3. IXA2C11Al-KB Sensor signal Damage to this circuit could remove overcurrent protection or spuriously trip the breaker. 1XA2C11C1-KB Breater 1A2C11 and bamage to this circuit could 1AlC11 interlocks cause a loss of remote breaker control, and spuriously close or trip the breaker 1A2C11, or disable the autotripping of breaker 1A2C11 on the racking of breaker 1AIC11 to the test position, or prohibit electrical tripping or closing of the . breaker. 1XAFC1102-KB Pemote breaker caa+ral Damage to this circuit could remove overcurrent protection or spuriously trip the breaker. ] Impe11 Corporation Revision 0 Pcport No. 01-0310-1435 PB-14

f% f f c)  % , V} 10CTR50 APPENDIX R. SECTION III.G CCMPLIANCE EVALUATION FIPE AREA / ZONE 1-PB-14-8 4160V Switchgear Poce Cateoory System Copponent Circuit-Schedule Function Consequence of Fire Mitigation , l Hot 4160V Bus 20, 1GA2C15PS-KC Power from diesel Loss of power to 4160, i;.; .*:: Pone. Dedicated shutdown system will J Shutdown (contd) Brkr 15 generator 2 from diesel oenerator 2 remain ave 11able. Equipment 1GA2C15P6-KC Power from diesel Loss of power to 4160V Bus 2C. generator 2 from diesel generator 2. 1GA2C15P7-KC Power from diesel Loss of power to 4160V Bus 2C. generator 2 from diesel generator 2. 1GA2C15P8-KC Power from diesel Loss of power to 4160V Bus 2C. generator 2 from diesel generator 2. 1GD0206DI-KC Bus 2 to diesel camage to this circuit could f generator 2 interface result in a loss of ability to relay power trip breaker RY1. 1GA2C15Cl-KC Auxiliary transformer Damage to this circuit could interlock cause loss of remote breaker control and/or cause breakers 12C15 and RY1 to spuriously operate. 1GA2C15C4-KC Generator potential to Darage to this circuit could synchronizer cause the generator's output breaker to trip, or if the diesel generator is sequencer started, the output breaker protective function is disconnected. Irpell Corporation Peport No. 01-0310-1435 PB-15 Pevision 0

f~ b) (-

                                                                                \                                                 .

10CFR50 APPENDIX R SECTION III.G CCFPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8

- 4160V Switchgear Room C'.tecory Systesi Component Circuit-Schedule Function Consequence of Fire Mitigation Hot' 4160Y Bus 2C 1GA2C15C9-KC Engine run signal to Damage to this circuit could Standby (contd) Brkr 15 breaker trip circuit trip the diesel generator 2 out-Equipment (contd) put breaker or close the breaker

, (contd) even if the diesel was not + running, j 1GA2C15CE-KC Generator stator Damage to this circuit could trip the generator output breaker. ! 1GA2C15CF-KC Phase current Damage to this circuit could trip , transformer circuit the generator output breaker. l for different current ) ICA2C15CG-KC Generator stator ground Damage to this circuit could  ! ground point sensor trip the generator or trip the ' a generator's output breaker. If i the diesel is sequencer started, the generator output breaker 1 protective function is disconnected. 1GA2C15CH-KC Generator metering and Damage to this circuit could 'l protective relays cause the generator output breaker to be opened on " Reserve Power,"

                                                                                 " Negative Phase Sequence," or
                                                                                 " Voltage Controlled Overcurrent."
If the diesel generator is sequencer j started, then the output breaker j

protective function is disconnected.

1GA2C15CJ-KC Generator metering and Damage to this circuit could and protective relays causethegenerator'soutpt 4 breakers to be opened on Negative Phase Sequence" or " Voltage f Controlled Overcurrent." If the diesel generator is sequencer started, then the output breaker protective function is disconnected.  ;

1GA2C15CK-KC Bus 2C potential to Damage to this circuit could ) to synchronizer cause Bus 2C to trip and isolate - i

itself from diesel generator 2 l

and offsite power. If the diesel  ; I is sequencer started, then the output breaker protective j function is disconnected. I i

}

l l Iepell Corporation

,     Rzport No. 01-0310-1435                                                     PB-16                                              Fevision 0 i

O O - 10CFR50 APPENDIX P. SECTION III.G COMPLIANCE EVALUATION FIRE APEA/ ZONE 1-PS-14-8 4160V Switchgear Room C5tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Het 4160V Bus 20, 1GA2C15CP-KC 1A2C15 breaker trip Damage to this circuit could _ Standby (contd)- Brkr 15 acknowledge to sequencer cause a false signal to the Equipment (contd) 503 sequencer indicating that the (contd) diesel gene .or's output breaker was eMsed and that bus it was ready for loading, or cause the sequencer to believe that the breaker was open and st n loading the bus. 1GAFC15CR-KC Remote breaker control Damage to ttis circuit could cause a loss of remote breaker control, anr spuriously trip the breaker, di' connecting diesel generator 7 from bus 2C. 1GA2C15CS-KC Sequencer 503 trip and Damage tr :his circuit could , I riose signals cause a ' as of remote breaker control, and spuriously close or trip the breaker. IGA 2C15CT-KC Sequencer 503 trip and Damage to this circuit could close signals cause a loss of remote breaker control, and spuriously trip the breaker or prevent sequencer control of the breaker. 1GA2C15CZ-KC Engine lockout /run Damage to this circuit could signals for breaker cause loss of remote breaker close control, and spuriously close the breaker. 1GA2C1501-KC Remote breaker control Loss of control power for RY1. 1XA2C15Cl-KC Remote breaker position This circuit is entirely contained indication within the fire area / zone. The circuit and its temination points are assumed destroyed. IXARY1001-KC Control circuit PCB trip Damage to this circuit could

                                                            -mechanism                                         cause the loss of remote breaker control, or spuriously trip bypass RY1 or close breaker 12C15 Irpell Corporation Report No. 01-0310-1435                                                                                          PB-17                                                                   Pevision 0
                        -                       .               .-                  .         . - . -     .    .  . _ - ~ .          .-         - . . . . -

O O 10CFP50 APPENDIX R. SECTION III.G COPPLIANCE EVALUATION O i FIPE AREA RONE l-PB-14-8 j 4160V Switchgear Room  ; C*teoory System Component Circuit-Schedule Function Consequence of Fire Mitigation i Hot 480V Swgr 1 480V Switchgear 1 Loss of 480V Switchgear 1. None. Dedicated shutdown system will

,   St:ndby                                                                                                           remain available.

! Equipment ! (contd)

Segr 1, IFBS102P2-KB Power feed from station Loss of power to 480V switchgear 1 None. Dedicated shutdown system will Brkr 02 service transforwer i from station service transformer 1. remain available, j 1FBS102P3-KB Power feed from station Loss of power to 480V switchgear 1 l service transformer 1 from station service transformer 1.
See above.

l 1FBS102P4-KB Power feed from station Loss of power to 480V switchgear 1 service transformer 1 from station service transforper 1. j 1FBS102PS-KB Power from station Loss of power to 480V switchgear 1 1 service transformer 1 from station service transformer 1. i lWBF102Cl-KC perote breaker position Damage to this circuit could cause

indication a loss of remote breaker control
!                                                                             at the control room panel C12.

i Breaker control could still be available via pushbutton at

~

480V switchoear 804, 1 IWBS102C3-KC Remote breaker trip and Damage to this circuit could ca . j close circuit spurious operation of the * <ater or cause a loss of remote breaker l control at the control room panel  ; J C12. Breaker control could still t I be available via pushbutton at { 480V switchgear 804 i l i I j i i l ) i l 4 l I i l 1

  !  Impell Corporation j     Peport No. 01-0310-1435                                                  PB-18                                                                        Revision 0

O O O i 10CFP50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION i FIRE AREA /ZCNE 1-PB-14-8 4160V Switchgear Room i j Cateoory System Component Circuit-Schedule Function Consequence of Fire Mitigation l Hot 480V Sugr 1 I WS103P2-K8 Power feed to 480V Loss of power to 480V Switchgear 3. None. Dedicated shutdown system will 1 Standby (contd) Brkr 03 Switchgear 3 remain available. { . Equipment (contd) IWBS103P3-KB Power feed to 480V Loss of power to 480V Switchgear 3. j Switchgear 3 IWBS103P4-KB Power feed to 480V Loss of power to 480V Switchgear 3. } Switchgear 3 i { IWS103PS-KB Power feed to 480V Loss of power to 480V Switchgear 3. 3 Switchgear 3 1 .; IWBS10X1-KC Pemote breaker . Damage to this circuit could a position indication cause spurious operation of 1 the breaker or cause a loss of remote breaker control at the control room panel C12. TF= breaker could still be closeJ via pushbutton at 480V switchgear 804 4 i IWBS10X4-KB Interlock Bus 1-3 and Damage to this circuit could cause 2-3 tie breakers a loss of remote breaker control at the control room panel C12. Breaker control could still be available via pushbutton at 480V swtichgear 804, or the interlock could be bypassed and allow the breaker to close when the switch-gear 2-3 tie breaker is closed. 1WBS10X6-KB Remote breaker control Damage to this circuit could cause a loss of remote breaker control, and spuriously close or trip the breaker. The breaker i could still be closed via i pushbutton at 480V switchgear 804 1WBS10X9-KB Interlock Bus 1-3 and Damage to this circuit could cause switchgear feed breaker a loss of remote breaker control . at the control room panel C12. Breaker control could still be available via pushbutton at 480V swtichgear 804, or the interlock i could be bypassed and allow the a breaker to close when the switch-l gear 3-3 tie breaker is closed. l 1 Impell Corporation ] Peport No. 01-0310-1435 PB-19 Revision 0 2 1

                                                                                                                                                    ).

10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-P8-14-8 4160V Switchgear Room Crtegory System Component Circult-Schedule Function Consequence of Fire Mitigation Hot 480V Sugr 2, 1X85202Cl-KC Remote breaker Damage to this circuit could cause None. Dedicated shutdown system will Standby (contd) Brkr 02 position indication a loss of remote breder control remain available. Equipment at the control room panel C12. (contd) Breaker control could still be available via pusnoutton at 480V switchgear 805. IX85202C3-KB Remote breaker control Damage to this circuit could cause a loss of remote breater control, and spuriously close or trip the creaner. The breaker could still De closed via pusnoutton at 480V switengear H05. Sage 2, IX85203C1-KC Remote breaker position Damage to tne circuit could None. Dedicated shutdown system will Brkr 03 indication prevent sequencer initiated remain availaole. closing of the tie creamer, but the breaker could still be closed via panel C12 or via a i pusnoutton on 480V switengear DOS. Damage could also cause a loss of remote breder control

                                                                                 .at the control room panel C12.

Breaker control could still be avallanie via pushoutton at 480V switchgear 805. IG85203C1-KC Sequencer 2 interlock Danage to tnis circuit could cause loss of remote breder control, and spuriously close the breaker. The breder could still De closed via pushoutton at switchgear 805. i I Impell Corporation Report No. 01-0310-1435 PB-20 Hevision 0

O O 10CFR50 APPENDIX R SECTION III.6 C0pFLIANCE EVALUATION O FIRE AREA / ZONE 1-Ps-14-8 4160V Switchgear Room Consequence of Fire Mitigation Crtegory System Component Circuit-Schedule, Function Hot 480V Sugr 2, 1XBS20367-KB Remote breater control Damage to this circuit could Standby (contd) Brkr 03 cause a loss of remote oreaKer Equipment (contd) . control, and spuriously close or trip the breaker. Tne breater could-(contd). still be closed via pushoutton at switchgear 805. 1WBS203C4-KB Bus tie 2-3 and 2-1 Damage to the circuit could cause breaker interlock a loss of remote breaker control at the control room panel C12. Breaker control could still be available via pushoutton at 480V switchgear 005. Or the interlock could oe Dypassed and allow the breaker to close when switchgear 2-1 tie breaker is closed. Swgr 3 1YBS303C3-KB Remote breaker control Damage to this circuit could None. Dedicated shutoown system will Brkr05 cause a loss of remote breater remain availaole. l' control, and spuriously close or trip the breaker. Tne breater could still be closed via pushbutton at switchgear 806. l 1YBS303C1-KC Remote breaker position Damage to this circuit could indication prevent remote operation of the breater. 1WBS303CI-KB Bus tie 3-1 interlock . Damage to this circuit could prevent renote control of the tie breaker from tne control room, but it could still be closed at the 480V switchgear 806, or the interlock could be Dypassed and allow the breaker to close when the switchgear 3-1 tie breakcr is close. Impell Corporation Report No. 01-0310-1435 PB-21 Revision 0

e, 3 m) (v 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION J FIRE AREA / ZONE 1-P8-14-8 4160V Switch 9 ear Room Cetegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 480V fCC 1 ---- Motor control center ! Loss of MCC 1. None. Dedicated snutdown system will Standby (contd) remain available. Equipaen t (contd) IFBS118P2-KB 480V power to MCC 1 Loss of MCC 1 will cause the loss of power to the following components required for normal / alternate shutdown

  • i MOV-8508 MOV-833 G-943 MOV-11008 MOV-813 P0-11 MOV-1202 MOV-822A A-9 MOV-7208 G-980 ICC 1A - Mator control center IA Loss of MCC 1A. None. Dedicated snutdown system will l

remain availaole. PCC 18 1FBS129PI-KC Power Loss of power to MCC 18 will None. Dedicated snutdown system will a cause the loss of power to the remain available. following components required for normal / alternate shutdown: 1 A-13A D-09 LSH/L/LL97A A-138 G-69 LSH/L/LL978 A-13C G-74A A-13D G-748 1FBS129P2-KC Power Loss of power to MCC IB will cause the loss of power to the following components required

for normal / alternate snutdown

- A-13A D-09 LSH/L/LL97A A-138 G-69 LSH/L/LL97B ] . A-13C G-74A A-13D G-748

IFBS129P3-KC Power Loss of power to MCC 18 will cause the loss of power to tne l
following components required i

for normal / alternate shutoown:

+                                                                          A-13A      0-09     LSH/L/LL97A A-138      G-69     LSH/L/LL978

] G-74A A-13C A-130 G-74u Impell Corporation Report No. 01-0310-1435 PB-22 Revision 0 l

                                                                                                                                     /

O 'CN

                                                                     \                                                               b                                                              U 10CFR50 APPENDIX R. SECTICN III.G COMPLIANCE EVALUATION' FIRE APEA/ZCNE 1-PB-14-8 4160V Switchgear. Room Catecory     System Component Circuit-Schedule Function                           Consequence of Fire                   Mitigation
;                                                          Hot          480V       MCC 2B   1GBS229P1-KC    Power                        Loss of MCC 2B will cause the    None. Dedicated shutdown system will l                                                          Standby      (contd)                                                          loss of power to the following   remain available.

j Equipment ' components required for normal / 1 (contd) alternate shutdown: A-14A D-10 LSH/L/LL97C A-14B G-70 LSH/L/LL97D A-14C G-75A

A-14D G-75B 1GBS229P2-KC Power Loss of MCC 2B will cause the loss of power to the following

, corponents required for normal / } alternate shutdown:

A-14A D-10 LSH/L/LL97C ,

A-148 G-70 LSH/L/LL97D j A-14C G-75A l A-140 G-758 1GBS229P3-FC Power Loss of MCC 2B will cause the loss of power to the following I components required for normal / j alternate shutdown: t A-14A D-10 LSH/L/LL97C i A-148 G-70 LSH/L/LL97D j A-14C G-75A A-140 G-758 1 l 1 i i I i i i ii l i

;                                                            Impe11 Corporation j                                                            peport No. 01-0310-1435                                                      PB-23                       .                                  Revision 0 1

10CFP50 APPENDIX R. SECTICM III.G COPPLIANCE EVALUATION FIPE AREA / ZONE l-PB-14-8 4160V Switchgear Room Ci.tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 120V 7.5 kVA - 7.5 kVA transformer loss of 7.5kVA transforver will None. Dedicated shutdown system will Standby Transformer cause the loss of power to the remain available. Equipment following components required for (contd) norrial/ alternate shutdown: Y-14 (vital bus 4). 37.5 kVA ---- 37.5 kVA transformer Loss of 37.5kVA transformer will None. Dedicated shutdown system will Transformer cause the loss of power to the remain available. following components required for normal / alternate shutdown: Y-15 (utility bus). 37.5/ IFB0181-KB Power Damage to this circuit could None. Dedicated shutdown system will 7.5kVA cause itss cf 460VAC power from remain available. Transformer MCC 1 feeding one side of manual transfer switch #7. This switch supplies 480V power to the 37.5kVA transformer feeding vital bus fl. 2, 3A, and 4 and the 7.5kVA alternate feed transformer for vital bus #4 Power from this switch also supplies power to the rod control system at panel C07 Power to th transformers and D07 could be manually restored by switching to the alternate feed from MCC 2. 1GB0238-KB Power Loss of power to the 37.5/7.5 kVA transformers will result in loss of power to vital bus 4, and alternate power feed to vital buses 1, 2, 3, 3A and 4 Irpell Corporatien Report No. 01-0310-1435 PB-24 Revision 0

O / 10CFR50 APFEWDIX P. SECTIch III.G CCMPLIANCE EVALUATICN FIRE AREA / ZONE l-PB-14-8 416CV Switchgear Room Cetegcry System Corponent Circuit-Schedule Function Consequence of Fire Mitigation I Hot 120Y Y-11 IHY1100-KB Power Loss of distribution panel Y-11 None. Dedicated shutdown system will Standby (contd) will cause the loss of power to reeafn available. Equipment the following components required (conto) for r.ortal/ alternate shutdown: CV-546 TCV-601A Y-llR TCV-601B PT-430 NE-1201 CV-530 TE-600 l Y-11P 1FY1107-FB Power Loss of distribution panel Y-11R None. Dedicated shutdown system will will cause the loss of power to remain available. the following components required l for normal / alternate shutdown: l TE-400A TE-400C TE-402C 1 TF-601A TE-601B TC-601A HCV-602 TI-400 TC-601B l 1 Y-12 IHY1200-KB Power loss of distribution panel Y-12 None. Dedicated shutdown system will will cause the loss of power to remain available. the following components required for normal 4 alternate shutdown: CV-722A CV-545 CV-531 Y-12P CV-722B PT-431 CV-722C Y-12R 1GY1207-KB Power Loss of cistribution panel Y-12R None. Dedicated shutdown system will ! will cause the loss of power to remain available. l the foll3 wing components required l for nor1ral/ alternate shutdown: TE-410A TE-412C LT-431 TI-410 Y-13/Y-33 lHY1300-KB Power Loss of ef stribution panels None. Dedicated shutdown system will Y-13 and f-33A will cause the remain available. I loss of rower to the following i components required for nomal/ alternate shutdown: SV-2401 TE-2401A SV-2402 TE-2412A SV-2403 TF-2422A I SV-2404 LT-2400A FCV-2300 NE-1202 FCV-2301 Y-13R LT-2400B LT-2400C Irpell Corporation Report No. 01-0310-1435 PB-25 Revision 0

                    \                                                                   L.)                                                                 (G 10CFR50 APPENDIX R. SECTICN III.G COMPLIANCE EVALUATION                                                     ,

FIRE APEA/ ZONE 1-PS-14-8 4160V Switchgear Poom Crtecory System Ceoponent Circuit-Schedule Function Consequence of Fire Mitigation Not 120V Y-13R 1HY1307-r8 Power loss of distribution panel Y-13R None. Dedicated shutdown system will Standby (cente) will cause the loss of power to remain available. Equipment the following components required (contd) for normal / alternate shutdown: TE-422C Y-14R IJY14C8-RB Power Loss of distribution panel Y-14R None. Dedicated shutdown system will will cause the loss of power to remain available. , the following components required for normal / alternate shutdown: LT-435 PT-1115C PC-1115A P-418 PCV-1115A PC-11158 PC-418A PCV-11158 PC-1115C PT-425 PCV-1115C PI-1115A j PT-459 FCV-1115A PI-1115B t PT-1115A FCV-11158 PI-1115C PT-11158 TCV-1115C Y-15 IWL101C3-KB Power Loss of distribution panel Y-15 None. Dedicated shutdown system will I will cause the loss of power to remain available. the following components required for normal / alternate shutdown: CV-304 YY-14 IWD0133D1-K8 Power Damsge to this circuit could None. Dedicated shutdown system will ' Inverter 4 cause a loss of power to remain available. Inverter 4 l l \ l l l Irpell Corporation l Perert No. 01-C310-1435 PS-26 Revision 0 l L. - - , _ . - - ._ _ , __. _

v C% 10CFR50 APPENDII P. SECTIcel III.E CopFLIANCE EVALUATION FIPE AREA /ZCIE 1-PB-14-8 4160V Switchgear Poem Category System Cet Cf reutt-Schedule Function Consequence of Fire Mitigation Not 125V D02 IFBS110P148 Pouer Loss of battery charger D02. None. Alternate power to 125V D' Bus 1 5tandy will remain available from Battery 1. Eeufpment (contd) IWB5110C14B Remote breder control Camage to this circuit could prevent remote operation and/or cause spurices operation of the breaker. DC3 1GB521h143 Power Loss of battery charger D03 None. Alternate power to 125V DC Bus I will remain available from Battery 1. IIBS210C248 Demote breaker control Damage to this circuit could prevent remote operation and/or cause spurious operation of the breaker. l l I i f l~ l Impe11 Corporatten l Pepcrt Me. C1-C310-1435 PB-27 Revision 0 1

10CFP50 APPENDIX R, SECTION III.G COMFLIANCE EVALUATION FIDE AREAntWE 1-PB-14-8 4160V Switchgear poem Catevery System Component Circuit-Schedule Function Consequence of Fire Mitigation Not PCS PPS Trip 1FC011X14C Safety injectio.1 scram Dameoe to this circuit could Lane, peactor scram breaker trip is Standby Circuits interlock trip the scran breaker and postulated due to the multiple diverse Equipment scram the reactor, or prevent failures required to prevent breaker (contd) undervoltage coil initiated trip (30), reactor scrar. j 1F0011K24C Safety injection scram Darage to this circuit could Interlock trip the scram breaker and l scram the reactor, or prevent ! undervoltage coil initiated . or safety injection condition l reactor scram. 1FQ011X44C Safety injection scram Damage to this circuit could interlock trip the scram breaker and scram the reactor, or prevent 4:ndervoltage coil initiated l or safety injection condition reactor scrap.

IWC11302448 Manual scram signal Damage to this circuit could l trip the scram breaker and

! scram the reactor, or prevent ! undervoltage coil initiated reactor scram. f IWC11305148 138kV loss of volt Darage to this circuit could l contact interlock trip the scram breaker and scram the reactor, or prevent l tripping the scram breaker on i loss of 138kV power. 1WC113065-tB Pressure level scram Damage to this circuit could interlock trip the scram breaker and scram the reactor, or prevent undervoltage coil initiated reactor scram. l IWC11309048 Scram A & B undervoltage Damage to this circuit could coil circuit trip the scram breaker and scram the reactor, or prevent undervoltage coil initiated l reactor scram. l l l l l l Irre11 Corporation l Berert re. 01-0310-1435 FB-28 Pevision 0 (

                                                         /"                                                                                               ("                                                                       %
                                                                                                                                                          \

a

                                                                                                                                                                                                                                      ]

10CFF50 APPEWOII R. SECTICW III.G COPPLIANCE EVALUATIcil FIPE ARES /20pE 1-PB-14-8 416CV Switchgear poem Category Systeer r-- 1. .. t Circult-Schedule Function Consequence of Fire Mitigation Not PC3 DPS Trip IWOO11309145 Scram A & B undervoltage Camage to this circuit could Staedby (contd) Circuits coli circuit trip the scram breaker and Eeuipment (coetd) scean the reactor. (centd) IWC113C274B Maeval $ CRAM signal Carage to this circuit could spuriously scram the reactor or prevent reactor scram from panel C03 1WC11307748 Manual SCPAft signal Camage to this ciregit could spuriously scram the reactor or prevent reactor scram from papel C03. 1Yt9141D148 Power to D07 Bamage to this circuit could result in loss of power to scram control circuits and create a reactor scram condition. 1WC1130044B Scram A & B undervoltage Damage to this circuit could (CC1) trip circuit spuriously scram the reactor or prevent reactcr scrap. CV-530 1FY1112C14C Pepote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. CV-530 will fail open on loss valve to spuriously close, of pouer. or open. I Impe11 forperation Report Fe. C1-C310-1435 P9-29 Revision 0

             /

1CCFRSC APFEECII R, SECTICk I!!.C CCMPLIANCE EVALUATICN FIFE AREA /ICkE 1-PB-14-8 4160V Switchgear Rcom C-tecery system Ccevocent Circuit-Scheeuie ruection Consecuence of rire nitigation Het RCS CY-546 1FY1112C24C Remote valve centrol Casage to this circuit could Operator ection to deenergize 120VAC/480VAC Stancy (conts') prevent remote cperation and/or pcwer to prevent / mitigate spurious Ecu1prent cause the valve to spuriously operation. CV-546 will fall closed on (conto) open or close. loss of power. Spurious actuation of the PORY, until operator action is taken to deenergize and close the valve, has been analyzed and will not result in an unacceptable condition (24,25). 1WY1112C24C PRD-425-Y2C interlock Carage to this circuit could result in the loss of reeote valve control, and/or cause the valve to spuriously open or prevent the valve free opening on loss of instrtment air to PCRVs. CV-531 1GY1215C14C Recote valve control Canage to this circuit could Operator action to deenergize 120VAC/460VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. CV-531 will fail open on loss valve to spuriously close or open. of power. CV-545 1GY1215C2-KC perote valve control / Damage to this circuit could Cperator action to deenergize 120VAC/4E0VAC position indication prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. CV-545 will fail closed on open or close. loss of power. Spurious actuation of the PCRV, untti operator action is taken to deenergize and close the valve, has been analyzed and will not result in an unacceptable condition (24,25). IIY121S*1-rc Pressurizer hich Carace to this circuit could pressure interlock result in the loss of remote valve control and/or cause the valve to spuriously open, or prevent it from openino. IIY1215C2-rf PFD-425-IIC interlock Damage to this circuit could result in the loss of rerete valve control, and/or cause the valve to spuriously open. Damage could also prevent opening or loss of instrument air to PORVs. 1GY1215C04C Remote valve control Camage to this circuit could prevent reeote operation and/or cause the valve to spuriously open er close. Irpell Cer;eration o - wa ci ciin-ia" PB-30 Fevisfon 0

f% p r\

O O )

10CF350 APPENCII P, SECTIC1f III.G CCFPLIANCE EVALUATICN FIRE APEA/ZCNE 1-PB-14-8 41ECV Switchgear Poce Catecery Tystem Component Circuit-Schedule Function Consequence of Fire Pitication - Hot PCS Pzr IFB5115P2-r8 Power This circuit is entirely contained None. Cables for dedicated shutdown Staecry (centd) Heater within the fire area / zone. The syster operation of pressurizer heater Ecuipment Grcup A circuit and its terwination group D are routed outside the fire area (ccetd) points are assumed destroyed. and will remain available. 1FB5115P3-NB Pcwer This circuit is entirely contained within the fire area / zone. The circuit and its termination points are assisaed destroyed. 1FE5115P4-KB Power Camage to this circuit could cause the loss of power to at least one of the heaters in the l pressurizer heater group. i 1FE5115PS-rB Power This circuit is entirely contained l within the fire area / zone. The circuit and its terwination points are assured destroyed. 1 FPS 115C3-tB Penote control Damage to this circuit could result in the loss of remote control and/or cause the pressurizer heaters to spuriously emergize or trip. 1FC104076-TB Centrol signal Dwage to this circuit could preveet operation of pressurizer heater group A. although ereup B wesid still operate cor ectly. 1FE5115C4-rB Pressurizer level Camace to this circuit could interlock result in the loss of remote contrcl and/or cause the l pressurizer heaters to spuriously energize or trip.

IFE5115C5-tB Pressurizer level Carage to this circuit could l interlock result in the loss of remote i

centrol and/or cause the t pressurizer heaters to spuriously trip. 1FB5115C6-tB Pressurizer level This circuit is entirely contained ! interlock within the fire area / zone. The l circuit and its termination points are assured destroyed. Irre11 Correratica Fegert Fo 01-C310-1425 FP-31 Pevision 0

10CFP50 APPDCII R. SECTION III.S CiprLIANCE EVALUATItu FIRE ASEA /2tWE 1-P8-14-8 4160V Seitchgear poem Category fastee Campeneet Circuit-Schle Function Conse mence of Fire Ritigation Not BCS Prr 1GB5215C3-RS Beeste breaker control Demoge to this circuit could Mene. Cables for dedicated shutdeun ' 5taney (cestd) Neater result in the loss of remote system operation of pressurizer heater l Egmisseet Group F control and/or spuriously greep D are routed outside the fire l (conte) epercise or trip the heaters, area and will ressin available, l 1ER$215C5-F3 Pressurizer level Dasege to this circuit could

  • interlock result in the less of reacte control and/or cause the presserizer heeters to spericesly trip.

1EB5215C7-K3 Presserf rer level This circuit is entirely contained

interlock within the fire area /rene. The l

circuit and its temination j points are assassed destroyed. i 1EC108077-r3 Centrol signal Damege to this circuit could prevent operation of pressurizer heater creep F. altheegh greep A i would still operate correctly. 1 l l \ l l 1sge11 Corporatica Fepert so. C1-C310-1435 PS-32 Pevision 0

                                                                                                                                                              ~

x,) & 10CFF50 APPECII F. SECTIC1s III.G CCP9tIAFCE EVALUATICN 7IFE APEA/ZCEE 1-PS-14-8 416CV Switergear Rece-Catecerv Tystew C M ecent Circuit-Schedule Fi.nction Ceesecuence of Fire P'itication ret FC5 Pzr 1FP51C9F7-tB Pcwer T>is circuit is entirely contained kore. Cables for dedicated shutdown Staedy (ccatd) Heater within the fire area /rene. The systerr operation of pressurizer beater Ecst; rect EmpC c!rcuit and its termination group D are routed outside the fire area (ccete) points are assused destroyed. and will reeafn availat'le. 1FBS1C9P3-tm Fwr This circuit is entirely contained within tre fire area / zone. The circuit and its termination points are assbeed destroyed. 1FB5105F4-KB Pcwer Cacage to this circuit could cause the loss of power to at least ene of the heaters in the pressur1zer heater group. 1FE5109PS-r3 Pcwer Casage to this circuit could cause the less of power to at least one of the heaters in the pressurizer heater group. 1FE510cca-g3 Perete centrol Camage to this circuit could result in the loss of reeete control and/or cause the pressurizer heaters to spuriously energize er trip. IFE51C9C5-FB Pressurfrer level Cmage to this circuit cculd intericck result in the loss of reecte centrol and/cr cause the pressurizer beaters to spurfeusly trip. 1FB51CSC6-r8 Pressurizer heater Damage to this circuit could group D interlock result in the Icss of remote centrol and/or cause the pressurizer teaters to spuriously energize or trip. 1FBSIC9C7-FB Fesote breaker trip Camage to this circuit could ciresit rescit in the Icss of remote centrol and/or cause the pressurizer heaters to spuriously trip, or prevent an auto trip. Manual heater control is avail-able from panel CC3, bewever. Irre11 Ccrperatica tercet Pe. C1-C31C-1435 FB-33 Pevisfen 0 l

O 10CFP50 APPDICII P. SECTICK III.E CDFLIseCE EVALUATICF FIPE AeEA/70mE 1-P9-14-8 416CT Switchgear poes Catsgery Syster Campement tiresit-Schoemle Ft. action Conseguence of Fire Mitigation l Ret PC5 Prr 1E85209C3-aB Pressurfrer heaters Dasege to this circuit could Operator action to transfer control of Stamey kater group C faterlock result in the isss of remote the required portion of pressurizer heater fenfammet Group C control and/or cause the group D to the dedicated shutdown panel. (centd) pressurizer heaters to Cables for dedicated shutdown system spuriously trip. operation of pressurizer heater group D are located outside the fire area and will resefn available. , IEFS20*C4-tB Resote breaker control Daeoge to this circuit could result in the loss of remote i control and/or cause the pressurizer heaters to spuriously l l energfre or trip. 1585209C5-t3 Presserf 2er level Dasege to this circuit could i interlock ressit in the loss of remote ! control and/or cause the pressurizer heaters to spuriously trip. I 1GES209C6-t3 seaste breater control Damage to this circuit could I result in the loss of remote control and/or cause the presserfrer heaters to spuriously trip. l l I l l l i l l Impe11 Carperatice Wesert so. C1-C31C-1435 PS-34 Revision 0

a l O O 10CF750 APPfMCII W. SECTION III.G C139LIAuCE f1ALUATIC# O FIPE APEA/7tWE 1-79-14-8 4160V Switchgeor poor Catego y fystem en :_,,t Cf rcsit-Schedule Function Consequence of Fire Pitigation het PC3 K-12C1 1WY11R3-r3 Power Loss of power to K -12C1. None. During operation of the dedicated Stonew (coett) shutdoun system, shutdown mergin will be Eemipseet determined by sampling primary system l bores concentration. l (centd) 1GC102C7443 Seeser signal Camege to this circuit could result in lem eff-scale or i erroneous indicatien. 1GC102C75-tB 5enser signal Demoge to this circuit could result in low off-scale or erreneous indication. 1GC1C2083-EE Power Caseee to this circuit could result in less of source range indication or erroneous indication. l l 1WC10200645 Seesor signal Camage to this circuit could I result in low eff-scale or l erroneous ind1 cation. 1MC102021-aB Indication signal came9e to this circuit could result in low off-scale er erroneous indication. , BE-12C2 1FC10205g48 Pomer Camage to t>fs circuit could home. During operation of the dedicated result in loss of source range shutdown syster, shutdown mergin will be indication or erroneous determined by samp11pg primary system indication. boron concentration. 1FCIC20eg43 Indicatten Damese to this circuit could result in low off-scale or erroneous indication. 1FC1C205043 Indication Damage to this circuit could result in low off-scale or erroneews indication. 1WC1C2005-Es Indication signal Damege to t>f s etremit could result in low off-scale or erroneous indication. 1wCIC2007-E5 Indication signal Danese to this circuit could result in low eff-scale er erroneous indication. Iepe11 Corperatten Fegert Fe. C1-C310-1435 PS-35 Pewision 0

r

           ,r                                                           e                                                                  /-~.

