Southern Callfornia Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 KENNETH P. BASKIN VICE PRESIDENT TELEPHONE 818-302-1401 September 2, 1988 U. S. Nuclear Regulatory Commission Attention:
Document Control Desk Washington, D.C. 20555 Gentlemen:
Subject:
Docket Nos. 50-206, 50-361 and 50-362 Updated Fire Hazards Analysis San Onofre Nuclear Generating Station Units 1, 2 and 3 (TAC Nos. 54814 and 54815)
In accordance with 10 CFR 50.71, Southern California Edison Company (SCE) is transmitting Revision 4 of the Updated Fire Hazards Analysis (UFHA) for the San Onofre Nuclear Generating Station, Units 1, 2 and 3. This annual revision includes additional information which amplifies, clarifies or updates the existing text and reflects all changes made in the San Onofre Units 1, 2 and 3 facility up to a maximum of six months prior to the date of this filing.
Changes to the UFHA identified after the six-month cutoff date will be incorporated in the next revision to the UFHA. Revision 4 consists of the appropriate revised UFHA pages for San Onofre Units 1, 2 and 3. Each revised page includes a vertical change bar drawn in the margin adjacent to the changed portion, the date of the change and the corresponding revision number.
This revision to the UFHA represents a significant effort by SCE to reflect a rmeassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and III.0, including deviations thereto approved in the NRC's Safety Evaluation dated June 29, 1988. Revision 4 to the UFHA also reflects revisions to the fire protection program and the proposed Fire Protection Technical Specifications and License Conditions (PCN-10/15-243 and -244, respectively) for San Onofre Units 2 and 3. In addition, the San Onofre Unit I specific information has been revised to reflect changes to the Unit 1 facility and revisions to the 10 CFR 50, Appendix R,Section III.G (safe shutdown) compliance assessment.
This revision to the UFHA does not alter any conclusions regarding the hoos u40 56,
Document Control Desk September 2, 1988 ability to achieve and maintain safe shutdown in the event of a fire for San Onofre Units 1, 2 and 3. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
If you have any questions regarding this matter, please call me.
Very truly yours, Enclosure cc:
(all w/o enclosure)
- 3. B. Martin, Regional Administrator, NRC Region V F. R. Huey, NRC Senior Resident Inspector, San Onofre Units 1, 2 and 3 D. 3. Kubicki, NRC Staff C. B. Ramsey, Inspector, NRC Region V
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA EDISON
)
COMPANY and SAN DIEGO GAS & ELECTRIC COMPANY )
for a Class 104(b) License to Acquire,
)
DOCKET NO. 50-206, Unit 1 Possess, and Use a Utilization Facility as
)
UPDATED FHA REVISION 4 Part of Unit No. 1 of the San Onofre Nuclear )
Generating Station SOUTHERN CALIFORNIA EDISON COMPANY and SAN DIEGO GAS & ELECTRIC COMPANY hereby submit Revision 4 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects a reassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0, including NRC approved deviations thereto. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
The Unit I specific information has been revised to reflect changes to the Unit 1 facility and revisions to the 10 CFR 50, Appendix R, Section-III.G (safe shutdown) compliance assessment.
The information included in this revision supersedes and replaces the previously issued UFHA information.
Subscribed on this 2nd_ day of September
, 1988.
Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By:
s/s Kenneth P. Baskin Subscribed and sworn to before me this 2nd day of September s/s C. Sally Seho Notary Public in and for the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:
s/s Charles R. Kocher
0g
.(g SAN DIEGO GAS & ELECTRIC COMPANY By:
s/s Gary D. Cotton David R. Pigott Samuel B. Casey Orrick, Herrington & Sutcliffe Attorneys for San Diego Gas & Electric Company By:
s/s David R. Pigott Subscribed and sworn to before me this 16th day of August 1988 s/s Stephanie E. Hitt Notary Public in and for the City and County of San Diego, California
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of SOUTHERN
)
CALIFORNIA EDISON COMPANY
)
and SAN DIEGO GAS & ELECTRIC
)Docket No. 50-206 COMPANY (San Onofre Nuclear
)
Generating Station Unit No. 1 CERTIFICATE OF SERVICE I hereby certify that a copy of the Updated Fire Hazards Analysis for San Onofre Unit 1 (Revision 4 to the UFHA for San Onofre Units 1, 2 and 3) was served on the following by deposit in the United States Mail, postage prepaid, on the _ 1__ day of September
, 1988.
