L-2003-162, Inservice Inspection Report: Submittal of the NIS-2 Forms Omitted from L-2003-162 Submittal
ML032180035 | |
Person / Time | |
---|---|
Site: | Turkey Point ![]() |
Issue date: | 07/22/2003 |
From: | Jones T Florida Power & Light Co |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
L-2003-162, L-2003-192 | |
Download: ML032180035 (128) | |
Text
FPL L-2003-192 10 CFR 50.55a U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Re: Turkey Point Unit 3 Docket No. 50-250 Inservice Inspection Report: Submittal of the NIS-2 Forms Omitted from L-2003-162 Submittal Florida Power and Light Company (FPL) submitted the Inservice Inspection Report for Turkey Point Unit 3 under L-2003-162 dated June 26, 2003. It was found that the submittal inadvertently omitted the inclusion of the NIS-2 Forms.
Form NIS-2, Owner's Report for Repairs and Replacement, is submitted as part of the Inservice Inspection Report in accordance with the provisions of the ASME Code,Section XI. The Unit 3 NIS-2 Forms were listed as an attachment to the Inservice Inspection Report, L-2003-162, however they were not attached. The purpose of this letter is to provide the omitted NIS-2 Forms for Turkey Point Unit 3, reporting the repairs or replacements performed prior to and during the Spring 2003 refueling outage, between the dates of October 28,2001 and March 28, 2003.
Should there be any questions, please contact Walter Parker at 305-246-6632.
Sincerely,
/aTh1 B Terry 0. Jones Vice President Turkey Point Plant SM Attachments NRC Regulatory Issue Summary 2001-05 waived the requirements that multiple copies of documents be submitted to the NRC ADq7 an FPL Group company
NIS-2 Reports Abstract The attached NIS-2 reports detail the repairlreplacement of Class 1, 2 and 3 piping and components for Florida Power and Light Company, Turkey Point Unit 3. These repairs or replacements were performed prior to and during the Spring 2003 refueling outage, between the dates of October 28, 2001 and March 28, 2003.
Piping and components were inspected/tested in accordance with Section Xl of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel code "Rules for Inservice Inspection ofNuclear Power Components, "1989 Edition, No Addenda.
NIS-2 LOG 02-002-3 5/7/2002 5/16/2002 02-03-3 5/16/2002 12/11/2002 02-004-3 3/18/2003 6/4/2003 02-05-3 5/28/2002 12/11/2002 02-006-3 3/23/2003 6/4/2003 02-007-3 3/23/003 6/4/2003 02-008-3 3/23/2003 6/4/2003 02-009-3 7/17/2002 9/11/2002 02-010-3 8/19/2002 9/12/2002 02-011-3 11/5/2002 1/23/2003 02-012-3 11/4/2002 11 //2002 02-013-3 11/4/2002 11/7/2002 02-014-3 11/4/2002 11/7/2002 02-015-3 11/5/2002 6/4/2003 02-016-3 3/23/2003 6/5/2003 02-017-3 11/12/2002 1/23/2003 02-018-3 3/23/2003 6/4/2003 02-019-3 3/23/2003 6/4/2003 02-020-3 12/212002 1/9/2003 02-021-3 3/23/2003 6/4/2003 02-022-3 3/23/2003 6/4/2003 02-023-3 12/9/2002 12112/2002 02-024-3 12/23/2002 1/9/2003 02-025-3 12/26/2002 1/9/2003 02-026-3 12/27/2002 1/9/2003 02-027-3 12/27/2002 1/9/2003
NIS-2 LOG (cont) 02-028-3 3/23/2003 6/412003 02-029-3 12/27/2002 1/9/2003 02-030-3 12/27/2002 1/9/2003 02-031-3 12/30/2002 1/912003 02-032-3 12/30/2002 1/9/2003 02-033-3 12130/2002 1/912003 02-034-3 12/30/2002 6/42003 02-035-3 12/3012002 1/9/2003 02-036-3 12/3012002 1/9/2003 02-037-3 1213012002 6/52003 03-001-3 1/7/2003 1/912003 03-002-3 1f/12003 1/912003 03-003-3 1/8/2003 1/9/2003 034004-3 1/912003 1/15/2003 03-005-3 3/16/2003 4/16/2003 03-006-3 3/17/2003 614/2003 03-007-3 3/1712003 6/412003 03-008-3 3/17/2003 6/4/2003 03-009-3 *5/28/2003 6/4/2003 03-010-3 3/2112003 4/16/2003 03-011-3 3124/2003 6/512003 03-012-3 3/24/2003 6/412003 03-013-3 3/2412003 6/42003 03-014-3 312412003 6/4/2003 03-015-3 3/24/2003 6/4/2003 03-016-3 3/2412003 4/16/2003 03-017-3 3125/2003 6/4/2003 03-018-3 3/26/2003 6/4/2003
NIS-2 LOG (cont.)
Report NiXo.C' ;, Report Date , ANTI Certiat 03-019-3 3/26/2003 6/4/2003 03-020-3 *4/1/2003 6/5/2003 03-021-3 *411/2003 6/4/2003 03-022-3 *4/3/2003 6/4/2003 03-023-3 *5/21/2003 61412003 03-024-3 *6/5/2003 6/11/2003 03-025-3 *61/52003 6/11/2003
- Work was performed prior to 3/28/2003
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 517r20O2
- 0. Owner Name 700 Universe Bivd. Juno Beach, FL 33408 Sheet I _ of 2 Address
- 2. Plant ---- I Point Turkey _ Plant-.. Unk 3 Name WON: 32003112 01 CR#: NA 9760 SW 344 Street Florida Ciy, FL 33035 Address Repair Organization, P.O. No, Job N4%.etc.
- 3. Work Performed Iby Florida Power & Libht Type Code Symbol Starp N/A Name Authorlzation Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Eqiration Date NIA
- 4. Identification of System: Cornponent Cooing Water _System C: 30 Quality Group C
- 5. (a)Applicable Construction Code B31.1 1955 Edition, .1........
N/A 8 .o ... Addenda.
_n .....N/A N. CodeCase (b) Applicable Edition of Section XJ Utilized for Repairs or ReplacemenIs IO 89 Edltion, ... N/A Addencla, N/A Code Case
- 6. identification of Components Repaired or Replaced and Replacement C ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement YeslNo 18 Nuts. Heavy Hex, ASTM A- NA NA NA SC 002737 1 UNK Replacement N 194, GR 7, 3/4-I UNC-2B UTC 437942_
16 Studs ASME SA193. GrB7. NA NA NA SC 0029493 1 UNK Replacement N 3/4"-IOUNC-2A UTC 437941 NA NA NA
- 7. Description of Woric Replace 18 Nuts (9 Inlet door &9 outlet door) and 16 Studs (6 Inlet door 10 outlet door) on 3E207C.
- 8. Tests Conducted: Hydrostatic: NA Pneumatic NA Nomlnal Operating Pressure NA I Other NA Pressure NA psig Test Temperature NA deg F 02.002-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Rerarks BOLTED CONNECTION, NO WELDING REQUIRED.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of Oe ASME Code, Section Xl.
Type Code Symbol Stamp WA Certificate of Aulthorization No. NJA _Expiration Date: WA Signed2/ o O DeG ~zJ* J%4-Date 5 - 'K -o.0 cjc, ~~~~~Owner or Owner's Desi gnee, Tilte , JI 0
CERTIFICATE OF INSERVICE INSPECTION I, tie undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factoy Mutual Insurance Company of Johnston, Rhode Island. have Inspected the components described in tis Owners Report during the period of 1/15/2002 to 57/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described Inthis Owners! Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report Furthermore, neither the Inspector nor his employer shall be lIable In any manner for any personal Injury or property damage or a loss or any kind arising fmn or connected with this Inspection.
/~ (7Comsslons
\v71qr Fe-CJfspector's Signature National Board, State, Providence. and Endorsernens Date S-// (C/a z-0 02-002-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required 6y the Provisions of the ASME Code Sectfon Xl
.wner Florida Power &Light Namne Date 5/16/2002 700 Universe Blvd. Juno Beach, FL 33408 Sheet I _ of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32007612- D01 CR#: NA 9760 SW 344 Street Florida City, FL 33035 Address repair Orvanizaton P.O. No. Job No.,e.
- 3. Work PerformecI by Florida Power &Lght Type Code Symbol Stamp N/A Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NWA
- 4. Identification of System: Component Cooling Water System #: 30 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacennents 19 89 EditIon, NIA Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacemer dtComponents
_I,.
ASME Repaired, Code Name of Name of Mfg Mfg Serial INational I Other Year Replaced, or Stamp Component Number I Board I Identification Built Replacement Yes/No
_4 - I 4 (1) Bolt- 34-10 UNC-2A, NWA NIA NIA SC# 0029493 1 NMA Replacement N ASME SA 193 Gr B7 UTC# 437941 (2) Nuts Heavy Hex 3/4w- NIA N/A N/A SC# 0027837 1 N/A Replacement N I0UNC,213 ANSIIASME ASTM- UTC9 431033 A-194 Gr 7 NA NA NA
- 7. Description of Work:
Replace one stud and 2 nuts on Inlet door of 3 B CCW Hx.
- j. Tests Conducted: Hydrostatic: NA Pneumatic NA Nominal Operating Pressure NA Other NA Pressure NA psig Test Temperature NA deg F 02-003-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED.
I 0 CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rufes of the ASME Code,Section XI.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: NIA Clnndn Keys *w y ,. - - ,
Date l Zl 2 Omer orOwner's Designee, TiUe
p CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 4/1192002 to 5/1612002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section XJ.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions P38WY- X' JC2'F !57 COnspector's Signature National Board, State, Providerse, and Endorsements Date 2 , //, a Z 0
02-003-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Owner Florida Power & Light Date 3/118/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Naie WO#: 31002665-01 CR#: NA 976CI SW 344 Street Florida City, FL 33035 Address Repair OrganzaSton. P.O. No, Job No., etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp N/A Name Authorization Number N/A 976CI SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C $
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A _Addenda, N/A Code Case (b) Appflcable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, _N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components
- I. *,.
ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Pump, model 2-112, CNTAM-4 Ingersoll- 0601001 NA SC 0239955-1 WA Replacement N Rand tUTC 437669 Pump, model 2-112, CNTAM-4 Ingersoll- 0368-88 NA NA N/A Replaced h Rand NA NA NA NA
- 7. Description of Work Replace *B AFW Pump with new pump.
. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure X Other VT-2 Pressure 1380 psig Test Temperature 82.9 deg F 02-004-3
Sheet 2 of 2 FORM NIS-2 (Back)
I
- 9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED. I ..
CERTIFICATE OF COMPLIANCE I We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: WUA -
Signe t4 e 151 Date 441/ a TS'03 '
Owner or Owner's Delsignee, Title I
0*
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Inspected the components described In this Owners Report during the pericot 6/8/2001 to 3/1812003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code. Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied.
concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
lxl)11s igntue~ Commissions _ __ 3_ _ _ _
I trt~ecters Signsture National Board, State, Providence, and Endorsements Date
/I 0
02-004-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 5428/2002 Wwrier Name I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 31002665- 05 CR#: NA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organkizaton, P.O. No, Job No., tc.
- 3. Work PerformecI by Florida Power & Light Type Code Symbol Stamp NA Authorization Number NJA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Auxiliary Feedwater System #: 7'5 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, NJA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, N-416-1 CodeCase
- 6. Identification of Components Repaired or Replaced snd Replacement Components ASME Repaired, Code Name of Name of Mfg Mrg Serial National Other Year Replaced., or Stamp Component Number Board Idelentification Built Replacement Yes/No (2) 2' Gate Valves, A-105 UNK NA NA SC 0052765 1 UNK Replacement N UTC 435588 & 435589 2TX2'XlI Reducing Tee, ASME UNK NA NA SC 0034321 1 UNK Replacement N SA-105, 3000#, socket weld UTC 443320 2TPipe, ASME SA-106 Gr B UNK NA NA SC 0030688-1 UNK Replacement N Sch 80 UTC 416327 2* Elbow ASME SA-10S, 3000# UNK NA NA SC 0034040 1 UNK Replacement N Socket weld UTC 430452 NA
- 7. Description of Work:
Add 2 Isolation valves to the 3 BAFW recirculation line Including piping, tee end elbow.