Y)- .Y Y 1CETp50 AFFENCII p. SECTICF III.G CCFPLIANCE EVAtt:ATICW FIFE AFTA/ICNE 1-P3-14-8 416CY Seitchgear Ecom Cate m fystee Ccercacet Circuit-Schedule Function Ccesecuence of Fire Mitigation Nt FCS LT-431 1GC1C4C78-K2 Seeser signal CanaM to this circuit could None. LT-430A will remain available at Staedy (cente) result in high eff-scale. Icw the dedicated shutdown panel. Equ*sseet eff-scale, er errenecus (coett) irdicatica. 141C4C3C-EB Seeser signal This circuit is entirely contaired within tre fire area /rene. The circuit and its tersinatica points are asswed destroyed. IIY1274-r8 Power Camage to this circuit could result in 1cw off-scale or errceecus indication. LT-435 lbr1C4035-r3 Serser signal Darace to this circuit could None. LT 430A will remain available at result in low cff-scale or the dedicated shutdown panel, erreneous indication. 1 W104081-K3 Sensor signal ramace to tPis circuit could res.it in high off-scale. Icw eff-scale, or erroneous intication. IIY1484-FE Power Damage to this circuit could result in icw off-scale er errenecus indicatien. PT-425 IW108CES-r3 PCI-425 pressure Casage to this circuit could None. PT-434A will remain available at interlock to FhR prevent opening or MCV-831 and the dedicated shutdown panel. MCV-813 and MCY-834 FCY-834. er cause loss ef creratten of PC-425. TwCIC8CC2-r5 Seeser signal Damage to this circuit could result in icw eff-scale or erroneous indication and deenergize the high pressure intericck to MOV-613 and PCY-834 ThT14".6-r3 Pcwer Carage to this circuit could result in icw off-scale er erroceous indication and teenergfre the hioh pressure interlock to MCV-813 and PCY-834 Irgell Cerreratice tesert se. C1-C31C-la35 PB-36 Pevision 0

10CTR50 APpDCII F. SECTION III.E CIDFLIANCE EVALUATION FIRE ASEA /ZeuE 1-pS-14-8 416CV Switchgear peep Category System Campeneet Circuit-Sc h te Function Consequence of Fire Mitigetton met DC5 FT-430 luc 10eeC143 Sensor signal Damese to this circuit could cperator action to deenergfre 120VAC/400VAC Stamey (contd) result in a pressere faterlock power to prevent / mitigate spurious festemaet closf ag presseriter sprey valves operation. Sporfous operation of the (esett) KV-430C and KY-430N. and/or spray valves pCV-430C and K V-430H will energfring pressurizer heater not affect safe shutdoen as the reactor groups A and 3. coolant pumps are tripped. Pressurizer code safey valves mill be available for over-pressere protection. Potvs will be available for system pressere control after dedicated shutdoen systee operation is initiated. 1WC10802fL43 Seesor signal Damese to this circuit could result in law off-scale or erroneous indication. Demoge to this circuit could result in a pressere interlock closing pressurizer sprey valves KV-430C and PCV-430N. and/or energf21pg presserfrer heater groups A and B. 1WC1000E343 pressere signal to Camage to this circuit could p-432 smitch result in low off-scale or erreneess indication. Demoge to this circuit could result in a pressere interlock closing presserfrer spray valves PCV-430C and PCV-43Gil, and/or enerefzfog presserizer heater beaks A and B. w I Isvell Carporatica Pegert Pe. C1-C310-1435 PE-37 Fevision 0

O O 10CD5C AMDCII R, SECTIts III.G CCurLIAeCE DAll'ATION O FIpE App /ZeuE 1-PB-14-8 4160T Switchgear poen Cateeery Sestem Campement Circuit-Scheeste Function Consegmence of Fire Ritigation het PCs FT-431 1 0 0802543 Sensor signal Camege to this circuit could Operator action to deenergize 120VAC/480VAC 5taney (esett) cause a low off-scale or power to prevent / mitigate spurious feufsmeet erroneous pressere indication. operation. Spurious actuation of the (coett) This will cause CV-546 to PORY, until operator action is taken to . spurisesly close or operate deenergize and close the valve, has been erratically. analyzed and will not result in an unacceptable condition (24,25). 1WC10802643 Senser sfgnal Damege to this circuit could cause CY-546 to spuriously close or operate erratically. 1WC100C2743 Sensor signal ramage to this circuit could cause CV-546 to spuriously , close or operate erratically. ' lur10404943 Sensor signal remage to this ciresit could result in the less of resote valve control. TE-ac2C 1F*103tf7-tB 5ensor signal Papeee to this circuit could home. TE-4C2s will remain available at result in hiah off-scale, low the dedicated shutdown panel, off-scale, or erroneous indicatten. 1MC103C1945 Sensor signal Camage to this circuit could result in low off-scale or erroneous indication. TE-4113 IWC10302243 Temperature indication Dasege to this circuit coule None. TE-4129 will remain available at cause a loss of temperature the dedicated shutdown panel. indication or cause erroneous temperature 1edication. , 12CIC306343 Sensor sfpiel Damage to this c1rcuit could result in high off-scale, low

  • off-scale, or erroneous indication.

IIY12R243 , Power Dasege to this circuit could cause a loss of pouer to TM-412 resulting in a loss of teoperature indication. Ispe11 Carreratica Icrert re. C1-c310-1435 PR-38 Pevision 0

i

             ,~                                                             ,.                                                                     ,

( ) ) ( )

            'J                                                             'J                                                                     LJ IMF50 AFFEnCII F. SECTICH III.G CCPPLIANCE EVAtt;ATICE FIFE AFEA/ZCNE 1-F?-14-8 416CV Switcheear Poan Ca'eeery       Systen Crucew-t Circuit-Sc>ecle Functica                          Ccesecuence of Fire                          Mitication het            FCS     TE-422C IFC1C4C71-K3     Seeser sigral                Casace to this circuit could          hone. TE-4228 will remain available at Stamey        (centd)                                                       result in high off-scale. Icw         the dedicated shutdown panel.

Ecu1 M cff-scale, or errorecus (crett') indication. TbCIC3025-r3 Seeser sigral Camage to this circuit could result in low eff-scale or errerecus indication. CDC5 G-FA 1GA2CC771-r3 Pcwer Less of power to G-8A. Cperator action to transfer control of G-8A to the dedicated shutdown panel. Cables for dedicated shutdown operation of G-SA are located outside the fire area and will recain available. Interruption of seal injection and seal cooling to the

 ~

reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). 1FA2CC7C2-r8 Auto start Icw pressure This circuit is entirely contained fr.hibit interlock within the fire area / zone. The circuit and its termination points are assisted destroyed. 1GA2CD7C1-st AJto start pWp Damace to this Circuit could spuricusly start or prevent auto starting of the pterp, and/or prevent resete cperation of the purp. 1GA2CC7C2-r3 Peacte pts p control Camage to this circuit could spuriously start or stop tre pump, and/or prevent remote cperatten of the pump. 1GA2CC7C2-rt Peset purp trip Camage to this circuit could result in loss of resete control and/cr prevent the purp free auto starting on sequencer 2 initiation. The purp could also be allowed to start en sequencer 2 initiation, even though MCV-1100C is aligred to Eus AIC. l l Irpell Cer;cratica Perert Fe. C1-C31G-1435 FB-39 Revision 0 1

10CFR50 APPEPDII R. SECTIts III.G Cl3tLIANCE EvaltiATItti FIRE ASEA /2mE 1-PS-14-8 416CV Seritekgeer poem Category System Camponeet Cfecuit-Schedule Function Consequence of Fire Mitigation Not CYC5 G-8A IGA 2CC7C44C Deset pesy trip Demoge to this circuit could Staney (contd) (centd) ressit in loss of resete control Egsfpment and/or prevent the pasp from auto (contd) starting on seguencer 2 inttfation. The peep could also be allowed to start on seguencer 2 initiation, even though POV-1100C is I al1gned in Bus AIC. 1GA2007C548 Dischcrge heater Damoge to this circuit could pressere interlock bypass the pressure interlock and spuriously start G-8A while G-88 is running, or prevent autostarting or the peop, and/or prevent remote operation of the pesp. 1EA2CC7A148 Sensor sfgnal Damage to thfs cfrcuit coald prevent peep operation. 1EA2C07C1-FC Indicatten signal Damage to this circuit could l prewest pump operat1on. Erroneous indication at panel ( C-47 is also possible. G-Et 1FA1C07P145 Power Loss of power to G-89. None. Cables for dedicated shutdoom system operation of G-6A are routed outside the ffre area and wt11 remein available. IFA1CC7C143 Auto start low pressure This circuit is entirely contained intibit faterlock within the fire area / zone. The  ! circuit and its terwination points are assened destroyed. - 1FA1CC7C24C Auto start pes 9 Damage to this circuit could  ; spurteesty start the pump, and/or prevent remote , operation of the pump, er prevent auto starting on sequencer fnitiattca. I Ieye11 Corporetten peprt Fe. Cl-C31C-le25 FS-40 pewfsfcn 0

                                                                                                                                                                                                                                                                             ~

l 10CFp50 AppfuCII p. SECTICE III.G CerLIANCE EVALUSTICK FIBE ASEA /20NE 1-pB-14-8 4160V 5mitchgoer pees Category System Campement Ciremit-5ctodele Function Consegnance of Fire Ritigation _ Not CVCS G-4B IFAICOK 3-as pesete pump control Damage to this circuit could Standby (conto) (contd) spurteesly start er step the Espalpment pump , and/or prevent remote (certd) operetten of the pump. 1FAICSK4-FC Weset pump trfy Camege to ttis eiresit could result in loss of remote control

and/or present the pesy from auto starting en seguencer l inttfation. The pump could l also be allowed to start on i segnancer 1 initiation, even theegh utV-1100C 1s aligned to bos A2C.

l IFAICCK5-EC peset pump trip Damese to this circuit could - result in less cf remote control and/or prevent the peep from aute starting en sequencer initiation. The peep comid also be allemed to start en segnancer 1 initiation. even though McV-1100C is aligned to bus A2C. IFAICSK6-E3 Discharge header Damage to this circuit could pr+ssure interlock typass the pressure faterlock and spuriously start the G-as enfle G-SA is running, or prevent autostarting of the peop. and/or prevent remote operetten of the peop. Indt1C07Al-t3 Senser sfgoal Damage to this cfrcutt could prevent pemy operetten. lum 1CSK1-EC Indication signal Damepe to this circuit could prevent pump operation. Errensees indicatten at panel C46 is also possible. E-942 1ES2A14C1-ES Interlett to G-8A Damege to this circuit could Operator action to transfer control of prevent autostart of G-942 G-942 to the dedicated shutdemn panel, uten G-SA is started, or Cables for the dedicated shutdeem system spuricasly start G-942 when operation of G-942 are located outside G-8A is not running, the fire area and will rerain available. Impe11 Corporatica perert po. 01-031C-1435 PS-41 Fevision 0

r-N N [ V b 10CFp50 APPEBCII F, SECTIC1i III.G CtprLIANCE EYALUATIC11 FIPE AREA /2(WE 1-PB-14-8 l 416CY Switchgear poor l Catecery Systee Conyement Circuit-Schedule Function Consequence of Fire Mitigation Met CYC5 G-943 IFPC129P14C Power Loss of power to G-943. None. Cables for dedicated shutdown system l l Stamey (coatd) operation of G-942 are routed outside the l Eesipsent fire area and will remain available. (coett) 1FBC129C14C GE8 inter 1cck Camege to this circuit could spuriously start the pump when G-88 is not r;;r.ning er prevent the pump from auto starting when G-88 is started and/or prevent its remote operation. IFBC129C34C Local pump control Damage to this circuit could [ prevent local manual start of the pump, or spuriously start the pump. 1WC129C44C Low bearing oil Camage to this circuit could !. rressure interlock prevent auto start of the pump, or spuriously start the puep. ! 5 8aF IIB 7A14C148 SIS initiated fan Damage to this circuit could Operator action to transfer control of control, s;criously start the fan and/or MG-8AF to the dedicated shutdown panel. prevent auto start of the fan. Cables for dedicated shutdown operation of 58AF are located outside the area and will recein available. 1 N-8BF 122A15C148 SIS initiated fan Damage to this circuit could None. Cables for dedicated shutdown syster coctrol. spuriously start the fan and/or operation of MG-8AF are routed outside the l prevent auto start of the fan, fire area and will recein available. l 1 1 l l [ I I l 1 1 Impe11 Carperatien Fevision 0 tercrt ro. 01-C310-1435 FB-42

p) ( v

                                                                      \

v

                                                                              )
                                                                                                                                        ,m
                                                                                                                                        \V}

10CFF50 APFEECIX P. SECTICN III.G CCMPLIA R E EVALUATICE i FIFE AFEA/ICNE 1-PP-14-8 4160V Switchgear Rom Cateeery Systee Cesperent Circuit-Scheeuie runction Consecuence cf Fire Mitigation Hot rYC5 CV-304 1FC107C714B Scienoid centrol power Camage to this circuit could Operator action to close FCV-1112 from the Standty (centd) prevent remote operation ard/or cedicated shutdown panel if isolation of l Equippect cause the valve to spuriously this ifne is required. CV-304 will open I (coctd) open or close. on pressure dif ferential if charging through loop A is required. CV-3C4/ IWY15CP48 12CVAC pcwer for CV-304, Loss of power to control room None. Yalves fail on loss of power to CV-305 CV-305, CV-267 CV-544 panel C09, causing CV-287, the position required for safe shutdown. CV-304, CV-305, and CV-544 to spuriously close and PCV-1115A, B, C to open. FC1-1112 IFCC1C7C14C Sequencer 1 initiatten Camace to this circuit could Operator action to position FCV-1112 from interlock result in the loss of rerote the dedicated shutdown panel, as required. valve control, and/or cause the Equiprent/ cables for dedicated shutdown valve to spuriously open, or syster operation of FCV-1112 are located prevent opening of the valve by outside the fire area and will remain secuencers 1 or 2. available. 1FCC107C24C Sequencer 2 initiation Damage to this circuit could interlock result in the loss of remote valve control, and/or cause the valve to spuriously open. 1FC107C11-r8 Positioner control Damage to this circuit could signal cause a loss of remote control and spuriously open the valve. Operation of the valve through sequencer 1 and 2 initiation ' would not be affected. 1FC107013-FB SV-1112 control reset Damage to this circuit could result in the loss of remote valve control. 1FC107027-KB 5ensor signal Carage to this circuit could

                                                       ,                   result in the loss of remote operation and/or cause the valve to spuriously open, IFC10702848  Senser signal                Parage to this circuit could cause the valve to spuriously open er close.

Irpell Ccrperatica pepert No. C1-0310-1435 PB-43 Fevision 0

10CF350 APPENCII R, SECTICW III.G COMPLIANCE EVALIJATION FIDE AREA /ZOWE 1-PS-14-8 4160V Switchcear Room Cateoory System Component Circuit-Schedule Function Consequence of Fire Mitigation Not CYC5 FCV-1112 IFC107037-KB SV-1112 position ramage to this circuit could Standby (contd) (contd) override solencid result in the loss of valve Equipment control power control through SV-1112 and (ceetd) cause the valve to spuriously open. 1WC107044-KB SV-1112 Control Damage to this circuit could . prevent reacte operation and/or cause the valve to spuriously open. 1WY11R7-KB Power Loss of power to FC-1112, PC430C, H and J, preventing operation of the valves. ! FCV-1112/ IFtC13001-EC Remote valve control Damage to this circuit could Operator actien to position FCV-1112 from ! FCV-456,7,8 result in the loss of remote the dedicated shutdown panel as required. valve control. Spurious actuation of FCV-456, FCV-457, and FCV-458 will not affect safe shutdown, as the sain feedwater pumps are tripped. i FT-1112 IFC107103-EB 5ensor signal Damage to this circuit could Operator action to position FCV-1112 from j result in erroneous indication the dedicated shutdown panel as required. j of charging flow rate and cause t spurious operation of FCV-1112. I l Power Loss of power to FCV-1112/ See FCV-1112 and FCV-1115A, B, C. ! FCV-1112/ IIY14P9-KB l FCV-1115A, FCV-1115A, B, C B, C l Control Signal Damage to this circuit could Operator action to fall open FCV-1115A by FCV-1115A 1FC107076-KB isolating instrument air at the doghouse, cause a loss of positioner control, causing FCV-1115A and verify FCV-1115D closed, and control seal FCV-11150 to close or result injection flow using renual valve located in a loss of instrument air upstream. Interruption of seal injection causing FCV-1115A to fail open. and seal cocifng to the reactor coolant pump seal for tre period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). Iepell Corpcration Revision 0 perert No. C1-031C-1435 PB-44

I f [% 10CFR50 APPEIElIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PS-14-8 4160V Switchgear Hoom Consequence of Fire Mitigation C-tegory System Component Circuit-Schedule Function Control Signal Damage to tnis circuit could Operator action to f ail open FCV-Ill56 by , Hot CVC5 FCV-11158 1GQ107077-KB cause a loss of positioner isolating instrument air at the doghouse. Standoy (contd) control, causing FCV-11156 and verify FCV-Il15E closes, and control seal Equipen t injection flow using manual valve located , FCV-1115E to close or result (contd) in a loss of instrument air upstrean. Interruption of seal injection causing FCV-1115s to f all open. and seal cooling to the reactor coolant pump seal for the period required to , initiate seal injection from tne dedicated shutdoun system has seen evaluated and determined to ce acceptacle (26). , Control Signal Damage to this circuit coule operator action to f ail open FCV-1115C oy FCV-1115C 1HQ107078-KB cause a loss of positioner isolating instrument air at the doghouse. l control, caasing FCV-1115C and verify FCV-1115F closed, and control seal FCV-1115F to close or result injection flow using manual valve located in a loss of instrument air upstream. Interruption of seal injection causing FCV-1115C to f all open. and seal cooling to the reactor coolant pump seal for the partod required to i initiate seal injection from the dedicated shutdown systen has been evaluated and determined to ne acceptacle (26). Damage to this circuit could See FCV-1115A, FCV-11158, and FCV-1115C FCV-1115/ 1WY14RS-K8 Power move. cause a loss of control power A. 8. C to FC-1115A, 8. C. closing valves FCV-1115A & D. 8 & E, C & F. Damage to this circuit could See PCV-IlldA, PCV-11156 and PCV-Ill5C PCV-1115 IWY141601-KB Power below, and FCV-Ill5A, FCV-Ill56 and cause a loss of power to A. 8. C YE-1115A. 8. C causing a low FCV-1115C move. offscale indication to FCV-1115A, 8. C. Tnts could open FCV-1115A 8. C and close PCV-1115A, S. C. Damage to this circuit could Operator action to deenergize 120VAC/480VAC PCV-1115A idQ107041-K8 Remote valve control / power to prevent / mitigate spurious indication prevent remote operation and/or cause the valve to spuriously operation. PCV-1115A will fail open on open or close. - loss of power. Impell Corporation Revision 0 Ceport No. 01-0310-1435 P8-45

O h O 4 V V V 10CFR50 APPENDIX P. SECTION III.G COMP 1.IANCE EVALUATION FIRE APEA/ZCNE 1-PB-14-8 4160V Switchgear Room Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CYCS PI-1115A/ IWC107057-KB Sensor Signal Damage to this circuit could Cperator action to fall open FCV-1115A by Standby (centd) PC-1115A cause a low off scale pressure isolating instrument air at the doghouse. Equipment indication which could cause verify FCV-11150 closed, and control seal (conte) FC-1115A to open FCV-1115A and upstream. Interruption of seal injection FCV-11150, and cause PC-1115A, and seal cooling to the reactor coolant to close PCV-1115A. pump seal for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). PT-1115A lWC107108-KB Sensor signal Damage to this circuit could Operator action to fail open FCV-1115A by result in high off-scale, low isolating instrument air at the doghouse, off-scale or erroneous indication, verify FCV-1115D closed, and control seal This could cause controller upstream. Interruption of seal injection FC-1115A to spuriously open or and seal cooling to the reactor coolant close FCV-1115A and FCV-11150, pump seal for the period required to and/or cause controller PC-1115A initiate seal injection from the dedicated to spuriously close PCV-1115A. shutdown system has been evaluated and determined to be acceptable (26). PCV-1115B 1WC107042-KB Remote valve control / Damage to this circuit could Operator action to deenergire 120VAC/480VAC indication prevent remote operation and/or power to prevent /sitigate spurious cause the valve to spuriously operation. PCV-1115B will fail open on open or close. loss of power. PI-1115B/ 1WC107058-KB Sensor Signal Damage to this circuit could Operator action to fail open FCV-11158 by PC-11158 cause a low offscale pressure isolating instrument air at the doghouse, indication which could cause verify FCV-1115E closed, and control seal FC-1115B to open FCV1115B and injection flow using manual valve located FCV-1115E and cause PC-1115B upstream. Interruption of seal injection to close POV-1115B. and seal cooling to the reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and deterwined to be acceptable (26). Impe11 Corporation R: pert No. 01-0310-1435 PB-46 Revision 0

10CFR50 APPENDIX P. SECTIfti III.G COPPLIANCE EVALUATICW FIpE AREA /70NE 1-Pp-14 8 4160V Switchgear Rocus Cateeory System Component Circuit-Schedule Function Consequence of Fire Mitigation hot CVCS PT-11158 IXQ107096-K8 Sensor signal Damage to this circuit could Operator action to fail open FCV-11158 by Standby (contd) result in high off-scale, low isolating instrument air at the doghouse. Equipment off-scale, or erroneous verify FCV-1115E closed, and control seal (contd) indication. This could cause injection flow using manual valve located controller FC-11156 to upstream. ' Interruption of seat injection spuriously open or close and seal cooling to the reactor coolant FCV-11158 and FCV-1115E, and/or pump seals for the period required to cause controller PC-11158 to initiate seal injection frem the dedicated - spuriously close PC-11158. shutdown system has been evaluated and determined to be acceptable (26). PCV-1115C IWC107043-K8 Remote valve control / Damage to this circuit could Operator action to deenergize 120VAC/460VAC indication prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously ooeration. PCV-1115C will fail open on

                                                                         - open or close.                        loss of power.

PI-1115C/ 1WQ107059-KB Sensor Signal Damage to this circuit could Operator action to fail open FCV-1115C by PC-1115C cause a low offscale pressure isolating instrument air at the doghouse, indication which could cause verify FCV-1115F closed, and control seal FC-1115C to open FCV1115C and - injection flow using manual valve located FCV-1115F and cause PC-1115C upstream. Interruption of seal injection to close PCV-1115C. and seal cooling to the reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). PT-1115C IWQ1070g7-K8 Sensor signal Damage to this circuit could Operator action to fail open FCV-1115C by result in high off-scale, low isolating instrument air at the doghouse, off-scale, or erroneous indication, verify FCV-1115F closed, and control seal This could cause controller injection flow using manual valve located FC-1115C to spuriously open or upstream. Interruption of seal injection close FCV-1115C and FCV-1115F, and seal cooling to the reactor coolant and/or cause controller PC-1115C pump seals for the period required to tp spuriously close PCV-1115C. Initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). ~ l l Impe11 Corporation Peport Fo, 01-0310-1435 PB-47 Revision 0 I

O O O 10CFR50 APPENDIX p. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8 416CV Switchgear Room Crtegory System Component Circuit-Schedule Function Consequene of Fire Mitigation Hot CVCS MCV-11008 1FB0147P1-KB Power Loss of power to McV-11008. Operator action to manually open MOV-11008 Standby (contd) The valve will fail as is, or MOV-110CC to initiate charging pump G-8A Equipment normally closed. operation from the dedicated shutdown (contd) system. 1FB0147C1-KB Position switch / torque Damage to this circuit could switch feedback prevent remote operation and/or l cause the valve to spuriously l open or close. l l 1FB0147C2-KB MCV-1100C open interlock Damage to this circuit could . I result in the loss of remote l valve control, and/or cause the valve to spuriously close. 1FB0147C3-KB Remote valve control Camage to this circuit could prevent remote operation and/or cause the valve to spuriously l open or close. 1FB0147C4-KC Sequencer 1 interlock Damage to this circuit could result in the loss of remote valve control, and/or cause the l valve to spuriously open, or t prevent is from opening. I 1FB0147C5-KC Remote valve control Damage to this circuit could I result in the loss of remote

valve control, and/or prevent operation via panel CO?.

l 1FB0147C8-KB Volume control tank Damage to this circuit could level interlock result in the loss of remote valve control, and/or cause the valve to spuriously close. l l I i o { Impe11 Corporation PIport No. 01-0310-1435 PB-48 Fevision 0 l

O O O 10CFR50 APPENDIX P SECTICN III.G COPPLIANCE EVALUATION FIRE APFA/ ZONE 1-PF-14-8 4160V Switchgear Poom Cctegory System Cogonent Circuit-Schedule Function Consecuence of Fire Mitigation Hot CVCS MOV-11000 lHB0378C5-KC Remote valve control Damage to this circuit could Operator action to manually open POV-11008 Stan &y (contd) result in the loss of remote or POV-11000 to initiate charging pump G-8A Equipment valve control. The valve will operation from the dedicated shutdown (contd) fail as is, normally closed. system. 1HB0378C7-KB Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. ' lHB0378C8-KB Volume control tank Damage to this circuit could level interlock result in the loss of remote

;                                                                           valve control, and/or cause the valve to spuriously close.
;                                 1XB2A71C1-KB  Volume control tank         Darage to this circuit could j                                               level interlock             result in the loss of remote valve control, and/or cause the valve to spuriously open.

M0Y-883 1HB0390Cl-KC Remote valve control / Damage to this circuit could Operator action to verify MOV-883 open 4 position indication prevent remote operation and/or to initiate charging pump G-BA operation j , cause the valve to spuriously from the dedicated shutdown system, a open or close. i ! lHB0390C3-KC Control power Damage to this circuit could 4 result in the loss of remote valve control. The valve will 1 fail as is, normally open, i lHB0390C4-KC Remote valve control Damage to this circuit could j result in the loss of remote j valve control. The valve will fail as is, normally open. 1HB0390C5-KC Remote valve control / Damage to this circuit could position indication result in the loss of rerote 'I valve control. The valve will l fail as is, normally open. 1 , 1HB0390C6-KC Remote valve control / Damage to this circuit could I position indication result in tre loss of remote ! valve control. The valve will fail as is, normally open. i 1 Iepell Corporation

!  Report Fo, 01-0310-1435                                                  PB-49                                                               Pevision 0 i

f v v d 10CFR50 APPENDIX P SECTICN III.G CCMPLIAkCE EVALUATICW FIRE AREA / ZONE l-PB-14-8 4160V Switchgear Poom Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot MSS CV-76,77, lWW10304-KB Interlock for CV-3,4, Damage to this circuit could Operator action to deenergize 125VDC and Standby 78,79 76,77,78 and 75 result in the transfer of valve 120VAC/4E0VAC power to prevent / mitigate Equipment control to the main steam spurious operation. Spurious actuation of (contd) pressure transmitter PT-459 the steam dump valves until operator (via YM-418A) or cause the action is taken to deenergize and close valves to spuriously open. the valves has been analyzed and will not result in an unacceptable condition (24,25). SV-85/ IFW10307-KB Solenoid control power Damage to this circuit could Operator action to deenergize 125VDC and SV-87 result in the transfer valve 120VAC/480VAC power to prevent / mitigate control to the main steam spurious operation. Spurious actuation of pressure transmitter PT-459 the steam dump valves until operator (via YM-418A) or cause the action is taken to deenergize and close valve to spuriously open. the valves has been analyzed and will not result in an unacceptable condition (24,25). SV-86/ 1GW10306-KB SV-86/SV-88 control Damage to this circuit could Operator action to deenergize 125YDC and SV-88 result in tt.e transfer valve 120VAC/480VAC power to prevent / mitigate control to the main steam spurious operation. Spurious actuation of pressure transmitter PT-459 the steam dump valves until operator (via YM-418A) or cause the action is taken to deenergize and close the valves has been analyzed and will not ! valve to spuriously open. result in an unacceptable condition (24,25). ] i SV-85,86, 1WD0128Dl-KB Solenoid control power Damage to this circuit could Operator action to deenergize 125YDC and 87,88 result in the loss of remote 120VAC/460VAC power to prevent / mitigate valve control or transfer spurious operation. Spurious actuation of valve control to the main steam the steam durp valves until operator pressure transmitter PT-459 action is taken to deepergize and close (via YM-418A). the valves has been analyzed and will not result in an unacceptable condition (24,25). l Impell Corporation Report Ho. 01-0310-1435 PB-50 Pevision 0

10CFR50 APPENDIX P SECTION III.G COMPLIANCE EVALUATION - FIPE AREA / ZONE l-PB-14-8 4160V Switchgear poem Category System Corponent Circuit-Schedule Function Consequence of Fire . -Mitigation Hot MS$ PC-418A IWQ100004-KB Control signal Damage to this circuit could Operator action to deenergize 125VOC and Standby (contd) cause valves CV3, CV4, CV76, CV77, 120VAC/480VAC power to prevent / mitigate Equipment CV78 and CV79 to spuriously close spurious operation. Spurious actuation of (contd) and/or result in low off-scale or the steam dump valves until operator erroneous indication, action is taken to deenergize and close

                              -                                                                                   the valves has been analyzed and will not result in an unacceptable condition (24,25).

lWQ108110-KB Loop continuity signal Damage to this circuit could result in low off-scale indication and keep the turbine bypass valves closed. 1WW10309-KB Controller output Damage to this circuit could signal to atmospheric cause valves CV3, CV4, CV76, dump valves CV77, CV78, CV79 to spuriously close or open. lWW10310-KB Controller output Damage to this circuit could signal to atmospheric cause valves CV3, CV4, CV76, dump valves CV77, CV78, CV79 to spuriously close or open. lWY14R5-KB Power Damage to this circuit could cause valves CV3, CV4, CV76, CV77, CV78, CV79 to spuriously close. IXY14R601-KB Power Damage to this circuit could cause valves CV3, CV4, CV76, CV77, CV78, CV79 to spuriously

                                        ,                                      close.

