L-2003-162, Inservice Inspection Report: Submittal of the NIS-2 Forms Omitted from L-2003-162 Submittal

From kanterella
(Redirected from L-2003-162)
Jump to navigation Jump to search
Inservice Inspection Report: Submittal of the NIS-2 Forms Omitted from L-2003-162 Submittal
ML032180035
Person / Time
Site: Turkey Point 
(DPR-031)
Issue date: 07/22/2003
From: Jones T
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2003-162, L-2003-192
Download: ML032180035 (128)


Text

FPL L-2003-192 10 CFR 50.55a U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Re:

Turkey Point Unit 3 Docket No. 50-250 Inservice Inspection Report: Submittal of the NIS-2 Forms Omitted from L-2003-162 Submittal Florida Power and Light Company (FPL) submitted the Inservice Inspection Report for Turkey Point Unit 3 under L-2003-162 dated June 26, 2003. It was found that the submittal inadvertently omitted the inclusion of the NIS-2 Forms.

Form NIS-2, Owner's Report for Repairs and Replacement, is submitted as part of the Inservice Inspection Report in accordance with the provisions of the ASME Code,Section XI. The Unit 3 NIS-2 Forms were listed as an attachment to the Inservice Inspection Report, L-2003-162, however they were not attached. The purpose of this letter is to provide the omitted NIS-2 Forms for Turkey Point Unit 3, reporting the repairs or replacements performed prior to and during the Spring 2003 refueling outage, between the dates of October 28,2001 and March 28, 2003.

Should there be any questions, please contact Walter Parker at 305-246-6632.

Sincerely,

/aTh1 B

Terry 0. Jones Vice President Turkey Point Plant SM Attachments NRC Regulatory Issue Summary 2001-05 waived the requirements that multiple copies of documents be submitted to the NRC ADq7 an FPL Group company

NIS-2 Reports

Abstract The attached NIS-2 reports detail the repairlreplacement of Class 1, 2 and 3 piping and components for Florida Power and Light Company, Turkey Point Unit 3. These repairs or replacements were performed prior to and during the Spring 2003 refueling outage, between the dates of October 28, 2001 and March 28, 2003.

Piping and components were inspected/tested in accordance with Section Xl of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel code "Rules for Inservice Inspection of Nuclear Power Components, "1989 Edition, No Addenda.

NIS-2 LOG 02-002-3 5/7/2002 5/16/2002 02-03-3 5/16/2002 12/11/2002 02-004-3 3/18/2003 6/4/2003 02-05-3 5/28/2002 12/11/2002 02-006-3 3/23/2003 6/4/2003 02-007-3 3/23/003 6/4/2003 02-008-3 3/23/2003 6/4/2003 02-009-3 7/17/2002 9/11/2002 02-010-3 8/19/2002 9/12/2002 02-011-3 11/5/2002 1/23/2003 02-012-3 11/4/2002 11 //2002 02-013-3 11/4/2002 11/7/2002 02-014-3 11/4/2002 11/7/2002 02-015-3 11/5/2002 6/4/2003 02-016-3 3/23/2003 6/5/2003 02-017-3 11/12/2002 1/23/2003 02-018-3 3/23/2003 6/4/2003 02-019-3 3/23/2003 6/4/2003 02-020-3 12/212002 1/9/2003 02-021-3 3/23/2003 6/4/2003 02-022-3 3/23/2003 6/4/2003 02-023-3 12/9/2002 12112/2002 02-024-3 12/23/2002 1/9/2003 02-025-3 12/26/2002 1/9/2003 02-026-3 12/27/2002 1/9/2003 02-027-3 12/27/2002 1/9/2003