Benjamin H. Vogler, Esq.
Staff Counsel U.S. Nuclear Regulatory Commission Washington, D.C. 20555 David R. Pigott, Esq.
Samuel B. Casey, Esq.
Orrick, Herrington & Sutcliffe 600 Montgomery Street San Francisco, California 94111 L. G. Hinkleman Bechtel Power Corporation P.O. Box 60860, Terminal Annex Los Angeles, California 90060 Michael L. Mellor, Esq.
Thelen, Marrin, Johnson & Bridges Two Embarcadero Center San Francisco, California 94111 Huey Johnson.
Secretary for Resources State of California 1416 Ninth Street Sacramento, California 95814 Janice E. Kerr, General Counsel California Public Utilities Commission 5066 State Building San Francisco, California 94102
-2 C. J. Craig Manager U.S. Nuclear Projects I, ESSD Westinghouse Electric Corporation Post Office Box 355 Pittsburgh, Pennsylvania 15230 A. I. Gaede 23222 Cheswald Drive Laugna Niguel, California 92677 Frederick E. John, Executive Director California Public Utilities Commission 5050 State Building San Francisco, California 94102 Docketing and Service Section Office of the Secretary U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Charles R. Kocher Associate.General Counsel Southern California Edison Company
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA EDISON
)
COMPANY, ET AL. for a Class 103 License to )
DOCKET NO. 50-361, Unit 2 Acquire, Possess, and Use Two Utilization
)
UPDATED FHA REVISION 4 Facilities and Related Licenses in
)
Connection with Units No. 2 and 3 of the
)
DOCKET NO. 50-362, Unit 3 San Onofre Nuclear Generating Station
)
UPDATED FHA REVISION 4 SOUTHERN CALIFORNIA EDISON COMPANY, ET AL. hereby submit Revision 4 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of. this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects a reassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0, including NRC approved deviations thereto. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
The Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and revisions to the 10 CFR 50, Appendix R.Section III.G (safe shutdown) compliance assessment.
The information included in this revision supersedes and replaces the previously issued UFHA information.
Subscribed on this '2nt_ day of September
. 1988.
Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By:
s/s Kenneth P. Baskin Subscribed and sworn to before me this 2nd day of September s/s C. Sally Sebo Notary Public in and for the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:
s/s Charles R. Kocher
SAN DIEGO GAS & ELECTRIC COMPANY By:
s/s Gary D. Cotton David R. Pigott Samuel B. Casey Orrick, Herrington & Sutcliffe Attorneys for San Diego Gas & Electric Company By:
s/s David R. Pigott Subscribed and sworn to before me this 16th day of August 1988 s/s Stephanie E. Hitt Notary Public in and for the City and County of San Diego, California
THE CITY OF ANAHEIM By:
s/s Gordon W. Hoyt Alan R. Watts Rourke & Woodruff Attorneys for the City of Anaheim By:
s/s Alan R. Watts Subscribed and sworn to before me this 11th day of August, 1988 qs Cathy Karpow Notary Public in and for the County of Orange, State of California
pl THE CITY OF RIVERSIDE By:
s/s B. D. Carnahan Alan R. Watts Rourke & Woodruff Attorneys for the City of Riverside By:
s/s Alan R. Watts Subscribed and sworn to before me this 15th day of August. 1988 s/ Margaret T. Archambault Notary Public in and for the County of Riverside
, State of California
TO UFHA MANUAL HOLDERS:
INSTRUCTIONS FOR THE INCORPORATION OF THE SONGS 1,2&3 UPDATED FIRE HAZARDS ANALYSIS REVISION 4.0 REVISION 4 IS A COMPLETE REPRINT OF THE FHA.
PLEASE REMOVE ALL EXISTING CONTENTS FROM THE UFHA BINDERS AND DISCARD.
PLACE THE ATTACHED BOUND VOLUMES IN THE CORRESPONDING BINDER.