PT-459 IWQ108119-KB Sensor signal Damage to this circuit could Operator action to deenergize 125V DC and result in bigh off-scale, low 120V AC/480V AC power to prevent / mitigate off-scale, or erroneous spurious operation. Spurious actuation of indication. This could the steam dump valves until operator cause controller PC-418A to action is taken to deenergize and close spuriously open or close CV3, the valves has been analyzed and will not CV4, CV76, CV77, CV78 and CV79. result in an unacceptable condition (24,25). lWQll2014-KB Sensor signal Damage to this circuit could result in low off-scale indication and keep the turbine bypass valves closed. Impell Corporation Peport No. 01-0310-1435 PB-51 Pevision 0

I /"N . i

                                                                          %Y                                                             N.Y 10CFR50 APPENDIX P. SECTION III.G CCMPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room Category    System Ccuponent Circuit-Schedule Function                      Consequence of Fire                    Mitigation Hot         MSS      MOV-14   1YB0364Cl-KB     Remote valve control      Damage to inis circuit could    Operator action to manually close MOV-14 Stsndby     (contd)                                                      prevent remote operation and/or Spurious actuation of this valve until Equipment                                                                cause the valve to spuriously   the operator action is performed, has been (contd)                                                                  open or close,                  analyzed and has been determined to be acceptable (24,25).

MOV-15 1YB0372Cl-KB Remote valve control Damage to this circuit could Operator action to manually close MOV-15. prevent remote operation and/or Spurious actuation of this valve until cause the valve to spuriously the operator action is performed, has been open or close, analyzed and has been determined to be acceptable (24,25). MOV-16 1YB0375Cl-KB Remote valve control Damage to this circuit could Operator action to manually close MOV-16 prevent remote operation and/or Spurious actuation of this valve until I cause the valve to spuriously the operator action is perforwed, has been open or close. analyzed and has been determined to be i i acceptable (24,25). MOV-17 lYB0379Cl-KB Remote valve control Damage to this circuit could Operator action to manually close MOV-17.

i. prevent rerote operation and/or Spurious actuation of this valve until cause the valve to spuriously the operator action is performed, has been open or close, analyzed and has been deterwined to be acceptable (24,25).

3 i i j l 1 1, i  ! Impell Corporation Report No. 01-0310-1435 PB-52 Revision 0

v 10CFP50 APPENDIX R. SECTION III.G CCMPLIANCE EVALUATION FIPE APEA/ ZONE 1-PB-14-8 4160V Switchgear Poem Catecory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot MSS PV-1611, 1WT10101-KB Manual turbine trip Damace to this circuit could Operator action to trip the turbine at the Standby (contd) PV-1612 result in the loss of remote turbine stand. Spurious operation of these Eculpeent valve control, and/or cause the valves until operator action is taken to (contd) valve to spuriously close, or manually trip the turbine, has been prevent them from being closed, analyzed and has been determined to be acceptable (24,25). 1WT10105-FB SCRAM A 8 B interlock Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close, or prevent them from being closed. 1WT10106-KB Generator disconnect Damage to this circuit could interlock result in the loss of remote valve control, and/or cause the valve to spuriously close. 1WT10108-KB Solenoid control Damage to this circuit could cause loss of remote control PV1611, PV1612, and/or cause SV-57 to spuriously close. 1WT10109-KB Low control oil Damage to this circuit could pressure interlock result in the loss of remote valve control, and/or cause the valve to spuriously close. 1WT10201-KB Power Damage to this circuit could result in the loss of remote valve control. 1WT10203-KB Auto-stop latch relay Damage to this circuit could reset result in the loss of remote valve control. 1WT10304-KB Turbine trip alares Damage to this circuit could cause loss of remote control to PV-1611 PV-1612 and/or cause erroneous alares. 1YD0113Dl-KB 125VDC Power Damage to this circuit could result in the loss of remote valve control for PV-1611, PV-1612, PV-1607, PV-1608, PV-1609 and PV-1610 Impe11 Corporation Peport No. C1-0310-1435 PB-53 Revision 0

J~ b (V\ 10CFR50 APPENDIX R, SECTION III.G CCPPLIANCE EVALUATION FIPE APEA/ ZONE 1-PB-14-S 4160V Switchgear Room

                                                                                                                                                          ~

Cet:gery System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot MSS PV-1612 IWT10305-KB Remote valve control Damage to this circuit could Operator action to trip the turbine at the Standby (contd) result in the loss of remote turbine stand. Spurious operation of this Equipment valve control, and/or cause the valve until operator action is taken to (contd) valve to spuriously c1cse. manually trip the turbine, has been analyzed and has been determined to be acceptable (24,25). AFW G-1CS 1FBS125PI-KC Power Loss of power to G-105. None. Dedicated auxiliary feedwater pump will remain available. Loss of auxiliary feedwater flow until operator action is taken to initiate auxiliary feedwater flow from the dedicated shutdown system, has been evaluated and deterwined to be acceptable (24,25). 1FBS125C1-KC Pemote Pump control Damage to this circuit could result in the loss of remote , control of pump G-los and MOV-1202 and/or spuriously open or prevent closing of MOV-1202 1FBS125C2-KC Alars circuit / indication Damage to this circuit could cause the loss of remote control of G-105 and McV-1202 and/or spuriously stop G-105. 1FBS125C8-KC MOV-1202 interlock Damage to this circuit could prevent operation of G-105 and M0Y-1202 from panel C-71. Operation of G-105 via handswitch at panel C-38 would not be affected. Irpell Corporation Pirort No. 01-0310-1435 PB-54 Pevision 0

m - g 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation l Hot AFV G-10S/ 1FBS125C9-KC 125VDC power remote Damage to this circuit could None. Dedicated auxiliary feedwater pump _ 4 St ndby (contd) POV-1202 valve control / position spuriously start the pump will reeafn available. Loss of auxiliary Equipment indication and/or cause MOV-1202 to feedwater flow until operator action is (czntd) spuriously open. Operation taken to initiate auxiliary feedwater flow , of the pump at panel C-38 from the dedicated shutdown system, has would be prevented, been evaluated and determined to be acceptable (24,25). _ i j MOV-1202 IFB0137P1-KC Power Loss of power to MOV-1202 None. Dedicated auxiliary feedwater , 1 pump will remain available. Loss of i auxiliary feedwater flow until operator action is taken to initiate auxiliary feedwater flow from the dedicated shutdown syster, has been evaluated and determined to be acceptable (24,25). 2 1FB0137C1-KC Position switch / torque Damage to this circuit could i switch feedback result in the loss of remote valve control. IFB0137C2-KC Remote valve control Damage to this circuit could , cause loss of remote control ! and cause the valve to l spuriously open and close.  ; i I 1 l i j 2 l j l i t i i 1 ) - i, i Impe11 Corporation Paport No. 01-0310-1435 PB-55 Fevision 0 1 i

a s g3 ( I E I

                                                                           /                                                           G'
                                        ,  10CFR50 APPENDIX R SFCTION III.G COPPLIANCF EVALUATION FIRE AREA / ZONE 1-PB-14-8 416CY Switchgear Poom Category System Component Circuit-Schedule Function                         Consequence of Fire                      Mitigation Hot          CCW     G-15A  IFBS121P2-KB    Power                       Loss of power to G-15A.           None. Ctepenent cooling water is not         .

Standby required to support dedicated shutdown Equipment system operation. Interruption of seal (contd) cooling and seal injection to the reactor , coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been , evalutated and determined to be acceptable (26). IFBS121Cl-KC Sequencer 1 interlock Damage to this circuit could spuriously start the pump and/or prevent remote operation. IFBS121C3-KB G-158 interlock Damage to this circuit could spuriously start the pump and/or prevent remote operation. 1FBS121C4-KB G-15C interlock Damage to this circuit could spuriously start the pump and/or prevent remote operation. 1FBS121C5-KB Pemote control / Damage to this circuit could indication spuriously start or stop the pump and/or prevent remote operation of the pump. IFBS121C7-KB G-15B interlock Damage to this circuit could prevent remote operation of the pump. 1FBS121C8-KB G-15C interlock Damate to this circuit could prevent remote operation of the pump. 1FBS121C9-KB Discharge pressure Damage to this circuit could interlock spuriously start the pump and/or prevent remote operation, or prevent it from autostarting. 1ABDND270-KB Remote control Damage to this circuit could prevent auto start or remote operation of the pump. Iripell Corporation Revision 0 Prport No. 01-0310-1435 FB-56

b

              )                                                       U 10CFRSC APPENDIX R. SECTICN III.G COMPLIANCE EVALUATION V

FIPE AREA / ZONE 1-PB-14-8 4160V Switchgear Room ~ Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CCW G-158 1GBS221C1-KC Sequencer 2 interlock Damage to this circuit could None. Component cooling water is not Standby (contd) spuriously start the pump and/or required to support dedicated shutdown Feufpment prevent remote operation.or system operation. Interruption of seal (contd) autostarting. cooling and seal injection to the reactor coolant pump seals for the period reouf red to initiate seal injection from the dedicated shutdown system has been evalutated and determined to be acceptable (26). IGBS221C2-KB G-15A interlock Damace to this circuit could spuriously start the pump and/or prevent remote operation. , 1GBS221C5-KB Pesote pump control Damage to this circuit could spuriously start or stop the pump, ard/or prevent remote operation of the pump. 1GBS221C7-KB G-15C interlock Damage to this circuit could prevent the pump from autostarting; however, hand

  • witch control from the control room is still available.

1GBS22108-KB Pressure interlock Damage to this circuit could spuriously start the pump and/or prevent remote operation, or autostarting. 1WBS221C3-KB G-15C interlock Damage to this circuit could prevent remote operation of the pump. lABON0269-KB Remote control Damage to this circuit could prevent autostart or remote operation of the pump. Impell Corporation R: port No. 01-0310-1435 PB-57 Revision C

                                                                         '                                                                                                                   d                 <

10CFR50 APPENDIX R. SECTION !!!.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-Pd-14-8 i 4160V Switchgear Koom Category System Component Circult-Scheoule Function Consequence of Fire nitigation Hot CCu G-ISC IHdO305C3-Ku G-ISA interlock Damage to tnis circuit could None. Component cooling water is not ' Standoy (contd) prevent remote operation required to support dea 1cated snutdown Equipment of the pop. system operation. Interruption of seal (contd) cooling and seal injection to the reactor ' coolant pop seals for the period required to initiate seal injection from the dedicated shutdown system nas ceen evalutated and detemined to be acceptable (26). 1HB0305C6-K8 Remote control / Damge to this circuit could indication spuriously start or stop the pump, and/or prevent remote operation of the pop. lH80305C8-KB Discharge pressure Damage to this circuit could interlock spuriously start the pump and/or prevent remote operation, or autostarting. 1H85305C1-KC Sequencer 2 interlock Damage to this circuit could spuriously start the pump and/or i prevent remote operation. l 1Hs5305C4-K8 G-ISA interlock Damage to tnis circuit could spuriously start tne pump and/or prevent remote operation. IHH5305C5-Ku G-158 interlock Damage to this circuit could prevent remote operation of tne pump. lABDN0268-K8 Remote control Damage to this circuit could I prevent autostart or remote operation of the pap. i t i

 !  Impell Corporation Report No. 01-0310-1435                                                 Po-58                                                                                                               Revision 0

b O 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION O J FIRE AREA / ZONE 1-P8-14-8 4160V Switchgear Room , Category System Component Circult-Schedule Function Consequence of Fire Nitigation Hot CCW G-964 IWD0120C1-K8 Bus 1C and 2C under Damage to this circuit could Operator action to start G-964 at 125VDC ~ Standby (contd) voltage autostart spuriously start the pump if in Bus 1. Interruption of seal cooling Equipment interlock the auto mode and/or prevent and seal injection to the reactor coolant l (contd) pump autostart. However, the pump seals for the period required to p op could still be controlled initate seal injection from the dedicated i via control room panel or P8-2 shutdown system has been evaluated and at DC switchgear room numer 1. determined acceptable (26). , IdD0120C2-KB Bus 1C and 2C under Damage to this circuit could voltage autostart prevent autostarting of the pump, interloct or if the pop is in auto mode, cause spurious starting. i IXUO120C3-KB Sus IC and 2C under Damage to tnis circuit could , voltage autostart prevent autostarting of tne pump, f interloca or if the pump is in auto moce. cause spurious starting. 1YD0120C6-K8 Pump discharge low Damage to this circuit could pressure interlock spuriously start the pump and/or , prevent remote operation or autostarting. Damage to this circuit could also cause the l p op to run continuously, l regardless of pressure level I if in the auto mode. l b MOV-720A 1G80288C3-KB Remote valve control Damage to this circuit could None. j result in the loss of remote valve control, and/or cause the valve to spuriously open or close. , l i

                                                                                                                                   ~

1 l l s l l i l Impe11 Corporation Report No. 01-0310-1435 PB-59 Revision 0  ; l l 1 -

           %                                                                                                                                3 3
                                                                                                                                              \
                                                                                                                                           ~.)

10CFR50 APPENDIX R. SECTION III.G CDsFLIANCE EVALUATION FIRE AREA / ZONE l-P8-14-8 4160V Switchgear Room Crtegory System Component Circuit-Scnedule Function Consequence of Fire stitigation Hot CCW #4UV-720s 1Fu0187PI-Ku Power Loss of power to fa#-720s. Tne hone. Standby (contd) valve will fail as is. Equipment (contd) IFe0187C1-Kd Position switen/ torque Damage to tnis circuit coulo switch feeocacs result in the loss of remote valve control. The valve will fall as is. IF80187C2-K8 G-13A interlock This circuit is entirely contained within the fire area / zone. The circuit and its termination points are assianed destroyed. 1F80187C3-KB Remote valve control Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open or close. CV-722A 1WQ106019-KB Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation, if required to support operation open or close. of the thermal barrier pump. CV-7228 1dQ106015-K8 Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause tne valve to spuriously operation, if requireo to support operation open or close. of tne tnermal carrier pwp. CV-722C IwQ106016-K8 solenoid control power Damage to tnis circuit coulo Operator action to oeenergize 120VAC/480VAC prevent realote operation and/or power to prevent / mitigate spurious cause tne valve to spuriously operation, if required to support operation open or close. of the thermal narrier pump. CV-722 lWY1204-KB Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC A.B.C result in the loss of remote power to prevent / mitigate spurious valve control. operation, if required to support operation of the thermal barrier pump. Impell Corporation Report No. 01-0310-1435 P8-60 Revtston 0

10CFR50 APPENDIX N. MCTION III.G C0ffLIANCE EVALUATION FIRE AREA / ZONE l-PS-14-8 4160V Switchgear Room C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot SWC G-13A IF85114P2-K8 Power Loss of power to G-13A. None. The saltwater cooling system is not Standby (contd) required to support dedicated shutdown Equipment system operation. (contd) IFBSil4C2-KB Remote control / Damage to this circuit could indication spuriously start or stop the pump, and/or prevent remote operation of the pump. IFBSil4C4-KB Autostart PS-28 low Damage to this circuit could pressure interlock prevent remote operation of the pump, or spuriously stop G-13A or spuriously start G-138. G-138 IG85214C3-K8 Remote control / Damage to tnis circuit coula Mone. Tne saltwater cooling systes is not indication spuriously start or stop tne required to support cedicated snutdown pwap, ana/or prevent remote system operation. ' operation of the pump. CVS A-9 IW80109P1-KB Power Loss of power to A-9. None. The reactor cavity cooling fans are required only to support operation of tne source range monitors. i lW80109Cl-K8 Remote control / indication Danabtothiscircuitcould spur sly start or stop the fan and/or prevent remote operation of the fan. , 1WB0109C3-KB TS-24 interlock Damage to this circuit could spuriously start or stop the fan and/or prevent remote operation of the fan. PO-11 IW80109C2-KB Damper control Damage to this circuit could None. The reactor cavity cooling fans are [ 4

result in the loss of remote required only to support operation of the I control, and/or cause the source range monitors.

damper to spuriously close. Impell Corporation l Report No. 01-0310-1435 PB-61 Revision 0 < I l

                                                                                                                                                                                                                                                             /%

O"% O"\ U 10CFR50 APPEN0!I R. SECTION III.G COW LIANCE EVALUATION FIRE AREA / ZONE 1-PS-14-8 4160V Switchgear Room Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot DG C-40 1GA2C15CY-KC Manual test Damage to this circuit could Operator action to trip diesel generator 2. . Standby allow test starting of the Dedicated snutdown system will remain Equipment diesel generator even if tne availaole. protective circuit sensed a (contd) proolem: or prevent seal In of tne diesel generator manual test start relay. IGNUG2C05-KC Emergency engine stop/ Damage to tais circuit could diesel generator load spuriously energize the engine start - complete stop solenoid $V-303, or spuriously indicates diesel . ready for loading or loading complete; or bypass the diesel stop interlocks. IGNDG2007-KC Engine stop switch Damage to this circuit could stop the engine, prevent remote operation of the diesel or prevent loading of the generator.  ! 1GNDG2C08-KC Unit available/ lockout Damage to this circuit could relay interlock stop the generator loading sequence or provide erroneous availability indication. 1GNDG2009-KC Sequencer 2 initiation Damage to this circuit could i spuriously start diesel . l generator 2 engine, and/or prevent its remote operation. IGNOG2C10-KC Sequencer 2 initiation Damage to tnis circuit could i ' spuriously start diesel generator 2 engine, and/or i l l prevent its remote operation. IGNDG2C12-KC Local / remote status Damage to this circuit could prevent loading of tne generator onto the Dus. IGNDG2C13-KC Generator 2 lockout Damage to this circuit could spuriously start diesel generator 2 engine, and/or prevent its auto starting by the sequencer, or prevent loading of the generator onto the bus, but the diesel engine would not stop. Impell Corporation Report No. 01-0310-1435 PB-62 Revision 0 _. ._ ._. ._. . . _ _ . . _ _ _ ~ _ . _ . . _ _ _ _ _ _ ._ _ _

t 10CFRb0 ArYEhuli M. M.CTION lil.G CuWLIANCE LWALUATiun Flue AxEA/lumE 1-Ps-14-d 4160V $witcngear Noam Category System Component Circuit-Senedule Function Consequence of Fire Mitigation Hot DG C-48 IFUO119D1-KC Diesel generator 1 Loss of diesel local control Operator action to trip diesel generator I. Standby '8" start circuit power panel C-48. The dedicated shutdown system will remain (contd) available. Equipment (contd) 1FD0126D1-KC Diesel generator 1 Loss of diesel local control n "A" start circuit power panel C-48. IFNDGIC05-KC Emergency engine stop/ Damage to this circuit could diesel generator load spuriously energize the

start - complete engine stop solenoid SV-303, or spuriously indicate the

! diesel was loaded or ready for i loading or deenergize the entire engine control circuit but not stop the diesel. 1 IFNDGIC07-KC Engine stop switch Damage to this circuit could spuriously stop tne engine,  ! I prevent remote operation of l tne ciesel or prevent loading ! of tne generator. ( IFla3GIC08-KC Unit availaole/locuout Damage to this circuit could relay interloct spuriously stop tne generator  ; loading sequence or provice  ; e*coneous availapility indication. \ i IFNDG1009-KC Sequencer 1 initiation Damage to this circuit could I spuriously start diesel generator 1 engine, and/or i prevent its remote operation. 1FIOGIC10-KC Sequencer 1 initiation Damage to this circuit could i spuriously start diesel  ; generator 1 engine, and/or  ; prevent its remote operation.

                                                                                                                                                                                                                                                            }[

1FNDG1C12-KC Local / remote status Damage to this circuit could  ; prevent loading of the generator onto the bus. . t IFNDGIC13-KC Generator 1 lockout Damage to this circuit could spuriously start diesel generator 1 engine, and/or prevent its autostarting by the I sequencer, or prevent loading I of tne generator onto the Dus, ' out tne diesel engine would not stop. , t impell Corporation a= et > 01 nu n 14% ps-63 Revision 0

s 3

                                                                                                                                      )

10CFR50 APPENDIX R, SECTICN III.G C0pFLIANCE EVALUATION FIRE AREA /20NE 1-PS-14-8 4160V Switchgear Room Crtegory System Component Circult-Schedule Function Consequence of Fire Mitigation G-62 IGD 022503-KC Remote indication Damage to this circuit could None. Dedicated shutdown system will Hot DG Staney (contd) spuriously stop the pump and/or remain availaole. Equipment prevent its remote operation. (contd) 1GD0225D8-KC Remote indication Damage to tnis circuit could spurtously stop the pump and/or prevent its remote operation. l G-14A lidis20C6-KC Remote pump control / Damage to this circuit coulo mone. Uedicated snutdown system will indication spuriously start or stop tne remain availaole, pump, and/or prevent remote operation of the p op. 1F81820C7-KC Remote control Damage to this circuit could spuriously stop the punp spriously start pumps G-74A and 8, and/or prevent remote operation of the pop. 1F81820C8-KC Remote control Damage to this circuit could result in the loss of automatic operation and/or loss of remote pump control. l G-748 1F81819C6-KC Remote pump control Damage to this circuit could None. Dedicated shutdown system will spuriously start or stop the remain available. pump, and/or prevent remote operation of the pump. IF61819C7-KC Remote pump control Damage to tnis circuit coula spuriously start or stop tne pump, and/or prevent remote operation of tne p op. IFald19CS-KC stenote control Damage to this circuit could result in tne loss of auto- _ matic operation and/or loss of remote pump control. Impe11 Corporation Reoort No. 01-0310-1435 PB-64 Revision 0 I

10CFR50 APPEh011 n. SECTION III.G CDpFLIANCE EVALUATIJN FIRE AREA /Zuhf. I-Ps-14-d 4160V Seitengear Noam Cetegory System Component Circult-Scneaule Function Consequence of Fire nitigation Hot DG G-75A IGu2619C6-KC Remote control / Damage to tnis circuit could none. Deatcated snuteuwe system will 5taney (contd) indication spuriously start or stop tne remain availaole. Equipment pump, and/or prevent remote (contd) operation of the pump. IG82819C7-KC Remote control Damage to this circuit could spuriously stop the pump, spuriously start pops G-75A and B. and/or prevent - remote operation of the pump. 1G82819C8-KC Remote control Damage to this circuit could i prevent autostart and/or remote operation of the pump. G-758 1G82820C6-KC Remote control / Damage to this circuit could hone. Dedicated shutdown system will indication spuriously start or stop the remain available. pise, and/or prevent remote operation of tt.e p op. igd 2820C7-KC Memote control Damage to tnis circuit could { spuriously stop tne pop or spuriously start ooth G-75A and G-7:Hs,and/or prevent remote operation of the pump. 1Gd2520C8-KC Remote control Damage to this circuit could I prevent autostart and/or l , remote operation of the pump. 1682820C9-KC Remote control Damage to this circuit could [ prevent autostart and/or remote operation of the pump. , i l G-76 1F0011403-KC Remote pop Damage to this circuit could None. Dedicated shutdown system will L l indication cause loss of remote pump remain available. l control and/or erroneous indication of pop status. 1FD0114D6-KC Pow r Loss of power to G-76. 1FD0114D8-KC Pump operation Damage to this circuit could ' indication result in the loss of remote pump control. i Impell Corporation Neport No. 01-031D-1435 Po-65 Kevision U t

       . . , . , _ _ . . . - .                                                                       .. -- -_ ,                                                                    ..n   _ . . __              , ~        , . , . - - -

w

 . . . _ , -              . . . . .              .-            -.         __ - _ .                   -       .       . ~-              - ._ - .-                    _       . - - .                . _ ,   . . . -                        ,_ .

T , g

                                                                      *                                                       \                                                                                            )
                                                                                                                                                                                                                           /

10CFR50 APPENDIX R, SECTION III.G C0pFLIAICE EVALUATION FIRE AREA /20mE 1-PS-14-8 4160V Switchgear Room Crtegory System Camponent Circuit-Schedule Functics Consequence of Fire Nitigation i I Hot DG PSL-180 1FHDGIC03-KC Low pressure / manual Damage to this circuit could None. Dedicated snutdown system will Staney (contd) test loss control sourtously start the diesel remain ave 11able.  : Equipen t power lockout generator or initiate loading  ! (contd) sequence and/or prevent starting of the diesel. i PSL-181 IFNDGIC04-KC Remote control / manual Damage to this circuit could hone. Dedicated shutdown system will i test start spuriously start tne diesel remain availaole.  ! 6 generator and/or prevent starting of the diesel. I PSL-215 1GhuG2004-KC Memote control / manual Damage to this circuit coula mone. Dedicated snutdown system will  ! test start spuriously start the diesel remain availaole. [ generator 2 and/or prevent , its remote operation.  ; i PSL-221 1GNDG2CO3-KC Low pressure / manual Damage to this circuit could None. Dedicated shutdown system will i test / loss of control spuriously start the diesel remain availele. Power lockout generator or initiate loading t sequence and/or prevent starting e of the diesel. [ t i

                                                                                                                                                    -                                                                                          t l

l I ! t i t

                                                                                                                                            .                                                                                                  t i

Impe11 Corporation ' Report No. 01-0310-1435 PB-66 Revision 0

(G 10CFR50 APPEh0!X R. SECTION !!!.G C0rFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-14-8 4160V $witchgear koon 1 Category System Component Circuit-Seneaule Function Consequence of Fire Mitigation Hot IJG Eut! IFAIC14C5-KC Generator output voltage Damage to tnis circuit could hone. Decicated snutoown system will Staney (contd) to 160 relays spuriously trip tne output remain availaole. Equipment oreaner. (contd) } IFD010501-KC Diesel generator 1 Loss of exciter caninet E08. exciter / regulator power 1FHIC01C4-KC Auto volt raise / lower. Damage to this circuit could remote field on/off result in the excitation circuit obtaining a spurious signal to raise or lower the generator's output voltage, and/or cause the inanility to raise or lower the output i voltage J IFHIC01C6-KC Remote at:to/manuel Damage to this circuit could

select.'wtor spuriously lower the operated potentiometer generator's output voltage t

control and/or cause the loss of remote voltage control. I '

;                           IFHIC01C7-KC      Auto and manual adjust       Damage to this circuit could f                                             indication, motor            spuriously raise or collapse

] operator potentiometer the generator's output voltage - control or cause a loss of remote j voltage control. IFHIC01CF-KC Power to interface Damage to tnis circuit could ' relays cause a loss of a Utesel gener-ator output or prevent ener-gization or deenergize tne ' I reset emergency shutdown coil. i IFHIC01CG-KC Offsite breakers open Damage to this circuit could a verification spuriously trip the generator and/or provide false position indicaton of the normal offsite feeder breaker 11CO2 and allow or prevent diesel generator i loading. s i l Impell Corporation Report No. 01-0310-;435 P8-61 Nevision U

         ,-                                                                                                         , ~ .

Qj ' QJ 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-PU-14-8 4160V $witchgear Room Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot DG EOS 1FHIC01CH-KC Block emergency shutdown Damage to this circuit could Staney (cetd) (contd) cause a loss of Diesel Equipment generator output or remove the (contd) " reverse power" emergency shut-down capability or cause the

                                                                        " reverse power" shutdown trip to be retained.

1FH1C01CJ-KC Voltmeter signal Damage to this circuit could spuriously cause the loss or unstaDility of generator output voltage. IfHIC01CL-KC Emergency snutdown Damage to tnis circuit could cause a loss of Diesel generator output or remove shutdown capaD111ty from control room panel C41 and Diesel generator room panel C44. 1FH1C01CM-KC Emergency shutdown Damage to this circuit could spuriously shutdown the generator or prevent its start or stop. 1FHIC01CS-KC Voltage regulator Damage to this circuit could setpoint indication result in loss of generator output and/or erroneous indica-tion at C41. Impe11 Corporation Report No. 01-0310-1435 PB-68 Revision 0

                                                                                                                                                   '1 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-14-8 4160V Switchgear Room Category Sys tem Component Circuit-Senedule Function                         Consequence of Fire                    Mitigation Hot         UG      E09     1GA2C15C4-KC     Generator volt sense        Damage to tnis circuit could      hone. Dedic.ted snutdown system will Standby     (contd)                          to synchron12er panel        trip the generators output       remain availaole.

Equipment creamer or disconnect tne (contd) generator output creaker protection function if tne diesel generator is sequencer started. 1GA2C15C5-KC Generator output voltage Damage to this circuit could to 160 relays spuriously trip the output breaker. 1GH2001C4-KC Auto voltage raise / lower Damage to this circuit could remote field on/off result in the excitation circuit obtaining a spurious signal to raise or lower the generator's output voltage, and/or cause the inability to raise or lower the output voltage. 1GH2C01C6-KC Remote auto / manual Damage to this circuit could select motor operated spuriously lower the pctentiometer control, generator's output voltage voltage regulator and/or cause a loss of indication remote voltage control. 1GH2C01C7-KC Auto and manual adjust Damage to this circuit could indication, motor oper- spuriusly raise or drop ated potentiometer tne generator's output control, remote manual voltage, or cause a loss switch. of remote voltage control. 1GH2001CF-KC Power to interface Damage to this circuit coula relays cause a loss of diesel generator output or deenergize or prevent energization of the reset emergency shutdown coll. 1GH2001CG-KC Offsite breakers open Danage to this circuit could verification spuriously trip the generator and/or provide false position indication of the normal offsite feeder breaker 12C02 and allow or prevent diesel generator loading. Impe11 Corporation Report No. 01-0310-1435 PB-69 Hevision 0

                                                                                        ~~.

p. 10CFR50 APPENDIX R. SECTION !!!.G CtWLIAhCE EVALUATION FIRE AREA /ZDNE 1-Pts-14-8 ~ 4160V Switchgear Room j Category Systen Component Circult-Schedule Function Consequence of Fire Mitigation Hot DE E09 IGH2C01CH-KC Block emergency shutdown Damage to this circuit could Standby (contd) (cratd) cause a loss of Diesel Equipment generator output or remove the '1 (contd) " reverse power" emergency shut-down capability or cause the

                                                                                   " reverse power" shutewn trip to be retained.

1GH2001CJ-KC Generator voltmeter Damage to this circuit could at C42 spuriously cause the loss of or unstability of generator output 4 vol tage. i' IGH2C01CL-KC Emergency shutdown Damage to this circuit could cause a loss of Diesel gener-ator output or remove snutdown { capa0111ty from control room panel C4I and Diesel generator rece panel C44, 1GH2C01CM-KC Emergency snutdown Damage to tnis circuit could spuriously shutdown the generator or prevent its start . or stop. l

'                                                                                                                                                      r 4

1GH2C01CS-KC Voltage regulator Damage to this circuit could , setpoint indication result in loss of generator  ! output and/or erroneous , indication at C41.  ; 1 I '

                                                                                                                                                     -f I

I i I , 1 1 i Impe11 Corporation Report No. 01-0310-1435 PB-70 Revision 0 ,

T [, p 'K 10CFR50 APPENDIX R, SECTION III.G C00FLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot GNI CV-532 1GD0220PI-KC Power Damage to tnis circuit could Operator action to open manual oypass for 5t:ndoy result in the loss of remote CV-532 to supply nitrogen for tne operation Equipment valve control, and/or cause tne of the PokVs and cloct valves from tne valve to spuriously close. dedicated snutdown panel. (contd) IGUO220C4-KC Remote valve control / Damage to this circuit could position inoication prevent remote operation and/or cause tne valve to spuriously open or close. Cold RHR G-14A IF85122P1-KC Power Loss of power to G-14A. None. Dedicated auxiliary feedwater pump Shutdown will remain availaole for single phase Equipment cooldown. IFBS122C1-K8 Remote pump control Damage to this circuit could spuriously start or stop the pump, and/or prevent remote operation of the p op. IFBS122C2-KC Breaker '.