- 8. Tests Conducted: Hydrostatic: NA Pneumatic NA Nominal Operating Pressure X
- Other VT-2 Pressure 105 psig Test Temperature 81.8 deg F 02-005-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY. I CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed A'
£o OwnEr's Dates Owne-r or Ownier's Designed', Title 0gr CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Inspected the components described In this Owners Report dunrf the period of 618/2001 to 5/28/2002 and state that to the best of my krnowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code. Section X1.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
knaw.4-, Commissions tJB72Y1 -' pL-?2S 6/ Inspector's Signature National Board, State, Providence, and Endorsements' Date J -t { ° 02-005-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wner Florida Power &Light Date 3/2312003 Noam 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant Kame WO#: 31009255 CR#: NA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organzution, P.O. No. Job No.. etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp , N/A Name Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Intake Cooling Water System #: 19 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacerhent Yes/No
+ -4. 4 4 4 Pump Johnston NIA N/A SC 0011053-1 I N/A Replacement N Pump Co.
IST #7
- 7. Description of Work:
Replace Pump, Check Valve, expansion joint and some degraded bolting. This NIS-2 documents pump replacement. Pump number IST#7 replaced IST#2. Other replacement documented on WO# 32008464
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure 18 Other VT-2 Pressure 18 psig Test Temperature 84.6 deg F 02-006-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NWA Certificate of Authorization No. N/A Expiration Date: N/A Sign _5i= =e l.5_ Date _________
Owner or Owner's Desigdnee, Title 0
CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period 411812001 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- 4lal Commissions /C 3251 Ins&fors Signature National Board. State. Providence. and Endorsements Date 6 //0 02-006-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Owner Florida Power & Light Date 3/?3/2003 Noae 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Ne WO#: 32008464 CRO: N/A
?760 SW 344 Street Florida City. FL 33035 Address e&par gOrgenizalfn. P.O. No. Job No., etc.
- 3. Work PerformecI by Florida Power & Light Type Code Symbol Stamp N/A
_ae Authorization Number NIA 9760 SW 344 Street Florida City. FL 33035 Address Expiration Date NIA
- 4. Identification of System: Intake Cooling Water System #: 1I9 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, _N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1969 Edition. NWA Addenda, NMA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Check Valve Atwood and 2-50286-A N/A SC 0052545-1 N/A Replacement N Morril UTC 436675 20 Studs, ASTM A193 87, 1- N/A NWA N/A SC 0044563-1 N/A Replacement N 1IB-8 un-2A x 19 long UTC 437106 40 Nuts, ASTM A194, 1-1"4 N/A NWA N/A SC 0044563-1 NWA Replacement N UN-2A UTC 437106 11 Studs from Alfthread ASTM NA NWA NA SC 0029507-1 NIA Replacement N A-193 Gr B7 1-1/4'-8UN-2A UC 442260 11 Nuts ASTM A-194 Gr 7, 1- N/A WA N/A SC 0027861-1 NIA Replacement N 1/4'-SUN-2B UTC 437162
- 7. Description of Work:
Replaced ICW Pump, Check Valve, Expansion joint and some bolting. Pump documented under WO# 31009255. Expansion Joint documented under WO# 32008465-01. Note: Bolting (Stock Code # 44563-1 Includes one stud (A193 Gr 37) with 2 Nuts (ASTM A-194 Gr7))
- 8. Tests Conducted: Hydrostatic: NIA Pneumatic N/A Nominal Operating Pressure 20 Other VT-2 Pressure 18 psig Test Temperature 84.8 deg F 02-007-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: N/A Signed ISI Date II/ I_
Owner or O4ner's Designee, Title 0
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the perioq 511/2002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.
concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions _ _ _ _
lStor's Signature Naftonl Board, State. Providence, and Endorsements Date 6/ _/_3 0
02-007-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Olwner Florida Power & Light Date 312312003 Na__
e 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 12 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32008465 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair OrganinUon, PO. No, Job No., etc.
- 3. Work Performed byI Florida Power & Light Type Code Symbol Stamp NIA Nam Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Intake Cooling Water System #: 19 Ouslity Group C
- 5. (a) Applicable Construction Code 631.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, WA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components I. T-.I. .Y.
ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No mi r-1 1-Expansion Joint Gartock NIA NIA SC 0014195-1 NIA Replacement N UTC 443801 i
- 7. Description of Work:
Replace 3B ICW Pump, Check Valve, Expansion Joint and bolting. Pump documented under WO#31009255, Check Valve and Bolting documented under WO 32008464.
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure 20 Other Vr-2 Pressure 18 psig Test Temperature 84.8 deg F 024008-3
Sheet 2 of 2 FORM NIS-2 (Back) 9- Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: NIA Signed _ _ s C), Date Y/ Io,,
Owner or Owner's Designee, TWe CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described in this Owners Report during the period 5/112002 to 3/2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code. Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or inplied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions 3 Z8 InVhlor's Signature National Board. State, Providence. and Endorsements Date 02-008-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wner Florida Power & Light Date 7117/2002 Name 700l Jniverse Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Narne WO#: 32011929 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address Repair OrgsnisaUoN, P.O. No, Job No, etc.
- 3. Work Performed by - Florida Power & Light Type Code Symbol Stamp NIA Narm Authorization Number NJA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Component Cooling Water System #: 30 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_* _ _. 1* 1 1- 4 (2) CapScrew, Heavy Hex, NtA NWA N/A SC 0027122-1 N/A Replacement N Asme SA-193, Gr B7. 3/4"-10 UTC 424688 UNC-2A x 3-3/4'
- 7. Description of Work:
CLEAN DIRTY TUBES
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A O
Other NIA Pressure N/A psig Test Temperature N/A deg F 02-009-3
Sheet 2 of 2 FORM NIS-2 (Bsack)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I 0 CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed _ . A-" - Date C ) Owner Own s Desig e, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Inspected the components described In this Owners Report during the period of 6127/2002 to 7/17/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions fZ8 A/6 71KCC
( Inspector's Signature National Board, State, Providence, and Endorsements Date 9-W-paM1 0
02-009-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wrier Florida Power & Ught Date 8119/2002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Namre WO#: 31012691 CR#:
S1760 SW 344 Street. Florida City, FL 33035 Address Repair Organizaton, P.O. No. Job No. eta.
- 3. Work PerformecI by Florida Power & Licht Type Code Symbol Stamp NIA Name Authorization Number N/A C1760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 7!5 Quality Group C
- 5. (a) Applicable Construction Code 931.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, NIA Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_ I.- 1 4* I Pipe 2" Sch 80 SA-106 Gr B N/A NIA N/A SC 0030668-1 N/A Replacement N UTC 443303 (3) Elbows, 2' 3000 Ibs SA-1 05, N/A N/A N/A SC 0034040-1 N/A Replacement N Socketweld UTC 442153
- 7. Description of Work:
Reroute Piping per CRN M-10330
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure 780
- Other VT-2 Pressure 780 psig Test Temperature 366 deg F 02-010-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-41,6.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY. 0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: NIA Signed \ ( t MA/
V l Date T/l /
0J (11wn1er)Owner's IgneeT 0 0
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 7/16/2001 to 8/19/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions A1 2 Ys14-AZ71' X go/ Inspector's Signature National Board, State, Providence, and Endorsements Date ,-Z- w-,
02-010-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner Florida Power& Light Date 11, 1t5/2002 Name, 700 Universe Blvd. Juno Beach, FL 33408 Sheet _ of 2 Addmss Turkev Point Plant Unit 0
- 2. Plant Na.e WO#: 320151124 DI CR#: N/A
?760 SW 344 Street Florida City, FL 33035
__Address Repafr Organizsfaon, P.O. No, Job No. etc.
- 3. Work Performec I by Florida Power & Light Type Code Symbol Stamp N/A Authorization Number N/A I9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NtA
- 4. Identification of System: Auxiliary Feedwater System #: 7 '5 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N)A Addenda, NA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A _Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components i I Yt ¶~~~~~~~~~~
ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_ T Pipe. Carbon Steel, SA-106 Gr NtA N/A NtA SC#0030635-1 NtA Replacement N B. Sch 80, 4' die UTC# 409477 Pipe, Carbon Steel, SA-106 Gr N/A N/A NIA SC#0030635-1 N/A Replacement N B, Sch 80, 4" dia , UTC# 416324 (1) Elbow, Carbon Steel, 45 NWA N/A N/A SC#0033895-1 N/A Replacement N deg. ASME SA-234 WPB SchUC#451 80, 4 dia UTC# 445941 (2) Elbow, Carbon Steel, 90 N/A N/A N/A SC#0033902-1 N/A Replacement N deg. ASME SA-234 WPB, Sch . UTC# 440977
- 60. 4"dia (1) Tee, Carbon Steel, SA-234 N/A NWA N/A SC#0033932 N/A Replacement N WPB, Sch 80,4" dia UTC# 445940
- 7. Description of Work:
Replace degraded piping section of Aux. Feed Steam Supply in Aux Feed Cage area. Ref. NIS-2# 02-015-3 for Support Bolting Replacement.
OTests Conducted: Hydrostatic: 780 Pneumatic N/A Nominal Operating Pressure 780 Other VT-2 Pressure 780 psig Test Temperature 416 deg F 02-011-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY. I CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. NIA -
Expiration Date: NIA Signed a5f:-- :5,Ov Date / 142: 03 L Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Insoected the components described In this Owners Report during the period of e/29/2002 to 11/512002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.
concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions j1(37 Y ( f Ft-3'28
- &pectors Signature National Board, State. Providence, and Endorsements Date /- Z3 -23 0
02-011-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI
- . Obner Florida Power & Light Date 11/412002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I _ of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Naie WO#: 3102440W 3 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizationr P.O. No, Job No., etc.
- 3. Work Performecdby ,Florida Power &Light Type Code Symbol Stamp N/A arne Authorization Number N/A 9760 SW 344 Street Florida City. FL 33035 Address Expration Date N/A
- 4. Identification of System: CVCS Charging and Letdown System #: 47 Quality Group B
- 5. (a)Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition. N/A Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name Of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification BuIlt Replacement Yes/No Gland, Stuffing Nut UnIon Pump N/A N/A SC# 0070930-1 N/A Replacement N UTC# 401315
- 7. Description of Work:
Repack pump,
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 02-012-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules df the ASME Code, Section Xl.
Type Code Symbol Stamp yWA Certificate of Authorization No. N/A Expiration Date: N/A Signed r &X) t 47 Date L/ $sa -
JO ~rO r's Desi e, Title (
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 1/1112002 to 11/4/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
//Go Inspeclortnature Commissions 1 I&7 4f RC3z National Board. State, Providence. and Endorsements 1'
//_7 00 S
Date 0
02-012-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
. Owner Florida Power &Light Name Date 11/412002 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32004054 CR#: NIA 9760I SW 344 Street Florida City, FL 33035 Address Repair Organizatio4,P.O. No, Job No. etc.
- 3. Work Performed by - florida Power & Lliht Type Code Symbol Stamp N/A Nam Authorization Number NIA 9760o SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: _
Intake Cooling Water _
_System #: 19 Ouality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components I I *I*
ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Suil Replacement Yes/No
_ r _ l . ..