NIS-2 LOG (cont) 02-028-3 3/23/2003 6/412003 02-029-3 12/27/2002 1/9/2003 02-030-3 12/27/2002 1/9/2003 02-031-3 12/30/2002 1/912003 02-032-3 12/30/2002 1/9/2003 02-033-3 12130/2002 1/912003 02-034-3 12/30/2002 6/42003 02-035-3 12/3012002 1/9/2003 02-036-3 12/3012002 1/9/2003 02-037-3 1213012002 6/52003 03-001-3 1/7/2003 1/912003 03-002-3 1f/12003 1/912003 03-003-3 1/8/2003 1/9/2003 034004-3 1/912003 1/15/2003 03-005-3 3/16/2003 4/16/2003 03-006-3 3/17/2003 614/2003 03-007-3 3/1712003 6/412003 03-008-3 3/17/2003 6/4/2003 03-009-3

  • 5/28/2003 6/4/2003 03-010-3 3/2112003 4/16/2003 03-011-3 3124/2003 6/512003 03-012-3 3/24/2003 6/412003 03-013-3 3/2412003 6/42003 03-014-3 312412003 6/4/2003 03-015-3 3/24/2003 6/4/2003 03-016-3 3/2412003 4/16/2003 03-017-3 3125/2003 6/4/2003 03-018-3 3/26/2003 6/4/2003

NIS-2 LOG (cont.)

Report NiXo.C' ;,

Report Date ANTI Certiat 03-019-3 3/26/2003 6/4/2003 03-020-3

  • 4/1/2003 6/5/2003 03-021-3
  • 411/2003 6/4/2003 03-022-3
  • 4/3/2003 6/4/2003 03-023-3
  • 5/21/2003 61412003 03-024-3
  • 6/5/2003 6/11/2003 03-025-3
  • 61/52003 6/11/2003
  • Work was performed prior to 3/28/2003
0.

Owner

2. Plant
3. Work Performed FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 5

Name 700 Universe Bivd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unk 17r20O2 of 2

3 01 CR#:

NA I by


I _

Name 9760 SW 344 Street Florida Ciy, FL 33035 WON: 32003112 Address Florida Power & Libht Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Cornponent Cooing Water

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XJ Utilized for Repairs or Replacemen
6. identification of Components Repaired or Replaced and Replacement C Repair Organization, P.O. No, Job N4%.

etc.

Type Code Symbol Starp N/A Authorlzation Number N/A Eqiration Date NIA

_System C:

30 Quality Group C

1955 Edition, N/A Addenda.

N/A CodeCase

.1 8

.o n

N.

Is IO 89 Edltion,... N/A

Addencla, N/A Code Case ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement YeslNo 18 Nuts. Heavy Hex, ASTM A-NA NA NA SC 002737 1 UNK Replacement N

194, GR 7, 3/4-I UNC-2B UTC 437942_

16 Studs ASME SA193. GrB7.

NA NA NA SC 0029493 1 UNK Replacement N

3/4"-IOUNC-2A UTC 437941 NA NA NA

7. Description of Woric Replace 18 Nuts (9 Inlet door & 9 outlet door) and 16 Studs (6 Inlet door 10 outlet door) on 3E207C.
8. Tests Conducted:

Hydrostatic:

NA I

Other NA Pneumatic NA Pressure NA psig Nomlnal Operating Pressure NA Test Temperature NA deg F 02.002-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Rerarks BOLTED CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of Oe ASME Code, Section Xl.

Type Code Symbol Stamp WA Certificate of Aulthorization No.

NJA

_ Expiration Date:

WA Signed2/

o O DeG

cjc,

~~~~~Owner or Owner's Desi

~zJ*

J% 4-Date 5 - 'K -o.0 gnee, Tilte JI 0

CERTIFICATE OF INSERVICE INSPECTION I, tie undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factoy Mutual Insurance Company of Johnston, Rhode Island. have Inspected the components described in tis Owners Report during the period of 1/15/2002 to 57/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners! Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report Furthermore, neither the Inspector nor his employer shall be lIable In any manner for any personal Injury or property damage or a loss or any kind arising fmn or connected with this Inspection.

/~ (7Comsslons

\\v71qr Fe-CJfspector's Signature S-//

(C/a z-National Board, State, Providence. and Endorsernens Date 0

02-002-3

.wner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required 6y the Provisions of the ASME Code Sectfon Xl Florida Power & Light Date 5/

Namne 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 16/2002 of 2

3 D01 CR#:

NA I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 32007612-Address Florida Power & Lght Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Component Cooling Water

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacemer repair Orvanizaton P.O. No. Job No.,e.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NWA System #:

30 Quality Group C

1955 Edition, NIA

Addenda, N/A Code Case nents 19 89 EditIon, NIA
Addenda, N/A Code Case dt Components Name of Component Name of Mfg NWA Mfg Serial INational I Number I Board I Other Identification Year Built
Repaired, Replaced, or Replacement

_I,.

ASME Code Stamp Yes/No

_ 4 I

4 (1) Bolt-34-10 UNC-2A, ASME SA 193 Gr B7 NIA NIA SC# 0029493 1 UTC# 437941 NMA Replacement N

(2) Nuts Heavy Hex 3/4w-NIA N/A N/A SC# 0027837 1 N/A Replacement N

I0UNC,213 ANSIIASME ASTM-UTC9 431033 A-194 Gr 7 NA NA NA

7. Description of Work:

Replace one stud and 2 nuts on Inlet door of 3 B CCW Hx.

j.

Tests Conducted:

Hydrostatic:

NA Other NA Pneumatic NA Pressure NA psig Nominal Operating Pressure NA Test Temperature NA deg F 02-003-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED.

0 I

CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rufes of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

Clnndn N/A Expiration Date:

NIA Date l

Z l 2 Keys *w y

p Omer orOwner's Designee, TiUe CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 4/1192002 to 5/1612002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section XJ.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions P38WY-2'F X' JC !57 National Board, State, Providerse, and Endorsements COnspector's Signature Date 2

, //,

a Z 0

02-003-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Owner 700

2. Plant 976C
3. Work Performed by 976C
4. Identification of System:

Florida Power & Light Name Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 3/118/2003 1

of 2

3 WO#: 31002665-01 CR#:

NA Unit Naie I SW 344 Street Florida City, FL 33035 Address Florida Power & Light Name I SW 344 Street Florida City, FL 33035 Address Auxiliary Feedwater Repair OrganzaSton. P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Appflcable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A _Addenda, N/A Code Case 1989 Edition, _N/A
Addenda, NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components
  • I.

Mfg Serial Number National Board Name of Component Name of Mfg Other Identification Year Built

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Pump, model 2-112, CNTAM-4 Ingersoll-Rand 0601001 NA SC 0239955-1 tUTC 437669 WA Replacement N

Pump, model 2-112, CNTAM-4 Ingersoll-0368-88 NA NA N/A Replaced h

Rand NA NA NA NA

7. Description of Work Replace *B AFW Pump with new pump.

Tests Conducted:

Hydrostatic:

N/A Other VT-2 Pneumatic NIA Pressure 1380 psig Nominal Operating Pressure X

Test Temperature 82.9 deg F 02-004-3

Sheet 2 of 2 FORM NIS-2 (Back)

I

9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED.

I..

CERTIFICATE OF COMPLIANCE I

We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

WUA -

Signe t4 e

151 Date 441/ a TS'03 Owner or Owner's Delsignee, Title I

0*

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Inspected the components described In this Owners Report during the pericot 6/8/2001 to 3/1812003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code. Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied.

concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

lxl)11s igntue~