THANK YOU, NES&L SERVICES
Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 KENNETH P. BASKIN TELEPHONE VICE PRESIDENT 818-302-1401 September 2, 1988 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Gentlemen:
Subject:
Docket Nos. 50-206, 50-361 and 50-362 Updated Fire Hazards Analysis San Onofre Nuclear Generating Station Units 1, 2 and 3 (TAC Nos. 54814 and 54815)
In accordance with 10 CFR 50.71, Southern California Edison Company (SCE) is transmitting Revision 4 of the Updated Fire Hazards Analysis (UFHA) for the San Onofre Nuclear Generating Station, Units 1, 2 and 3. This annual revision includes additional information which amplifies, clarifies or updates the existing text and reflects all changes made in the San Onofre Units 1, 2 and 3 facility up to a maximum of six months prior to the date of this filing.
Changes to the UFHA identified after the six-month cutoff date will be incorporated in the next revision to the UFHA. Revision 4 consists of the appropriate revised UFHA pages for San Onofre Units 1, 2 and 3. Each revised page includes a vertical change bar drawn in the margin adjacent to the changed portion, the date of the change and the corresponding revision number.
This revision to the UFHA represents a significant effort by SCE to reflect a reassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and III.0, including deviations thereto approved in the NRC's Safety Evaluation dated June 29, 1988. Revision 4 to the UFHA also reflects revisions to the fire protection program and the proposed Fire Protection Technical Specifications and License Conditions (PCN-10/15-243 and -244, respectively) for San Onofre Units 2 and 3. In addition, the San Onofre Unit 1 specific information has been revised to reflect changes to the Unit I facility and revisions to the 10 CFR 50, Appendix R,Section III.G (safe shutdown) compliance assessment.
This revision to the UFHA does not alter any conclusions regarding the B8o907 o52 8 88092 PDR ADOCK& 05000206 F
PNU goo
Document Control Desk September 2, 1988 ability to achieve and maintain safe shutdown in the event of a fire for San Onofre Units 1, 2 and 3. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
If you have any questions regarding this matter, please call me.
Very truly yours, Enclosure cc:
(all w/o enclosure)
J. B. Martin, Regional Administrator, NRC Region V F. R. Huey, NRC Senior Resident Inspector, San Onofre Units 1, 2 and 3 D. J. Kubicki, NRC Staff C. B. Ramsey, Inspector, NRC Region V
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA EDISON
)
COMPANY and SAN DIEGO GAS & ELECTRIC COMPANY )
for a Class 104(b) License to Acquire,
)
DOCKET NO. 50-206, Unit Possess, and Use a Utilization Facility as
)
UPDATED FHA REVISION 4 Part of Unit No. 1 of the San Onofre Nuclear )
Generating Station
)
SOUTHERN CALIFORNIA EDISON COMPANY and SAN DIEGO GAS & ELECTRIC COMPANY hereby submit Revision 4 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects a reassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and III.0, including NRC approved deviations thereto. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
The Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and revisions to the 10 CFR 50, Appendix R,Section III.G (safe shutdown) compliance assessment.
The information included in this revision supersedes and replaces the previously issued UFHA information.
Subscribed on this day of M
1988.
Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By:Z -
A Kenneth P. B skin Vice President Subscri ed and swor to before me this c
day of
,/0 dayofOFFICIAL SEAL C. SALLY SEBO Notary PublIc-California LOS ANGELES COUNTY My Comm. Exp. Apr. 20,1990 Notary Public in ali for the County of.
Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:
Charles R. Kocher
- e Subscribed on this _45 day of C1ix 44-1988.
Respectfully submitted, SAN DIEGO GAS & ELECTRIC COMPANY By:
Gar~y D./ otton_
Senior ice President Subscribed and sworn o before me this
/Z day of
/&
OFRCIAL SEAL
/
1 STEPHANIE E. HITT NOTARY PUBLIC-CALIFORNIA PRINCIPAL OFFICE IN SAN DIEGO COUNTY MyCnMsion Exp. Aug. 30, 1991 Notary Pulic in and for the County of 1 Los Angeles, State of California David R. Pigott Samuel B. Casey Orrick, Herrington & Sutcliffe Attorneys for San Diego Gas & Electric Company By:_
David R. Pigott
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of SOUTHERN
)
CALIFORNIA EDISON COMPANY
)
and SAN DIEGO GAS & ELECTRIC
)
Docket No. 50-206 COMPANY (San Onofre Nuclear
)
Generating Station Unit No. 1 CERTIFICATE OF SERVICE I hereby certify that a copy of the Updated Fire Hazards Analysis for San Onofre Unit 1 (Revision 4 to the UFHA for San Onofre Units 1, 2 and 3) was served on the following by deposit in the United States Mail, postage prepaid, on the
/
day of r
, 1988.