(10) Studs, Tap End. Cover 1 - N/A N/A N/A SC#0014188-2 NIA Replacement N 8 UNC-2A x 5-1/2 Lg, ASTM A- UTC# 394431 193 87 (4) Studs, Tap End, Cover 1-8 N/A N/A NIA SC#00141882 NIA Replacement N UNC-2A x 5-1/2 Lg. ASTM A- UTC# 443068 1935B7 (14) Nuts, Heavy Hex, ASME N/A N/A N/A SC#0027840-1 N/A Replacement N SA-194 Gr 2H, 1"-8 UNC-28 UTC# 442400
- 7. Description of Work:
Remove one nut at a time and replace IN , Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure NIA Other N/A Pressure N/A psig Test Temperature NIA deg F 02-013-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPIUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NWA Expiration Date: NIA Signed _ e LjS >~AA&gO v (Za ,M te Ii djo-,
I ia dzn - Trid- . I
<C> vWn" >Evl 61 C. v"aolw raw I It LI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have inspected the components described in this Owners Report during the period of 711912002 to 11/412002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
4217;,,
Inspector's Sia le Commissions 06J7'i4 f ZS3Z8 National Board, State, Providence, and Endorsemerns
)
Date 02-013-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
- Owher Florida Power & Ught Date 111412002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32015737 CR#: N/A 9760 SW 344 Street, Florida City, FL 33035 Address Repair Organization, PD. No. Job No, ec
- 3. Work Performed by - Florida Power & Liaht Type Code Symbol Stamp NIA Name Authorization Number . N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Component Cooling Water System #: 30 Ouality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No m I 4- 4- - 4--
(1) Nut Heavy Hex. ASTM A- N/A N/A N/A SC# 0027837-1 N/A Replacement N 194 Gr 7. 3/4M-l0-UNC-2B UTC# 437942
- 7. Description of Work:
Clean Dirty Tubes. Replace missing Channel head nut
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A 0 Other N/A Pressure NIA psig Test Temperature N/A deg F 02-014-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A-Certificate of Authorization No. N/A Expiration Date: N/A Signed Date /,,t e _
OworO er's Desigr, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of 8/30/2002 to 1114/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions t (i 7r. r ) 3 z8 a Inspector! Sigature National Board, State, Providence, and Endorsements Date 02-014-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 11/5/2002 '
.wn&r Nare 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address Turkey Point Plant Unit 0
- 2. Plant Narne WOa: 32015112-01 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organinzaon, P.O. No. Job Oa,etc.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp N/A Nare Authorization Number NfA 9760 SW 344 Street Florida City, FL 33035 NIA Address Expiration Date
- 4. Identification of System: Auxiliary Feedwater System : 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, _ N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, NWA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components
,ASME Repaired. Code Name of Name of Mfg Mtg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement 'YeslNo t r-, I (4) Cap Screws, Hex Head, N/A N/A N/A SC#0027296 NIA Replacement N Steel Grade 5, Zinc Plated 112- UTC# 377966 13x3 (8) Nut, Heavy Hex, ASTM A NIA N/A N/A SC#0027922 N/A Replacement N 563 Gr B CS UTC#416380
- 7. Description of Work.
Replace degraded Pipe, Note: This NIS-2 for support 80117-R-332-03 and 80117-R-332-04 Bolting material replacement.
'8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A
_ -. A iuther N~ Pressure N psig Test Temperature N deg F 02-015-3
Sheet 2 of 2 FORM NIS-24Badk)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Do ate: NIA Signed 4-- - 13I E Date IMID7 Owne er or Owner's Designee>Witle CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 8/27/2002 to 11/512002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
6 X v Commissions X 3Z ?
ns ctor's Signature National Board, State, Providence, and Endorserments Date _ 11/n 0
02-015-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Sedion XI
- Owner Florida Power &Light Date 3rd !3/2003 Naime 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Nam WO#: 31021701I CR#: NWA I1760 SW 344 Street, Florida City, FL 33035 Adress Repair Organizaton, P.O. No. Job No, aetc
- 3. Work Performet I by Florida Power & Light Type Code Symbol Stamp N/A No"e Authorization Number WA i9760 SW 344 Street Florida City, FL 33035 Expiration Date NWA ddress
- 4. Identification of System: Intake Cooling Water -System #: I9 Quality Group C
- 5. (a)Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, NWA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, NIA Code Case
- 6. identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp lComponent Number Board Identification Built Replacement Yes/No (1) Valve 1-112' Gate Bronze NIA NIA NWA SC# 0052741 NWA Replacement N ASTM 661, Class 200. A00ps! UTC 446134 WOG FNPT ends
- 7. Description of Work:
Replace Valve
- 8. Tests Conducted: Hydrostatic: NIA Pneumatic NIA Nominal Operating Pressure 5 Other VT-2 Pressure 5 psig Test Temperature 88 deg F 02-016-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA N Expiration Date: N/A Signed _ _ Date Ž1 .AI J 0,3 Owner or Ownees Desilee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have inspected the components described in this Owners Report during the period 511/2002 to 3/2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
liln X/ s Inspector Sinature
"' Commissions _ R 5 3 Natinal Board. State, Providence, and Endorsements Date 02-016-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 11112/2002-
- owner Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#; 32018187-03 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizatio. PO. No, Job No., etc.
- 3. Work Performed by Florida Power & Llght Type Code Symbol Stamp N/A Name Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 N/A Address Expiration Date
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components
- ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identfication Built Replacement
- Yes/No
_ 1 '- .- _ - I (8) Nuts, Heavy Hex. ASME SA- N/A NIA NIA SC# 0027832-1 N/A Replacement N 194 Gr 2H Carbon Steel, 1- UTC# 435416 13-UNC-2B (2) Rod, Threaded ASME SA- N/A N/A N/A SC# 0029486-1 NA Replacement N 193 Gr B7 1/2-13 UNC-2Ax 6' UTC# 435452 long
- 7. Description of Work:
Remove Clamp for Inspection, replace damp bolting on support H-334-01
'0 Tests Conducted: Hydrostatic: N/A Pneumatic NWA Nominal Operating Pressure N/A Other NMA Pressure N/A psig Test Temperature N/A deg F 02-017-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code.Section XI.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: NIA Signed OS S
'6 N Date l CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston. Rhode Island. have Insoected the components described In this Owners Report during the period of 10123I200, to 11/1212002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code.Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions ad Y1 A$3 78 Inspector's Signature National BSard. State, Providence. and Endorsements Date /-3 02-017-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- Owner Florida Power & Light Date 3/23/2003' Narm 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Nome WO#: 32012859-01 CR#: NIA 9760 SW 344 Street ,Florida City, FL 33035 Address Repor OrganIzatlon, P.O. No. Jbb No, etc.
, 9760 SW 344 Street Florida City. FL 33035 Expiration Date NtA Address
- 4. Identification of System: Residual Heat Removal _System #: 50 Ouality Group B
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/AAddenda, NIA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Narne of Mfg Mfg Serial National Other Year Replaced, or ,Stamp b Component Number Board Identification Bullt Replacement Yes/No Plate, ASTM A240 type 316 N/A N/A N/A SC# 0030303-1 N/A Replacement N S.S. # 3/8 UTC# 443118 Rod, Threaded, CS ASME SA- N/A N/A NIA SC# 0029481-1 NIA Replacement I 193 Br B7, 3/8 -24 UNF-2A x 4L UTC# 410463 Nuts (3), 300 Series S.S. Hex, N/A N/A NIA SC# 0029050-2 NIA Replacement N Machine Screw, Size 318"-24 LITC# 372969 UNF-2B Washer, Flat (2) 316 S.S. 3/8" NtA N/A N/A SC# 0029050-3 N/A Replacement N ID x 7/8 OD UTC# N/A
- 7. Description of Work.
Install shim modification-to pump base per CR-02-0845 and MSP#02-058 8.Tests Conducted: Hydrostatic: NIA Pneumatic NIA Nominal Operating Pressure NIA 0* Other VT-3 Pressure N/A psig Test Temperature N/A deg F 02-018-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Rernarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp I NIA Certificate of Authorization No. N/A Expiration Date: N/A '
I Signed-- ISI Date y I i apJ JWrn`3r or Owner's Desigilee, Title 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period 7/24/2002 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions /c 3'8
/;nector's Signature National Board, State. Providence, and Endorsements Date _ _ _ _ _ _ _ _
02-018-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI
- Owher Florida Power &Light Date 3/23/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Name WO#: 32018187-01 CR#: N(A 9760 SW 344 Street, Florida City, FL 33035 Address Repair Organization, P.O. No, Job No, etr.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp N/A Wame Authorization Number IWA 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Address
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C a.
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition. N/A Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Comnonent Number Board Identification Buit ReDoacement Yes/No
.1. 4 -+ -+ 4. 4.
(2) Elbow, Carbon Steel, SA- N/A NWA NMA SCO 0033902-1 NIA Replacement N 234 Gr. WPB, 4' dia. 90 deg. UTC# 447005 Sch 80 Searmless Pipe, Carbon Steel, SA-106, N/A N/A N/A SC# 0030635-1 N/A Replacement N Grade B. Seamless Plain Ends. UTCN 416324 4' Sch 80 (24) Nuts, Heavy Hex SA-194 NWA NA WA SC# 0027832-1 N/A Replacement N Gr 2h Carbon Steel, 112'- UTC# 445901 13UNC-2B (6) approx 5Slengths, Threaded N/A WA N/A SC# 0029486-1 N/A Replacement N Rod, SA-1 93, Gr. B7, Size 1/2'- UTC# 442843 13 UNC-2A
- 7. Description of Work:
Replace Degraded Pipe sections and replace bolting on supports H-334-11 and H-334-12, Note: Bolting replaced on H-334-11 (2 studs, and 5 Wuts) -_33_-__ - - --------
- Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure X Other VT-2 Pressure 750 psig Test Temperature 385 deg F 02-019-3
Sheet 2 of 2 FORM NIS-2 (Back) 0
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N416.1 WAS INVOKED FOR THIS REPLACEMENT ACTMTY.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA I
- Certificate of Authbrizatidn No. NIA Expiration Date: NIA i Sig. .- IS I SII nr-e e; - Date 4/I I1f4l/c Owner or Owner's Desigh'e, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insnected the components described In this Owners Report during the perici 1011712002 to 3t2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
V < .. , , Q Commissions X 376' In_ cte's Signature National Board, State, Providence, and Endorsements Date 66-14/41 7 7-02-019-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power &Light Date 1212/2002 W" r Warne 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Warne WO#: 3201781101 CR#: 02-1639 9760 SW 344 Street Florida City, FL 33035 Address Repair organization, P.O. No, Job No, tc.
- 3. Work Performed by Forida Power & Light Type Code Symbol Stamp N/A arne Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA -
Address
- 4. Identification of System: Auxiliary Feedwater System #: 75 Ouality Group C
- 5. la) Applicable Construction Code B31.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial iNational Other Year Replaced, or Stamp Component Number I Board Identification Built Replacement Yes/No
- I I I I I l Pipe, Carbon Steel, ASME A- NIA N/A N/A SC# 0030635 N/A Replacement N 106 Gr. B Seamless, 4 Sch 80 UTC9 416324 (2) Elbows, 90 Deg. Carbon N/A N/A N/A SC# 0033902 N/A Replacement N Steel, SA-234 Gr WPB 4' Sch UTC# 440977 80
- 7. Description of Work:
Replace degraded Pipe
- 8. Tests Conducted: Hydrostatic: NIA Pneumatic N/A Nominal Operating Pressure X Other VT-2 Pressure 750 psig Test Temperature 385 deg F 02-02D-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.
CERTIFICATE OF COMPLIANCE We certify thBt the statements made In the report are correct and this replacement conforms to the nries of the ASME Code,Section XV.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: NIA Signed 0, 03 5 l r.L N -DZ Datet t 2- LI ?-
690 Owner or Owner's Designee, Title I 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have InsDected the components described In this Owners Report during the period of 10/101200Z to 12/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described I this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Aamo I Inspector's Signature Commissions 146 IP (ft-3748 Nabonal Board, State, Providence, end Endorsementa 12 Date //9/0 3 0
02-020-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power & Light Date 3123/2003 Narme 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit WO#: 32018583-01 CR#: 02-1639 9760 SW 344 Street Florida City, FL 33035 Address Repair Orgalizatlio. P.O. No, Job No.. etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp NIA Name Authorization Number NMA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NfA
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a)Applicable Construction Code 831.1 1955 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N....
...... Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (30) Pipe, Carbon Steel. ASME NIA WA NIA SC 0030635-1 N/A Replacement N A-SA-106 Gr B, Seamless, 4" UTC# 447411 Sch 80 (4) Bolts. Stud, All-Thread, N/A NIA N/A SC# 0026265-1 N/A Replacement N ASME SA-193 GR B7, 314"-10 UTC# 432641 UNC-2A x 4 1/4.
(4) Nuts, Heavy Hex, C.S. SA- N/A NIA NIA SC# 0027084-1. NIA Replacement N 194 Gr 2H 314'-10 UNC-2B UTC# 433908 Zinc Coated (12) Nuts, Heavy Hex, C.S. SA- NMA N/A NIA SC# 0027084-1 NIA Replacement N 194 Gr 2H 3/4-l0 UNC-2B3 UTC# 444694 Zinc Coated (4) Nuts, Heavy Hex, C.S. SA- NIA WA N/A SC#0027962-1 NIA Replacement N 194 Gr. 2H, Size 5/"-11 UNC-2B UTC0 444374
- 7. Description of Work:
Replace degraded pipe and degraded bolting on supports
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure X _
Other VT-2 Pressure 750 psig Test Temperature 385 deg F 02-021-3
Sheet 2 of 2 FORM NIS-2 (Back)
I
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A I
Sig I SOI Seihe Tite Date 4lI/ol Owner or Owner's Desisdhee, Title 0
CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut have inspected the components described in this Owners Report during the perioq 10/2512002 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code.Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/A/( 7 6 ctor's Signature Commissions ft - *- '
National Board. State, Providence. and Endorsements Date 6 I/e9 0
02-021-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 3/23/2003
@2wnrlr Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Name WO#: 32018705-07 CR#: Ckg by 9760 SW 344 Street Florida City, FL 33035 IWA Addrss Repair Organiztilon, P.O. No, Job No., etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp N/A Name Authorization Number NIA 9760 OSWf 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a)Applicable Construction Code B31.1 1955 Edition, NIA W. .. A
...... Addenda, d.n... NWA Case
...... .. Code C.