                                                       . ip circuit       Damage to this circuit could spuriously stop the pump and/or l

prevent its remote operation. G-148 IG85222C1-K8 Remote pump control Damage to this circuit could None. Dedicated auxiliary feedwater pump l will remain availaole for single pha,e spuriously start or stop the l pop, and/or prevent remote cooldown. operation of the pop. l l

                                                                                                                                                        ~

l - Impe11 Corporation Report No. 01-0310-1435 P8-71 Revision 0

                                                                          .g                                                              ,s 10CFRSO APPEhulX k M CTION !!!.G CurFLIAnCE LVALUATION FIRE AkEA/lohE I-Pu-14-8 4160V Switengear noom Category System Component     Circuit-Schedule Function                         Consequence of Fire                     Mitigation Cald        Rift     MOV-813  IF80169PI-K8     Power                        Loss of power to MOV-813.        Maintain power to MOV-813 locued out Shutdown    (contd)                                                                                          during power operation to prevent spurious Equipment                                                                                                    operation.

(contd) Danage to this circuit could IF80169Cl-K8 Remote valve control result in the loss of remote valve control, and/or cause the valve to spuriously open. 1F 80169C2-K8 Low reactor coolant Damage to this circuit could pressure interlock remove the RCS high pressure interlock. 1F80169C3-K8 Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. Valve will fall as is, normally closed. MOV-814 1G80271C1-Ku Remote valve control Damage to this circuit could none. Tnts line is isolated oy MOV-813. result in the loss of remote Operation of MOV-8141s not required for valve control, and/or cause the single pnase cooldown. valve to spuriously open. MOV-822A 1FH0164P1-K8 Power Loss of power to MOV-822A. None. Tnts valve is not required for single phase cooldown. 1F80164C1-K8 Remote valve control Damage to this circuit could prevent remote operation and/or Cause the valve to spuriously open or close. 1F80164C2-KB Position switch / torque Damage to this circuit could switch feedback result in the loss of remote valve control. Valve will fail as is. 4 Impell Corporation Report No. 01-0310-1435 P8-72 Revision 0

l O O 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION O FIRE AREA / ZONE l-PS-14-8 4160V Switchgear Room Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation MOV-8228 IG80266Cl-KB Remote valve control Damage to this circuit could None. This valve is not required for Cold RMt pre. vent remote operation and/or single phase cooldown. Snutdoom (contd) cr.use tne valve to spuriously Equipment (contd) epen or close. MOV-833 ifs 0170PI-KB Power Loss of power to MOV-833. None. Tnis line is isolateo oy MuV-834. Operation of MOV-833 is not required for single pnase coolooem. lib 0170Cl-Ks Remote valve control Damage to this circuit coulo result in the loss of remote valve control, and/or cause the valve to spuriously open. 1F80170C2-K8 Position switch /tortiue Damage to this circuit could switch feedback result in the loss of remote valve control. Valve will fail as is, normally closed. MOV-834 IG80272Cl-K8 Remote valve control Damage to this circuit could Maintain power to MOV-834 locked out result in the loss of remote during power operation to prevent spurious valve control, and/or cause the operation. valve to spuriously open. 1G80272C2-KB Low reactor coolant Damage to this circuit could pressure interlock remove the RCS high pressure interlock. TE-600- IWQ106026-Ks Sensor signal Damage to this circuit could None. Tnis instrument is not required for result in hign off-scale, low single pnase cooldown. off-scale, or erroneous indication. TR-600 IWQ106009-Ks Temperature recorder Damage to tnis circuit could None. ,Tnis instrument is not requireo for signal result in nign off-scale, low single pnase cooloown. off-scale, or erroneous indication. HCV-602 IFQ106018-KB Remote valve control Damage to this circuit could None. Tnis valve is not required for result in the loss of remote single phase cooldown. valve control, and/or cause the valve to spuriously open. lWYllR501-KB Power Loss of power to HCV-602. Imoell Corporation PS-73 Revision 0 Reoort No. 01-0310-1435

m (-- /O U 10CFR50 APPEh01X k, SECTION III.G CupFLIANCE EVAL 0ATION FIRE AkEA/ ZONE 1-P8-14-8 4to0V Switcngear Room Category System Component Circuit-Scnedule Function Consequence of Fire Mitigation Cold RtSt HCV-602/ IXY11R502-Kd Power Loss of power to TI/TC 601A, None. Tnis equipment is not required for shutdom (contd) TE-601A,5 601B and HCV-602, single phase cooldown. Equipment (contd) None. This equipment is not required for TE-601A,B 1WY110902-K8 Power Damage to this circuit could cause a loss of power to single phase cooldown. auxiliary coolant rack C-23 and cause a low scale temperature indication on TI-601 A and 8. TE-601A 1FQ106024-KB Sensor signal. Damage to this circuit could None. This equipment is not required for result in high off-scale, low single phase cooldown. off-scale, or erroneous indication. This would cause the flow controller TC-601A to spuriously open or close TCV-601A. IFQ106005-KB Indicator Damage to this circuit could controller signal result in low off-scale or erroneous indication. Tnis could cause the flow controller to spuriously close TCV-601A. TE-601B 1GQ106025-Kd Sensor signal Damage to this circuit could None. This equipment is not required for result in hign off-scale, low single phase cooldown. off-scale, or erroneous indication. This could cause the flow controller TC-6018 to spuriously open or close TCV-6018. 1GQ106006-KB Indicator Damage to this circuit could controller signal' result in low off-scale or erroneous indication. This could cause the flow con-troller to spuriously close TCV-6018. Impe11 Corporation Report No. 01-0310-1435 P8-/4 Revision U

               ^

J b 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION U

                                                                                                                                                                ~

FIRE AREA / ZONE 1-P8-14-8 4160V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Csid CCW TCV-601A 1FQ106010-K8 Valve position feedback Damage to this circuit could None. The component cooling water system Shutdown result in the loss of is not required to support dedicated Equipment posit'on indication, shutdown system operation. (contd) 3 IFQ106011-K8 Control signal Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open. TCV-60ld IGQ106012-Kd Valve position feedoacx Damage to tnis circuit coulo None. Tne component cooling water system result in the loss of valve is not requireo to support oeoicateo position indication. snutdown system operation. 1GQ106013-Ku Control signal Damage to tnis circuit could result in the loss of remote valve control, and/or cause tne valve to spuriously open. l 1 1 i j a 1 4 4 Impe11 Corporation Report No. 01-0310-1435 PB-75 Revision 0 1

                                                                                                                                                           )
            \                                                                C)                                                                 .

10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION ' FIRE AREA / ZONE 1-Pu-14-8 4160V $witcngear koom

                                                                                                                                                                                ~

Category System Component Circuit-Schedule Functiors Consequence of Fire Mitigation IFY3312CA-KC Solenoid control power Damage to this circuit could Operator action to oeenergize 120VAC/48uvAC High/ Low RCh SV-2401 p)wer to prevent / mitigate spurious Pressure result in tne loss of ce note valve control, and/or cause tne operation. Vent valves will fall closeo on Interface valve to spuriously open. loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close tne valves, ' has oeen analyzed, and will not result in an unacceptable condition (24,25). SV-2402 IFY3312CB-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. Vent valves will fail closed on valve to spuriously open. loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). , 1FY3312CI-KC Power Damsge to this circuit could Operator action to deenergize 120VAC/480VAC SV-2401/ SV-2402 car.se a loss of control power power to prevent / mitigate spurious te these valves. operation. Vent valves will fail closeo on 4 Ioss of power. Spurious actuation of tne ! vent valves, until operator action is l taten to deenergize ano close tne valves, t nas oeen analyzed, ano will not result in

!                                                                                                                 an unacceptaole conoitton (24,25).

a 1FY3312CJ-KC Power Damage to tnis circuit coJld prevent remote operation and/or cause the valve to spuriously open or close. SV-2403 IF Y3312CC-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious

  • valve control, and/or cause the operation. Vent valves will fail closed on ,

valve to spuriously open. loss of power. Spurious actuation of the vent valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). I l Impell Corporation Report No. 01-0310-1435 Pu-76 Kevision 0

s-.= ._ _ . , _ y' . .;

  • 10CFR50 APPENDIX R, SECTION III.G CUNPLIANCE EVALUATION FIRE AREA / ZONE 1-Pd-14-8 4160V Switchgear Room Consequence of Fire Mitigation j Category System Component Circuit-Schedfle Function r High/ Low P3 SV-2404 IFY3312CD-KC Solenoid control power Damage to this circuit could ' Operator action to deenergize 120VAC/480WAC l result in the loss of remote power to prevent / mitigate spurious Pressure (contd) operation. Vent valves will fail closed on I Interface- . valve control, and/or cause the valve to spuriously open. loss of power. Spurious actuation of the

] (contd) vent valves, until operator action is l taken to deenergize and close the valves, i has been analyzed, and will not result in l i an unacceptaole condition (24,25). t s SV-2403/ IFY3312CK-KC Power Damage to this circuit could Operator action to deenergize 120WAC/480WAC ,

SV-24G4 result in tne loss of. remote power to prevent / mitigate spurious 4 valve control. operation. Vent valves will f ail closea on 4

loss of power. Spurious actuation of the l vent valves, until operator action is l j tagen to deenergize and close the valves, i 4

  1. has seen analyzed, and will not result in 6 an unacceptaole condition (24,25). i j  !

i l 'IFY3312CL-KC Power Damage to this circuit could t i prevent remote operation and/or  ; I cause the valve to spuriously ' i open or close. I Q SV-2401, 1FY3312PI-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC 02, 03, 04 result in the loss of power to prevent / mitigate spurious control power to these valves. operation. Vent valves will fall closed on { loss of power. Spurious actuation of the 9 vent valves, until operator action is j i taken to deenergize and close the valves, has been analyzed, and will not result in

an unacceptable condition (24,25).

I f i 1 , i 4 l t 3 i i i . ! I i 1

!                Impell Corporation Report No. 01-0310-1435                                                                P8-77                                                                       Revision 0 i                                                                                                                                                                                                      6
   -,m_            -                              ,      _ __,                                     --.             . _ . _ _ _      -.                                                _ _ _ _ _ _ _ _

_ ... - . - . _-. - -. -_. - -, _ . - . - . . ~ 10CFR50 APPENDIX R. SECTION III.G CtMPLIANCE EVALUATIOh l FIRE AREA / ZONE l-P8-14-8 4160V Switchgear Noca Category- Systen Component Ci rcuit-Schedule Function Consequence of Fire Mitigation

                                                                                                                                                                  }

Hip / Low CVCS CV-527 IFY121P04-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC Pressure prevent remote operation and/or power to prevent / mitigate spurious Interface cause the valve to spuriously operation. Spurious actuation of tnis close, valve, until operator action is taken to (contd) 1 deenergize and close the valve has been ! analyzed, and determined to be acceptable ' (24,25). i CV-527/ IFY121P01-KC Power Damage to this circuit could Operator action to deenergize 120VAC/480VAC i 1 CV-525 result in the loss of remote power to prevent / mitigate spurious l valve control, and/or cause the operation. Spurious actuation of the valve to spuriously close. seal return and letdown valves, until

- operator action is taten to deenergize and close tne valves, has been analyzee and oetermined to oe acceptable (24,25).

{ IFM1111C3-KC Remote valve control / Damage to tnis circuit could position indication cause the valves to spuriously 4 open or close, and/or prevent j the valves from oeing closed. ' i CV-528 1GY2A36P4-KC Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. Spurious actuation of tnis ] i close. valve, until operator action is taken to I deenergize and close the valve, has been analyzed, and determined to ne acceptable (24,25). 1 i l l t i i i I j f Irpell Corporation , Report No. 01-0310-1435 PB-78 Revision 0

                                                                                       .~                                   _

D f r k 10CFR50 APPEN0!K R SECTION Ill.6 COMPLIANCE EVALUATION FIRE AREA / ZONE 1-P5-14-8 4160V Switengear Roan

          - Crtegory Systen Component                     Circuit-Schedule Function                                        . Consequence of Fire                              Mitigation High/ Low CVCS        CV-528/                   16Y2A36P1-KC                 Power                            Damage to this circuit could        Operator action to deenergize 120VAC/480WAC Pressure    (contd) CV-526                                                                                    result in the loss of remote        power to prevent / mitigate spurious operation. . Spurious actuation of this Interface                                                                                                     valve control, and/or cause the                                                              '

l (contd) valve to spuriously close, valve, untti operator action is taken to ^ deenergize and close the valve, has been analyzed, and determined to be aceptable (24,25). 4 I IGY2909C5-KC Remote valve control / Damage to this circuit could j position indication cause the valves to spuriously ' open or close, and/or prevent l the valves from being closed. ! Spurious RCS G-2A IXA1A03P1-Kd Power Loss of power to G-2A. None. Turbine trip will deenergize this Upe='ation pump. l '

Equipment

! 1XA1A03P2-K8 . Power Loss of power to G-zA. I ImA1A03Cl-K8 L e e oil p op interlock Damage to this circuit coulo 1 spuriously start the pump and/or I prevent its remote operation. i. j IM1A03C3-K8 RCS loop temperature Damage to this circuit could i differential interlock spuriously start the pump and/or ! prevent its remote operation. l Damage to this circuit could 4 1M1A03C4-K8 011 lift pressure i interlock spuriously start the pump and/or prevent its remote operation. l I ElB03C2-KB Sequencer trip Damage to this circuit could initiation spuriously stop the pump and/or prevent its remote operation. I WlA03C2-K8 Remote breaker control Damage to this circuit could j spuriously start or stop the i i: pump, and/or prevent remote operation of the p o p. l x

                                                                                                                                                                                                                    .\

l i ! Impell Corporation Report No. 01-0310-1435 -PB-79 Revision 0 i,

  .__,-_4                        _ . - . . - . . .       _ . .     ,,        ,                        i,,                         __    -.-               __    ,,                                        _ , , ,

{\ bx U 10CFR50 APPENDII R. SECTION III.G CopFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-14-8 4160V Switchgear Rooe Consequence of Fire Mitigation + Cr;tegory System Component Circuit-Schedule Function I dl803P1-K8 Loss of power to G-28. None. Turnine trip will deenergize this Spurious RCS G-28 Power pump. Operation (contd) Equipment idAls03P2-K8 Power Loss of power to G-28. (contd) I dluG3Cl-Kn Diesel generator and Damage to tnis circuit could undervoltage trip spuriously stop G-2A, G-25, " ano 6-2C and/or prevent i remote operation. l I dlB03C4-KB Remote Dreaker control Damage to this circuit could ' spuriously start or stop the pump, and/or prevent remote operation of the pump. IIA 1003C3-K8 Lube oil pump interlock Damage to this circuit could spuriously start the pump and/or l prevent its remote operation. 1 1XA1803C5-KB RCS loop temperature Damage to this circuit could 1 differential interlock spuriously start the pump and/or l prevent its remote operation. l I dlB03C6-K8 011 lift pressure Damage to this circuit could interlock spuriously start the pump and/or prevent its remote operation. I i l l i l i l r

                                                                                                                                                                                              +

i l i Impell Corporation Report No. 01-0310-1435 PS-80 Revision 0 l

w IEfx50 AP/EhblX R. SECTION 111.6 COMPLIAhCE HALUAT10N Flui AREA / LONE l-Pa-14-d 4160V Switcngear Moon Consequence of Fire Mitigation Category System Component Circuit-Schedule Function Spurious RCS G-2C IWA1A0lPI-KB Power Loss of power to G-2C. None. Turnine trip will deenergize this Operation (contd) pump. Equipment (contd) IWA1A01P2-K8 Power Loss of power to G-2C. lWA1A01C2-KB Remote breaker control Damage to this circuit could spuriously start or stop the puso, and/or prevent remote operation of the pump. lWA1A01C3-K8 RCS loop temperature Damage to this circuit could differential interlock spuriously start the pump and/or prevent its remote operation. 1hA1A01C4-K8 011 lift pressure Damage to this circuit could interlock spuriously start the pump and/or prevent its remote operation, lYAIA0lCl-Ks Oil pump interlocs Damage to tnis circuit could spuriously start tne pump and/or prevent its remote operation. PCV-430C Positioner signal Damage to this circuit could None, as reactor coolant pumps are IFQ100005-Kn result in the loss of remote tripped. valve control, and/or cause the valve to spuriously close. PCV-430H Positioner signal Damage to this circuit could None, as reactor coolant puips are 1GQ100006-KB result in the loss of remote tripped. valve control , and/or cause the valve to spuriously close. I l l l l l Impell Corporation Nevision 0 Report No. 01-0310-1435 Pu-81 1 -

l I - rh 10CFd50 APPEN011 R SECTI(A !!!.G CGEPLIANCE EVALUATION FINE ANEA/ Zone 1-Ps-14-8 4160V Switengear doon Category System e- rrt Circuit-Senedule Function Consequence of Fire nitigation l Spurious CVC5 6-42 1Hb2A10CI-Ks Remote p op control / Damage to tnis circuit could operator action to trip offsite/ diesel Operation position indication spuriously start tae pump and/or generator power will deenergize this pump. Equipment prevent its remote operation. (centd) 1H82A10C2-Ks Local pump control Damage to this circuit could spuriously start the pop and/or prevent its remote or local operation. CV-305 TWQ107070-KB Solenoid control power Damage to this circuit could Operator action to deenergize 120VAC/480VAC result in the loss of remote power to prevent / mitigate spurious valve control, and/or cause the operation. Spurious actuation of this valve to spuriously close. valve untti operator action is taken to doenergize and close the valve, has been analyzed and determined to be acceptable (24,25). CV-334 1FQ107033-K8 Solenoid control power Damage to this circuit could Operator action to close manual valve prwvent remote operation and/or located upstream of CV-334. cause the valve to spuriously open or close. l l ImV1404-Ks Solenoid control power Damage to tnis circuit could ! result in the loss of remote j valve control , and/or cause tne i valve to spuriously open. I ( Damage to this circuit could Operator action to desnergize 120VAC/480VAC CV-525 1FY121P02-KC Remote valve control prevent remote operation and/or power to prevent / mitigate spurious cause the valve to spuriously operation. Spurious actuation of this open or close. valve, untti operator action is taken to deenergize and close the valve, has been analyzed and determined to be acceptable (24,25). CV-526 1GY2A36P5-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent remote operation and/or power to prevent / mitigate sourious cause the valve to spuriously operation. Spurious actuation of this l close. valve, untti operator action is tauen to l deenergize and close tne valve, has been analyzed and determined to se acceptacle l ' (24,25). Impell Corporation Report No. Oi-0310-1435 Ps-82 Nevision U l

10CFR50 APPENDIX R, SECTION III.G C0ffLIANCE EVALUATION FIRE AREA /ZDNE 1-PS-14-8 4160V 5=1tchgear Room Crtegory System rampanent C.rcuit-Sched: ale Function Consequence of Fire 8titigation Spurious CYCS FCV-1102A 11dQ107007-K8 FCV-1102A solenoid Damage to this circuit could Operator action to deenergize 120VAC/480WAC Operation (contd) control prevent remote operation and/or power to prevent / mitigate spurious Equipment cause the valve to spuriously operation. FCV-1102A will fait closed on (contd) open or close. loss of power. Spurious actuation of tnis i valve, until operator action is tanen to deenergize and close the valve, nas been analyzed and oetermined to ne acceptable i (27). l FCV-1102s lwQ107009-Ks FCV-1102s solenoid Damage to tnis circuit could Operator action to close manual valve control pre /ent remote operation ana/or located counstream of FCV-Ilo2A. cause the valve to spuriously I open or close. FCV-1102A, IwY1411-K8 Power Damage to this circuit could See FCV-1102A and FCV-11028 aoove. , FCV-11028 cause a loss of power and prevent operation of FCV-1102A and FCV-11028. IXQ107016-KB Remote valve control Damage to this circuit could l cause a loss of remote valve control. Damage to this circuit could also cause FCV-1102A to spuriously open and/or FCV-11028 to spuriously close or prevent Fyr-1102A t.~ : oeing opened and/or FCV-11028 from being closed. FCV-11150 1GD02050A-KC Remote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent control of FCV-11150 power to prevent / mitigate spurious via tne nitrogen supply operation. FCV-Ill5D will fail closed on system or tne normal plant loss of power. Instrument air system. IGUO205DB-KC Remote valve control uamage to tnis circuit could prevent control of FCV-IllbE via tne nitrogen supply system. Control via the normal plant instrument air system would still be availaole. I Impe11 Corporation Report No. 01-0310-1435 PB-83 Revision 0

              /-                                                           ,
                                                                                                                                                 ,~,

i

              'a)                                                          s v'
                                                                                    !                                                            (

xs' 10CFR50 APPENDIX R, SECTION III.G C091.IAXCE EVALUATION FIRE AREA / ZONE 1-P8-14-8 4160V $witchgear Room C*tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious CVCS FCV-1115E 1G00205EA-KC Remote valve control Damage to this circuit could Operator acton to deenergize 120VAC/480VAC Operation (c>ntd) prevent control of FCV-11150 power to prevent / mitigates spurious E.m, ipment via tne nitrogen supply operation. FCV-Ill5E will f at i closed on (contd) system or the normal plant loss of power. instrument air system. 1G00205EB-KC Remote valve control Damage to this circuit could prevent control of FCV-Ill5E via the nitrogen supply system. Control via tne normal plant instrument air systen would still oe availaole. FCV-1115F 1G30205FA-KC Renote valve control Damage to this circuit could Operator action to deenergize 120VAC/480VAC prevent control of FCV-1115F power to prevent / mitigate spurious via tne nitrogen supply operation. FCV-1115F will fall closed on system or the normal plant loss of power. Instrument air system. 1GD0205FB-KC Remote valve control Damage to this circuit could prevent control of FCV-1115F via the nitrogen supply system. Control via the normal plant instrument air system would still De availaole. FCV-1115/ 1GD020502-KC Power Damage to tnis circuit could Operator action to deenergize 120VAC/480VAC D E.F prevet tne control of FCV-11150, power to prevent / mitigate spurious E F via the nitrogen supply operation. system. Control via the normal plant instrument air system would still oe available. IG00205D6-KC Power Damage to this circuit could prevent the control of FCV-11150 E, F via the nitrogen supply i system. Control via the l normal plant instrument air system would still De availadle. 1GYYO23P3-KC Power Damage to this circuit could prevent the control of FCV-1115D, E. F via the nitrogen supply system. Control via the normal plant instrument air system would still ne available. Incell Corporation Report No. 01-0310-1435 PB-84 Revision 0

C O O

                                             - 10CFR50 APPEIGIX R, SECT 10el III.G COpFLIANCE EVALUATIdel FIRE AREA /2DuE 1-Ps-14-8 4160V Suitchgear Room Crtegory System rampneent Circuit-Schedule Function                         Consequence of Fire                   Etigation le0V-11008 interlock       Damage to this circuit could     Operator action to manually close Spurious CVCS       MOV-1100C 1680147C9-KB Operation (contd)                                                       prevent remote operation and/or  IWW-1100C.

Etsuipment cause the valve to spuriously (contd) open or close. 1682A76C2-KB Remote valve control Damage to this circuit could l prevent remote operation and/or cause the valve to spuriously open or close. 1Gd2A76C3-K8 Volume control tant Damage to this circuit could level interloca prevent remote operation and/or cause the valve to spuriously open or close. igm 2A76C5-Ks Volume control tant Damage to tais circuit could interlock result in loss of remote valve control and/or cause tne valve to spuriously close. l i I l l l Impell Corporation Revision 0 Report No. 01-0310-1435 P8-85

          ,~
          &                                                          A.,)                                                             Y_,Y 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION l

FIRE AREA / ZONE l-P8-14-8 4160V Switchgear Room l Cstegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious MSS SV-89/ IW10305-Ks Remote valve control Damage to tnis circuit could Operator action to deenergize 12bVUC power Operation SV-90 transfer control of valves CV-3 to prevent / mitigate spurious operation. Equipment CV-4 to tne main steam pressure Spurious actuation of tne concenser otanp transmitter PT-459 (via YM-4188) valves, until operator action is tacen to (contd) or cause the valve to spuriously ceenergize and close tne valves, nas oeen open. analyzed and will not result in an unacces, table conottion (24,25). SV-119 IFM127C42-KC Remote valve control Damage to this circuit could Operator action to deenergize 125VDC power prevent remote operation and/or to prevent / mitigate spurious operation, cause the valve to spuriously open or close. SV-119/ IFM127C57-KC Remote valve control / Damage to this circuit could Operator action to deenergize 125VDC power SV-123 position indication prevent remote operation and/or to prevent / mitigate spurious operation, cause the valve to spuriously open or close. SV-120 IFM127C43-KC Remote valve control Damage to this circuit could Operator action to deenergize 125VDC power prevent remote operation and/cr to prevent / mitigate spurious operation. cause the valve to spuriously open or close. Impell Corporation Revision 0 Report No. 01-0310-1435 P8-86

[ q , 10CFN50 APPENDIX R MCTION Ill.G CuffLIANCE EVALdATION FINE AREA / ZONE l-Pti-14-8 4160V $witchgear Rotan Crtegory System Component Circult-Schedule Function Consequence of Fire Mitigation Remote valve control / Damage to this circuit could Operator action to deenergize 125VDC power Spurious MSS SV-120/ 1FM127C58-KC to prevent / mitigate spurious operation. Operation (contd) SV-122 position indication prevent rem 6te operation and/or l Equipment cause the valve to spuriously open or close. (contd) / IFM127C44-KC Remote valve control Damage to this circuit could Operator action to deenergize 125VDC power SV-121 prevent remote operation and/or to prevent / mitigate spurious operation. cause the valve to spuriously open or Close. 1FM127C59-KC Remote valve control / Damage to this circuit could Operator action to deenergize 125VDC power SV-121/ to prevent / mitigate spurious operation, l' SV-124 position indication prevent remote operation and/or cause tne valve to spuriously open or close.

                       $V-122  IFM127C45-KC   Remote valve control         Damage to tnis circuit could      Operator action to deenergize 12dvuc power prevent remote operation and/or   to prevent / mitigate spurious operation.

cause the valve to spuriously open or close. SV-123 IFM127C46-KC Remote valve control Damage to this circuit could Operator action to deenergize 125VDC power l prevent remote operation and/or to prevent / mitigate spuricus operation. cause the valve to spuriously open or close. IFM127C47-KC Remote valve control Damage to tais circuit could Operator action to deenergize 125VDC power SV-124 prevent remete operation and/or to prevent / mitigate spurious operation. cause the valve to spuriously I open or cisse. 1 Impell Corporation Revision 0 Report No. 01-0310-1435 P8-87  : l

O . O 10CFR50 APPENDIX R. SECTIOD III.G C0pFLIANCE EVALUATION O FIRE AREA /ZDNE 1-PB-14-8 4160V Switchgear Roan Category System Component Circuit-Schedule Function Consequence of Fire Mit t ention Spurious AFd MOV-1204 1F80127P1-KC Power loss of power to MOV-1204. None. Spurious operation of tnis valve Operation will not affect the operation of the Equipment dedicated auxiliary teeesater po p. (contd) 1Ft:0127Cl-KC Position switch / torque Damage to this circuit coulo sulten feedoact result in the loss of remote control. Tne valve will fail as is, normally closed. IF50127C2-KC Remote valve control Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1FB0127C4-KC Remote valve control Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously close. CRS G-27N IFBS119P2-K8 Power Loss of power to G-27N. Operator action to trip offsite/ diesel generator power will deenergize this pop. 1FBS119C7-KC Remote pump control Damage to this circuit could spuriously start or stop the p op, and/or prevent remote operation of the p o p. 1FBS119C9-KC Pump control / indication Damage to this circuit could spuriously start or stop the pop, and/or prevent remote operation of tne pop. IfoS119CA-KC Containment spray Damage to tnis circuit could initiation interlock spuriously start or stop tne pup, and/or prevent remote operation of the p op. 1FSS119CC-KC Undervoltage locuout Damage to tnis circuit could spuriously stop the pump and/or prevent its remote operation. Impe11 Corporation Report No. 01-0310-1435 PB-88 Revision 0

_ _ _ . _ _ _ . . = - _______ _ _ _ ______ _ __ _ _ _ _ _ _ __ _ ______ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ , d a 10CFM50 APPEh011 W. SECTION III.G COMPLIANCE LWALGATION

                                                                                                                                                                                                                                                ~

FletE AREA / ZONE 1-Ps-14-8 4to0V Suitchgear Room Category System e - -- _ at Circuit-Schedule Function Consequence of Fire Nitigation Spurious CRS G-275 1G85219C7-KC Remote pump control /. Damage to this circuit could Operator action to trip offsite/ diesel Operation (contd) indication -spuriously start or stop the generator power will deenergize this pump. Equipment - pump, and/or prevent remote (contd) operation of the pump. 1GBS219C9-KC Pop control / Damage to this circuit could indication spuriously start or stop the pump , and/or prevent remote operation of the pump. 1GBS219CA-KC Containment spray Damage to this circuit could initiation interlock - spuriously start or stop the ptmp , and/or prevent remote operation of the p o p. 1GBS219CC-KC undervoltage interlock Damage to this circuit could spuriously stop the pump and/or prevent its remote operation. CV-82 IFM1111C8-KC Control power / position Damage to this circuit could operator action to close manual valve indication prevent runote operation and/or located upstream. cause the valve to spuriously open or close. IFM1111CC-KC Control power Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1FM1111CD-KC Control power / position Damage to this circuit could indication prevent remote operation and/or cause the valve to spuriously open or close. CV-114 1911214CA-KC Control power and Damage to this circuit could Operator action to close manual valve position indication prevent remote operation and/or located upstreas. cause the valve to spuriously open or close. 1GM1214C8-KC Control power Damage to this circuit could prevent remote operation and/or cause the valve to spuriously open or close. 1GM1214CC-EC Control power and Damage to this circuit cuuta position indication prevent remote operation and/or cause the valve to spuriously open or close. Impell Corporation

                   * ~ " . ni nun-lam                                                                                              Pd-89                                                                                             Revision 0

i p d ( 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION l ' FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Spurious SIS MOV-356 IFB0158C1-KB Remote valve control Damage to this circuit could None. Spurious actuation of this valve Operation result in the loss of remote will divert flow from the seal injection Equipment valve control, and/or cause the flowpath to the cnarging safety injection (contd) valve to spuriously open. flongatn. The effects of the spurious actuation nave oeen analyzed. Tne analysis demonstrates that adequate flow will remain availaole for seal injection (28). IFo0158C2-Kd Position switcn/ torque Damage to tnis circuit coulo switch feedoacx result in tne loss of remote valve control. The valve will f ail as is, normally closed. IF80158P1-Ks Power Loss of power to MW-356. MOV-357 1G90243C1-KB Remote valve control Damage to this circuit could None. Spurious actuation of this valve result in the loss of remote util divert flow from the seal frdection valve control, and/or cause the flowpath to the charging safety injection valve to spuriously open. flowpath. The effects of the spurtous actuation have been analyzed. The analysis demonstrates that adequate flow will remain available for seal injection (28). MOV-353 1H80335Cl-KB Remote valve control Damage to this circuit could mone. Spurious actuation of this valve result 11 the loss of remote will divert flow from the seal injection valve control, and/or cause tne flowpatn to the cnarging safety injection valve to spuriously open. flowpath. Tne ef fects of tne spurious actuation nave been analyzed. Tne analysis demonstrates tnat adequate flow will remain availaole for seal injection (28). Impell Corporation Report No. 01-0310-1435 P B-90 Revision 0

10CFR50 APPEh011 a. SECTIon III.G CtsFLIAmCE EVAWATI0e FIDE AREAn0aE l-Ps-14-d 4160W :witengear noen Category 51 sten Component Circutt-Seneoule Function Consequence of Fire Mitigation spurious Fs6 FCV-456 luull2011-Ka Remote valve control Damage to tnis circuit could mone. Mata fecesater pues,s are trippee. Operation cause a loss of steam generator A Egalpment level setpotat stgaal, causing (contd) FCV-456 to spuriously open. 1MQ112024-KB Remote valve control Damage to this circuit could cause a loss of remote valve control, spuriously open the valve. ad cause pumps G-3A and G-38 to trip. I i l FCT-457 14112012-KB Remote valve control Damage to this circuit could Isone. Main facesater pumps we tripped. cause a loss of steam generator 8 level setpoint signal, causing FCY-457 to spuriously open. 1MQ112025-KB Remote valve control Damage to this circuit could cause a loss of remote valve control, spuriously open tne valve. and cace peeps G-3A and G-3s to trip. l FCV-45d luyll2013-Es Remote valve cetrol uamage to tais circuit could home. nate fecesater posips are trippes. cause a loss of steam generator C l level setpotat signal, causing FCY-458 to spuriously open. l l 1MQ112026-Ks Remote valve control Damage to this circuit could cause a loss of remote valve control and spuriously open the valve ad then cause pumps G3A and G38 to trip. i l FT-456 1FQ112031-KB Sensor signal Damage to this circuit could home. Main fecesater puuss are tripped. I cause erroneous feeduater flou j indication and spuriously open or close FCV-456. l l l 1 l l Impell Corporatton keport Eo. 01-0310-1435 - Ps-9i Revis1on U i l

                                                                                                                                                                                                \

10CFR50 APPENDIX R. SECTIOut III.G CDPPLIAACE EVAUMTID4 FIaE MEA /ID4E 1-PS-14-8 4160v 5eitchgear Roan Category Systen Connement Circutt-Schedale Fwattien Consequence of Fire Ritigation

                                                       $surtous F16                                                   FT-457    1GQ112032-G              Sensor signal                                   Damage to this circuit could     none. Rain feeesater peups we tripped.