Benjamin H. Vogler, Esq.
Staff Counsel U.S. Nuclear Regulatory Commission Washington, D.C. 20555 David R. Pigott, Esq.
Samuel B. Casey, Esq.
Orrick, Herrington & Sutcliffe 600 Montgomery Street San Francisco, California 94111 L. G. Hinkleman Bechtel Power Corporation P.O. Box 60860, Terminal Annex Los Angeles, California 90060 Michael L. Mellor, Esq.
Thelen, Marrin, Johnson & Bridges Two Embarcadero Center San Francisco, California 94111 Huey Johnson Secretary for Resources State of California 1416 Ninth Street Sacramento, California 95814 Janice E. Kerr, General Counsel California Public Utilities Commission 5066 State Building San Francisco, California 94102
-2 C. 3. Craig Manager U.S. Nuclear Projects I, ESSD Westinghouse Electric Corporation Post Office Box 355 Pittsburgh, Pennsylvania 15230 A. I.-Gaede 23222 Cheswald Drive Laugna Niguel, California 92677 Frederick E. John, Executive Director California Public Utilities Commission 5050 State Building San Francisco, California 94102 Docketing and Service Section Office of the Secretary U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Charles R. Kocher Associate General Counsel Southern California Edison Company
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA EDISON
)
COMPANY, ET AL. for a Class 103 License to )
DOCKET NO. 50-361, Unit 2 Acquire, Possess, and Use Two Utilization
)
UPDATED FHA REVISION 4 Facilities and Related Licenses in
)
Connection with Units No. 2 and 3 of the
)
DOCKET NO. 50-362, Unit 3 San Onofre Nuclear Generating Station
)
UPDATED FHA REVISION 4 SOUTHERN CALIFORNIA EDISON COMPANY, ET AL. hereby submit Revision 4 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects a reassessment of San Onofre Units 2 and 3 relative to the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0, including NRC approved deviations thereto. This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.
The Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and revisions to the 10 CFR 50, Appendix R,Section III.G (safe shutdown) compliance assessment.
The information included in this revision supersedes and replaces the previously issued UFHA information.
Subscribed on this day of,
!7,in
, 1988.
Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By:
Kenneth P. Baskin Vice President Subscr'bed and sworn to efo e me this 9L day of.
OFFICIAL SEAL C. SALLY SEBO Notary Public-Califomia D LOS ANGELES COUNTY My Comm. Exp. Apr. 20, 1990 Notary Public in cndfor the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:
\\to(,
Charles R. Kocher
SAN DIEGO GAS.& ELECTRIC COMPANY By:
David R. Pigott Samuel B. Casey Orrick, Herrington & Sutcliffe Attorneys for San Diego Gas & Electric Company By:
Subscribed and sworn tq before me this day of
.1.
/616&
OFFICIAL SEAL STEPHANIE E. HITT NOTARY PUBLIC-CALIFORNIA PRINCIPAL OFFICE IN SAN DIEGO COUNTY My Commission Exp. Aug. 30, 1991 giNotary Pub1 c in and for the City and County of San Diego, California
0 THE CITY OF ANAHEIM By:
ixcl 1
Alan R. Watts Rourke & Woodruff Attorneys for the City of Anaheim By:
Subscribed and sworn t before me this OFFICIAL SEAL day of CATHY KARPOW NOTARY PUBILIC cALIFORNIA PRINCIPAL OFFICE IN ORANGE COUNTY My Commission Ekpires May 19, 1989 Notary Public 1 and for the County of Orange, State of California
THE CITY OF RIVERSIDE By:
Alan R. Watts Rourke & Woodruff Attorneys for the City of Riverside By:
Subscribed and sworn to before me this 15th day of August, 1988 Notary ublic in and for the County of Riverside State of California OFFICIAL SEAL MARGARET 1. ARCHAMBALT Notary Public-Caliornia PRINCIPAL OFFICE IN RIVERSIDE COUNTY My Comm. Exp. 5-6-91