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda. WJA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp e Component Number Board Identification Built Replacement Yes/No (1) Pipe Clamp,4' CS ASME NIA N/A N/A SC# 0403668-1 WA Replacement N SA-36 UTC# 447596
- 7. Description of Work:
Remove and Replace Supports in Zone 13 (1-334-06)
- 8. Tests Conducted: Hydrostatic: WA Pneumatic WIA Nominal Operating Pressure N/A Other NMA Pressure N/A psig Test Temperature NIA deg F 02-022-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NWA Certificate of Authorization No. NIA Expiration Date: N/A Signed c45 Is'44-, Date Owner or Owner's Designee, TIe 6
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the period 112212002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
lie or's Signature
/_______ Commissions 4 _
National Board, State, Providence, and Endorsements Date _
02-022-3
FORM NiS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
. Ovwner Florida Power S Light NaKe Date 12/9/2002 7001Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 0
- 2. Plant WO#: 32018`187-02 CR#: 02-1984 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizatfon, P.O. No, job Noa etc.
- 3. Work Performed by Florida Power &Llht Type Code Symbol Stamp N/A Nane Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Auxiliary Feedwater _System #: 75 Quality Group C
- 5. (a) Applicable Construction Code - E31.1 19 55 Edition, N/A -Addenda. N/A Code Case (bplcbeEiino eto iUiie o ear rRpaeet (b) Applicable Editlon of Section XI Utilized for Repsirs or Rep~lacements 19 89 EditIon, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mg Serial Natonal Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Weld Filler Metal. ER70S- N/A NIA NJA SC# 0011910 N/A Repair N 2,Weld Build-up on Existing UTC# 408016 Piping.UT#481 Weld Filler Metal, ER70S-2, N/A N/A N/A SC# 0011909 NIA Repair N Weld Build-up on existing UTC 407289 Piping. = 40.28
- 7. Description of Work:
Aux. Feedwater 4 Pipe Weld Build Up.
.Tests Conducted: Hydrostatic: NIA Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure NIA psig Test Temperature N/A deg F 02-023-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Reinarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELDCONTROL MANUAL. 0 CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. NMA -
Expiration Date: NIA I_1 j.
Date I Z. IZ' OZ..... t Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described in this Owners Report during the period of 10117/200. to 12/9/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described Inthis Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions AAY 7ZWJ Xr a ,-3ZA
- /nspector's Signature National Board, State, Providence, and Endorsements Date /Z_ /__________
0 02-023-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Fbrida Power & Light Date 1V123/2002 Owner Nanx 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addnmss
- 2. Plant Turkey Point Plant Unit 0 Nane WO#: 32018700- 03 CR#: NIA 9760 SW 344 Street, Florida City, FL 33035 Address Repair Organizaon P.O. No. Job No, tc.
- 3. Work PerformecI by Florida Power & Light Type Code Symbol Stamp WA Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Addrss Expiratfon Date N/A
- 4. Identification of System: Auxiliary Feedwater _System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case 4b) Applicable Edition of Section Xi Utilized for Repairs or Replacenients 19 89 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacemer ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Bunt Replacement Yes/No Pipe Clamp, 4' Carbon Steel, 3 Bergen N/A N/A SC#034356-1 N/A Replacement N bolt, BP Part #6150 Paterson UTC# 422539
- 7. Description of Work:
Remove supports and ihspect pipe, replace clamp on support 4-YPH-39 B. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 02-024-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLiANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. WA Expiration D;ate: N/A Signed In? O's5LC 5,4W. Date 1/ 0/ 03 Owner or Owner's Designee, Title 1 a
0s CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 10/25I200. to 12/2312002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A,,-
C/ Inspector's Signature Commissions a/37Zf ^,5 Zt National Board, State, Providence, and Endorsements Date //or Af I 'I 0
02-024-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
' Wner Florida Power & Light nme Date 12/26/2002 700ItUniverse Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 0
- 2. Plant Name WO#: 32018700-04 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization, P.O. No, Job No., etc.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp N/A Kame Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. IdentifIcation of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code, B31.1 1955 Edition, NWA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_ 5 4-I. . 4 Paddle end from Strut, Bergen N/A NA SCt#010&601-1 N/A I Replacement N Telescoping Rigid. BP Part# Paterson 2100-7 UTC# 388782 1 1-1 t-1 1 l~ ~~4 .- 4 5 4. 4.-.4 4 I
I . .LS 6.h
- 7. Description of Work:
Replace Paddle on Strut of Support H-336-03, Paddle from New Strut Welded to existing stut.
Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 02.025-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.
0 CERTIFICATE OF COMPiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. NIA Expiration Date: NIUA Signed t56' ' Owner or Owners Designee, Title Date l/ 9 lo 3 0
CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston. Rhode Island, have Insoected the components described in this Owners Report during the period of 0I/25&200, to 12/26/2002 and state that to the best of my knowiedge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described inthis Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
' /J) U Inspectors Signature Commissions / ' ye -rA'8 National Board, State, Providence, ard Endorsements J-'
Date Zhle2 02.025-4
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power &Light Date 1227/2002' Owner Nalm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Name WO#: 32018705-09 CR#: NO 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizaflon, P.O. No, Job No. etc.
- 3. Work Performed by - Florida Power & Licht Type Code Symbol Stamp - A Karne Authorization Number NIA 9760 SW 344 Street Florida City. FL 33035 Address Expiration Date NIA
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, NIA Code Case (b
plcal dtono etonX tlie o episo epae et (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built I Replacement Yes/No
_ '- _ l Bergon Paterson Pipe Clamp Bergen N/A N/A SC# 0403668-1 NWA Replacement Part No. 2600 Paterson UTC# 0000447596 I I I
- 7. Description of Work:
Inspection of piping after damp removal Train #2 Zone 17,Replaced damp for Support H-334-16
' ests Conducted: Hydrostatic: NWA Pneumatic NIA Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 02-026-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A slarla
_______ Date I l / 3 0 Owner or Owners Designee, Title I C, (A:f, O0 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described in this Owners Report during the period of 11/22/200. to 12127/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions &/g7zfYr1 few ?Z 8 T Inspector's Signature National Board, State. Providence, and Endorsements Date / /9 lo3 02-026-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- Owher Florida Power & Light Date 12/2712002 Narm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkev Point Plant Unit 0 Name WO#: 32018705-10 CR#: NIA 1760 SW 344 Street Florida City, FL 33035 Address Repair rganization. P.O. No, Job No.. eM
- 3. Work Performecdby Florida Power & Light Type Code Symbol Stamp NIA Nane Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Cuality Group C
- 5. (a) Applicable Construction Code 831.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Nameof Mfg Serial National Other ~ ~~~~Repaired, Code Name of Name ol MfG MfG SeNl National Oter Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 4 BP Part #2600- Bergen NIA N/A SC#0403668-1 NIA Replacement N 2.5 Paterson UTC# 447596
- 7. Description of Work:
Replace Pipe Clamp on Support H-334-20, 8 Tests Conducted: Hydrostatic: NWA Pneumatic N/A Nominal Operating Pressure NIA O
Other NIA Pressure N/A psig Test Temperature NIA deg f 02.027-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPUiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NWA Expiration D;ate: N/A I e Signed Os£ *..A4V Date I I e/0 3 C)I
- Owner or Owner's Designee, Title Coo 0
CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 11221200Z to 12/27/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concemning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Alwo Commissions MC 71Z Yl- A 3'zg j:
National Board, State, Providence, ard Endorsements (I Inspectors Signature Date /03 I
0 02-027-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
&Nner Florida Power & Light Date 3/2312003 Nane 700 1Jniverse Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Name WO#: 32015705-12 CR11: N/A 9760 SW 344 Street Florida City, FL 33035 Address Kupaer Organizawn, F.C. No, Job No., etc.
- 3. Work Performed by - Florida Power & Light Type Code Symbol Stamp , NA Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group
- 5. (a) Applicable Construction Code B31.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replaceinent Yes/No BP Part No.2600-2.5,4" Pipe Bergen N/A WA SC# 0403668-1 WA Replacement N Clamp Paterson UTC9 0000447596
- 7. Description of Work-Inspection of piping after pipe damp removal, Replaced Pipe Clamp on R-332-05.
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure NIA Other N/A Pressure NIA psig Test Temperature N/A deg F 02-028-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: NIA Signed I IS S-T!& Date _____S_____
Owner or Owners Designee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the periof 1115/2002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.
concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
A64eInsqct/rsSignature Commissions fjC-3 .__8 National Board, State, Providence. and Endorsements Date W /(/a3 -
02-028-3
FORM NIS-2 OWN8RS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- Owner Florida Power & Light Date 12/27/2002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I Address of 2
- 2. Plant Turkey- Point Plant Unit 0 Name WO#: 32018705- 02 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization P.O. No, Job No, et.
- 3. Work Performec I by Florida Power & Light Type Code Symbol Stamp NIA Namn Authorization Number NJA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NtA
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, NtA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 EditIon, N/A Addenda, N1A Code Case
- 6. IdentIfication of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial Nation Other Year Replaced, or Stamp Component Number Identification Built Replacement Yes/No Pipe Clamp. 4 BP Part# 2600- Bergen N/A NtA SC# 0404668-1 N/A Replacerent N 2.5 Paterson UTC# 447596 I
- 7. Description of Work:
Replace Pipe Clamp on Support R-332-03 8 Tests Conducted: Hydrostatic: NtA Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature NWA deg F 02429-3
Sheet 2 of 2 FORM NIS-2 tBack)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
S CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. NMA Expiration Date: N/A 6*
Signed . 6 1-== Ce. 64 V, Owriror Owners Designee, Title I Date 1 I 13103
',- 6' CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Insoected the components described in this Owners Report during the period of I1/25/200, to 12127/2002 snd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions Sag 72 d rc 5g 7 6U / Inspectors Signature National Board, State. Providence, and Endorsements Date 11,916 02-029-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Sectio Xl
- Owner Florida Power & Light Date 12/27/2002 Name I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I Of .. 2 Address Turkey Point Plant Unit 0 2.Plant Name WOU: 32018700-11 CR#: N/A 9760 SW 344 Street Florida City. FL 33035 Address Repair INganizaae. P.O. No,Job No, etc.
-3. Work Performed by Florida Power & Liht Type Code Symbol Stamp I N/A Narm Authorkaion Number N/A 9760 SW 344 Street Florida City. FL 33035 Expiration Date NrA Address
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code i31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code I Name of Component Name of Mfg Mfg Serial National Number Board Other Identification Year Built Replaced, or Repbacement Stamp Yes/No Pipe Clamp, 4 BP Part # 6150 Bergen N/A N/A SC# 0034356-1 N/A Replacement N Paterson UTC# 422539
- 7. Description of Work:
Replace Clamp on support 3-AFH-10 40.Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 024030-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED. 0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: WA
~~~~~~~~~~~~~~~ ° C'W-Sinned l
>~~~~~~~
os5 '! .,
Owner or Owner's Designee, Title '
Date 44e3
'rl 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insmected the components described in this Owners Report during the period of I l21/200 to 12/2712002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
zoa1( / Inspectors Signature Commissions A471ZYr AI- 1s8 National Eoard. State. Providence, and Entdorsernents r
Date . I'f/O g
,--1 0
02-030-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- Owner Florida Power & Light Date 12/30/2002 Narm 700 Universe Blvd. Juno Beach, FL 33408 Sheet I Of ... 2 Address
- 2. Plant Turkey Point Plant Unit 0 Name WO#: 32018705-14 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address No, Job No, etc.