Operation (contd) cause erroneous fecesater flou Egefonent indication and spuriously open (conto) or close FCT-457 l FT-458 1HQ112033-M Sensor signal Damage to this circuit could mene. Main feeesater pisips s e tripped, cause erroneous feessater flos inetcattan and spurtously open i or close FCV-456. l i FT-460 IFQ112034-u wser signal Damage to tats circuit could home. main feeenater pumps se trippes. spurtously close tne male feeenater control valve and/or cause a reactor scran. l t ! IFY1t10- u Pouer Damage to this circuit could cause a loss of pouer to FT-460 ( ! causing FCV-456 to close. and/or cause a reactor scram.

FT-461 1GQ112035-G 5ensor signal Damage to this circuit could bene. Main feeesater pumps we trt yee.

spuriously close the main l i feeenster control valve and/or i cause a reactor scran. ISTR10-G Pouer Damage to this circuit could l cause a less of pouer to FT-460 I causing FCV-456 to close, and/or cause a reactor scran. l FT-462 1HQ112030-2 Sensor signal Damage to tais circuit could home. Main feeenater peups we tripped. l spuriously close tne main feehter control valve and/or cause a reactor scram. leffkl0-Es Pouer Damage to tais circuit coule cause a loss of pouer to FT-460 causing FCV-4% to close, ana/er caJse a reactor scram. l Imeell Carperation Report No. 01-0313-1435 PS-92 Revision 0

          ,Q                                                             ,/ m
               )                                                         k

(,m) kv  % gj 10CFR50 APPEEDIX R. SICTIM III.E CDFLIANCE EVAtuATIO4 (IRE AREA /IchE 1-PS-14-3 41bCV Settcagear doom C'teyry Systes r,=creent Circutt-Senecale Function Consequence of Fire Mittytton spurtous (c LT-453 IFy112023-Es Sensor signal Damasge to this circuit could mone, nata feemater pgs re tripped. Operattan (contd) cuse FCV-456 to close, arts /or Eutpas:t caase a reactor scras. (contd) idTRICDS-G Po.er Damage to this circutt cculd cause a loss of power to LT-453 caese FCV-456 to close and/or cause a reactor scraa. Sensor signal Damasge to this circuit could none. Mata feetater pgs we tripsei. l LT-454 1d]112029-G cause FCV-457 to close, arus/or cause a reactor scrau. Sensor signal Damasge to this circsit could mone. Mata feedwater pas we tripped. LT-455 1FQ112023-t3 cause FCV-458 to close, and/or cause a reactor scram. I'sY11004-0 Power Damage to this circuit could cause a loss of power to LT-455, cause FCV-453 to close and/or cause a reactor scram. Alternate etch TE-40CA sensor st,nal damage to tats circuit coald hone. 1FQ1330SI-Es i Snutacan caase erroneous loop A celta T E44tpnent temperature inotcation. l TE-400A/ IdQ1GE39-Ed Temperature ladication Damage to tais circuit could Nane. TE-4;X)C cause a loss of loop A differential temper 4tdre indication. ImT1403-KS Power Damage to this circuit could cause a loss of power to TR-400 and cause a loss of temperature recorder data, i Impell Corporation deport ko. 01-0310-1435 Po-93 devision 0

10CFA50 APPENDIE R. SECTIan III.G CDIFLIANCE EVALaMTIDE FIAE AREA /2 DIE 1-PS-14-8 4160V Switchgear meam C; :+ of Fire IHtigst en Category System Campement Cteceit-Schedule Function Etternate ACS TE-400C 1FQ103005-G 5ensor signal Damage to this circuit could Bene. Shoteous (centd) cause erroneous lose A delta T Egelpment temperature indicatten. (cantd) TE-4104 1EQ103074-EB Sensor sipal Omege to this circuit could bene. cause erreneens lese B delta T temperatore ind1catlen. TE-410A/ 1eQ103000-Es Temperature indication Damage to tais circuit could home. f cause a loss of loop B l TE-412C i difforential temperatare indication. TE-412C 1Gul040td-Es sensor signal Damage to tais circuit could home. cause erroneous leap s seita T tamperature indicatten. l I TE-4204 5ensor signal Damage to this circuit could none. l 1HQ1030M-aB cause erroneous 1eep C delta T l temperature indicatten. TE-4204/ Ital 10241-EB Sensor signal Dmage to this circuit could leone. TE-420C cause erroneous leap C delta T temperature indicatten. l TE-420C INQ10309-KB Sensor signal Damage to this circuit could Rome. l cause erroneous 10ep C delta T temperature indication. SIC G-13C in85313C1-Es Benote pop cocal Damage to tais circuit could FJee. Saltmeter cooling system is not prevent remote operetten of required to support dedicated shutdeun the pg. and/or cause the systee operation. l pop to spuriously start j or stop. t l l Impe11 Corporation Report No. 01-0310-1435 PS-94 Revision 0 l

( - O O 10CFRSO APPENDIE R. SECTION III.E CopFLIANCE EVAL 11ATION FIRE AREA /2DeE i-Ps-14-8 4160V $witchgear Room Category System Campenent Circuit-Scheeule Function Consequence of Fire stitiention citernate SIS G-50A IGA 2005PI-Es Pouer Loss of poseer to G-504. Operator action to trip offsite/dtesel 54utdesse generator power util seenergize tais pump. Equipment IEA2C05C1-K8 Remote pump control Damage to tais circuit could spuriously start or stop tne pump me/or prevent its remote operation. 1GA2C05C2-KC 5equencer 2 and HV-853A Damage to this circuit could laterlock spuriously start er stop the pemp, and/or prevet remote operation of the pump. G-508 1FAIC05P1-KB Power Loss of peser to G-50B. Operator action to trip offsite/ diesel generator panel will doenergize this pump. 1FAIC05C1-EB Remote pump control Damage to this circuit could spuriously start or stop the pump and/or prevent its remote operation. 1FA1C05C2-EC Sequencer 1 and HV-8538 Damage to this circuit could interlock spuriously start or stop the pump, and/or prevent remote operation of the pump. l i Impell Corporation Revision 0 Rerort No. 01-0310-1435 P8-95

    -.            .           .       . . .             . ~.                     -       -- .~ <            . ..     .---. .-. . . -    .                   .              ,.
                                                                                                  -                                                                 m
                                                                                                 .\

f\ l 10CFit50 APPENDIX R. SECTION III.G C(MPLIANCE EVALUATIOR FIAE AAEA/ ZONE 1-Ph-14-8 4160V Switcngear Moon i Category Systen Camponent Circuit-5cnedule Function Consequence of Fire mitissation Alternate SIS nuv-450A, 160021101-KC Power panege to tnis circuit could hone. Main teeesater and safety in,1ection

         $hutdoom (contd) S.C                                                                       result in tne loss of remote       pumps are tripped.

]~ Equipmen t valve control. ] (contd) j MOV-850A 1G80274C2-KC Remote valve control Damage to tnis circuit coulo None. Main feedsater and safety in,lection ' result in the loss of remote penps are tripped. ' valve control, and/or cause the valve to spuriously open. 1 1680274C8-KC Sequencer 2 time delay Damage to this circuit could initiation result in the loss of remote

valve control, and/or cause the valve to spuriously open.

} a } IG80274CD-KC Sequencer 2 time delay Damage to this circuit could initiation result in the loss of remote ! valve control, and/or cause the valve to spuriously open. I 2 i RN-5508 1G80180P1-K8 Power Loss of power to M)W-850s. None. Main feeerater and safety in,iection } pumps are tripped. f 1Fu0180Cl-KC Sequencer 1 time celay Damage to tais circuit could i initiation result in tne loss of remote 1 valve control, and/or cause tne i valve to spuriously open. 1 l IGuC180C3-Es Remote valve control Damage to tnis circuit could result in the loss of remote i; valve control, and/or cause the I valve to spuriously open. j IG80180C9-K8 Position switch / torque Danap to this circuit could 1 switch feceack result in the loss of remote valve control. l l i 2 Impell Corporation , ceport Fo. 01-0310-1435 PS-96 Revision U i ,

         ,m.                                                                  (m )                                                         -,   1

( G'j / 10CFR50 APPEND 11 R. SECTION Ill.G C0ffLIANCE EVALUATION FIRE AREA /20NE 1-P8-14-8 4160V Switchgear Room Category System Comoonent Circuit-Schedule Function Consequence of Fire Mitigation Re%te valve control Damage to this circuit could None. Main fee <hvater and safety injection Alternate SIS Mov-850C 1HB0391C1-KC pumps are tripped. Shutdown (contd) result in the loss of remote Equipem t valve control. (contd) Damage to this circuit could 1HB0391C9-KC Sequencer 2 time delay initiation result in the loss of remote valve control, and/or cause the valve to spuriously open. 1HdO391CC-KC Sequencer 1 time delay Damage to this circuit could initiation result in tne loss of remote valve control, and/or cause tne valve to spuriously open. lHbO391CD-KC 5equencer 2 time celay Damage to tnis circuit could initiation result in the loss of remote valve control, and/or cause tne valve to spuriously open. SV-524/ 1GD0251Al-KC Sequencer 2 time delay Damage to this circuit could None. Main feedwater and safety injection HV-851A initiation result in the loss of remote pumps are tripped. valve control, and/or cause the valve to spuriously open. 1GD0251A2-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control, and/or cause the valve to spuriously open. 1GD0251A6-KC SV-500 control Damage to this circuit could prevent operation of HV-851A or its charging system. 1GD0251A7-KC SV-501 control Damage to this circuit could l prevent operation of HV-851A or l tts enarging system. l l l Impe11 Corporation Report No. 01-0310-1435 PB-97 Revision 0

                                                                                                                                          , ~

s 10CFR50 APPENDII R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-P8-14-8 4160V Switchgear Room C tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Alternate SIS SV-526/ 1GUO253Al-KC Sequencer 2 time delay Damage to tnis circuit could None. Main teeavater and safety injection Shutdouri (contd) HV-853A initiation result in tne loss of remote pumps are tripped. Equipment valve control, and/or cause tne valve to spuriously open. (contd) 1Guo253A3-KC Remote valve control / Uamage to tnis circuit could position indication result in tne loss of remote valve control, and/or cause the valve to spuriously open. SV-528/ 1FD015181-KC Sequencer 1 control Damage to this circuit could None. Main feedwater and safety injection HV-8518 result in the loss of remote pumps are tripped. valve control, and/or cause the valve to spuriously open. 1FD015182-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control, and/or cause the valve to spuriously open. 1FD015186-KC SV-502 control Damage to this circuit could prevent operation of HV-851tl or its charging system. IFD015187-KC SV-503 control Damage to this circuit could prevent operation of HV-8516 or its charging system. SV-530/ 1FD0153mi-(C Sequencer 1 initiation Damage to tnis circuit could None. Main feedwater and safety injection HV-8536 result in tne loss of remote ptsps are tripped. valve control, and/or cause the valve to spuriously open. IFD015333-KC Remote valve control / Damage to tnis circuit could position indication result in the loss of remote valve control, and/or cause the valve to spuriously open. IFD015387-KC Solenoid control Damage to this circuit could cause a loss of remote control if HV-853A is open or opening, causing HV-853A to close. If HV-853A is closed, damage could cause CV-875A to open and CV-37 to close. Impe11 Corporation Report Mo- 01-0310-1435 Po-93 Nevision 0

b 10CFR50 APPENDII R. SECTION III.6 COWLIAmCE EVAttJATION FIRE AuEA/altE 1-PS-14-8 4160V Switchgear Room C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation ( Alternate FW5 G-3A 1GA2C04C3-K8 motor control and Damage to this circuit could Operator action to trip offsite/ diesel l Shutdoun indication spuriously start or stop the generator power will deenergize this pump. l Equipment . pas, and/or prevent remote t (contd) rperation of the pump. ! 1GA2C04C4-KB Sequencer 2 interlock Damage to this circuit could and SV-875A Indication result in the loss of remote l pump control or cause  !

                                                                                                                                                                                                                                                                ~

i SV-875A to spuriously open. l or prevent SV-875A fron l opening. I I 1GA2C04El-KC Motor control Damage to this circuit could spuriously stop tne pump and/or prevent its remote operation. , i 1GA2C04E3-kC HV-8534 safety Damage to tais circuit could injection feed to G-3A spuriously stop tne pump and/or i interloca prevent its remote operation. IGA 2C04E4-KC 5equencer 2 anc Damage to tais circuit could HV-853A interloca spuriously stop the po p and/or cause a loss of remote pop control. Damage could also cause SV-875A to i spuriously open. , 1GA2C04P1-KB Pouer Loss of power to G-3A t 1SA2C04P2-KB Pouer Loss of power to G-3A IIA 2C04C1-KC Remote indicattar Damage to this circuit could result in the loss of remote pump  ; control. t Ammeter and overcurrent Damage to this circuit could i IIA 2C04Al-K8 relays spuriously trip the pump. i I t s Impell Corporation Report No. 01-0310-1435 P8-99 Revision 0

G a a 10CFR50 APPEWII R. SECTION !!I.G COIPLIANCE EVALUATION FIRE AREA /204E 1-PS-14-8 4160V Switchgear Roan Category System Component Circult-Schedule Function Consequence of Fire Nitiestion E1 ternate FWS A-17A G-3A ?@e oil cooler fan None. Main feeemater pumps se tripped. ,

                              . Shutdomst (catd)

Egi.t ament 1G40282C2-KB Automatic control Damage to this circuit coula  ! (conto) spuriously stop t7e fan and/or prevent remote ',peration of the fan. IGuG282C3-Km G-3A oreaker interloca panage to tais circuit could spuriously stop the fan and/or prevent remote operation of the fan. CV-36 1GA2C04CB-ES Remote valve control Damage to this circuit could None. Main fecesater pumps we tripped. cause a loss of pump remote i operation and/or cause CV-36 to spuriously close, or disable the open or close interlocks  ; for valve CV-36. CV-36/ 1GA2C04C2-KB CV-36 control /SV-875A Damage to this circuit could Nene. Main feedseter pumps we tripped. CV-875A position indication cause a loss of pump remote operation and/or prevent closing CV-36, or disaole the open or close interlocks for valve CV-36. l CV-875A 1GA2C04C9-KS $V-875A control Damage to tais circuit could None. Main feeesater pumps se tripped. result in tne loss of remote control of EJA and SV-873A i anofor cause SV-875A to spuriously  ! open or close. . l I l i Impe11 Corporation i Report No- 01-0310-1435 PS-100 Revision 0  ; i

(. ,, Q/ ,/ 10CFK50 A/PEhDIA k. MCTION 111.6 CUWLIANCE EdAu!ATlum FIkE AREA /luhE 1-Po-14-d 4160V witcngear Moon Category Systes Component Circuit-Schedule Function Consequence of Fire Mitigation Alternate Fd5 G-35 1FA1C04C3-K8 Motor control and Damage to this circuit could Operator action to trip offsite/ diesel indication spuriously start or stop the generator power will deenergize this pump. Shutdoen (contd) Equipment ptanp. and/or prevent remote operation of the pump. (contd) 1FA1C04C4-KB 5equencer 1 interlock Damage to this circuit could and SV-8758 indication result in the loss of remote ptmp control or cause SV-8758 to spuriously open, or prevent SV-8758 from opening. 1FAICMEl-KC Motor control Danage to this ci.cuit could spuriously stop the pump and/or prevent its remote operation. 1FA1C04E3-KC HV-853s safety Damage to this circuit could injection feed to G-38 spuriously stop tne pump and/or interloca prevent its remote operation. 1/AIC04E4-KC Sequencer 1 and Damage to tnis circuit could HV-853s interloca spuriously trip the ptsap ana/or result in tne loss of remote control of tne ptsep. Damage could also cause $V-8758 to spuriously open. IFAIC04P1-K8 Power Loss of power to G-3A 1FA1C04P2-KB Power Loss of power to G-3A 1MIC04C1-KC Remote indication Damage to this circuit could result in the lots of remote pump control. l MIC04Al-KS A:eneter and overcur*ent Damage to this circuit could relays spuriously trip the pump. Impell Corporation Report No. 01-0310-1435 P8-101 Revision 0

3 7--- p (v ) (a) (a ) 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA /ZOME 1-PB-14-8 4160V Switchgear Room Category Sntes Component Circuit-Schedule Function Consequence of Fire Mitigation Alternate FWS A-17B - G-38 lube oil cooler fan None. Main fee &ater pgs are tripped. _ Shutcown (contd) 0;donent 1F81A1571-KC Power Loss of power to A-178 (contd) IFulA15C2-KC Automatic control Danage to tnis circuit could spuriously stop tne fan and/or prevent remote operation of the f an. 1F31AlbC4-KC Automatic control Damage to this circuit could spuriously start or stop tne fan ana/or prevent remote operation of the fan. IFalA15C3-K8 G-38 breaker interloct Damage to this circuit could spuriously stop the fan and/or prevent remote operation of the f an. CV-37 1FA1C04CS-KB CV-37 control Damage to this circuit could None. Main fee &ater pimps are tripped. cause a loss of pump remote operation and/or cause CV-36 to spuriously close or disable the open or close interlocks for valve CV-37. CV-37/ 1FA1C0aC2-KB CV-37 control /SV-8758 Damage to this circuit could None. Main fee &ater pimps are tripped. CV-875B position indication cause a loss of pump remote operation and/or prevent closing CV-37, or disable the open or close interlocks for valve CV-36. SV-525/ 1GD0252Al-KC Remote valve control Damage to this circuit could None. Main fee &ater pumps are tripped. HV-852A cause a loss of remote control to HV-852A, tnis will result in dV-2900 HV-8slA, and HV-853A closing and HV-852A and HV-854A opening, or HV-852A could spuriously close. 1GD0252A2-KC Remote valve control / Damage to this circuit could position indication cause a loss of remote control to HV-852A, this will result in SV-2300, HV-851A, and HV-853A closing and HV-852A and HV-854A opening, or HV-852A could spuriously close. Impe11 Corporation Report No. 01-0310-1435 PB-102 Revision 0

                                                                                                                                                ~
           ,f                                                           f*"'
         \      'l                                                    I Lj
                                                                               \                                                             (gi )

O 10CFK50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AKEA/lukt 1-P5-14-8 4160V dwitengear doom Category System Component Circuit-Scnedule Func tion Consequence of Fire Mitigation Alternate FWS SV-527/ 1GD0254Al-KC Sequencer initiated Damage to this circuit could None. Main feeovater pugs are tripped. Shu*.down (conto) HV-854A closure of HV-854A cause a loss of remote control Egipmen t to HV-854A, this will result in (contd) SV-2900. HV-851A, and HV-853A closing and HV-852A and HV-854A opening, or HV-854A could spuriously close. 1GDD254A2-KC Remote valve control / Damage to this circuit could position indication cause a loss of remote control to HV-854A, this will result in SV-2900, HV-851A, and HV-853A closing and HV-852A and HV-854A opening, or HV-854A could spuriously close. SV-529/ IFD0152B1-KC Sequencer initiated Damage to this circuit could None. Main feeevater pumps are tripped. HV-8528 closure of HV-8528 cause a loss of remote control to HV-8528, this will result in SV-3900 HV-8515, and HV-8538 closing and HV-8526 and HV-8546 opening, or HV-852n could spuriously close. IF0015262-KC Remote valve control / Damage to this circuit coe 4 position indication cause a loss of remote contral to HV-8526, this will result in SV-3900, HV-8518, and HV-8538 closing and HV-8528 and HV-8548 opening, or HV-8528 could spuriously close. CV-8758 IFAIC04C9-KB SV-875B control Damage to this circuit could None. Main fee & vater pumps are tripped. result in the loss of remote control of G3B and SV-875B and/or cause SV-875B to spuriously open or close. l l l Impell Corporation Report No. 01-0310-1435 Po-lu3 Revision 0

s \ \s 10CFR50 APPENDIX R SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-PB-14-8 4160V Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Alternate FMS SV-531/ 1FD015481-KC Sequencer initiated Danage to this circuit could None. Msin feedsater pises are tripped. Shutdown (contd) HV-8548 closure of HV-8548 cause a loss of remote control Equipment to HV-8548, this will result in (contd) SV-3900, HV-8518, and HV-8538 closing and HV-8528 and HV-8546 opening, or HV-854B could spuriously close. IFD015482-KC Remote valve control / Damage to this circuit coulo positim indication cause a loss of remote control to HV-8528, tnis will result in SV-3900, HV-8516, and HV-8536 closing and HV-os2d and HV-8548 opening, or HV-8526 could spuriously close. Dedicated RCS TE-402A IwQ103083-KB Sensor signal Damage to this circuit could These cables are to be spared as part Shutdown result in high off-scale, low of the dedicated shutdown sy; tem Equipment off-scale, or erroneous design. indication. RCS TE-412A 1XQ103080-KB Ser.sor signal Damage to this circuit could These cables are to be spared as part result in high off-scale, low of the dedicated shutdown system off-scale, or erroneous design. Indication. RCS TE-422A IXQ103073-KB Sensor signal Damage to this circuit could These cables are to be spared as part result in high off-scale, low of the dedicated shutdown system l off-scale, or erroneous design. indication. l Impe11 Corporatinet Report No. 01-0310-1435 PB-104 Revision 0 l

rw x i

        ,r]'
        \

() j 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA /20NE 1-PS-20-11A Health Pnysics and Locaer Roan Effects of Fire on Safe wwtoown Capaniitty A fire in tnis fire area / zone could result in the loss of tne following portions of systems used to acnteve hot staney and cold stutdown: Chemical and Volume Control System (CVCS)

                                         -     Cables for the following components:

' - Chrging flow control valve Main Steam System (MSS)

                                         -     Cables for the following components:
                                               -     Atmospheric steam dump valves
                                               -     Turbine stop valves Component Cooling Water System (CCW)
                                         -     Cables for the following components:
                                               -     Thermal bsrier pump

' Diesel Generator Systems (DG)

                                         -     Caoles for tne following components:
                                               -     Diesel generator i local control ,enel l
                                               -     Exciter caninet for diesel generabr 1
                                               -     Diesel generator I staney fuel oil pump Essential Electric Systems
                                         -     Caoles for the following components:
                                                -     120V vital buses
                                                -     Battery charger D02

! Impe11 Corporation Pu-105 Revision u Heport No. 01-0310-1435 L . _ _ _ .

O

             ~

O 10CFR50 APPEIOIX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-P8-20-11A Health Physics and Locker Room Damage to control power caoles for cnarging flow control valve FCV-1112 and feedwater regulator valves FCV-456, FCV-457 ano , 4 FCV-458 could cause the valves to f ail open. Operator action may be required to close a manual valve to isolate the charging loop A line if charging through the seal in,lection , f lowpath. The main feedwater pumps should De tripped from the ,j . control room. , Damage to cables for the turbine stop valve actuators PV-1611 and PV-1612 could cause the turbine stop valves to remain open. Operator action will be required to manually trip the turbine at the turbine stand. I One train of other systems required for not standoy and cold j shutdown will remain free of fire damage. j An exemption request for the lack of area-wide suppression and partial area detection, per the requirements of Section III.G.3, will be provided. 4 I l 1 4 1 1 i 2 Impe11 Corporation Report No. 01-0310-1435 PB-106 Revision 0

V N 10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-20-IIA Health Physics and Locker Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 120V Y-11 IHYliOO-Kd Power Loss of distribution panel Y-Il None. Alternate power to tne vital $tandby will cause tne loss of power to bus will remain availaole from MCC-2. Equipment tne following components required for normal / alternate shutoown: Y-11K CV-546 NE-1201 TE-600 TCV-601A TCV-60lu CV-530 P T-430 Y-12 1HY1200-KB Power Loss of distrioution panel Y-12 None. Alternate power to the vital will cause the loss of power to bus will remain available from MCC-2. the following components required for normal / alternate shutdown: CV-545 Y-12R CV-7228 CV-531 PT-431 CV-722A CV-722C Y-13/Y-33 1HY1300-KB Power Loss of distribution panel Y-13 None. Alternate power to the vital and Y-33 will cause the loss of bus will remain available from MCC-2. power to the following components required for normal / alternate shutdown: TE-2401A TE-2412A TE-2422A FCV-2300 FCV-2301 Y-13K LT-2400A LT-24006 LT-2400C NE-1202 125V L102 IFBS110PI-KB Power Loss of oattery enarger IAl2. None. Alternate power to 125V DC dus I will remain availaole from uattery 1. lWBS110Cl-K6 Remote breaker control Damage to this circuit could prevent remote operation and/or cause spurious operation of the breaker. CVCS FCV-1112/ IFD013001-KC Remote valve control Damage to this circuit could Operator action to close manual valves FCV-456,7,8 result in the loss of remote located upstream will be required if valve control. charging through the seal injection flowpath. Spurious actuation of FCV-456, FCV-457 and FCV-458 will not affect safe shutdown, as the main feedwater pumps will be trippeu from the control room. Impell Corporation Report No. 01-0310-1435 P8-107 Revision 0

m U J J 10CFR50 APPENDIX R SECTION III.G CUWLIANCE EVALUATION FIRE AREA / ZONE 1-PB-20-llA Health Physics and Locker Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot MSS SV-85,86, LWD 0128Dl-KB Solenoid control power Damage to this circuit could None. Steam d ep control through the Standby 87,88 result in the lost of remote valve positioner will remain available. Equipment control or transfer valve control (contd) to the main steam pressure transmitter PT-459 (via YM-418A). PV-1611/ lYD0113Dl-KB 125V DC power Damage to this circuit could Operator action to trip the turbine at PV-1612 result in the loss of remote the turbine stand. valve control for main stop valves PV-1611. PV-1612, and for the governor valves. CCW G-964 IWD0120C2-KB Bus 1C and Sus 2C Damage to this circuit could None. Component cooling pumps G-lbA, undervoltage auto start prevent auto starting of tne G-158 G-15C will remain availaole. interlock pop, or if the pop is in tne auto mode cause spurious starting. IXD0120C3-KB Bus IC and Bus 2C Damage to this circuit could undervoltage auto start prevent auto starting of the interlock p ap, or if the p e p is in the auto mode cause spurious starting, lYD0120C6-KB Pep discharge Damage to this circuit could low pressure interlock spuriously start the pump and/or prevent its remote operation, or autostarting. Damage to this circuit could also cause the pop to run continuously, regardless of the pressure level if in the auto mode. Impell Corporation Report No. 01-0310-1435 PB-108 Revision 0

                   \                                                                                                                      bi U

10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-PB-20-11A Health Physics and Locker Room Category _ System Component Circuit-Schedule Function Consequence of Fire Mitigation

  ~ Hot         DG      C-48   1FD011901-KC      Diesel generator 1,          Loss of diesel local control    None. Diesel generator 2 will remain
  -Standby                                       "B" start circuit power panel C-48.                          availaole.

Equipment (contd) IFD012601-KC- Diesel generator 1 Loss of diesel local control "A" start circuit power panel C-48. E-08 IFD010501-KC Diesel generator 1 Loss of exciter caninet E-08. None. Diesel generator 2 will remain exciter / regulator power availaole. G-76 1F00114D6-KC Power Loss of power to G-76. Non e. Diesel generator 2 will remain , available.

IFD011408-KC Pump operation Damage to this circuit could indication result in the loss of remote pimp control.

Cold None Shutdown Equipment High/ Low None

Pressure Interface l

4 Spurious None Operation l Equipment Alternate None i Snutdown Equipment Dedicated None i Shutdown Equipment 4 4 Impe11 Corporation Report No. 01-0310-1435 P8-109 Revision 0

  . . - . - .  . . -    -      ...   . ~ , . - . - . _.   ..       .                    _ .         .                           . . , .   ... - . . . . - . ~    ,. - .-                             . . . .  , , , .   -. ..

t

  • 10CFk50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATidN j FIRE AREA / LONE 1-P8-32-118 HVAC Equipment Room l-1 i

Effects of Fire on Safe Shutdown Capability 4 j The design basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe J shutdown components or cables within the fire area / zone. 4 i 1 i i i I i i l-e t i i l i i i I i i i  ! i i i 4 Impe11 Corporation Revision 0 Report No. 01-0310-1435 P8-110

                                                                                                                            ~_ . _ - - _ . _ . _ _     .      ._      . _

i 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-PB-32-118 i HVAC Equipment Room Category System Component Circuit 'c.hedule Function Consequence of Fire Mitigation Hot Mone 4

                 'Staney Equipment                                                                                                                                            .

I Cold None j ' Shutdown

Equipment 3

Hign/ Low None 1 Pressure Interface , i t i Spurious None Operation

Equipment t

Alternate None Shutdown Equipment 4 i Dedicated None

!                     Shutdown j                      Equipment l

l a I J t i i l Impe11 Corporation Report No. 01-0310-1435 P8-111 Revision 0 i

  ._ ____      . _ _ .       . . . .._.. _ _ ... .. . - -            . - . . . . _ . _ _ - , . . .        _ . _ . . . - ._           m _. _. . .       . . ..__            _ . .- ,

w i-10CFR50 APPENDIX R, SECTION 111.G C0WLIANCE EVALUATiuN

                                    '                                                                                                                                                   ?

I FlkE AREA /ZuhE. I-Pd-30-IIC Counting Roon  : j Effects of Fire on Safe Snutdown Cap sility ) The design basis fire will not affect the capability to achieve and maintain cold shutdown, as there are no safe i shutdown components or caoles within the fire area / zone. f

4 1 5 1

! i { } .i l  ! I r i t l 1 l 1 j 1 i 4 , I i 1 ,

                                                                                                                                                                                       ?

1 i Impell Corporation j Report No. 01-0310-1435 P8-ll2 Hevision 0 i<

I 10CFR50 APPENDIX R SECTION III.G COWLIANCE EVALUATION l FIRE AREA /2ONE 1-P8-30-11C Counting Room 1 Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot ~ None i Standby Equipment i Cold None j Shutdown Equipment

Hign/ Low None

, Pressure ! Interface I 4 j Spurious Ihne 4 Operation 1 Equipment Alternate None Shutdown i Equipment 4 i Dedicated None , Shutdown i Equipment I 4 t s I t ) Ir.pell Corporation F8-113 Revision 0 Report No. 01-0310-1435 i

F l 10CFR50 APPENDIX R SECTION III.G COPFLIANCE EVALUATION j FIRE AREA /40NE 1-P8-30-11D i Communications Room i I 4 Effects of Fire on Safe Snutoown Capanility j j The design casts fire will not affect the capanility to  ; ' achieve and maintain cold snutdown, as there are no safe shutdown components or cables within the fire area / zone. j i 2 , l - l 4

                                                                                                                                                -l l

1 1 4 l i i i i I I 1 l 1 . 4 ,l 4 i j i i ( l i i j Impe11 Corporation' Report No. 01-0310-1435 P8-114 Revision U , I i

,I i 10CFR50 APPENDIX R, SECTION III.G C0fFLIANCE EVALUATION FIRE AREA / ZONE l-P8-30-Il0 Communications Room Category System Component Circult-Schedule Function Consequence of Fire Mitigation + Hot None

'      5taney                                                                                                                                                       i j       Equipment l,

4 Cold None l Shutdown

Equipment .