Repair Organization, PMO.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp I N/A Namn Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date NtA Address
- 4. Identification of System: Auxiliary Feedwater _System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaoed, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 3WCS 3 Bolt A36 Bergen N/A N/A SC# 0034355-1 N/A Replacerpent N Paterson UTC# 447504 Threaded Rod, ASME SA-193 N/A N/A N/A SC# 0029486-1 NIA Replacement N Or B7. 1/2-13 UNC 28 _UTC# 442843 (4) Heavy Hex Nuts, ASME SA- N/A NIA N/A SC# 0027832-1 NIA Replacment N 194 i r 2H. 1/2 13 UNC 2B UTCI435416
- 7. Description of Work:
Replace Clamp on Support 3-AFX-7 and replace bolting on Support H-330-01
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A
_ -\L KE umner NIA Pressure N/A psig Test Temperature NIA deg F O2031-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp NMA Certificate of Authorization No. N/A Expiration Date: NIA Signed *J 4-"_ Date I I 0o3 ao Owner-r Owner's Designee, Title 7 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 1115/2002 to 12/3012002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Ae W".171- Commissions fr'79ZtV-g3Z8 j-6/ Inspector's Signature National Board, State. Providence, and Endorsements Date 17 Ah 7 02-031-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- Owner Florida Power &Light Oate 1213012002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 0
- 2. Plant Nam WOO: 32018705-08 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Addres Repair Orguralzation, P.O. No, Job No., etc.
- 3. Work Performed bj I Florida Power & Light TyDe Code Svmk d1Stamo . NIA NaWe Authorization Number N/A 9760 SW 344 Street Florida CityFL 33035 N/A Address Expiration Date
- 4. identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition. N/A Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 4 ASME SA-36, Bergen N/A N/A SCtS 0403668-1 N/A Replacenwent N BP Part # 2600-2.5 Paterson UTC# 447596
- 7. Description of Work:
Replace Pipe Clamp on support H-334-07 8.Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 02-032-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: NIA Signed e J - -
v -Se_7 W - 15 w-4,1 I. ---
Date I l 3 °03 dI ---
W C ('< __ __ ---- Ownei-or Owner's Designee, Title __
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a vaid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have inspected the components described in this Owners Report during the period of 11111/200. to 1213012002 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
____ ____o___Signature Commissions '/>'J f~L 328 3 Inspectors
( I Signature National Board, State, Providence, and Erndorsements Date ,// S A+/°- _
S 02-032-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
- Owner Florida Power & Ught Date 12130/2002 Harm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of i 2 Address Turkey Point Plant Unit 0
- 2. Plant Nare WON: 32018700-13 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizatimor P.O. No, Job No., etc.
- 3. Work Performed by - Florida Power & Light Type Code Symbol Stamp N/A Nare Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System#: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A _Addenda, N/A_ Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition. N/A _Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No N (2) All Thread, ASME SA-193 NIA N/A NIA SC# 0029486-1 WA Replacement N Gr B7, 1/2-13 UNC-2A. UTC# 442843 (8) Heavy Hex Nuts, ASME SA- NIA NIA N/A SC# 0027832-1 NIA Replacement N 194 <r 2H. 112-13 UNC-2B UTCN 445901
- 7. Description of Work:
Replace Bolting on Support 4-AFX-8
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure NIA I Other N/A Pressure N/A psig Test Temperature NIA deg F 02-033-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
S CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code: Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed 61 - _s
_1__N 0e5Fi 5fr OwnrFor Owner's Designee, Title Dae Date ' 0 610if33 0
CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described hI this Owners Report during the period of 12118/200, to 1213012002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Qlz Inspector's Signature Commissions /I/* 7 Z A' 3-z ~
National Board, State, Promidence. and Endorsements I
Date 3 02-033-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wner Florida Power & Light Date 12130/2002 Narne I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address
- 2. Plant Turkey Point Plant Unit 0 Narne WO#: 32018187-07 CR#: 02-2046 9760 SW 344 Street Florida City, FL 33035 Address Repair Organzatm, P.O. No, Job No., etc.
- 3. Work Perform&ei by Florida Power & Liaht Type Code Symbol Stamp NIA Rame Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Appflcable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_ S i
Weld Buildup of Pipe on Train 2 N/A NWA NIA WPS-89 N/A Repaired N AFSS FPL Weld Control Manual
- 7. Description of Work:
Perform Weld buildup in corroded areas, Build up to minimum .300 per MRA 32018187-01
- 8. Tests Conducted: Hydrostatic: NA Pneumatic N/A Nominal Operating Pressure NIA 0 Other NWA Pressure N/A psig Test Temperature NIA deg F 02-034-3
Sheet 2 of 2 FORM NIS-2 1Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NIA Certificate of Authorization No. NIA Expiration Date: N/A Signed CK R< - * / IS;ewAqpAe)-, DtI Date 4.V!za?
Owner or Owner's Desigtee, Title z 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report dwing the period o 10/26/2002 to 12/30/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connted with this inspection.
X0/00_P Commissions fi e z8 In& r's Signature National Board. State, Providence. and Endorsements Date ~,41 /6 75.
I - I 02-034-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power &Light Date 12/30/2002 2b Owner Name I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addrss Turkey Point Plant Unit 0
- 2. Plant Name WO#: 32018700-02 CR#: WNA 9760 SW 344 Street Florida City, FL 33035 Addres Repair Organizaton, P.D. No4Job No., tc
- 3. Work Performed by Florida Power & Ught Type Code Symbol Stamp .NIA Name Authorization Number NtA 9760 SW 344 Street Florida City, FL 33035 Expiration Date NfA Address
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a)Applicable Construction Code B31.1 1955 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, N/A Addenda. NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg MW9 Serial National Other Year Replaced, or Stamp b Component Number Board identification Built Replacement Yes/No Pipe Clamp, 4 ASME SA-36. Bergen N/A N/A SC# 0403668-1 N/A Replacement N BP Part# 2600-2.5 Paterson UTC# 447596
- 7. Description of Work:
Replace Pipe Clamp on Support H-330.04
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A Omser N/A Pressure N/A psig Test Temperature N/A deg F 02-035-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NMA Certificate of Authorzatioh No. WIA Expiration Date: N/A Signed Date I I 103 O
9K wrer or Owners Designed, Wel s
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 10/25/200,c to 12130/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance wlth the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described hIthis Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable hI any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
ZA Commissions A1677yr f C 3-s 2 i' 61 Inspectoes Signature National Board, State, Povidenoe, and Endorsements Date / A9 A T I
S 024035-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power &Light Date 12130/2002
- . Owner I
700 Ur-iverse Blvd. Juno Beach, FL 33408 Sheet 1 of.. 2 Addr
- 2. Plant Turkev Point Plant Unit 0 Name WOM: 32018706. 406 CR#: NJA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organaticon PM. No. Job No., etc.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp ,_ NIA 9aFe Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N.A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacenierts 19 89 Edition, N/A Addenda N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacernenit Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Bunt Replacement Yes/No (2) Pipe Clamps, 4' ASME SA- Bergen N/A NIA SCU 0403688-1 N/A Replacement N 36, BP Part# 2600-2.5 Paterson UTC# 447596
- 7. Description of Work:
Replace Pipe Clamps on H-334-01 and H334-21
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure NJA 0
Other NIA Pressure NJA psig Test Temperature N/A deg F 02436-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NfA Certificate of Authorization No. N/A Expiration Date: N/A Signed t< Dat Date I1 /61o-7 Owner or Owner's Designee. Tkle 1 cf< I0 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of 12/181200 to 12130/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
A-J Commissions A/67ZYV PIZY J-(I Inspector's Signature National Board. State, Providence, and Endorsements Date // t /O3 0
02.036-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power & Ught Date 12/30/2002
- Owner Name I
700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addresa
- 2. Plant Turkey Point Plant Unit 0 Wame WO#: 32018187-08 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organizatlon, P.O. No, Job No., et.
- 3. Work Perlormned by Florida Power & Ught Type Code Symbol Stamp I NIA Nare Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: Auxiliary Feedwater _System #: 75 Quality Group C
- 5. (a) Applicable Construction Code % 831.1 19 55 Edition, NtA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition 1 N/A Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (30) Pipe, 4- Carbon Steel, N/A N/A N/A SC# 0030635-1 N/A Replacement N ASME SA-106 Gr B. Sch 80 UTC# 416324 (1) Elbow, 4" 90 deg, Carbon N/A N/A N/A SC# 0033902-1 N/A Replacement N Steel, ASME SA-234 Gr WPB UTC# 447005 Sch 80 (8) Nut, Heavy Hex, ASME SA- N/A N/A N/A SC# 0027832-1 N/A Replacement N 194 Gr 2H, 1/27-13 UNC 2B UTC# 445901 (2) lengths, Threaded Rod, N/A N/A N/A SC# 0029486-1 NIA Replacement N ASME SA-193 Gr B7, 112"-13 UTC# 442843 UNC 2A
- 7. Description of Work:
Replace corroded Aux Feed Steam Supply (Train 2) pipe and also replace bolting on support R-334.02 O Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure 760 Other VT-2 Pressure 760 psig Test Temperature 495 deg F 02-037-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Rehiarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE NA416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: NIA Signed Date e !
werorOne'sit Title 0
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insnected the components described In this Owners Report during the period a 10129/2002 to 12/30/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A/L I)tpores Signature Commissions /,- - Z National Board, State, Providence, and Endorsements Date 02-037-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- 3wner Florida Power & Light Date 1/7/203 I
700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address Turkey Point Plant Unit 3
- 2. Plant Name WO#: 32018705-13 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address fRpaiJ Organizalon, P.O. No, Job No., etc.
- 3. Work Performed by Florida Power S Light Type Code Symbol Stamp NIA NHae Authorization Number WA 9760 SW 344 Street Florida City, FL 33035 NJA Address Expiration Date I
- 4. Identification of System: Auxiliary Feedwater .System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, NWA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No t t I I I (2) Threaded Stud, 5/8-11UNC- N/A NIA NIA SC# 0029490-1 NJA Replacement N 2A ASME SA-193 Gr 87 UTC# 443307 (3) Threaded Stud, 1/2-13UNC- NIA N/A N/A SC# 0029486-1 NJA Replacement N 2A, ASME SA-193 Gr B7 UTC# 442843 (12) Nuts. Heavy Hex, ASME N/A N/A N/A SC# 0027832-1 NWA Replacement N SA-194 GR 2H, 12r-13UNC- UTC# 445901 2B.
(8) Nuts, Heavy Hex, ASME SA- N/A N/A N/A SC# 0027962-1 N/A Replacement N 194 Gr-2H, 5&81 1UNC-2B UTC# 444374
- 7. Description of Work:
Replace bolting on pipe clamps for supports 4-AFX-1, 4-AFX-6 and 4-AFX-7 Nominal Operating Pressure N/A
- 08. Tests Conducted: Hydrostatic:
Other NIA N/A Pneumatic Pressure N/A NIA psig Test Temperature NWA deg F 03-001-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp NIA Certificate of Authorization No. WA Expiration Date: NWA Signed ,
05-e6 5 4ph
, Date 1 86 /0°3 C)
A-Owner or Owners Designe'e. The
'Cot, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors end the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Inspected the components described In this Owners Report during the period of 117/2003 to 1/7/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code.Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.
concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions //t72nI tZz JE 0 -t Inspector's Signature National Board, State, Providence, and Endorsements Date //9/0 I
03-001-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wner Florida Power 8 Light Date 1/7/2003 '
Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WOO: 32018700-08 CR#: NWA 9760 SW 344 Street Florida City, FL 33035 Addres Repair Organization, P.O. No. Job No, etc.
- 3. Work Performed by - Florida Power & Light Type Code Symbol Stamp N/A Name Authorization Number N/A 9760iSW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. ia) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired,. Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
- 4 t- 1 Paddle End from Strut, BP Bergen N/A N/A SC# 0100601-1 N/A Replacemnent N Part# 2100-7 Paterson UTC# 388782 Load Pin manufactured from N/A N/A N/A SC# 0029992-1 N/A Replacment N Round Stock, 1 ASTM A-193 UTC# 443308 GrB (2) Studs from Alhthread, 3/4 - N/A NIA N/A SC# 0029493-1 N/A Replacement N 10 UNC-2A, ASME SA-193 Gr UTC# 437941 87 (8) Heavy Hex Nuts, ASTM A- N/A N/A NIA SC# 0027837-1 N/A Replacement N 194 Gr 7, 3I4'-10 UNC-2B UTC# 437942
- 7. Description of Work:
On support R-337-02 replace paddle on strut, from new strut UTC#388782, replace bolting on pipe clamp, and replaced Load Pin
.Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure NIA Other N/A Pressure NIA psig Test Temperature N/A deg F 03-002-3
Sheet 2 of 2 FORM NIS-2 (Back)
I
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. _ NIA Expiration Date: N/A 03 Sinnpd aJg1 105e v0 _AG-_ Date !I / I 4IIR 1 I'S e}
Owner or Owners Designee, Title' CIK CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described in this Owners Report during the period of 11712003 to 117/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
A40* (jppectors Signature Commissions( FEZ4 6> 5238 National Board, State, Providence. and Endorsements Yf Date / /4 M?