4 t i High/ Low None ! Pressure j Interface i Spurious None Operation Equipment i a ,. ( Alternate None d Shutdown l Equipment i Dedicated None , Shutdown i

;      Equipment f

i, l 1 i i 1 i, IKpell Corporation Report No. 01-0310-1435 P8-ll5 Revisfon 0 i

i a i i 10CFR50 APPENDIX R, SECTION III.G C0pFLIANCE EVALUATION .  ; 2 ) , 1 FIRE AREA / ZONE l-P8-30-11E

                                                                                                ' Radioactive Material Storage Room                                                                                                   i Effects of Fire on Safe Shutdown Capapility i

The design oasts fire will not affect the capaoility to-i acnteve and maintain cold snutdown, as there are no sete ,

'                                                                                   snutdown components or caoles within tne fire area / zone.

9 i i i i 1 1 i i , i  ! t 1 I I l 4 t l u i k i *

$                                                                                                                                                                                                                                    i 1

i s I Impell Corporation . Report No. 01-0310-1435 P8-ll6 Revision 0 - I l )

O 10CfR50 APPENulX R. SECTION III.G COMPLIANCE EVALUATI9N FIRE AREA / ZONE l-PS-30-IIE Radioactive Material Storage Room Category System Component Circult-Schedule Function Consequence of Fire Mitigation Hot None Staney Equipment Cold None Shutdown Equipment High/ Low None Pressure Interface Spurious None Operation Equipment Alternate None Shutdown Equipment Dedicated None Shutdown Equipment i Impell Corporation , Report No. 01-0310-1435 Pd-ll7 Revision 0

O O O e 100CFR50 APPEIOIX R, SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE l-PB-20-12 Offices-First Floor Effects of Fire on Safe Shutdown Capanility A fire in tnis fire area / zone could result in the loss of i the following portions of systems used to acnteve not standby and cold snutoown: Chemical and Volume Control System (CVCS)

                                       -    Cables for the following components:
  • Charging flow control valve >

i Main Steam System (MSS) i i - Cables for the following components: i

  • Atmospheric steam dump valves I - Turbine stop valves ,

i Component Cooling Water System (CCW)

                                       -     Cables for the following components:
                                             -    -Themal barrier pump Diesel Generator Systems (DG) l                                      -     Cables for the following components:
                                             -     Diesel generator 1 local control panel
;                                            -     Exciter caoinet for diesel generator i j
  • Diesel generator i stanopy fuel oil pump Essential Electric Systems s

4 - Cables for tne following components:

                                              -    120V vital bus.s I

Battery charger D02 l 1 - 1

)
;   II.pell Corporation                                                                       Revision 0 Report No. 01-0310-1435                                       PB-118 l

N

                       -  10CFR50 APPENDIX R, SECTION III.G C(MPLIANCE EVALUATION FIRE AREA / ZONE 1-P8-20-12 Of fices-First Floor -

Damage to control power caeles for charging flow control valve FCV-Ill2 and feedwater reipalator valves FCV-456, FCV-457 and FCV-458. Operator action may be required to close a manual valve to isolate the chwging loop A line if chwgtng through the seal injection flowpath. The main feedwater pugs should De tripped from the control room. Damage to cables for the turpine stop vavle actuators PV-1611 - and PV-1612 could cause the turnine stop valves to remain open. Operator action will be required to manually trip the turbine at the turnine stana. One train of other systems requirea for hot standay and cold shutdown will remain free of fire damage. An exemption request for the lack of area-wide suppression and pwtial wea detection, per the requirements of Section III.G.3, will oe provided. Igell Corporation Report No. 01-0310-1435 PB-119 Revision 0

 .__ _ _ _. _ .___ _                                   = _ - -      _ . _ - . _ . _-         .    . . _ _ - . _   ..__--,___m._.._.                      _ .           . ._ _ _ _ . .                 .

F

                                                                                                                                                                                                             )

J . - 100CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-20-12 Offices-First Floor . Cetegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 120V Y-11 1HY1100-K8 Power Loss of distribution panel Y-11 Mone. Alternate power to the vital bus ' 2 Staney will cause the loss of power to will remain avallanle from MCC-2. Equipment the following components required for normal / alternate snutdown: ' Y-11R CV-b46 E-1201 TE-600 TCV-601A TGV-0018 CV-530 PT-430 Y-12 1HY1200-Ku Power Loss of distrioution panel Y-12 None. Alternate power to tne vital ous will cause the loss of power to will remain availaole frue MCC-2. the following components required for normal / alternate snutdown: CV-545 Y-12K CV-7228  ! CV-531 PT-431 CV-722A [ CV-722C Y-13/Y-33 lHY1300-K8 Power Loss of distribution panel Y-13 None. Alternate power to the vital bus and Y-33 will cause the loss of will remain available frun MCC-2. r power to the following components  ! required for normal / alternate  ! shutdown: , Y-13R E-1202 TE-2401A TE-2412A TE-2422A FCV-2300 i FCV-2301 LT-2400A LT-24008 l LT-2400C 125V DD2 IF85110P1-K8 Power Loss of power to battery None. Alternate power to 125V DC sus 1 I charger 002. will remain availaole frun Battery 1. l eS110C1-K5 Remote breater control Damage to this circuit could prevent [ remote operation and/or cause  ! spurious operation of tne creater. i CVCS FCV-1112/ IFD013001-KC Remote valve control Damage to tnis circuit could operator action to close manual valves t FCV-456,7,8 result in the loss of remote located upstream will be required if i valve control. charging througn tne seal injection [ flowpath. Spurious actuation of FCV-456, 7 FCV-457 and FCV-458 will not affect safe r shutdown as the main feedwater pumps will t be tripped from the control room, f Impe11 Corporation } PS-120 Revision 0 l Report No. 01-0310-1435

a t / U 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EWALUATION Find AREA /ZuhE i-Pd-20-12 Of fices-First Floor Category Systes Component Circuit-Schedule Func tion Consequence of Fire Mitigation IWUO12801-Ks Solenoid control power Damage to tnis circuit could None. Steam ousp control Enrough tne Hot MSS SV-85. 86 Standby 87. 88 result in the loss of remote valve positioner will remain ava11 ante. Equipment control or transfer of valve control to the main steam pressure transmitter PT-459 (via YM-418A). PV-1611/ 1YD0113DI-KB 125VDC power Damage to this circuit could Operator action to trip the turbine PV-1612 result in the loss of remote at the turbine stand. valve control for main stop valves PV-1611, PV-1612 and for the governor valves. Bus 1C and Bus 2C Damage to this circuit could None. Component cooling ptmos G-15A, CCW G-964 LWD 0120C2-KB undervoltage auto start prevent auto starting of the pump, G-158, G-15C will remain available. interlock or if the pump is in the auto mode cause spurious starting. IX00120C3-K8 Bus IC and Bus 2C Damage to this circuit could unoervoltage auto start prevent auto starting of the pump, interlock or if the pump is in the auto mode. cause spurious starting. IY00120C6-K8 Pump discharge Damage to tnis circuit coulo low pressure interlock spuriously start tne pump and/or prevent its remote operation, or autostarting. Damage to this circuit could also cause the pump to run continuously, regardless of the pressure level if in the auto mode.

                                                                                              ^

Impell Corporation Heport No. 01-0310-1435 Pu-121 Hevision 0

  . . _ _ . . _ . __ _ _. .           . .          ._    .       ~ . ,     _ ._              _ _ . ..                  _. .-       ._._... -._ -          _ . _ - - .   ... _ . . . . _

i, m O i i 10CFR50 APPENDIK R, SECTION !!!.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-20-12 Offices-First Floor j Cate m System Component Circuit-Schedule Function Consequence of Fire Mitigation j 9 Not DG C-48 1FD011901-KC ' Diesel generator 1 Loss of diesel local control None. Diesel generator 2 will remain [ 5taney "B" start circuit porer panel C-48. available. Equipment (contd) IFD0126D1-KC Diesel generator 1 Loss of diesel local control "A" start circuit power panel C-48. E-08 1FD010501-KC Diesel generator 1 Loss of exciter cabinet E-08. None. Diesel generator 2 will remain exciter / regulator power availaole. I G-76 1FD011406-KC Power Loss of power to G-16. None. Diesel generator 2 will remain ' availaole.  ; IF0011408-KC Pump operation Damage to this circuit could  ; indication result in the loss of remote pump control. j Cold None Shutdown -  ; Equipment High/ Low None Pressure i Interface i

      .Sourious None Operation Equipment Alternate None Shutdown                                                                                                                                                                                  ,

Equipment i Dedicated None ' Shutdown Equipment t l l I

                                                                                                                                                                                                ~!,

Impe11 Corporation Riport No. 01-0310-1435 P8-122 Revision 0 ' vr+ w -. + y- _ , , , ,_

U(N 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-Po-20-13A DC Switengear Room Effects of Fire on Safe Snutoown Capaoility A fire in tnis fire area / zone could result in the loss of tne following portions of systems used to acnieve hot standoy and cold shutdown: Reactor Coolant System (RCS)

                             -    Reactor protection system trip circuits Chemical and Volume Control System (CVCS)
                             -    Cables for the following components:
  • Charging flow control valve Main Steam System (MSS)
                             -    Cables for the following components:
                                   . Atmospheric steam dump valves
  • Turbine stop valves Component Cooling water System (CCW)
                             -    Caoles for the following components:
  • Tnenaal oarrier pump Diesel Generator Systems (OG) .
                             -    Cables for the following components:
                                   -     Diesel generator 1 local control panel
                                   -     Exciter caoinet for diesel generator 1
                                   -     Diesel generator 1 standby fuel oil pump Impe11 Corporation Report No. 01-0310-1435                               Pu-123                            Revision 0
                  - _ . - - . ._- -. .         . . - -            -- . . .                  .    -    - .~. . , .       .
                                                                                                                    ~ss O.                                     -

10CFR50 APPENDIX R. SECTION III.G C(MPLIANCE EVALUATION FIRE AMEA/ ZONE 1-P8-20-13A DC Switchgear Room Essential Electric Systems  ;

                                             -         120VAC vital bus Inverters 1, 2, 3, 4 i

125VDC Bus 1 ' - Battery Cnargers A and 8

                                             -         Cables for the following components:
                                                       . 120VAC vital buses
                                                       . Inverters 1, 2, 3, 4

' . Battery chargers A and B

  • 125VDC Bus 1 Damage to control power cables for charging flow control valve .

FCV-1112 and feedwater regulator valves FCV-456. FCV-457 and l FCV-458 could cause a loss of remote valve control. Operator action may be required to close a manual valve to isolate the e charging loop A line if charging through the seal injection flowpath. The main feedwater pumps should De tripped from the control room. Damage to caoles for the turbine stop valve actuators PV-1611 and PV-1612 could cause the turoine stop valves to remain j open. Operator action will ne required to manually trip the i turoine at the turoine stand. One train of other systems required for hot standoy and cold shutdown will remain free of fire damage. i 1 An exemption request for the lack of area-wide suppression, per the requirements of Section III.G.3, will be provided. t i ~! I i i Impe11 Corporation Report No. 01-0310-1435 P8-124 Revision 0

N  % v 10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-20-13A DC Switchgear Room Consequence of Fire Mitigation I Category Systen Component Circuit-Schedule Function 1 Inverter 1 Loss of Inverter 1. None. Alternate power to the vital Hot- 120V YO1/ ------ ous will remain availaole from MCC-2. Stindoy Inverter 1 -> Equipment . 1HD0135-Ks Powar Tnis circuit is entirely (conto) contained within the fire area / zone. The circuit and its termina-tion points.are assumed destroyed. Inverter 2 Loss of Inverter 2. None. Alternate power to the vital YO1/ ----- Inverter 2 bus will remain available from MCC-2. lHD0136-K8 Power This circuit is entirely contained within the fire area / zone. The circuit and its termina-tion points are assimed destroyed. Inverter 3 Loss of Inverter 3. None. Alternate power to the vital YO1/ ---- - Inverter 3 bus will remain available from MCC-2. lH00137-K8 Power This circuit is entirely contained within the fire area / zone. The circuit and its termina-tion points are assumed destroyed. Inverter 4 IWD0133D1-Ks Power Damage to this circuit could None. Alternate power to tne vital cause a loss of power to Dus will remain availaole from MCC-2. inverter #4. Y-11 1HY1100-Ks Power Loss of distrioution panel Y-11 None. Alternate power to tne vital will cause tne loss of power to bus will remain available from MCC-2. the following components required for normal / alternate snutdown: Y-11R CV-546 E-1201 TE-600 TCV 401A TCV-6018 CV-530 PT-430 Y-12 1HY1200-K8 Power Loss of distribution panel Y-12 None. Alternate power to the vital will cause the loss of power to bus will remain available from MCC-2. the following components required for normal / alternate shutdown: CV-545 Y-12R CV-722A CV-531 PT-431 CV-7228 CV-722C Itpell Corporation Report No. 01-0310-1435 PB-125 Revision 0

j'~ r rm 10CFR50 APPENDIX R, SECTION Ill.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PS-20-13A l DC Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 120V Y-13/Y-33 lHY1300-KB Pow r Loss of distribution panel Y-13 None. Alternate power to the vital Standby (contd) and Y-33 will cause the loss of bus will remain available from MCC-2. Equipment power to the following components (contd) required for norinal/ alternate - shutdown: TE-2401A TE-2412A TE-2422A FCV-2300 FCV-2301 NE-1202 LT-2400A LT-24006 LT-2400C 125V 001 ------ DC Bus 1 Loss of DC Bus 1. None. Train 2 125V DC electrical distribution system will remain available. Alternate power to the vital buses is available from MCC-2. 1FD0143-K8 Power Loss of powr to distrioution switchgear 001 free oattery i cnarger UU2. s 1600142-K8 Power Loss of power to distrioution switengear 001 from battery cnarger 003. 002 ----- Battery Charger A Loss of battery charger 002. None. Train 2 125V DC electrical distribution system will remain available. Alternate power to the vital buses is availaole from MCC-2. 1FBS110P1-KB Power Loss of power to battery charger D02. I IWBS110Cl-KB Remote breaker control Damage to this circuit could prevent remote operation and/or 3 cause spurious operation of the J breaker. 4 003 ----- Battery Charger B Loss of battery charger 003. None. Train 2 125V DC electrical distrioution system will remain availaole. Alternate power to the vital ouses is availaole from MCC-2. 1G8S210PI-K8 Power Loss of power to cattery - charger 003. IX8S210C2-KB Remote creaker control Damage to this circuit could prevent remote operation and/or cause spurious operation of the

                                                       .                       breaxer.

Iripell Corporation Report No. 01-0310-1435 PB-126 Revision 0 i

O O O 10CFR50 APPENDIX R, SECTION III.G C0fFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-20-13A DC Switchgear Room C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 125V 004 IHD0144-KB Power Loss of power to distrioution None. Train 2 125V DC electrical - Stan &y (conLu) switchgear 001 from station distrioution system will remain availaole. Equipment oattery 004. Alternate power to tne vital ouses will remain availaole from MCC-2. j (conto) IHD0144P2-Kn Power Loss of power to distrioution switcngear 001 fran station oattery UO4. 1 RCS RPS Trip 1YD0141DI-KB Power to 007 Damage to this circuit could None. Heactor scram is initiated Circuits result in a loss of power to the if power to D07 is lost. scram control circuit and create i a reactor scram condition. CVCS FCV-lll2/ IFD013001-KC Remote valve control Damage to this circuit could Operator action to close manual valves FCV-456,7,8 result in the loss of remote located upstream will be required if valve control. charging through the seal injection flowpath. Spurious actuation of FCV-456, FCV-457, and FCV-458 will not affect safe shutdown as the main feedwater pumps will be tripped from the control room. i MSS SV-85,86, LWD 0128DI-KB Solenoid control power Damage to this circuit could None. Steam dump control through the 87,88 result in a loss of remote valve positioner will remain availaole. control or transfer of valve control to the main steam pressure transmitter PT-459 (via YM-418A). PV-1611, 1YDoll301-KB 125VDC Power Damage to tnis circuit could Operator action to trip tne turoine at

;                                   PV-1612                                                 result in the loss of renote      the turoine stano.

valve control for main stop valves PV-1611 PV-1612 ' and for the governor valves. i i e Irpell Corporation Report No. 01-0310-1435 P8-127 Revision 0

           ,-                                                                                                                             pa n.

N_ ,,I _ w.- 10CFM50 APPENDIX k, StCTION !!!.G C0rfLIANCE EVALUATION FIRE AREA /40NE 1-Po-20-13A DC Switchgear Koom Crtegory System Component Circuit-Schedule Func tion Consequence of Fire Mitigation Hot CCW G-964 1FD0120C1-KC Remote p e p Damage to this circuit could None. Camponent cooling pums G-15A, St:ndby control spuriously start or stop the G-158, G-ISC will remain availaole. Eq Jipmen t pump, and/or cause the loss of (contd) remote control of the pump. LWD 0120C2-KB Bus IC and Bus 2C Damage to this circuit could undervoltage auto staat prevent auto starting of the interlock pep, or if the pep is in the auto mode cause spurious starting. 1XD0120C3-KB Bus 1C and Bus 2C Damage to this circuit could undervoltage auto start prevent auto starting of the interlock punp, or if the pap is in the auto mode cause spurious starting. 1YUO120C6-Ko Pump discharge pressure Damage to this circuit could interlock spuriously st4rt the pump and/or prevent its remote operation, or autostarting. Damage to tnis circuit could also cause the punp to run continuously, regardless of the pressure level if in the auto mode. 1YD012001-KB Power This circuit is entirely contained within the fire area / zone. The circuit and its termina-tion points are assumed destroyed. IFD012004-KC Power Damage to this circuit could spuriously start the pump and/or prevent its remote operation. DG C-43 1FD011901-KC Diesel Generator 1 "B" Loss of diesel local control None. Diesel generator 2 will remain start circuit power panel C-48. available. IFD0126Dl-KC Diesel Generator 1 "A" Loss of diesel local control start circuit power panel C-48. E-08 IF0010501-KC Diesel generator I Loss of power to exciter None. Diesel generator 2 will remain exciter / regulator power caoinet E-Od. availaole. Impe11 Corporation Report No. 01-0310-143S Pd-128 Revision 0

O ' O 10CFRSO APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-20-13A DC Switchgear Room Category System Component Circuit-Schedule Function Consequence of Fire Mitigation G-76 1FD011406-KC Power Loss of power to G-76. None. Diesel generator 2 will remain Hot DG Standby (contd) available. Equipment (contd) IFD011408-KC Pump operation Damage to this circuit could , indication result in the loss of remote pump control. Cold None ' Shutdown Equipment High/ Low None Przssure Interface Spurious None Operation i Equipment Alternate None Shutdown Equipment Dedicated None Shutdown Equipment 4 I t Impe11 Corporation Paport No. 01-0310-1435 PB-129 Revision 0

O ' 10CFR50 APPENDIX R. SECTION.111.6 COWLIANCE EVALUATION I FIRE AREA / ZONE l-Ps-20-13s sattery Room No. I , u l' Effects of Fire on Safe Snutdown Capanility A fire in this fire area / zone could result in the loss of

!                                                          the following portions of systans used to achieve hot standby and cold shutdown:

1 Essential Electric Systems l

                                                                  -               Battery No. 1 4
                                                                  -               Cables for the following components:
                                                                                  -    125VDC Bus 1                                                                              i The fire protection features provided for the protection and separation of the safe shutdown systems within the 1

fire area / zone meet the requirements of 10CFR50 i Appendix R, Section III.G.2. One train of systems j needed for hot standby and cold shutdown will

remain free of fire damage.

} i i l i i 4 Irpell Corporation Report No. 01-0310-1435 P8-130 Revision 0

J O O 10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE l-PB-20-138 Battery Room No. 1 Crtegory Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 125V 004 ---- Battery #1 Loss of battery bank 004 and None. Train 2 electrical distribution Stan4y 125V DC Bus No. 1. systems will remain available. Alternate Equipment power to vital buses 1, 2, 3, and 4 is available from MCC-2.  ;

IHD0144-K8 Power Loss of power to distrioution switchgear 001 from station oattery 004. 1H00144P2-KB Power Loss of power to distrioution i switchgear 001 from station i Dattery UO4. I j Cold None Shutdown Equipment 1 High/ Low None

,   Pressure i   Interface                                                                                                                                        ,

i j Spurious .None Operation Equipment

Alternate None j Shutdown Equipment Dedicated None 1 Shutdown i

Equipment

}

I i i r i l i Impell Corporation Report No. 01-0310-1435 PB-131 Revision 0 '

m ( '

                                                                                                                .?

10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION ' t FIRE AREA / ZONE 1-P8-29-13C sattery Room Attic Effects of Fire on Safe shutoown Capao111ty A fire in this fire area / zone could result in the loss of ! the following portions of systems used to achieve not j standby and cold shutoown: Main Steam system (MSS) f

                                            -     Cables for the following components:

3 - Atmospheric steam dump valves

                                                  -     Turbine stop valves Component Cooling Water System (CCW) i i
                                            -     Cables for the following components:

j

                                                  -     Thermal barrier pump                                          r i

Essentis1 Electric Systems )J i ! - CaDies fer the following components:

                                                  -     120VAC vital buses f
  • Battery cnargers A and b
  • 12bvDC uus 1 i Uamage to caoles for the turbice stop valve actuators PV-1611 and PV-1612 could cause the turoine stop valves to remain <

open. Operator action will De required to manually trip the  ! turbine at the turnine stand. t One train of other systems required for hot standby and wid shutdown will remain free of fire damage. f An exemption request for the lack of area-ride supperssion per 1 the requirements of Section III.G.3 will be provideG. - l i 1 l l

     .Irpell Corporation                                                                             Revision U Report No. 01-0310-1435                                        P8-132 q

I

  =---.

_ O O O 4 10CFR50 APPEN011 R SECTION III.G COWLIANCE EVALUATION i FIRE AREA / ZONE 1-PB-29-13C Battery Room Attic Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 120V Y-11 1HY1100-KB Pow r Loss of distribution panel Y-11 None. Alternate power supply to the Sttndby will cause the loss of power to vital bus will remain available from MCC-2. i Equipment the following components required

'                                                                                  for normal / alternate shutdown:

Y-llR CV-546 PT-430 TE-600 TCV-601A TCV-6018 CV-530 NE-1201 Y-12 lHY1200-K8 Power Loss of distribution panel Y-12 None. Alternate power supply to tne will cause tne loss of power to vital bus will remain availante from EC-2. 4 the following components requireo for normal / alternate snutdown: CV-7226 CV-545 Y-12d CV-722A CV-722C CV-531 PT-431 l Y-13/Y-33 1HY1300-K8 Power Loss of distr 1Dution paaal Y-13 None. Alternate power supply to tne 4 and Y-33 will cause the loss of vital ous will remain availaole from MCC-2. power to the following components required for normal / alternate shutdown: TE-2412A TE-?422A TE-2401A FCV-2300 FCV-2301 .NE-120? LT-2400B LT-2400C LT-2400A Y-13R 125V t'U2 IFBSil0Pl-KB Power Loss of battery charger 002. None. Train 2125V DC electrical distribution system will remain available. Alternate power to the vital buses is available from MCC-2. lWBS110Cl-KB Remote breaker control Damage to this circuit could prevent remote operation and/or cause spurious operation of the breaker. D04 lHD0144-X8 Power Loss of power to distrioution None. Train 2 125V DC electrical switcngear D01 from station distrioution system will remain oattery 004, availaole. Alternate power to tne vital ouses is availaole from EC-2. 1HD0144P2-Ks Power . Loss of power to distribution switchgear 001 from station l Dattery 004. Irpell Corporation Report No. 01-0310-1435 PB-133 Revision 0

(m .f% d 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE l-P8-29-13C Sattery Room Attic C3tegory System Component Circuit-Scheoule Function Consequence of Fire Mitigation SV-85,86, 1WU0128DI-Kb Solenoid control power Danage to tnis circuit could hone. Steam cunp control througn tne Hot MSS Stindoy 87,88 result in tne loss of remote valve positioner will remain availaole. control or transfer of valve Equipment (contd) control to tne main steam pressure transmitter PT-459 I (via YM-418A). 1 PV-1611/ 1YD0113D1-KB 125VDC power Damage to this circuit could Operator action to trip the turoine at j PV-1612 result in tne loss of remote the turbine stand. valve control for main stop valves PV-1611 PV-1612 and for the governor valves. CCW G-964 LWD 0120C2-KB Bus 1C and Bus 2C Damage to this circuit could None. Component cooling pues G-15A, undervoltage autostart prevent auto starting of the G-158. G-15C will remain available. interlock pump or if the pump is in the auto mode cause spurious starting. IXD0120C3-KB Bus 1C and Bus 2C Damage to this circuit could undervoltage autostart prevent pump from auto interlock starting, or if in the auto mode cause spurious starting i l lYD0120C6-KB Pump discharge Damage to this circuit could low pressure interlock spuriously start the pump and/or ' prevent its remote operation, or autostarting. Damage to tnis circuit could also cause tne ptsnp to run continuously regardless of the pressure level if in the auto mode. I k I I i i

!  Impell Corporation                                                                                                                              Revision 0 Report No. 01-0310-1435                                                      P8-134

_. - _ _ _ _ _ . . . , _ _ _ . _ . . _ . < .m.. -_ . -. . ..m. ,.

  ,s.

4 i

10CFM50 APPEN0lX R, 5ECTION III.G C0pe)LIANCE EVALOATION <

E FIRE AREA / ZONE 1-PS-29-13C Battery Room Attic f Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Cold . 'None .., Shutdown 4 Equipment t ) High/ Low None . l Pressure I Interface l Spurious None i Operation i Equipment' ) Alternate None 4 Shutdown { Equipment I Dedicated None l Shutdown Equipment i l. i i l i I i i i 4 4 l s i i i ' i 1 l Impell Corporation

Report No. 01-0310-1435 PB-135 Revision 0

1 ? ~ O

  • 10CFR50 APPENDIX R, SECTION III.G COW LIANCE EVALUATION FIRE AREA / ZONE l-PB-32-14 Instrument Shop-Second Floor Effects of Fire on Safe Shutdown CapaDility The design basis fire will not affect the capaoility to achieve
                                                                           ' and maintain cold snutdown, as there are no safe shutdown i                                                                           - components or caoles within the fire area / zone.

i s l 4 ? I l 1 i i 1 i i  ! i i l l i

)

i I I i i. i i Impell Corporation l Report No. 01-0310-1435 PB-136 Revision 0 1

_ _ . _ _ _ . . - - _ . , . . . , . _ . _ _ . _ . . . _ . - . __,_ _ . . . _ . . . _ _ . . .m.. ._m . r I '10CFK50 APPEh0IX R,-SECTION Ill.G CurfLIAhCE EVALOATIuN t ! FIRE AREA /40NE 1-Po-32-14 i Instrument Snop-second Floor f f Category System Component Circuit-Schedule - Function Consequence of Fire Mitigation a i Hot .None i Staney ! Equipment l

!          Cold        None

} Shutdown j Equipment

  • i j High/ Low None 1 Pressure i Interface 1 Spurious None

! Operation l Equipment l Alternate None Shutdown ' Equipment l Dedicated None ! Shutdown j Equipment 4 i. l t 1 i I , I I l > i

)

1 4 Impe11 Corporation Report No. 01-0310-1435 P8-137 Revision U

   . .. - . . -           . _ ....     -_ . . -. . . .....-..-_.m     . - . , - . _ . _ . . . . . _ _ _ . _ . _ . . . . - . . . _ . _ . . . . - . .
                                                                           .                                                                           - . . . , _ . _ _ . .            ...   ._           . . . .. . _ _ _         ~ . ..

a

                                                                                                                                                                                                                                             ?

1

 !                                                                 10CFR50 APPENDIX R. SECTION III.6 CorLIANCE EVALUATION t                                                                                            .               . -

1 FIRE AREA / ZONE 1-PB-35-15 TSC HVAC Room l i Effects of Fire on Safe Shutdown Capability The design basis fire will not affect the capability to achieve i and maintain cold shutdown, as there are no safe shutdown components or cables within the fire area / zone.  : i i .' i f I }  ! i t a  ! 4  ! i i l l t i 1 t l I . I I i l s  ! ) t 4 i j Impe11 Corporation-Report No. 01-0310-1435 PB-138 Revision 0

                                                       . ._      - .. ...           .._.m.          _ . _ _ . . . - _ .   ._.. . . _ . _ . _ .                                                    . _-        _     _ . .

s 10CFR50 APPENDIX R. SECTION III.6 COW LIANCE EVALUATION. Fini AREA / ZONE l-Po-J5-15 T:4 rNAC Room ' Category System Cossonant Circuit-Schedule . Function Consequence of Fire Mit t ention Hot none , Standby Equipment 1 Cold None Shutdown Equipment i High/ Low None Pressure Interface [ l Spurious None Operat1on Equipment

                                                                                                                                                                                                                            ?

i Alternate None i Shutdown Equipment I t t Dedicated None Shutdown i Equipment l t i I i i i .I )  ! I Impell Corporation i Report No. 01-0310-1435 P8-139 Revision U  ;

O O O 10CFR50 APPENDIX R. SECTION III.G C(HPLIANCE EVALUATION FIRE AREA / ZONE l-P8-42-16 Control Room Complex Effects of Fire on Safe Shutdown Capao111ty A fire in this fire area / zone could result in the loss of the following portions of systems used to achieve hot standby and cold shutdown: Reactor Coolant System (RCS)

                             -    Reactor protection system trip circuits
                             -    Caoles for the following components:
                                   . PORVs
                                   . Bloct valves
                                   . Pressurizer heaters
                                   . Source range monitors
                                   . Pressurizer level transmitters
                                   . Pressurizer pressure transmitters
                                   . Primary system temperature transmitters Chemical and Volume Control System (CVC5)
                             -     Caoles for the following components:
                                   . Charging pumps and associated support equipment
                                   . Charging RWST isolation valves
                                   . RWST isolation valve
                                   . Charging loop A control valves
                                   . Charging loop A flow transmitter
                                   . Seal injection flow control valves
                                   . Reactor coolant pump seal flow pressure transmitters Main Steam System (MSS)
                             -     Cables for the following components:
                                   . Atmospheric steam dump valves
                                   -     Steam generator level transmitters
                                   . Main steam header pressure transmitter                          t
                                   . Turoine stop valves
                                   -     Reheater isolation valves t

t Impe11 Corporation Report No. 01-0310-1435 PB-140 Revision 0

O8 O J 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATI0ri FIRE AREA / ZONE l-PS-42-16 Control Room Complex Auxiliary Feemsster System (AFw)

                           -     Cables for tne following components:
  • Motor driven auxiliary feedwater pump
                                 -     Steam driven auxiliary feedwater pump
                                 -    Aux 111ry feedwater control valves Component Cooling Water System (CCW)
                           -     Cables for the following components:
  • Component cooling water pumps
                                 . CCW heat exchanger isolation valves
                                 -     Thernal b arter pump
                                 -     Therinal byrier outlet valves
                                 -     CCW to RHR heat exchanger flow control valves Saltwater Cooling System (SWC)
                           -     Cables for the following components:
                                  -    Saltwater cooling pumps Residual Heat Removal System (RHR)
                            -    Caoles for the following components:
                                  . Residual heat removal pumps
                                  . Residual heat removal inlet isolation valves
                                  . Residual heat removal discnege isolation valves
                                  -    RHR heat exchanger isolation valves
                                  . RHR inlet and discharge temperature transmitters
                                  -    RHR flow control valve Diesel Generator Systems (OG)
                            -     Cables for the following components:
  • Diesel generators and associated support equipment Gaseous Nitrogen System (GNI)
                            -     Cables for the following components:
  • PORV/ block valve nitrogen supply control valve Impell Corporation Report No. 01-0310-1435 P8-141 Revision U
   -    __     m - _ _       _ _

v Cm

'                                 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION                    ,

FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Essential Electric Systems ! - 120VAC vital buses

                                       -     Cables for the following components:                            -
                                             -     4160V buses
                                             -     480V switchgear                                           -
                                             -     480V motor control centers I                                             -     120V vital buses
                                                                                                              ~

( Tne fire protection features provided for the protection and ? j separation of the safe shutdown systems witnin the fire 1 area / zone do not meet the separation requirements of 10CFR50 j Appendix R. Section III.G.2. Tne deaicated snutdown system I will be used to achieve cold snutdown in tne event of fire. Operator action will be tamen from the control room to i deenergize offsite and normal onsite power sources to prevent t and mitigate spurious equipment operation. Operator action l will also De taken to locally control certain valves used for i hot stan@y. j Reactor scram breaker trip is postulated for a fire in this fire area / zone. 4 l The interruption of seal cooling and seal injection to the d reactor coolant pumps for the period required to initiate seal j injection from the dedicated shutdown system has been evaluated and detemined to be acceptable (26). 1 The loss of auxiliary feedwater flow for the period required to initiate auxiliary feedwater flow from the dedicated i shutdown system has been evaluated and determined to be acceptable (24,25). \ l Damage to cables for the PORVs and their associated block

'                                valves could cause the PORVs to spuriously actuate when the olock valve is not available to isolate the lines. Spurious actuation of the POKV, until operator action is taken to I

deenergize and close the valves, has oeen analyzed, and will

 '                               not result in an unacceptable conottion (24,25).                              -

i li l Ixpell Corporation Report No. 01-0310-1435 PB-142 Revision 0

_ _ _ - . _ ~ . _ . . . _ _..... - i O O 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION O FIRE AREA / ZONE l-P8-42-16 > d Control Roora Complex I Damage to the cables for RwST flow control valves MOV-Il006 and MOV-11000, and volume control tans isolation valve l MOV-1100C could prevent suction flow to tne cnarging pumps 1-from Ene RW5T. Operator action will be required to manually .: ] close MuV-1100C and open MOV-1100s or MOV-11000, to provice ' cnarging flow from tne HudT and prevent cavitation of the l charging pop den the volume control tank empties. Tne time j availaole for operator action to prevent chargning pump damage is currently under evaluation. 3' i Damage to caoles for the turbine stop valves could cause the valves to remain open, preventing turbine trip. Operator action will be required to manually trip the turbine at the i turbine stand. Spurious actuation of the valves, until 4 j operator action is taken to manually trip the turbine, has been analyzed and will not result in an unacceptable condition ] (24,25). l Damage to cables for the atmospheric steam dep valves and ' condenser dump valves could cause these valves to spuriously j open. Spurious actuation of these valves, until operator ] action is taken to deenergize and close the valves, has been

;                                                     analyzed and will not result in an unacceptable condition j                                                       (24,25).