0 03-002-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 1/8/2003 Nare I 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant iame WO#: 32018700-14 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repalr Orgadsiaon P.O. No. Job No, eta.
- 3. Work Performed by Florida Power &Light Type Code Symbol S rStamp N/A Name Authorization Numt NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Auxiliary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components T F I ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
_ w Pipe Clamp. 3' CS. BP Part# Bergen N/A N/A SC# 0034355-1 NA Replacerrent N 6150, 3 Bolt Paterson U'TC# 447504 t 1* 1--I t 4 4 + *9*
- 7. Description of Work:
Replace Clamp on support 3-AFX-8 Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F
.03-003-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED. i CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Sinnd E a z>r t: 5 _- v/v Date I E3 /°0
-. S, -
A Ownri or Owner's Designee, Title-Lov<
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described in this Owners Report during the period of 111412002 to 1/812003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code. Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A2'~
6J Inspector's Signature Commissions &/6 7,YrAc 37z&
National Board, State, Providence, and Endorsements Date /- I - O 3 03-003-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 119/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32018700-12 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Organnfdon, P.O. No, Job No. etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp I N/A Naffe Authorization Number- NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Auwdilary Feedwater System #: 75 Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No 1010 (2) Pipe Clamps, 4- BP Part# Bergen N/A N/A SC# 0403668-1 N/A Replacement N 2600-2.5. ASME SA-36 Paterson UTC# 447596
- 7. Description of Work:
Replace damps on supports H-337-02 and R-337-05 Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 03-004-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NIA Certificate of Authorization No. NIA Expiration Date: N/A Sined al,. . _ _. . iDate 'l9 /03 A Owner or Ownees Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of I191200, to 119/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions J6772-Y-)3?76 National Board. State. Providence, and Endorsements 7
I r6os Signature Date Z I I f S
03-004-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 3111612003 Name I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addreas
- 2. Plant Turkey
._ , Point . Plant
_ Unit 3 Name WO#: 32003971- 02 CR1: 02-1640 9760 SW 344 Street Florida City, FL 33035 Address RepaIrOpaniznfon, P.O. No, Job No. etc.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp NIA Name Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Containment Emergency Filters System #: 56 Quality Group B
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No SV-3-2905, Reweld Canopy NIA N/A N/A Existing N/A Replacement N seal weld Existing
- 7. Description of Work:
Cut Seal Weld, Rework valve and reweld seal weld
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NWA Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 03-05-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
I CERTIFICATE OF COMPLIANCE We certify that the statements made I the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NfA Expiration D.ate: N/A Signed ZS/ :X r44~
r"" - 't >A Date X/de 3 Owner or Owners Desigheevritie CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a vasld commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the period 111412003 to 3/1612003 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
(J iectors Signature Commissions A* .35Z8 National Board, State, Providence, and Endorsements Date 4-/G-v ?
03-005-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power &Light Date 31117/2003 Name 700 Ur ilverse Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Nam. WO: 32009982.~01 CR#: NrA 9760 SW 344 Street Florida City, FL 33035 Ajddrns Repair O"ganizaUon, P.O. No. Job No. etc
- 3. Work Performe d by Florida Power &Lbiht Type Code Symbol Stamp N/A Hame Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NIA
- 4. Identification of System: Spent Fuel Pit Cooling System #: 33 Quality Group C
- 5. ta) Applicable Construction Code 931.1 19 55 Edition, N/A Addenda, N.A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition. N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components
- -r I ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification BuIlt Replacement Yes/No Bonnet from Valve, 27 NIA NJA NJA SC0237682-1 N/A Replacement N Diaphram SA-351 Gr CF8, UTC# 434928 Class 150
- 7. Description of Work:
Replace bonnet and diaphram
'6 Tests Conducted: Hydrostatic: N/A Pneumatic NJA Nominal Operating Pressure X Other Vr-2 Pressure 120 psig Test Temperature 81 deg F 03.006-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED. I e CERTIFICATE OF COMPLIANCE We certify that the statements made Inthe report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. WA Expiration Date: NWA SignesZI is/
A S_ perJjc Date __ _ __I _
Owner or Owner% Designee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have Inspected the components described Inthis Owners Report during the periq 6/5/2002 to 3/17)2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, conceming the examinations and corrective measures described Inthis Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable Inany manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions / 5?&
lIsr~ed&-r Signature National Board, State, Providence, and Endorsements Date 034006-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power &Light Date 3117/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of. 2 Addes Turkey Point Plant Unit 3
- 2. Plant Name WO#: 30005430-01 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Addmss Repair OrgarlztiloN P.O. No. Job No., etc.
- 3. Work Performed by - Florida Power &Light Type Code Symbol Stamp N/A NWo Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Addres
- 4. Identification of System: Auxiliary Feedwater System 9: 75 Quality Group B
- 5. (a)Applicable Construction Code 631.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
- - I. 4 .1 4. 4-.4. .4.
(4) Bonnet Studs, ASTM-A-193 N/A N/A N/A SC# 0062455-1 NIA Replacement N GR B7 UTC# 402077 (8) Nuts, Carbon Steel, SA-194 N/A NA NIA SC# 0027957-1 N/A Replacement N Gr 2H Ull 443838
- 7. Description of Work:
Disassemble, clean, Inspect, repair, replace bonnet nuts and studs and reassemble
- 8. Tests Conducted: Hydrostatic: NIA Pneumatic WA Nominal Operating Pressure N/A 0 Other N/A Pressure N/A psig Test Temperature N/A deg F 03-007-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I 0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: NWA Signed ~ - , _v z Date /17/03 Owner or Owners Designd'e, Title 0
CERTiFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the periaq 912512002 to 3/1712003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/J0f Commissions / r 3X National Board. State, Providence, and Endorsements
-I orie Signature Date C6/l/o3 03-0074
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Secton Xl
- wner Florida Power& Light Date 3/17/2003 Name 7f00 Universe Blvd. Juno Beach, FL 33408 Sheet .1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant Name WOM: 33004384-01 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address RepSor Organization, P.O. No, Job No., eft.
- 3. Work Performed by Florida Power &Light Type Code Symbol Stamp . NA Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Address
- 4. Identification of System: Main Feedwater System #: 747 Quality Group B
- 5. (a) Applicable Construction Code 931.1 1955 Edition, N/A Addenda, N/A Codi l Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, NIA Codi l Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (1) Bonnet Stud, CS ASTM A- N/A N/A N/A SC# 0028046-1 NIA Replacement N 193 B16 1 3/44-8 UN2A x 8 3/4" UTC# 393975 (5) Bonnet Stud, CS ASTM A- NWA NA N/A SC# 0028046-1 . N/A Replacement N 193 B16 1 3/4"-8 UN2A x 8 3/4" UTC# 448140 (5) Nut, Heavy Hex, 1-3/4"-8 N/A N/A NA SC# 0027992-1 NIA Replacement N UN-2B, ASTM A-194 Gr 7 LTC# 449340
.I
- 7. Description of Work:
Disassemble, inspect and reassemble. Replace 6 bonnet studs and 5 nuts
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A W Other N/A Pressure N/A psig Test Temperature NIA deg F 03-008-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp NrA Certificate of Authorization No. NIA -Expiration Date: NIA Signed /5/ Moore c Date Y/71P;!
Owner or Owners Designed Tite CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period 3/712003 to 3/1712003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
I lnsp6fi-sSignature 451 Commissions _ _ _3 _ _
National Board, State, Providence, and Endorsements Date -' "Alla 03-008-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date Sf28/2003 7ar 700 Universe Blvd. JIuno Beach. FL 33408 Sheet I of 2 Addrss Turkey Point Plant Unit 3
- 2. Plant Narm WO#: 3300458101 CR#: 03-0522 9760 SW 344 Street Florida City, FL 33035 Addres kepair Organlzation. P.O. No, Job No_, etc.
- 3. Work Performed by Florida Power &Light Type Code Symbol Staffn WJA Authorization Nurnt NtA 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Address
- 4. Identification of System: Steam Generator Wet Layup _System #: 78 Quality Group i
- 5. (a) Applicable Construction Code 631.1 1955 Edition, _NA Addenda, NIA Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, NA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced.-or Stamp Component Number Board Identification Built Replacement Yes/No flat Bar, CS, ASTM A-36 3/8' WA NWA NIA SC# 0029702-1 NIlA Replacement N UTC# 433598
- 7. Description of Work:
Replace Supports H-5 and H-6 on SGWL system, supports removed for inspection.
8.Tests Conducted: Hydrostatic: N/A Pneumatic NIA Noninal Operating Pressure N/A 0 Other VT-3 Pressure NWA psig Test Temperature NtA deg F 03-009-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
I 0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. NMA Expiration Date: NWA -
Signed _X/ -5)'Ac/O Date /
, 0, 6i\ner or Owneres Designed' Ttie 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period a 3/9/2003 to 5128/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable inany marnner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A_ Commissions Af 3Zfi National Board, State, Proidence, and Endorsements 03-009-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI
- Jner Florida Power & Light Date 3/21/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of ; 2 Address
- 2. Plant Turkey Point Plant Unit 3 WO#: 32003812-01 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization. P.O. No. Job No.. etc.
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp N/A Name Authorization Number NWA 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Addzs
- 4. Identification of System: Intake Cooling Water System #: 19 Quality Group C
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, NIA Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, NIA Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No 1 9 A (14) Cover Studs, Tap End, 1-- N/A NfA NIA SC# 0014188-2 NIA Replacement N 8 UNC-2A x 5-1/2" ASTM A- UTC# 443068 193 Gr B7
- 7. Description of Work:
Open and dean basket strainer, replace the cover studs
' Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 03-010-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Cerfcate of Authorization No. NWA Expiration Date: N/A Signed //5/ si- Date tlt/1/3 Owner or Owner's Designee, 'title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the perio4 2/2712002 to 3121/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising froAr connected with this Inspection.
Commissions jn-c536' L/Inspector's Signature National Board. State, Providence, and Endorsements Date 03-010-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
- owner Florida Power &Light Date 3/24/2003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Piant Hare WO#: 31005379-01 CR#: NJA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization, P.O. No, Job No, etc.
- 3. Work Performed by Florida Power & Lbaht Type Code Symbol Stamp N/A anae Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 NIA Address Expiration Date
- 4. Identification of System: Safety Injection -System #: 62 Quality Group A
- 5. (a) Applicable Construction Code 831.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial INational Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No
-. I t
- t - t 1-~~~~~~~~~~~~~~~~~~~~~~~~~~
Valve, 2- Piston Check SS Edwards N/A N/A SC# 0052484-i NIA Replacement N UTC# 436261 Coupling, 2 6000#, SA-182 Gr N/A N/A N/A SC# 0047748-1 N/A Replacement N 316 Socketweld ends IJTC# 433574 Pipe, 2" Sch 160, SA-3121376 NWA N/A NA SC# 0030938-1 NIA Replacement N F316 SS UTC# 427841
- 7. Description of Woric Replace Valve 3-873C
- 8. Tests Conducted: Hydrostatic N/A Pneumatic N/A Nominal Operating Pressure N/A Other VT-2 Pressure 1470 psig Test Temperature 91 deg F 03-011-3
Sheet 2 of 2 FORM NIS-2 (Back) 9- Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY. I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code.Section X(.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed Date _______
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insaected the components described in this Owners Report during the period or 3/24/2003 to 3124/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal irjury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions Y zs _
Inspector nature National Board, State, Providence, and Endorsements Date 14 -5 o a
03-o 1-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner Florida Power & Light Date 312412003 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of . 2 Address
- 2. Plant Turkey Point Plant Unit 3 Nane WO#: 32003412-01 CR#: NWA 9760 SW 344 Street Florida City, FL 33035 Address Repair OrganiLzton, P.O. No, Job No. etc.
- 3. Work Performed by Florida Power & Llht Type Code Symbol Stamp NIA Name Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: Reactor Coolant _System #: 41 Quality Group A
- 5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, WA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements \ 1989 Edition, NJA Addenda, NWA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp
_ Comronent T Number I Board
_ Identification Built Reolacement
-_ Yes/No-Pressurizer Safety Valve, Crosby NIA N/A SC# 0053561-1 N/A Replaced N 1500# class, 4 NJA Pressurizer Safety Valve, Crosby NWA NIA SC# 0053561-1 NA Replacement 1500# class, 4' UTC# 389248 Studs. Threaded Rod, ASME NtA N/A N/A SC# 0029566-1 N/A Replacement N SA-453. Gr 660 Class B 1-114'- UTC# 447963 8 UN-2A Nuts, Heavy Hex, 1-114'-8 UN- NWA NWA NWA SC# 0027843-1 NWA Replacement N 25, ASME SA-194 Gr 2H UTC# 448737
- 7. Description of Work.
Replace relief valve (SN# H51249-1361) with spare relief valve (SN# H51249-1581)
- Tests Conducted: Hydrostatic: N/A Pneumatic NWA Nominal Operating Pressure X Other Vr-2 Pressure 2280 psig Test Temperature 547 deg F 03-012-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: N/A I I Signed I S I Z %JP-¶iP hAS &,- Date %tI I it; ,t Owner or Owneres Designre, Tide I CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described hI this Owners Report during the period 9/2412002 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners! Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A0/40I ~~or's Signature Commissions _ _ _ _ _ _ _
National Board, State, Providence, aid Endorsements Date 6z .
0 03-12-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
)wner Florida Power &Light Date 3 M/2003' Nare 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addres
- 2. Plant Turkey Point Plant Unit 3
__ -1 Kanae WON: 3200341 1- 01 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Addrns Repair OrgAnzafloh, PFO.No, Job No., etc.
- 3. Work Performec dby Florida Power &Licht Type Code Symbol Stamp NIA anme Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 Addrs Expiration Date NIA
- 4. Identification of System: Reactor Coolant _System #: 41 Quality Group A
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda. N/A Code Case I.
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacen ients 19 89 Edition, N/A Addenda. NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacemen
- ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or , Stamp
_ Comoonent 4.
Number
_ _. Board Identification Built Replacement _ Yes/No
..4-v Pressurizer Safety Valve Crosby NIA NIA N/A WA Replaced N NWA I I
Pressurizer Safety Valve Crosby N/A N/A SC# 0053561-1 NIA Replacement v UTC# 389249 (8) Studs. Threaded Rod, WA WA NWA SC# 0029566-1 N/A Replacement N ASME SA-453, Gr 660, 1-114-- UTOC 447963
- 8. UN-2A (16) Nuts, Heavy Hex, SA-194, NIA NIA NIA SC# 0027843-1 NIA Replacement N Gr 2H, 1-1/4-8 UN-28 UTC# 448737
- 7. Description of Work, Replace Relief Valve (SN# N69877-00-0005) with spare Relief Valve (SN# N6987700-0004)
' Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure X Other VT-2 Pressure 2280 psig Test Temperature 547 deg F 03.013-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp INIA II Certificate of Authorization No. NIA Expiration Date: NfA I
Signed PO .A03,W Date t/ I p/a ,
Owner or Owneres Desidee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 9/24/2002 to 312412003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions AR g _4 Inspe s Signature National Board, State, Providence, and Endorsernents Date C /6 03.0134
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi
- wner Florida Power & Light Date 312412003 warml .. I 700 Universe Blvd. Juno Beach, FL 33408 Sheet I 'of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WO#: 32003410-01 CR#: NJA 9760 SW 344 Street Florida City, FL 33035
Address ___epalianlzjjlon,?~Q. No, Job No. eO.
- 3. Work Performed by Florida Power & Ltght Type Code Symbol Stamp INJA NKma I I Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Address I,
- 4. Identification of System: Reactor Coolant _System #: 41 Quality Group A I I
- 5. (a) Applicable Construction Code B31.1 1955 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements , 19 89 Edition, NIA Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components
- n ASME Repaired, Code Name of Name of Mig Mfg Serial National Other Year Reptaced, or Stamp Component Number I Board Identification Built Replacement Yes/No Pressurizer Safety Valve Crosby N/A NWA N/A N/A Replaced N N/A Pressurizer Safety Valve Crosby N/A N/A SC# 0053561-1 N/A Replacement N UTC:# 389085 AStudslbrieaded Rox _N/A NIA N/A SC# 0029566-1 N/A Replacement N ASME SA-453, Gr 660, 1-1/4"- UTC# 447963.
- 8. UN-2A (16) Nuts. Heavy Hex, 1-1/4"- N/A N/A N/A SC# 0027843-1 N/A Replacement N 8UN-2E, ASME SA-194 Gr 2H UTC# 448737
- 7. Description of Work:
-Replace-Relief-Valvel4N#454-24913 362 ithspare-relief valve4SN 1H51249-1579)
' Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure X Other VT-2 Pressure 2280 psig Test Temperature 547 deg F 03.0144
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I1, CERTIFICATE OF COMPLIANCE
. I
- --Wicartifyltha'the stiterfris -made-in-t-report dre crrectundhis-replacement-cnforms-to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. INIA Expiration Date: NWA I
- Signed _
15*/ SvDate Date 441 # J1631 Owner or Owner's Desigrbe, Title I,
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Inspected the components described In this Owners Report during the period 9124/2002 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners. Report In accordance with the recquirements of ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions A J
-I or's Signature Natioall Board, State, Providence, and Endorsements Date 6 /&/I3 s
03-014-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Sp wriwner Florida Power & Light Oate 3124/2003 700 Urniverse Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Narrie WO#: 29016850-01 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization. P.O. No, Job No., etc
- 3. Work Performed by Florida Power & Light Type Code Symbol Stamp NWA Naie Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date N/A
- 4. Identification of System: Reactor Coolant System #: 441 Ouaflty Group A
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, NIA Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of l Name of Mfg i Mfg Serial National, Other Year Replaced, or Stamp Component I~am of Mfg INumber Boardi Identification Reolacement Yes/No
-- I ~ ~; ~ ~~~~
I1 i
-I
_BuiK 4
- _ *l _
Bonnet Assembly N/A N/A N/A SC# 0223705-1 NIA Replacement N UTC# 442732 (8) Nuts, Heavy Hex, 1-1/4'-8 NIA I N/A N/A SC# 0056776-1 NtA Replacement N UN-2B,_ASME SA-194 GrB6 lUTC# 400719 (8) Studs, ASME SA-453, Gr B ! NIA ! N/A N/A SC# 0056927-1 l N/A Replacement N 660,1-1/4 UTC# 400731 I~~~~~~~~~~~~~~~~~~~~~~~~
- 7. Description of Work:
Delete Bonnet extension and replace bonnet per PCM-98-008
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure X
- Other VT-2 Pressure 2280 psig Test Temperature 547 deg F 03-015-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REOUIRED.
i Bi CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Diate: N/A Signed C= Ag 5e~v./D Date Y/7/v73-Owner or Owner's DesigneE Title 0*
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the slate of Florida and employed bv HSBCT of Hartford. Connecticut, have inspected the components described in tlis Owners Report during the pericd ¶1/3/1999 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concemning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions A4 3 8 National Board, State, Providence, and Endorsements 0
03-015-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI
- wner Florida Power &Light Date 312412003 "are 700 Universe Blvd. Juno Beach. FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant Name WO#: 33004373-01 CR1: 03-0446 9760 SW 344 Street, Florida City, FL 33035 Address Repair " enizatO. P.O. No. Job No, at.
- 3. Work Performed by Florida Power 8 Light Type Code Symbol Stamp N/A Nan*
Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: Safety Injection System #: 62 Ouatity Group A
- 5. (a) Applicable Construction Code B31.1 1955 Edition. NIA Addenda, N/A Code Case pplcabeEdtioofSecion tiizdfrepi (ib) Applicable Edition of Section XIM Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, NtA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg l Mfg Serial INational' Other Year Replaced, or Stamp Component I Number I E~oard i Identification I Built Replacement Yes/No Shim, Flat Bar, A-36 Carbon N/A ; N/A N/A SC# 0206836-3 N/A Replacement N Steel N/A I
- _ _ _ _ _~
.t
~ ~ II I
I I
- r~~ I
- 7. Description of Work:
Add shims to support per CR 03-0446,
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other VT-3 Pressure N/A psig Test Temperature N/A deg F 03-016-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
I I, .
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: NIA Signed S55Ew. Date _
Owner or Owneres Designee, Title I-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.00 - 0 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors end the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 319/2003 to 3124/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Sig nature Commissions 3Z5 I ,/nspetor'sSignature National Board, State, Providence, and Endorsements Date 4/ /4 03 0
03-016-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REP LACEMENTS As Required by the Provisions of the ASME Code Section Xl Oer Florida Power & Light Date 31;2512003 Nama 700 Universe Blvd. Juno Beach, FL 33408 Sheet of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Name WOM: 32011891-01 CR#: NIA 9760 SW 344 Street Florida City, FL 33035 Address RepairOrganization, P.O. No, Job No.,etc.
- 3. Work Performed by Florida Power & Licht Type Code Symbol Stamp NWA Nam ~~~~~~~Authorization Number NWA 9760 SW 344 Street Florida City. FL 33035 Extiration Date WA Address Expiration Date N/A
- 4. Identification of System: Supports and Hangers System #: 105 Ouality Group B
- 5. (a) Applicable Construction Code , 1_3311 1955 Edition, N/A Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, NIA Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp i Component Number Board Identification Built Replacement Yes/No SF Snubber 3-1038 PSA-35 PSA 11934 NWA NWA NA NIA Rpae Replaced N N/A Snubber 3-1038 PSA-35 PSA 42410 N/A [0015324-1 2003 1Replacemnent N 10000448596 Snubber 3-1039 PSA-10 PSA 16241 N/A NIA NIA Replaced N
_ __ __ _ IN /A _ _ _ _ _ _
Snubber 3-1039 PSA-10 PSA 7782 NIA N/A N/A 1 Replacement N NIA i l t i 1~~~~~~~~NI N/A
- 7. Description of Work:
Inspect/Functionally Test/Rebuild snubbers as required. (This NIS-2 is I of 3).
S. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A 0 Other VT-3 Pressure N/A psig Test Temperature NIA deg F 03-017-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NIA Certificate of Authorization No. N/A Expiration Date: N/A Signed IS/ IS )1Sk - Date 6/p/D s Owner or Owner's'Designee, Title 0
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the perio 6)26/2002 to 3/25/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_ _ _ _ _ _ Commissions
__ _ My - Z J&nsaectnr's Sianature National Board, State, Providence, and Endorsements I----------
Date -
03-017-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- ne; Florida Power & Light Date 3/26/1?003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet of 2 Address
- 2. Plant Turkey Point Plant Unit 3 0a4re WOMl 32011891-01 CR#: N/A 9760 SW 344 Street Florida Ciy, FL 33035 Address Repair Organization. PO. No, Job No., etc.
- 3. Work Performed by Fldrida Power &Light _ Type Code Symbol Stamp N/A Narne Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 E t e Address Address
~~~~ ~Expiration Date N/A
- 4. Identification of System: Supports and Hangers System #: 105 Quality Group A
- 5. (a) Applicable Construction Code, __B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utiized for Repairs or Replacements 19 89 Edition, N/A Addenda, N/A Code Case,
- 6. Identification of Components Repaired or Replaced and Replacement Components Repaire, ,ASME 1 Repaired, Code Name of i Name of Mfg I Mfg Serial National, Other Year j Replaced, or Stamp Component ! Number Board Identification Built I Replacement Yes/No w
Snubber 3-1048 PSA-10 PSA 15718 N/A lN/A N/A Replaced N I
N/A Snubber 3-1048 PSA-10 PSA 16238 N/AtI NIA N/ elcmn I N/A Snubber 3-1049 PSA-10 PSA 7782 NIA IN/A N/A Replaced N
_ _ _ ___ INIA Snubber 3-1049 PSA-10 PSA 11461 NIA IN/A N/A I Replacement N NIA NIA I __ _ _ __ _ _ _ _ _
- 7. Description of Work:
Inspect/Functionally Test/Reuild snubbers as required. (This NIS-2 is 2 of 3)
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A 0 Other VT-3 Pressure N/A psig Test Temperature N/A deg F 03-018-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed 5= -Z ,6Z Date 6e7/ r Owner or Owner's Ded!gnee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the perio 612612002 to 3/26/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.
concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions /:e: ' [i 4 cto'sgignture National Board, State, Providence. and Endorsements Date 6**,4-1 9`3 0
03.018-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl
- wrier Florida Power & Light Date 34?6/2003 o- -----. - ..