Damage to cables for the reheater isolation valves could cause { the valves to remain open. Operator action will be required 1 g to manually close tne valves. Spurious actuation of tne j valves, until operator action is tanen to close the valves, J has seen analyzed and will not result in an unacceptaole condition (24,25). j i Damage to cables for the residual heat removal inlet isolation i valves MOV-dl3 and MUV-814, could cause tne two series isolation valves to spuriously open. Spurious actuation of MOV-813 will be prevented by locking out power to the valve I during power operation.

                                                     . Damage to cables for the residual heat removal discharge                                           :

isolation valves MOV-833 and MOV-834 could cause the two ' series valves to spuriously open. Spurious actuation of MOV-834 will be prevented by locking out power to the valve i during power operation. l i l Ispell Corporation 4 Report No. 01-0310-1435 P8-143 Revision 0 . i

O O O 10CFR50 APPENDIX R, SECTION 111.6 COWLIANCE EVALUATION ! FIRE AREA / ZONE l-PB-42-16 Control Room Complex 4 1 4 Damage to cables for the reactor head vent valves and e pressurizer head vent valves could cause the two series high/ low pressure interface valves to spuriously open. The spurious actuation of these valves, until operator action is taken to deenergize and close the valves, has been analyzed, and will not result in an unacceptable condition (24,25). Damage to cables for the seal return and letdown isolation valves could cause the two series valves in each line to l remain open. The spurious actuation of these valves, until

;                           operator action is taken to deenergize and close the valves, has been analyzed, and determined to be acceptable (24,25).

Damage to cables for auxiliary pressurizer spray isolation i valve CV-305 could cause tne valve to spuriously open. j Spurious actuation of tne valve, until operator action is taken to deenergize and close tne valve, nas oeen analyzeo and ' determined to be acceptaole (24,25). t Damage to cables for primary plant makeup water control valve FCV-Il02A could cause tne valve to spuriously actuate, allowing primary plant makeup water to oe supplied directly to ) 4 the charging pump suction. Spurious actuation of this valve, 4 until operator action is taken to deenergize and close the valve, has been analyzed and determined to be acceptable (27). Damage to cables for the boric acid supply valves FCV-11028 and CV-334 could cause these valves to spuriously open, s

'                           allowing concentrated boric acid to be supplied to the charging pump suction. Operator action will be required to close manual valves to isolate these lines.

] Damage to cables for the refueling water pumps could cause j these pimps to spuriously start. Containment spray could be r inadvertently initiated as the cables for the containment i spray isolation valves could also be affected by a fire in this fire area / zone. Operator action to trip offsite power will deenergize the planp, and close a manual valve located at the refueling water pumps, and prevent depletion of the RWST i inventory (31). 1 t Izpell Corporation l Report No. 01-0310-1435 PB-144 Revision 0 j f

C O O 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Damage to circuits for alternate shutdown system components will not affect safe shutdown as these systens~are not credited for a fire in this fire area / zone. Spurious actuation of the safety injection and main feedwater systen components will not affect safe shutdown as the safety injection ano main feedwater pumps are tripped oy operator action to trip offsite power. Damage to circuits for charging safety injection isolation valves MOV-35ts, m#-357 and mW-358 could cause these valves to spuriously open. Spurious actuation of these valves will divert charging flow from the seal injection flowpath to the charging safety injection floupath. The effects of the spurious actuation have been analyzed. The analysis indicates that adequate flow will remain available for seal injection (28). Impe11 Corporation Report No. 01-0310-1435 P8-145 Revision 0

10CFN50 APPEh0IX k, SECTION III.G CUW LIANCE EVALUATION FIRE AREA /ZohE l-P8-42-16 Control Room Congslex Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus IA 1XAIA02Cl-K8 Remote breaker control Damage to this circuit could Maintain this breaker racked out to Staney Brkr 02 cause a loss of remote breaker prevent bus IA and 18 intertie.

Equipment control, and spuriously close or trip the breaker.

Bus IC IWAIC01C2-KB Remote trip and close Damage to this circuit could Operator action to trip offsite power i Brkr 01 bus IC to IA tie breaker cause a loss of remote breaker prior to exiting the control room, control, and spuriously close or j trip the breaker, lWAIC01Al-KB Sensor signal Damage to this circuit could cause a loss of overcurrent i protection or could cause the breaker to trip on overcurrent. l IFAIC01Cl-KC Sequencer 502 trip Damage to tnis circuit could i ano lockout trip the creamer, prevent i closing of the creaker, or prevent a trip on sequencer I initiation. Bus IC IWAIC10Al-K8 Anneter circuit Damage to this circuit could None. Dedicated snutdown system will Brkr 10 renove overcurrent protection or remain availaole. Exemption for lacx

,                             (XO6)                                                cause the breaker to trip on        of area-wide suppression / detection overcurrent,                        per III.G.3.

l 1WAIC10Cl-KB Remote breaker control Damage to this circuit could ' cause a loss of remote breaker control, and spuriously trip the l breaker, or prevent closing or j tripping the breaker. i l 1 1 I,apell Corporation Report No. 01-0310-1435 PB-146 Revision 0 l I . _. __

E

                                                                                                                                                   ~

10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATIDN FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Consequence of Fire Mitigation Category System Componant Circult-Schedule Function Damage to this circuit could none. Dedicated shutdoun system will Hot 4160V Bus IC IW1C11Al-K8 Ammeter circuit remove overcurrent protection or remain avall ele. 5taney (contd)- Brkr 11 trip the breder on overcurrent. Equipent (IOS) (contd) Remote orem er position Damage to this circuit could luAIC11Cl-KC indication cause the loss of remote pre m er control and/or result in a loss of Ore mer position inoication at panel C41. I d1C11C2-Kd Remote breamer control Damage to this circuit could cause a loss of remote tre m er control, and spe riously close or trip the oremer. Generator potential Damage to this circuit could None. Dedicated shutdown system will Sus IC IFA1C14C4-KC remain available, Brkr 14 to spchronizer cause the generator output breaker to trip. If the diesel r generator is sequencer started, thee the output breaker protective function is disconnected. I' Damage to this circuit could IFAICl4CH-KC Generator metering and l cause the generator output breaker protective relays l ' to open on " Reserve Power."

                                                                                " Negative Phase Sequence." or
                                                                                " Voltage Controlled Overcurrent."

If the diesel generator is sequencer started, then the output bremer protective function is disconnected. 1FAIC14CJ-KC Generator metering Damage to this circuit could and protective relays cause tne generator's output areamers to se opened on " Negative Phase Sequence" or " Voltage Controlled Overcurrent." If the diesel generator is sequencer startes, taen tne output areaser protective function is disconnected. i Impe11 Corporatton Ceport 40. 01-0310-1435 PB-147 Revision 0 l

                                                                                ^                                                 ,.

f'~ I ) , l 10CFA50 AP/END11 k, SECTION 111.G COWLIANCE EWALUATION FIRE AREA / ZONE 1-Po-42-16 Control doom Complex l Category Systes en=panent Circuit-Schedule Function Consequence of Fire Mittoation i Hot 4160V Bus IC IFA1C14CK-KC Sus 1C potential Damage to this circuit could 5taney (contd) Brkr 14 to synchron12er cause Bus 1C to trip and isolate l itself from diesel generator I 1 Equipment (contd) (contd) and offsite power. If the diesel is sequencer started, then the output breaker protective function j is disconnected. IFAIC14CP-KC 1AIC14 breaker trip Damage to this circuit could acknowledge to sequencer cause the sequencer to spuriously 502 stop loading the bus or signal the i sequencer that the output breaker l ' was closed and that Bus IC was ready for loading. 1FA1C14CR-KC Remote breaker control Damage to this circuit could cause a loss of remote breaner control, and spuriously trip tne breaker, disconnecting diesel generator I from ous IC. 1FAIC14C5-KC Sequence 502 trip and Damage to tnis circuit could close signals cause a loss of remote creaner control, and spuriously trip tne creamer or prevent tripping of the creamer, altnougn it could still ne controlled at AIC. IFA1C14CT-KC Sequence 502 trip and Damage to this circuit could close signals cause a loss of remote breaker control, and spuriously trip the breaker, or prevent sequential l l control of the breaker. InARI1 Col-KC Control circuit PCB Damage to this circuit could trip mechanism cause a loss of remote breaker control, and spuriously trip the breaker. l l l l Impe11 Corporation Report no. 01-0310-1435 Pu-148 Revision u

10CFR50 APPENDII R. SECTION III.E C0pFt.IANCE EVALUATION FIRE AREA /20aE 1-PB-42-16 Control Room complex Category Systen rn-panent Circuit-Schedule Function Consequence of Fire Mitiestion r Hot 4160V Bus 2C IIA 2C01Al-KB Curret anneter circuit Damage to this circuit could Operator action to trip offsite power Staney (contd) Setr 01 remove overcurrent protection or prior to emiting the control room. Equipment spuriously trip the breaker. (contd) IIA 2C01C2-K8 Remote breaker control Damage to this circuit could cause a loss of remote breaker i control, and spuriously close or trip the breaker. 1GA2C01Cl-KC Sequencer 503 trip Danage to this circuit coula and locuout cause a loss of remote breaner control, and spuriously trip or prevent tripping of tne oremer. Sus 2C IIA 2C02C4-K8 Remote bre mer control / Damage to tais circuit could operator action to trip offsite power Brkr 02 feeder from auxiliary cause a loss of remote bre m er prior to exiting the control room. transforsutr C control, and spuriously close or L trip the breaker. None. Dedicated shutdown system will ' Sus 2C IIA 2C1041-K8 Sensor signal Damage to this circuit could trkr 10 remove overcurrent protection or remain available. (107) spuriously trip the breaker. IIA 2C10C1-KB Remote breaker control Damage to this circuit could l cause a loss of remote breaker control, and spuriously close or [ trip the breaker. Sus 2C IIA 2C11Al-KB Sensor signal Damage to this circuit could None. Dedicated shutdown system will Brte 11 remove overcurrent protection or remain availaole. f (108) spuriously trip the breamer. j l 1XA2C11C2-Ks Remote oreaner control Damage to tnis circuit could remove overcurrent protection or spuriously trip the creamer.  ; Impe11 Corporation , Report No. 01-0310-1435 P8-149 Revision 0

                                                                                                                                            /

10CFR50 APPENDIX R. SECTION III.G COPFLIANCE EVALUATION FIRE AREA /20hE 1-PB-42-16 Control Moom Complex Category System Component Circuit-Scnedule Function Consequence of Fire Mitigation Hot 4160V Bus 2C IGA 2C15C4-KC Generator potential to Damage to this circuit coulo None. Dedicateo snutoown system will 5taney (contd) Brur 15 synchronizer cause tne generator's output remain availaole. Equipmen t breater to trip, or if tne diesel (contd) generator is sequencer started, tne output breaker protective function is disconnected. 1GA2C15CH-KC Generator metering and Damage to this circuit could protective relays cause the generator output breaker to be opened on " Reserve Power,"

                                                                         " Negative Phase Sequence," or
                                                                         " Voltage Controlled Overcurrent."

If the diesel generator is sequencer started, then the output breaker protective function is disconnected. 1GA2C15CJ-KC Generator metering and Damage to this circuit could protective relays cause the generator's output breakers to be opened on " Negative Phase Sequence" or " Voltage Controlled Overcurrent." If tne diesel generator is sequencer started, then the output Dreater protective function is cisconnected. 1GA2C15CK-KC sus 2C potential to Damage to this circuit could to synchronizer cause bus 2C to trip ano isolate itself from ciesel generator 2 and offsite power. If the diesel is sequencer started, tnen the output creater protective function is disconnected. 1GA2C15CP-KC lA2C15 breaker trip Damage to this circuit could acknowledge to sequencer cause a false signal to the 503 sequencer indicating that the diesel generator's output breaker was closed and that bus IC was ready for loading, or cause the sequencer to believe that the breaker was open and stop loading the bus. 1GA2C15CR-KC Remote breaker control Damage to this circuit could cause a loss of remote breaker control, and spuriously trip the breaker, disconnecting diesel generator 2 from bus 2C. Impe11 Corporation Report No. 01-0310-1435 P8-150 Revision 0

O O ' O 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE I-P8-42-16 Ccntrol Room Complex C-tegory Systa r._ ,- _ = t Circuit-Schedule Function Consequence of Fire Mitigation Hot 4160V Bus 2C IGA 2C15CS-KC Sequencer 503 trip and Damage to this circuit could Staney (contd) Brkr 15 close signals cause a loss of remote breaker Equipment (contd) control, and spuriously close or  ; trip the breaker. (contd) 1GA2C15CT-KC Sequencer 503 trip and Damage to this circuit could close signals cause a loss of remote breaker control, and spuriously trip the brewer or prevent sequencer control of the creater. 12ARY1C01-KC Control circuit PCs Damage to this circuit could trip mecnanism cause a loss of remote bremer control, or spuriously trip bypass Dremer RY1 or close ore mer 12Cib.

                          $wgr 1       IdBS102C1-KC       Remote bremer position Damage to this circuit could               None. Dedicated snutdown system will 480V indication                    cause a loss of remote breaker      remain availaole, Brkr 02 control at the control room panel C-12. Breaker control could still be available via pushDutton at 480V switchgear 804.

Swgr 1 IWBS103C6-KB Remote breaker control Damage to this circuit could None. Dedicated shutdown system will Brkr 03 cause a loss of remote breaker remain available. control, and spuriously close or trip the breaker. The breaker could be closed via push button at 480V switchgear 804, lWBS103Cl-KC Remote breaker Damage to this circuit could position indication cause spurious operation of the breaker or cause a loss of remote breaker control at the control room panel Cl2. Tne creaker could still De closed via pushbutton at f ' 480V switengear a04. Remote bremer control Damage to this circuit coulo None. Dedicated snutoown system will - Swgr 2 IX85202C3-K8 orar 02 cause a loss of remote pre m er remain availaole. control, and spuriously close or trip the breamer. The breaker could be closed via push Dutton at 480V switchgear 805. Impell Corporation Report No. 01-0310-1435 PB-151 Revision 0

O O O 10CFR50 APPENDIX R SECTION Ill.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot 480V Swgr 2 IX85202Cl-KC Remote breaker Damage to this circuit could cause Staney (contd) BrKr 02 position inoication a loss of remote areaker control Equipment (contd) at tne control room panel C12. (contd) Breater control could still be availaole via pushoutton at 480V swtichgear uGS. Swgr 2 IX8520367-K8 Remote breaker control Damage to this circuit could None. Dedicated shutdown system will Brkr 03 cause a loss of remote breaner remain available, control, and spuriously close or trip the breater. The breaker could be closed via push button at 480V switchgear 805. IX85203Cl-KC Remote breaker position Damage to the circuit could indication prevent sequencer initiated closing of the tie breaker, but the breaker could still be closed via panel C12 or via a pushbutton on 480V switchgear 805. Damage could also cause a loss of remote breaker control at the control room panel C12. Breaker control could still be available via pushoutton at 480V switcngear 805. 1Gd5203Cl-KC Sequencer #2 interlock Damage to tnis circuit could cause loss of remote breaser control, and spuriously close the breaker. The creaxer could still be closed via pushouttun at switchgear 805. Swgr 3 lYBS303Cl-KC Remote breaker position Damge to this circuit could None. Dedicated shutdown system will Brkr 03 indicator prevent remote operation of remain available. the breaker. 1YBS303C3-KB Remote breaker control Damage to this circuit could cause a loss of remote braaker control, and spuriously close or trip the breaker. The breaker could be closed via push button at 480V switchgear 806. Impell Corporation Report No. 01-0310-1435 Pu-152 Revision 0

              -                                                                       L                                                                  d
                                                             '0CFR50 APPENDIX R. $ECTION !!!.6 COWLIANCE HALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex Category System Component            Circuit-Schedule Function                          Consequence of Fire                          Mitigation Hot             120V     37.5/       1G80238-K8       Power                         Loss of power to the 37.5/7.5         None. Dedicated shutdown system will Staney                   7.5 kVA                                                    kVA transformers will result          remain available.

Equipment Transformer in loss of power to vital bus 4 (contd) and alternate power feed to vital buses 1, 2, 3, 3A and 4. 1F80181-KB Power Damage to this circuit could cause loss of 4dOVAC power from MCC 1 feeding one side of manual transfer switch #7. This switch

!                                                                                         supplies 480V power to the J                                                                                          37.5KVA transformer feeding vital bus fl. 2, 3A, and 4 i                                                                                          and tne 7.5kVA alternate feed I                                                                                          transformer for vital Dus 94.

Power from tnis switch also supplies power to the rod control system at panel C07. j Power to the transformers and i i 007 could oe manually restored oy switching to tne alternate l feed from MCC 2. Y11 ---- Vital bus 1 Loss of vital bus 1. None. Dedicated shutdown system will remain available. , 1HY1100-KB Power Loss of distribution panel Y-11 , < will cause the loss of power to the following components required for normal / alternate shutdown: CV-546 TE-600 Y-11R PT-430 TCV-601A IE-1201 i i CV-530 TCV-6018  : i ~ t i I i , Y-11R - - - - Regulated Bus 1 Loss of Y-llR. None. Dedicated shutdown system will i remain available. {; IFY1107-KB Power Loss of distribution panel j YllR will cause tne loss of power to tne following

                            .                                                             components required for normal /

I alternate snutdown: l TE-400C TE-400A TE-601A 4 TC-601A TE-402C TE-60lu 1 HCV-602 TC-60lts TI-400 I i l Impell Corporation , Report No. 01-0310-1435 P8-153 Revision 0

)

O O

  ~

10CFR50 APPEWIX R. SECTION III.G C(MPLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation

 . Not         DG       Y-12       ---              Vital Sus 2                 Loss of Y-12                        Mone. Dedicated shutdown system will Standby    (contd)                                                                                              remain available.

Equipment 1HY1200-K8 Power Loss of distribution panel Y-12 (contd) will cause the loss of power to the following components required for normal / alternate shutoown : CV-545 PT-431 CV-7226 Y-12R CV-531 CV-722A CV-722C Y-12R --- Regulated dus 2 Loss of Y-12R. None. Dedicated shutdown system will remain available. 1GY1207-K8 Power Loss of distrioution panel Y12R will cause the loss of power to the following components required for normal / alternate shutdown: TE-410A TE-412C LT-431 TI-410 Y-13 - - - - Vital Bus 3 Loss of Y-13. None. Dedicated shutdown system will remain availaole. Y-33 ---- Vital Bus 3A Loss of vital ous 3A. None. Dedicated shutdown system will remain availaole. Y-13/Y-33 1HY1300-KB Power Loss of power to Y-13 and Y-33 None. Dedicated snutdown system will will cause the loss of power remain available. to the following camponents required for normal alternate shutdown: TE-2401 LT-2400A FCV-2300 TE-2412A LT-24006 FCV-2301 TE-2422A LT-2400C E-1202 Y-13R Y-13R - - . - Regulated Bus 3 Loss of distribution panel Mone. Dedicated snutdown system will - Y-13R. remain available. Loss of power to Y-13R will cause

                                                                                                ~

1HY1307-K8 Power > the loss of power to the following components required for normal / alternate shutdown: TE-422C Impe11 Corporation Report No. 01-0310-1435 P8-154 Revision 0

n U t) Os 10CFR50 APPEhulX R, SECTion Ill.G CuWLIANCE EVALUATION Flue AREA / ZONE l-P8-42-16 Control noom Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation

                                    ---         Vital Bus 4                 Loss of Y-14.                     None. Dedicated shutdown system will Hot         120V     Y14 remain available.

Staney (contd) Equipment (contd) Regulated Bus 4 Loss of Y-14R. None. Dedicated shutdown system will Y14R remain available. IJY1408-KB Power Loss of power to distribution panel Y14R will cause the loss of power to the following can;:enants required for normal / alternate shutdown: LT-435 PT-1115A PCV-1115C P-418 PT-11158 FCV-1115A PT-425 PT-1115C FCV-11156 PT-459 PCV-1115A FCV-1115C PC-418A PCV-1115d PC-1115A PC-11155 PI-1115A PI-11158 ! PC-1115C PI-1115C IwYl4K3-Ks Power Loss of power to distrioution l panel Y14R will cause tne loss of I power to the following components required for normal / alternate shutoown: LT-435 PT-1115A PCV-1115C P-418 PT-11158 FCV-1115A PT-425 PT-1115C FCV-11158 PT-459 PCV-1115A FCV-1115C PC-418A PCV-11158 PC-1115A PC-11158 PI-1115A PI-11158 PC-1115C PI-1115C IWL101C3-KB Power Loss of power to distribution None. Dedicated shutdown system will Y15 panel Y-15 will cause the loss remain available. of power to the following components required for norma 1/ alternate shutdown: CV-304 Loss of Inverter 4. None. Dedicated shutdown system will YV14 ---- Inverter 4 Inverter 4 remain availante. IwD013301-Kd Pow r Damage to tnis circuit coula cause a loss of power to l Inverter 4. i Impell Corporation ! Report No. 01-0310-1435 P8-155 Revision 0 l

\ [ l V \ q 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-PS-42-16 Control Room Complex ! Category Systen en-panent Circuit-Schedule Function Consequence of Fire Mitigation l i Hot 120V V29 - Vital Bus 5 Loss of Y-29. None. Dedicated shutdown system will l 5taney (contd) remain available. Equipment (contd) 1GYV29P2-KC Power Loss of power to vital ous 5 could cause tne loss of power to tne following components required for normal / alternate snutcomm: LT-3400A LT-34006 LT-3400C TE-3402A TE-3411A TE-342;A l FCV-3300 FCV-3301 CV-3201 SV-3200 SV-3214 l - SV-3205 SV-3203 SV-3211 SV-3202 SV-3204 CV-3213 RCS CV-530 1FY1112C1-KC Remote valve control / Damage to this circuit could Operator action to deenergize 120V AC/ position indication result in the loss of remote 480V AC power to prevent / mitigate valve control, and/or cause the spurious operation. CV-530 will valve to spuriously open or fall open on loss of power. close. CV-546 1FY1112CD-KC Remote valve control Damage to this circuit could Operator action to deenergize 120V AC/ prevent remote operation and/or 480V AC power to prevent / mitigate cause the valve to spuriously spurious operation. CV-546 will fail open or close, closed on loss of power. Spurious actuation of the PORV, until operator action is taken to deenergize and close the valves, nas been analyzed, and will not result in an unacceptaole conottion (24,25). IFY1112C2-KC Remote valve control / Damage to tnis circuit could position indication prevent remote operation and/or + cause the valve to spuriously open or close.

 -                                        IWY1112C2-KC      PRD-425-12C interlock      Damage to this circuit could result in tne loss of remote valve control, and/or cause the valvs to spuriously open or prevent the valve from opening l

on loss of instrtament air to PORVs. I i Impe11 Corporation , Report Mo. 01-0310-1435 FB-156 Revision 0

O O - O 10CFst50 APPEN0It R. SECTION III.G CWIPLIAmCE EVALUATION FIRE AREA /20hE 1-Ps-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire mitigation Hot RCS CV-530/546 1FY1112PI-KC Power Tnis circuit is entirely Operator action to oeeneergize 120V AC/ Staney (contd) contained within the fire area / 480V AC power to prevet/ mitigate spurious < Equipment zone. The circuit and its operation. CV-530 will f all open on loss l (contd) termination polits are assumed of power. CV-546 will fall closed on loss ' destroyed. of power. Spurious actuation of the PORV. untti operator action is taken to deenergize and close the valve, has been wealyzed, and will not result in an unacceptable condition (24.25). i f CV-531 1GY1215C1-KC Remote valve control Canage to this circuit could Operator action to deenergize 120V AC/ ! result in the loss of remote 480V AC power to prevent / mitigate spurious . valve control, and/or cause the operation. CV-531 will fall open on loss I valve to spuriously open or of power. t close. 1 l CV-545 1GY1215CO-KC Remote valve control Damage to this circuit could Operator action to deenergize 120V AC/ prevent remote operation and/or 480V AC power to prevent / mitigate spurious cause the valve to spuriously operation. CV-545 will f ai t closed on loss open or close. of power. Spurious operation of the PukW. I until operator action is tamen to deenergize and close the valve, has been analyzed, and will not result in an unacceptaole conettfort (24.25). 16Y1215C2-KC Nemote valve control / Damage to this circuit could

position indication result in the loss of remote l valve control, and/or cause the valve to spuriously open or close.

IIY1215C1-KC Pressurizer high Damage to this circuit could pressure interlock result in the loss of remote valve control and/or cause the valve to spuriously open, or prevent it from opening. 1XY1215C2-KC PRD-425-IIC interlock Damage to this circuit could result in the loss of remote valve control, and/or cause the valve to spuriously open. Damage could also prevent opening or loss of instrument air to PORVs. i Impe11 Corporat1on Report No. 01-0310-1435 P8-157 Revision 0

          ,                                                                                                                                  y\

i,, ) l x,) I

                                                                        '    )                                                              (x    <

10CFR50 APPENDIX R. SECTION III.G COPFLIAhCE EVAWATION FIRE AREA / ZONE 1-PS-42-16 Control Room Cowlex Catevry System Component Circult-Schedule Function Consequence of Fire Mitigation Hot RCS CV-531/545 1GY1215PI-KC Power This circuit is entirely contained Operator action to deenergize 120V AC/ within the fire area / zone. The 480V AC power- to prevent / mitigate spurious Staney (contd) circuit and its termination points operation. CV-531 will fall open on loss Equipment (contd) are assumed destroyed. of power. CV-545 will fail closed on loss of power. Spurious operation of the PURV, untti operator action is taken to deenergize and close tne valve, nas oeen analyzed, and will not result in an unacceptacle condition (24,25). Przr IFdS115C3-Ks Remote control Damage to this circuit could hone. Caoles for dedicated snutoown system Heaters result in the loss of remote operation of pressurizer heater group p are Group A control and/or cause tne routea outside tne fire area and will pressurizer neaters to spuriously remain available. energize or trip. 1F85115C4-K8 Pressurizer level Damage to this circuit could interlock cause a loss of remote control and/or cause the pressurizer heaters to spuriously trip or energize. IFBS115C5-KB Pressurizer level Damage to this circuit could interlock cause a loss of remote control and/or cause the pressurizer heaters to spuriously trip. 1FBS115C6-KB Pressurizer level This circuit is entirely contained interlock within the fire area / zone. The circuit and its termination points are asstmed destroyed. 1FQ104076-K8 Control signal Damage to tnis circuit could prevent operation of pressurizer heater group A, althougn group u would operate correctly. l i l l Impe11 Corporation teoort No. 01-0310-1435 PS-158 Revision 0

O O O 10CFR50 APPENDII R. SECTION III.G CorLIANCE EVALUATION FIRE AAEA/ ZONE l-PS-42-16 Contrcl koom C g lex Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigatton Damage to tnis circuit coulo None. Caoles for oedicated snutdown system Hoc RCS Przr IG85215C3-Es menote bremer control cause a loss of remote control operation of pressortzer heater group 9 are Staney (contd) waters and/or cause the pressurtzer routed outstee tne fire area and will Equipment Group 5 heaters to spuriously trip. remain availaole. (contd) IGBS21cC4-K8 Pressurizer level Damage to this circuit could interlock cause a loss of remote breaker control and/or spuriously energize or trip the heaters. IGBS215C5-K8 Pressurizer level Damage to this circuit could interlock cause a loss of remote control and/or cause the pressurizer heaters to spuriously trip. IGBS215C7-K8 Pressurizer level This circuit is entirely interlock contained within the fire area / zone. The circuit and its termination points are assumed destroyed. 1GQ104077-Ks Control signal Damage to this circuit could pmvent operation of pressurizer heater group 8. altnough group A would operate correctly. Impell Corporation Report No. 01-0310-1435 P8-159 Revision 0 l

  .~   ,      - . . .      .- ..- .           -    .- .,     ~     ..      ..        .         . .     ..-       .-.     -.~.-.            .   . .. _._~.-_ - -
                                                                                                                                                                              +

L 10CFR50 APPENDIX R, SECTION III.E COWLIANCE EVALUATION FIRE AREA /20NE l-PB-42-16 Control Room Complex 1 Cnteery System Component Circuit-Schedule Function - Consequence of Fire Mitiention Przr IFBS109C5-KB Pressurizer level Damage to this circuit could None. Cables for dedicated shutdown system i Hot RCS Staney (contd) Heaters interlock cause a loss of remote control operation of pressurizer heater group D '- Eguipment Group C and/or cause the pressurizer are routed outside the fire area and will. (contd) heaters to spuriously trip. remain available. , t IFBS109C4-KB Remote control Damage to this circuit could  ; result in the loss of remote , control and/or cause the pressurizer heaters to spuriously energize or trip. , IFBS109C7-K8 Remote creaker trip Danage to tnis circuit coulo. l circuit - result in tne loss of remote l control and/or cause the l l pressurizer neaters to spuriously ! trip, or prevent an auto trip. l Manual heater control is avail-able from panel C03, however. - l i t 4 r i Impell Corporation t Report No. 01-0310-1435 PS-160 Revision 0 l.