Warm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 _ of .2 Address
- 2. Plant _ _ Turkey Point Plant Unit 3 Norne WO#: 32011891- 01 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address Repair Orgs nihzaon, P.O. No. Job No, etc.
- 3. Work Performed by Florida Power S Light __ Type Code Symbol Stamp _ NIA Narre NIA 9760 SW 344 Street Florida City, FL 33035 Authorization Number NtA Address Expiration Date
- 4. Identification of System: Supports and Hangers System I:
105 Ouality Group A
- 5. (a) Applicable Construction Code - _ B31.1 19 55 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME I e i Repaired, Code Name of I Name of Mfg Mfg I Serial 'National Other i Year Replaced, or Stamp Component Number i Board Identification I Built I Replacement Yes/No I u I .
Snubber 3-1075 PSA -1/2 PSA 18074 N/A N/A I N/A ! Replaced N
- I N/A Snubber PSA-3-1094 3PSAI I N/A i Snubber 3-1075 PSA-1t2 PSA 18072 N/A 1NIA ' NtA I Replacement N
! IiN/A I i
_- I Snubber 3-1094 PSA- 3 1 PSA 17424 N/A I N/A I N/Ai Replaced N I N/A Snubber 3-1094 PSA- 3 PSA 27092 N/A I N/A I N/A l Replacement N j..
l.. N/A &
A I i I
- 7. Description of Work:
Inspect/Functionally Test /Rebuild snubbers as required. This NIS-2 is 3 of 3.
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A
- Other VT-3 Pressure N/A psig Test Temperature N/A deg F 03-019-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks MECHANICAL CONNECTION. NO WELDING REOUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed ______ _ == /9 Date
_...-io 4/i/"iY Owner or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut. have inspected the components described in this Owners Report during the perio 6/26/2002 to 3/26/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_ ~~ inn~ture______________ _Commissions / 3 eS Ino~oestor'rs Ainnahirr, National Board, State, Providence, and Endorsements Date __ C___ a-_
03-019-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl iwner Florida Power &Light Date 41112003 Kam 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant arne WOK: 33005095-02 CR#: N/A 9760 SW 344 Street Florida City, FL 33035 Address iepair Organizatior PDO.No, job No., tc.
- 3. Work Performed by FIirda Power & Light Type Code Sy nbol Stamp NIA Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 N/A Address Expiration Date
- 4. Identification of System: Containment Spray System #: 68 Quality Group B
- 5. (a) Applicable Construction Code. B31.1 19 55 Edition. N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identificatiorl of Components Repaired or Replaced and Replacement Components ASME Repaired. Code Name of Name of Mfg Mfg Serial National Oter Year Replaced, or Stamp Component Number I Board identification Built Replacement Yes/No Pump, Pullout assembly, Size 4 Goulds NIA N/A SC# 0069617-1 N/A Replacement N x6 UTCA 358104
- 7. Description of Work:
This NIS-2 to document the replacement of pump casing and to perform weld build up and machining of casing.
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure NIA
- s ^h0-M~l
-l
%r 7 we'd Pressure 295 psig Test Temperature 95 deg F 03-020-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp NIA Certificate of Authorization No. NIA Expiration Date: N/A Signed Date _ __ _ _
Owner or Owner's Designee, Title 0
CERTIFICATE OF INSERViCE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have hIsoected the components described I this Owners Report during the period c 3112003 to 4/i12003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
xa4JO59 Commissions 5?g National Board, State, Providence, and Endorsements Insff Signature Date 0
03-020-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 4/112003 Name 700 Universe Blvd. Juno Beach. FL 33408 Sheet 1 of 2 Address Turkey Point Plant Unit 3
- 2. Plant Narme WO#: 33004558-01 CR1#: 03-0452 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization, P.O. No, Job No.. atc.
- 3. Work Perforrned by Firda Power & Light Type Code Symbol Stamp N/A Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: CVCS Charging and Letdown System #: 47 Quality Group A
- 5. (a) Appflcable Construction Code B31.1 19 55 Edition, NWA Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, WIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components I
ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number I Board Identification Built Rerdaacemevt A VacftJ 4 I I (1) pc 6"x 10 plate carbon N/A N/A N/A SC# 0030265-1 N/A Replacement N steel. A-36, 1/2- thick UTC# 443829 (4) pc's 2' x 2 x 1/4" cut to N/A N/A WA SC# 0029598-1 N/A Replacement N length, Angle A-36 carbon steel, UTC# 428831
- 7. Description of Work:
Repair broken support H-4 per CR 03-0452
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NWA Nominal Operating Pressure N/A 0 Other VT-3 Pressure N/A psig Test Temperature NWA deg F 03-021-3
Sheet 2 of 2 FORM NIS-2 JBack)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: N/A Signed /S/ -S Dt Date 6tZ441-a-T 4
Owner or Owner's Designee60ite CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period o 319/2003 to 4/1/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__ __ __ __ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Commissions i 3 National Board, State, Providence, and Endorsements lop ctoes Signature Date 03-021-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS I As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 4/3/2003 arme 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Unit 3 Nare WO#: 31016675-01 CR#: 01-1481 9760 SW 344 Street Florida City, FL 33035 Address Repair Organinzaton, PO. No, Job No0, et.
- 3. Work Performed by Flbdda Power & Light Type Code Symbol Stamp NIA Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date NIA Address
- 4. Identification of System: Intake Cooling Water System #: 1i Quality Group C
- 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda, WA_ Code Case I I (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Edition, . NIA
. .. .. - Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components 9 r 9 1 ASME Repaired. Code Name of Name of Mfg Mfg Serial Nabonal Other Year Replaced, or Stamp Component Number Board I Identification Built Replacement Yes/No Angle Steel, ASTM A-36, 4" x N/A N/A N/A SC# 0043839-1 N/A Replacement N 3' x 3/8' LUTC# 441680 I
- 7. Description of Work:
Rework support to MRA-CR-01-1481-01
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure NWA 0 Other VT-3 Pressure NIA psig Test Temperature N/A deg F 03-022-3
Sheet 2 of 2 FORM NIS-2 (Back)
- 9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WiTH THE FPL WELD CONTROL MANUAL. I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. NIA Expiration Date: MA Signed / S/ & Date 6^/R/c > P Owner or Owneres Designa, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period o 9/1712001 to 41312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions /C Z Ipectores Signature National Board, State, Providence, and Endorsements Date -4 ° 3 0
'03-022-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Oner Florida Power & Light Date 5/211/2003 Name 700 Universe Blvd. Juno Beach. FL 33408 Sheet 1 of 2 Address
. 2. Plant Turkey Point Plant Unit 3 Name WO#: 32022760-01 CR1: N/A 9760 SW 344 Street Florida City, FL 33035 Address rtepair Oranizaltion, P.O. No, Job Now, etc.
- 3. Work Performed by Forida Power & Light Type Code Symbol Stamp N/A Name' Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address
- 4. Identification of System: Component Cooling Water System #: 30 Ouality Group C
- 5. (a) Applicable Construction Code - 531.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Appflcable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (6) Nuts, Heavy Hex, 3/4 NIA N/A N/A SC #0045910-1 N/A Replacement N UNC-2B, ASME SA-194 Gr 7 UTC# 419593 (4) Studs from All thread, 314 - N/A NIA NA SC # 0029493-2 N/A Replacement N 10UNC-2A, ASTMA-193GrB7 irUTC# 449812
- 7. Description of Worki Replace channel head nuts (6) and studs (4)
- 8. Tests Conducted: Hydrostatic: N/A Pneumatic NIA Nominal Operating Pressure N/A 0 Other NIA Pressure N/A psig Test Temperature N/A deg F 03-023-3
Sheet 2 of 2 FORM NIS-2 (Back) 9- Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: MA Signed r
/S-'
S A, r
£C>L- Date 64,>-
Owner or Owners Desiyhee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report during the period c 1213112002 to 512112003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, conceming the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
,, o e Commiss'ions f' 3ZE National Board, State, Proidence, and Endorsements Insp 9w's Signature Date /dA/l3 1
03-023-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS I As Required by the Provisions of the ASME Code Section Xl Florida Power &Light Date 5U2912003 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1 of 2 Address
- 2. Plant Turkey Point Plant Uhit 3 Klem WO: 32015300-01 CR#: NWA 9760 SW 344 Street Florida Cfty, FL 33035 Address Repair Orftn-1 P. No. Job No. ec
- 3. Work Performed by Flkibia Power& Light Type Code Symbol Stamp NIA Authorization Number NIA 9760 SW 344 Street Florida City, FL 33035 W/A Address Expiration Date
- 4. Identification of System: Containment Airlocks I Hatches _System #: 51 Quality Group B
- 5. (a)Applicable Construction Code B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case.
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired. Code
_ Name of Name of Mi Serial Niational Other Year Replaced, or Stamp Camponent Number Board Identification Built Replacement Yes/No Vaive, 2 Gate, 800 Class, SW N/A NWA NWA SC# 0052777-1. NIA Replacement N ends. SA351-CF8M. Pressure UTC# 448720 Seal Pipe. 2 ASME SA,3121376 N/A N/A NfA SC# 0030803-1 N/A Replacement N Type 304, Seamless Sch 10 UTC# 391850 Pipe Cap, 2. 3000 lbs, ASME NIA N/A N/A SC# 0046389-1 N/A Replacement N SA-182 F304 UTC# 447986
- 7. Description of Work.
Perform P-34 Mod with valve 3-40-205 change
- sts Conducted: Hydrostatic: NIA Pneumatic N/A Noninal Operating Pressure X Other VT-2 Pressure 100 psig Test Temperature htsf deg F 03.024-3
Sheet 2 of 2 FORM NIS-2 (Back) 9-Remarks ALL WELDING PERFORMED INACCORDANCE WiTH THE FPL WELD CONTROL MANUAL CODE CASE N-4$6.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date: WA Signed __ Date _________
Owner or Owners Designee, Title e CERTIFICATE OF INSERVICE INSPECTION 1.the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florkda and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report during the period a 911612002 to 5r9/2003 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described i this Owners' Report. Furthermore, neither the Inspector nor his employer shal be liable Inany manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions _ _3 _ _
I ctors Signature Nallonal Board. State. Providence. and Endorsements Date_________
03-024-3
FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power &Ught Date 6/152003 Mane 700 Universe Blvd. Juno Beach, FL 33408 Sheet I of 2 Addness
- 2. Plant Turkey Point Plant Unit 3 Raun WO#: 32000625-01 CR#: N/A 9760 SW 344 Street Florida City. FL 33035 Address Repair Orgaramon, P.O. o. Jeob No. etc.
- 3. Work Performed by Florida Power &Ught Type Code Symbol Stamp NJA Nme Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Address Expiration Date NtA
- 4. Identification of System: Main Feedwater _System #: 74 duality Group B
- 5. (a)Applicable Construction Code 931.1 1955 Edition, NIA Addenda, NWA Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA Addenda, NIA Code Case
- 6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (4) Pipe,2 ASME SA-106 Gr 6 NWA WNA NWA SC# 0030663-1. N/A Replacement N Sch 80 Carbon Steeel UTC# 428095 (2)Elbows. 1-12? 90 deg. N/A WIA NWA SC# 0034037-1 NWA Relacement *N ASME SA-105 Carbon Steel UTC# 444383 3000#.
(1)Valve, 1-11r Gate Carbon N/A NtA NtA SC# 0052751-1 NIA Replaoement N Steel ASTM A-105 Class 1500 UTC# 379986 Sch 80
- 7. Description of Work NIS-2 Isto doccument replacement of valves 3-20-710 and associated piping.
. sts Conducted: Hydrostatic: N/A Pneumatic N/A Nominal Operating Pressure N/A Other VT-2 Pressure 1543 psig Test Temperature 101 deg F 03.025-3
Sheet 2 of 2 FORM NIS-2 (Back)
I 9- Remarks ALL WELDING PERFORMED IN ACCORDANCE WiTH THE FPL WELD CONTROL MANUAL.
CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section )X.
Type Code Symbol Stamp N/A Certificate of Authorkiztion No. N/A -Expiration Date: NMA Signed Date 4C/4Z Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut. have Insoected the components described In this Owners Report during the period o 3/412002 to 615/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described Inthis Owners' Report In accordance with the requirements of ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.
commissions 3Z e Ispectors Signature National Board, State, Providence, and Endorsements Date 03-025-3