O O O 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA /2ONE 1-P8-42-16 Control Room Complex Category System Component Circuit-Schedule ' Function Consequence of Fire Mitigation Hot RCS Przr IG8S209C5-Ka Pressurizer level Damage to this circuit could cause - Operator action to transfer contral of tne Standby (contd) Heaters interlock a loss of remote control and/or required portion of pressurizer neater Equipment Group D cause tne pressurizer heaters group D to tne cedicated snutouwn panel. to spuriously trip. Caoles for_deatcateo snutdown operation of (contd) pressurizer neater group u are located outside the fire area and will remain available. 1GBS209C4-KB Remote breaker Damage to this circuit could cause control a loss of remote control and/or cause the pressurizer heaters to spuriously trip. 1G85209C6-K8 Remote breaker Damage to this circuit could cause control a loss of remote control and/or cause the pressurizer heaters to spuriously trip. ME-1201 IWYllR3-KB Power Loss of power to NE-1201 None. During operation of the dedicated shutdown system shutdown margin will be detensined by sampling primary system boron concentration. IGQ102083-K8 Power Damage to this circuit could result in loss of source range indication or erroneous indication. IGyl02074-Ka Sensor signal Damage to tnis circuit could result in low off-scale or erroneous source range indication. 1GQ102075-Ks Sensor signal Damage to tnis circuit could result in low off-scale or erroneous indication, lWQ102006-K8 Sensor signal Damage to this circuit could result in low off-scale or erroneous indication. lWQ102021-K8 Sensor signal Damage to this circuit could result in low off-scale or - erroneous indication. Impell Corporation Report No. 01-0310-1435 Pu-161 Revision 0

O O

  • O 10CFR50 APPENDIX R. SECTION I11.6 ConPLIANCE EfALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex Consequence of Fire Mitigation Category Systen Component Circult-Schedule Function Damage to this circuit could None. During operation of the dedicated Hot RCS E-1202 1FQ102059-K8 Power shutdown system shutdown margin will be result in loss of source range Staney (contd) determined by sampling primary system Equipment indication or erroneous source range indication. boren concentration.

(contd) 1FQ102049-K8 Indication Damage to this circuit could result in low off-scale or erroneous indication. IFQ102050-KB Indication Damage to tais circuit could result in low off-scale or erroneous indication. i IWQ102005-K8 Sensor signal Damage to this circuit could result in low off-scale or erroneous indication. I IWQ102007-K8 Sensor signal Damage to this circuit could i result in low off-scale or erroneous indication. i LT-431 IXY12R4-KB Power Damage to this circuit could None. LT-430A will remain availaole result in low off-scale or at the dedicated shutdown panel. erroneous indication. 1 Sensor signal This circuit is entirely contained IWQ104030-KB within the fire area / zone. The circuit and its termination points are assumed destroyed. 1GQ104078-KB Sensor signal Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication. i 4 1 1 i l Impe11 Corporation Revision 0 Report No. 01-0310-1435 P8-162

O O

  • O 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Cag lex Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot RCS LT-435 INQ104Il-KC Signal loop Damage to this circuit could None. LT-430A will remain availaole at the result in low off-scale or dedicated snutdown panel.

Standoy (contd) Equipment erroneous indication. (contd) Damage to this circuit could IWQ104035-K8 Sensor signal result in low off-scale or erroneous indication. IXY14R4-K8 Power Damage to this circuit could result in low off-scale or erroneous indication.

                              'WQ104081-K8   Sensor signal               Damage to this circuit could result in high off-scale, low off-scale, or erroneous indication.

PT-425 IWY1406-K8 Power Damage to this circuit could None. PT-434A will remain available result in low off-scale or at the dedicated shutdown panel. erroneous indication and deenergize the high pressure interlock to MOV-813 and MOV-834. Idll08002-KB Sensor Signal Damage to this circuit could result in low off-scale or erroneous indication, and deenergize the high pressure interlock to MOV-813 and MOV-834. 1WQ108085-K8 RCS pressure Damage to tnis circuit could interlock to prevent opening of MOV-813 MUV-813 si MOV-834 and MOV-834, or cause loss of operation of PC-425. ! 1FQ10812-KC Sensor signal Damage to this circuit could cause hign-offscale, low-offscale or erroneous indication, and/or ! remove the RCS pressure interlock to RHR valves MOV-813 and MOV-834. 1FQ10813-KC PYV-425 loop continuity Damage to this circuit could J result in low off-scale or erroneous indication, and/or remove the RCS pressure interlock i to RHR valves MOV-813 and MOV-814. Impell Corporation Report No. 01-0310-1435 P8-163 Revision 0

10CFR$0 APPENDIX k MCTION 111.6 COWLIANCE EVALUATION FlKE AREA /luht 1-Po-42-16 Control Koom Complex Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot RCS PT-430 IWQ104001-KB Sensor signal Damage to this circuit could Operator action to deenergize 120VAC/480VAC Standby (contd) result in a pressure interlock power to prevent / mitigate spurious Equipment closing pressurizer spray valves operation. Spurious operation of the PCV-430C and PCV-430H, and/or spray valves PCV-430C and PCV-430H will (contd) not affect safe shutdown as the reactor energizing pressurizer heater groups A and 8. coolant pumps are tripped. Pressurizer i code safety valves will be available for over-pressure protection. PORV's will be available for system pressure control after dedicated shutdown system operation is initiated. 1WQ104020-KB Sensor signal Damage to this circuit could result in low offscale or erroneous indication. Damage to this circuit could result in a pressure interlock closing pressurizer spray valves PCV-430C and PCV-430H, and/or energizing pressurizer heater groups A and d. , 1Wy104023-K8 Sensor signal Damage to tnis circuit could result in low offscale or I erroneous indication. Damage to this circuit could result in a pressure interlock closing pressurizer spray valves PCV-430C and PCV-430H, and/or energizing pressurizer heater I groups A and 8. j 3 1FQ10411-KC Pressurizer transmitter Damage to this circuit could signal result in high off-scale, low i off-scale, or erroneous indication. This could cause spurious operation of PCV-430C, PCV-430H and pressurizer heater r groups A and B. Impell Corporation Report No. 01-0310-1435 PU-164 Revision 0

               .. _               _             _ _  . . _ . ,         . . .        .  .. _             _ __ .~_               =.                 _ .        ..      m  . . .                   -. _      __

O N-

                                  '                                                                                                                                                       J 10CFR50 APPENDIX R. SECTION III.G C0fFLIANCE EVALUATION                                                                          I t
  • l FIRE AREA / ZONE 1-P8-42-16  !

Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire -Mitigation

                                            . PT a31                           Pressurizer. transmitter Damage to this circuit could                      Operator action to deenergize 120WAC/480VAC            l Hot           RCS                      IFQ104I2-KC signal                        cause a high off-scale, low                  power to prevent / mitigate spurious                   i l                      Stadey'       (contd)                                                                                                               operation. Spurious actuation of the PORV,
                    - Equipment                                                                              off-scale, or erroneous-1 indication. . This could result              until operator action is tamen to                      +

i (contd) in CV-546 spuriously opening deenergize and close tne valve, nas oeen , or closing. analyzed, and will not result in an i unacceptaole condition (24,25). i IwQ108025-Ku Sensor signal Damage to this circuit could , 4 cause a low off-scale or I erroneous pressure indication.  ; This will cause CV-546 to spuriously close or operate c erratically. IWQ104026-K8 Sensor signal Damage to this circuit could cause CV-546 to spuriously i close or operate erratically. [ t a 1WQ104027-K8 Sensor signal Damage to this circuit could  ! cause CV-546 to spuriously 1 close or operate erratically. I IWQ104049-K8 Sensor signal Damage to this circuit could result in the loss of remote l' valve control. l, TE-2401A 1FY3309ID-KC Sensor Signal Damage to this circuit could None. TE-402A will remain available 4 result in high off-scale, low on the dedicated shutdown panel. off-scale, or erroneous  ! indication. ( l TI-2401A 1F Y330911-KC Sensor signal Tnis circuit is entirely contained None. TE-402A will remain availaole on the < 1 within tne fire area / zone. Tne oedicated snutdown panel. I circuit ano its termination  ; points are assumed destroyed. 4 TE-2412A 1FY3309IE-KC Sensor Signal Damage to this circuit could None. TE-412A will remain availaole on the result in high off-scale, low dedicated shutdown panel. off-scale, or erroneous ] I indication. l 1 f Impell' Corporation I Reoort No. 01-0310-1435 P8-165 Revision 0 i

;i

3  %,

                                                                                                                                                  )
                                                                               \-

[G {G 10CFR50 APPENDIX R. SECTION llI.G COMPLIANCE EVAL 0ATION FIRE AREA /lohE l-P8-42-16 Control Room Complex Category Systen Component Circuit-Schedule Func tion Consequence of Fire Mitigation Hot RCS TI-2402A/ IFY330912-KC Sensor signal This circuit is entirely contained None. TE-402A and TE-412A will remain Standby within the fire area / zone. The availaole at the dedicated shutdown panel. (contd) 2412A Equipment circuit and its termination y (contd) points are assumed destroyed. TE-2422A IFY3309IF-KC Sensor signal Damage to this circuit could None. TE-422A will remain available at result in high off-scale, low the dedicated shutdown panel, off-scale, or erroneous indication.

!                      TI-2422A/ 1FY330915-KC     Sensor signal              This circuit is entirely contained None. TE-422A will remain available at TI-2009A                                              within the fire area / zone. The   the dedicated shutdown panel, circuit and its termination points are assuned destroyed.

i j 1FY330917-KC Sensor signal This circuit is entirely contained i within the fire area / zone. The circuit and its termination points are assumed destroyed. TE-3402A lGY290410-KC Sensor sigr.a1 Damage to this circuit could Non e. TE-402A will remain r.vailaole at tne result in high off-scale, low dedicated shutoown panel. off-scale, or erroneous indication. Damage to this circuit could None. TE-412A will remain available at the TE-3411A IGY2904IE-KC Sensor signal result in high off-scale.. low dedicated shutdown panel. off-scale, or erroneous . Indication. l l TI-3402A/ IGY2904Il-KC Sensor signal This circuit is entirely contained None. TE-402A and TE-412A will remain 3411A within the fire area / zone. The available at the dedicated shutdown panel. circuit and its termination points are assumed destroyed. 1GY2904I2-KC Sensor signal This circuit is entirely contained within the fire area / zone. The circuit and its termination points are assur:ed destroyed. Impell Corporation Report No. 01-0310-1435 P8-166 Kevision 0 i

10CFR50 APPENDIX R,.SECTION III.G C0pFLIANCE EVALUATION , FIRE AREA / ZONE 1-P8-42 . ! Control Room Conglex Category System. Component Circuit-Schedule Function Consequence of Fire Mitigation Hot RCS TE-3421A IGY2904IF-KC Sensor signal Damage to this circuit could None. TE-422A will remain available at the

result in high off-scale, low dedicated shutdown panel. .

Staney (contd) Equipment off-scale,or erroneous (contd) indication. , 4 TI-3421A/ 1GY290417-KC Sensor signal This circuit is entirely contained None. TE-402A will remain availaole at the dedicated snutdown panel. ! 3009A within tne fire area / zone. The I circuit and its termination ' points are assumed destroyed. l 4 TE-402C IFQ103087-Kd Sensor signal Damage to tnis circuit could . None. It-402u will remain availaole at tn. i result in hign off-scale, low cedicated snutdown panel. off-scale, or erroneous 3 i indication. j i lWQ103019-K8 Sensor signal Damage to this circuit could result in low off-scale or i erroneous indication. j TE-4118 IWQ103022-KB Temperature indication Damage to this circuit could None. TE-4128 will remain available at cause a loss of temperature the dedicated shutdown panel. I indication or cause erroneous O temperature indication. Sensor signal- Damage to this circuit could ) IXQ103063-KB result in high off-scale, low i off-scale, or erroneous ! indication. IXQ108113-KB Temperature controller Damage to this circuit could cause a loss of temperature indication or cause erroneous temperature indication. 4 IXY12R2-Ku Power Damage to tnis circuit could ' cause a loss of power to TM-412 resulting in a loss of i temperature indication. 1 i Impell Corporation Report No. 01-0310-1435 PB-167 Revision 0 L

p q gm 10CFR50 APPENDIX R. SECTION III.G COWLIANCE EVALUATION FIRE AREA /20NE 1-PB-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot RCS TE-422C IHQ104071-K6 Sensor signal Damage to tnis circuit could None. IE-42/6 will remain availaole at tne Staney (contd) result in hign off-scale, low dedicated snutdown panel. Equipment off-scale, or erroneous (contd) indication. lWQ103025-KB Sensor signal Damage to this circuit could result in low off-scale or erroneous indication. RPS Trip IWQll3027-KB Remote scram signal Damage to this circuit could Reactor scram is postulated for control Circuits spuriously scram the reactor or room fire (5). prevent reactor scram from pushbutton at panel C03, lWQll3077-KB Remote scram signal Damage to this circuit could spuriously scram the reactor, or prevent reactor scram from pushbutton at panel C13. 1FQOll3C1-KC Safety injection scram Damage to this circuit could interlock trip the scram breaker and scram the reactor, or prevent undervoltage coil initiated reactor scram. IF40113C2-KC Safety injection scram Damage to this circuit could interlock trip the scram DreaKer and scram tne reactor, or prevent undervoltage coil initiated or safety injection condition reactor scram. 1FQOll3C4-KC Safety injection scram Damage to this circuit could interlock trip the scram breaker and scram the reactor, or prevent undervoltage coil initiated or safety injection condition reactor scram. Impell Corporation Report No. 01-0310-1435 Pd-168 Hevision 0

N Q 10CFR50 APPENDIX R SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE l-P8-42-16 Control Room Complex. Consequence of Fire Mitigation Category System Component Circult-Schedule Function Hot RCS RCS Trip IWO11324-KB Manual scram signal Damage to this circuit could trip the scram breaker and Stanty (contd) Circuits scram the reactor, or prevent Equipment (contd) undervoltage coil initiated (contd) reactor scraa. lW113051-KB 138kV loss of volt Damage to this circuit could contact interlock trip the scram breater and scram the reactor, or prevent tripping the scram Dreaxer on loss of 138KV power. lW0ll3065-K8 Pressure level scran Damage to this circuit could interlock trip tne scram breater and scram the reactor, or prevent j undervoltage coil initiated reactor scram. Scram A & B undervoltage Damage to this circuit could I 1WO11324-KB i coil circuit trip the scram breater and scram the reactor, or prevent undervoltage coil initiated reactor scram. lWO113091-KB Scram A & B undervoltage Damage to this circuit could coil circuit trip the scram breaker and scram the reactor. lW0ll324-KB Scram A & B undervoltage Damage to this circuit could ! coil circuit spuriously scram the reactor or prevent reactor scram, i 4

Impe11 Corporation Revision 0 Report No. 01-0310-1435 PB-169

O /] D 10CFR50 APPENDIX R, SFCTION III.G C0WLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex Category Systen Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS G-8A IGA 2C07C5-KB Discharge header Damage to this circuit could Operator action to transfer control Standby pressure interlock oypass tne pressure interlock and of G-8A to the cedicated snutdown Equipment spuriously start G-8A while panel. Caoles for dedicated snutdown G-86 is running, or prevent auto- operation of G-8A are routed outstoe (contd) tne fire area and will reumain availaole. starting of tne pump, and/or prevent remote operation of the Interruption of seal injection and seal pump. cooling to the reactor coolant pump seals for tne period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). 1GA2C07C1-KC Auto start punp Damage to this circuit could i spuriously start or prevent auto starting of the pump, and/or 4 prevent remote operation of the punp. 1GA2007C2-KB Remote pump control Damage to this circuit could spuriously start or stop the pump, and/or prevent remote operation of the punp. l 1GA2C07C2-KC Reset pump trip Damage to this circuit could result in loss of remote control and/or prevent the punp from auto starting on sequencer 2 l initiation. Tne pump could also i be allowed to start on sequencer 2 initiation, even tnough MUV-1100C is

'                                                                                                      aligned to Bus A1C.

1GA2C07C4-KC Reset pump trip Damage to this circuit could result in loss of remote control and/or prevent the punp from auto starting on sequencer 2 initiation. The punp could also be allowed to start on sequencer 2 initiation, even though MOV-1100C is aligned to Bus AIC. IXA2C07Al-KB Sensor signal Damage to this circuit could prevent pump operation.

  +

Impell Corporation Report No. 01-0310-1435 PB-170 Revision 0

f 0

                %                                                            b                                                               V 10CFR50 APPENDIX R SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE l-PB-42-16 Control Room Conglex Category System Component Circuit-Schedule Function                         Consequence of Fire                     Mitigation Hot         CVCS     G-88 1FAlC07C6-KB     Discharge hea6er             Damage to this circuit could      None. Cables for dedicated shutdown system Standby     (contd)                        pressure interlock           bypass the pressure interlock and operation of G-8A are routed outside the Equipment                                                               spuriously start G-88 while       fire area and will remain available.

(contd) G-8A is running, or prevent auto-starting of the pump, and/or prevent remote operation of the pump. , IFAIC07C2-KC Auto start punp Damage to this circuit could spuriously start the pump, and/or prevent remote 1 operation of the punp or prevent auto starting on

!                                                                              sequencer initiation.

l ? IFAIC07C3-Kes Remote punp control Uamage to this circuit could spuriously start or stop tne l punp, and/or prevent remote operation of tne punp. IFAIC07C4-KC Reset pump trip Damage to this circuit could result in loss of remote control and/or prevent tne puup from auto starting on sequencer initiation. The pump could also be allowed to start on j sequencer 1 initiation, even though MOV-1100C is aligned 1 to bus A2C. l I 1FAlC07C5-KC Reset puno trip Damage to this circuit could result in loss of remote control and/or prevent the punp from auto starting on sequencer initiation. The punp could

;                                                                               also be allowed to start on i                                                                              sequencer 1 initiation, even though MOV-1100C is aligned to l

t bus A2C. lWAIC07Al-KB Sensor signal Damage to this circuit could prevent pump operation. 11pell Corporation Reoort No. 01-0310-1435 PB-171 Revision 0

v3 [ >

                                                                            \

O 10CFR50 APPENDIX R. SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE l-PB-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation i Hot CVCS MOV-Il00B IF80147C3-KB Remote valve control Damage to this circuit could Operator action to verify MOV-1100s or Stan @y (contd) prevent remote operation and/or MOV-11000 open to initiate charging pump Equipnment cause the valve to spuriously G-8A operation from the cedicated snutoown open or close. system. (contd) 1Fu0147C4-KC Sequencer 1 interlock Damage to this circuit could result in tne loss of remote valve control, and/or cause the valve to spuriously open, or prevent is from opening. 1FB0147C5-KC Remote valve control Damage to this circuit could 1 result in the loss of remote valve control, and/ur prevent

operation via panel C09.

4 1FB0147C8-KB Volume control tank Damage to this circuit could level interlock result in the loss of remote valve control, and/or cause the i valve to spuriously close. 1W80147C9-KB Volume control tank Damage to this circuit could level interlock result in the loss of remote valve control, and/or cause the valve to spuriously open. i i I l i i 1 i i Impell Corporation Report No. 01-0310-1435 PB-172 Revision 0 a

O

               '\

{N 10CfR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION FINE ANEA/ ZONE 1-Pu-42-16 Control Room Complex Crtegory System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS MOV-Il000 1H80378C7-KB Remote valve control Damage to this circuit could Operator action to verify MOV-11008 or Standby prevent remote operation and/or MDV-11000 open to initiate charging pump l (contd) cause the valve to spuriously G-8A operation from the dedicated shutdown Equipment 1 2 (contd) open or close. system. I I IH80378C8-KB Volume control tank Damage to this circuit could ] level interlock result in the loss of remote 4 valve control, and/or cause the valve to spuriously close. 1H80378C5-KB Remote valve control Damage to this circuit could result in the loss of remote I valve contrel. The valve will f ail as is, normally closed. 1XB2A71Cl-K8 Volume control tank Damage to this circuit could level interlock result in the loss of remote ' j valve control, and/or cause the valve to spuriously open. I l l 3 a l 4 i j i l l + 1 i 7 1 Impell Corporation Report No. 01-0310-1435 P8-173 Revision 0

f ( O . O 10CFR50 APPENDIX R. SECTION III.G COMPLIANCE EVALUATION - FIRE AREA /IONE 1-PB-42-16 Control Room Complex C-tegory System Component Circuit-Schedule Function Consequence of Fire Mitigation MOV-883 iHt,0390C1-KC Remote valve control / Damage to this circuit could Operator action to verify MOV-883 open to Hot CVCS initiate charging pump G-8A operation Standoy (contd) position indication prevent remote operation and/or cause the valve to spuriously from the dedicated shutoown system. Equipment (contd) open or close. 1H80390C4-KC Remote valve control Damage to this circuit could result in the loss of renote valve control. The valve will f all as is, normally open. 1HB0390C6-KC Remote valve control / Damage to this circuit could position indication result in the loss of remote valve control. The valve will f all as is, normally open. CV-304 Solenoid control power Damage to this circuit could Operator action to close FCV-1112 from 1FQ107071-KB the dedicated shutdown panel if the prevent remote operation and/or cause the valve to spuriously isolation of tnis line is required. open or close. CV-304 will open on pressure differential of charging tnrough loop A is required. CV-304/ IWY1508-KB 120VAC power for CV-304 Loss of power to control room panel None. Valves fail as requir M f r safe CV-305 CV-305, CV-287 CV-544, C09, causing CV-304 CV-305, CV-287 shutdowr.. and PCV-1115A,8,C and CV-544 to spuriously close, and PCV-1115A, 8, and C to open. Impe11 Corporation Report No. 01-0310-1435 P8-174 Revision 0

k 10CFR50 APPENDIX R SECTION III.G COMPLIANCE EVALUATION FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS FCV-1112 IWY11R7-KB Power Loss of power to FC-1112, operator action to position FCV-Ill2 Standby PC-430C, H and J, preventing from the dedicated shutdown panel, as (contd) required. Equipment /caDies for dedicated Equipment operation of tne valves. shutdown system operation of FCV-1112 are (contd) located outside the fire area and will remain availaole. IFQ107011-KB Positioner control Damage to this circuit could signal cause a loss of remote control and spuriously open thes valve. Operation of the valve tnrough sequencer 1 and 2 initiation would not affected. IFQ107013-KB SV-1112 Control Reset Damage to this circuit could result in the loss of remote valve control. IFQ107027-KB Sensor signal Damage to this circuit could cause a loss of remote operation, and/or cause the valve to spuriously open. 1FQ107028-K8 Sensor signal Damage to this circuit could cause the valve to spuriously open or Close. IFQ107037-KB SV-1112 positioner Damage to this circuit could I override solenoid result in the loss of valve control power control through SV-1112 and cause the valve to spuriously open. { , 1FQO107C1-KC Sequencer 1 initiation Damage to this circuit could interlock result in the loss of remote valve control, and/or cause the valve to spuriously open, or prevent opening of the valve Dy sequencers 1 or 2. 1FQ0107C2-KC Sequencer 2 initiation Damage to this circuit coulo interlock result in the loss of remote valve control, and/or cause the valve to spuriously open. IFQ107II-KC Sensor signal Damage to this circuit could cause FCV-1112 to spuriously open or cause a low flow , indication to converter PY-1112. Impe11 Corporation Report No. 01-0310-1435 P8-175 Revision 0

f 1 V(~'s 10CFR50 APPENDIX R, SECTION III.G COMPLIANCE EVALUATION - FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Category System Component Circult-Schedule Function Consequence of Fire Mitigation Hot CVC5 FCV-1112 IwQ107044-KB SV-1112 Control Damage to this circuit could St ney (contd) (contd) result in the loss of remote Equipment valve control, and/or cause the (contd) valve to spuriously open. FCV-1112 IFD013001-KC Remote valve control Damage to this circuit could Operator action to position FCV-1112 FCV-456,7,8 result in the loss of remote- from the dedicated shutdown panel as valve control. required. Wurious actuation of FCV-456 FCV-457 and FCV-458 will not affect safe snutdown as the main feedwater pumps are tripped. 1XY14R9-KB Power Loss of power to FCV-1112/ See FCV-1112 FCV-1115A, FCV-Ill5ts and FCV-1112/ 1115A,B,C 1115A.B.C. FCV-1115C. FT-1112 IFQ107103-KB Sensor signal Damage to this circuit could Operator action to position FCV-ill2 from result in erroneous indication the dedicated shutdown panel as required. of cnarging flow rate and cause spurious operation of FCV-1112. FCV-1115A 1FQ107076-KB Control signal Damage to this circuit could Operator action to fall FCV-1115A open by cause a loss of positioner isolating instraent air at the dognouse.

  • control, causing FCV-1115A verify FCV-11150 closed, and control seal and FCV-11150 to close or injection flow using manual valve located '

! result in a loss of instrument testream. Interruption of seal injection air causing FCV-1115A to and seal cooling to the reactor coolant ' f ail open. pop seals for the period required to ' 1 initiate seal injection from the dedicated i ? shutdown system has been evaluated and detemined to be acceptable (26), a 1 l 4 i l l IIpell Corporation Report No. 01-0310-1435 PB-176 Revision 0 i

                                                                                \

b)' c 10CFR50 APPENDIX R, SECTION III.G COPFLIANCE EVALUATION FIRE AREA / ZONE I-PB-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation I Hot CVCS FCV-11158 1GQ107077-K8 Control signal Damage to this circuit could Operator action to f ail open FCV-11158 Dy I 5tindby (contd) cause a loss of positioner isolating instrument air at the doghouse, Equipment control causing FCV-11158 and verify FCV-1115E closed, and control seal (contd) FCV-1115E to close' or result injection flow using manual valve located in a loss of intraent air upstream. Interruption of seal injection causing FCV-II158 to open. and seal cooling to tne reactor coolant pump seals for the period required to initiate seal injection from the dedicated snutdown system nas seen evaluatea and determined to be acceptaole (26). l FCV-1115C 1HQ107078-Ks Control signal Damage to this circuit could Operator action to fail open FCV-1115C oy cause a loss of positioner isolating instrument air at the doghouse, control causing FCV-1115C and verify FCV-1115F closed and control seal FCV-1115F to close or result injection flow using manual valves located in a loss of instroent air upstream. Interruption of seal injection causing FCV-1115C to open, and seal cooling to the reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system has been evaluated and determined to be acceptable (26). 4 i FCV-1115 IWY14R8-KB Power Damage to this circuit could See FCV-1115A, FCV-11158, and FCV-1115C. j A B.C cause a loss of control power to FC-1115A,B.C. closing valves FCV-1115A & D, 8 & E. C&F. PCV-1115 IWY141601-KB Power Damage to this circuit could See PCV-1115A, PCV-III58 and PCV-1115C. 1 A, B, C cause a loss of power to l YE-1115A,8,C, causing a low offscale indication to FCV-1115A,8,C. Tnis could open FCV-1115A,8,C and close 4 PCV-1115A,8,C. i 1 Impe11 Corporation Report No. 01-0310-1435 PB-177 Revision 0

10CFR50 APPENDIX R SECTION III.G C0pFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16 Control Room Complex C-tegory System Component Circult-Schedule Function Consequence of Fire Mitigation Hot CVCS PCV-1115A IWQ107041-K8 Remote valve control / Damage to this circuit could Operator action to fall FCV-1115A open Sttndby (contd) Indication prevent remote operation and/or by isolating instrument air at the Equipment cause the valve to spuriously doghouse, verify FCV-11150 closed, and open or close. control seal injection flow using manual (contd) . valve located upstream. Interruption of-seal injection and seal cooling to the reactor coolant pump seals for the period required to initiate seal injection from the dedicated shutdown system nas been evaluated and determined to oe acceptable (26). PT-1115A IWQ107108-KB Sensor signal Damage to this circuit could Operator action to f ail FCV-1115A open result in high off-scale, low by isolating instrument air at the off-scale or erroneous indication. dognouse, verify FCV-11150 closed, and Tnts could cause controller control seal injection flow using manual FC-1115A to spuriously open or valve located upstream. Interruption of close FCV-1115A and FCV-11150 seal injection and seal cooling to tne and/or cause controller PC-1115A reactor coolant pump seals for the period to spuriously close PCV-1115A. required to initiate seal injection from the dedicated shutdown system has oeen evaluated and determined to De acceptaole (26). PI-1115A/ IWQ107057-KB Sensor signal Damage to this circuit could Operator action to fail open FCV-1115A PC-1115A cause a low offscale pressure by isolating instrument air at the indication which could cause doghouse, verify FCV-IIISD closed, and FC-1115A to open FCV-1115A and D, control seal injection flow using manual and cause PC-1115A to close valve located upstream. Interruption of PCV-1115A. seal injection and seal cooling to the reactor coolant pump seals for the period required to initiate seal injection from - the dedicated shutdown system has been evaluated and determined to ne acceptable (26). Irpell Corporation Report No. 01-0310-1435 PB-178 Revision 0

O O 10CFR50 APPENDIX R. SECTION III.G COWLIAhCE EVALUATION FIRE AREA / ZONE 1-PB-42-16 Control Room Complex. Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS PCV-1115B IWQ107042-K8 Remote valve control / Damage to this circuit could Operator action to f all open FCV-11158 by Standby (contd) Indication prevent remote operation and/or isolating instrument air at the dognouse, Equipment cause the valve to spuriously verify FCV-1115E closed, and control seal open or close. injection flow using manual valve located (contd) upstream. Interruption of seal injection and seal cooling to tne reactor coolant pump seals for tne period required to initiate seal injection from tne dedicated snutdown system nas oeen evaluated and determined to oe acceptaole (26). PT-11158 IXQ107096-KB Sensor signal Damage to this circuit could Operator action to f ail open FCV-11158 oy result in high off-scale, low isolating instrument air at the doghouse, off-scale, or erroneous verify FCV-1115E closed, and control seal indication. This could cause injection flow using manual valve located controller FC-11158 to upstrema. Interruption of seal injection spuriously open or close and seal cooling to tne reactor coolant FCV-11158 and FCV-1115E and/or pump seals for tne period required to cause controller PC-1115B to initiate seal injection from the dedicated spuriously close PCV-11158. shutdown system has been evaluated and determined to De acceptable (26). 2 . d l PI-1115B/ IWQ107058-KB Sensor signal Damage to this circuit could cause Operator action to fail open FCV-11158 by 1 PC-11158 a low offscale pressure indication isolating instrument air at the doghouse, wnich could cause FC-1115B to open verify FCV-1115E closed, and control seal FCV-11158 and E, and cause PC-1115u injection flow using manual valve located to close PCV-11158. upstream. Interruption of seal injection and seal cooling to tne reactor coolant pianp seals for tne period required to initiate seal injection from tne dedicated shutdown system nas been evaluated and determined to De acceptaDie (26). 1 i Irpell Corporation Report No. 01-0310-1435 PB-179 Revision 0

3 m. l i v> V d 10CFR50 APPENDIX R, SECTION III.G COWLIANCE EVALUATION FIRE AREA / ZONE 1-PB-42-16 Control Room Complex Category System Component Circuit-Schedule Function Consequence of Fire Mitigation Hot CVCS PCV-1115C IWQ107043-KB Remote valve control / Damage to this circuit could Operator action to f ail open FCV-Ill5C Dy Standby (contd) Indication prevent remote operation and/or isolating instrument air at the dognouse, Equipment cause tne valve to spuriously verify FCV-Ill5F closed, and control seal (contd) open or close, injection flow using manual valve located upstream. Interruption of seal injection and seal cooling to tne reactor coolant ptmp seals for the period required to initiate seal injection from the dedicated shutdown system nas Deen evaluated and I determined to De acceptable (26). PT-1115C IWQ107097-KB Sensor signal Damage to this circuit could Operator action to f ail open FCV-1115C Dy result in high off-scale, low isolating instrument air at the dognouse, off-scale, or erroneous indication. verify FCV-1115F closed, and control seal This could cause controller injection flow using manual valve located FC-1115C to spuriously open or upstream. Interruption of seal injection close FCV-1115C and FCV-1115F and seal cooling to tne reactor coolant and/or cause controller PC-1115C pimp seals for tne period required to to spuriously close PCV-1115C. initiate seal injection from the dedicated 4 shutdown system nas oeen evaluated and determined to De acceptable (26). PI-1115C/ 1WQ107059-KB Sensor signal Damage to this circuit could cause operator action to fail open FCV-IllbC oy PC-1115C a low offscale pressure indication isolating instrument air at tne doghouse, 1 wnicn could cause FC-1115C to open verify FCV-1115F closed, and control seal FCV-Ill5C and F, and cause PC-1115C injection flow using manual valve located to close PCV-1115C. upstream. Interruption of seal injection and seal cooling to the reactor coolant 4 pump seals for the period required to initiate seal injection from tne dedicated snutdown system has been evaluated and determined to De acceptable (26). Irpell Corporation Report No. 01-0310-1435 PB-180 Revision 0

!                                                              10CFR50 APPENDIX R, SECTION III.G C0fFLIANCE EVALUATION FIRE AREA / ZONE 1-P8-42-16}}