Commissions

_ 3_

National Board, State, Providence, and Endorsements I

trt~ecters Signsture I

/

Date 0

02-004-3

Wwrier

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 54 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 28/2002 I

of 2

3 05 CR#:

NA I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 31002665-Address Florida Power & Light 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced snd Replacement Components Name of Name of Mfg Mrg Serial National Component Number Board Ide Repair Organkizaton, P.O. No, Job No.,

tc.

Type Code Symbol Stamp NA Authorization Number NJA Expiration Date NIA

'5 Quality Group C

19 55 Edition, N/A

Addenda, NJA Code Case 19 89 Edition, N/A
Addenda, N-416-1 CodeCase Other lentification Year Built
Repaired, Replaced., or Replacement ASME Code Stamp Yes/No (2) 2' Gate Valves, A-105 UNK NA NA SC 0052765 1 UTC 435588 & 435589 UNK Replacement N

2TX2'XlI Reducing Tee, ASME UNK NA NA SC 0034321 1 UNK Replacement N

SA-105, 3000#, socket weld UTC 443320 2T Pipe, ASME SA-106 Gr B UNK NA NA SC 0030688-1 UNK Replacement N

Sch 80 UTC 416327 2* Elbow ASME SA-10S, 3000#

UNK NA NA SC 0034040 1 UNK Replacement N

Socket weld UTC 430452 NA

7. Description of Work:

Add 2 Isolation valves to the 3 B AFW recirculation line Including piping, tee end elbow.

8. Tests Conducted:

Hydrostatic:

NA Other VT-2 Pneumatic NA Pressure 105 psig Nominal Operating Pressure X

Test Temperature 81.8 deg F 02-005-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

I CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed

£o OwnEr's Date s 0gr A'

Owne-r or Ownier's Designed', Title CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Inspected the components described In this Owners Report dunrf the period of 618/2001 to 5/28/2002 and state that to the best of my krnowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code. Section X1.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

knaw.4-,

Commissions tJB72Y1 pL-?2S National Board, State, Providence, and Endorsements' 6/

Inspector's Signature Date J

-t

{

° 02-005-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

  • wner Florida Power & Light Date Noam 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 3/2312003 1

of 2

3 WO#:

31009255 CR#:

NA Unit

2. Plant Kame 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power & Light Name 9760 SW 344 Street Florida City, FL 33035 Address Repair Organzution, P.O. No. Job No.. etc.

Type Code Symbol Stamp

, N/A Authorization Number NIA Expiration Date NIA System #:

19 Quality Group C

4. Identification of System:

Intake Cooling Water

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, NIA
Addenda, 1989 Edition, NIA
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacerhent ASME Code Stamp Yes/No

+

-4.

4 4

4 N/A Pump Johnston Pump Co.

NIA SC 0011053-1 IST #7 I N/A Replacement N

7. Description of Work:

Replace Pump, Check Valve, expansion joint and some degraded bolting. This NIS-2 documents pump replacement. Pump number IST#7 replaced IST#2. Other replacement documented on WO# 32008464

8.

Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure 18 Test Temperature 84.6 deg F 02-006-3 Other VT-2 Pressure 18 psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NWA Certificate of Authorization No.

N/A Expiration Date:

N/A Sign

_5i=

=e l.5_

Date _________

Owner or Owner's Desigdnee, Title 0

CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period 411812001 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

  • 4lal Commissions

/C 3251 National Board. State. Providence. and Endorsements Ins&fors Signature 6 //0 Date 02-006-3

Owner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power & Light Date 3/

Noae 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit

?3/2003 of 2

3 4

CRO:

N/A I by Ne

?760 SW 344 Street Florida City. FL 33035 WO#:

3200846 Address Florida Power & Light

_ae 9760 SW 344 Street Florida City. FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1I

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components e&par gOrgenizalfn. P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date NIA 9

Quality Group C

1955 Edition,

_N/A

Addenda, N/A Code Case 1969 Edition.

NWA

Addenda, NMA Code Case ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Check Valve Atwood and 2-50286-A N/A SC 0052545-1 N/A Replacement N

Morril UTC 436675 20 Studs, ASTM A193 87, 1-N/A NWA N/A SC 0044563-1 N/A Replacement N

1IB-8 un-2A x 19 long UTC 437106 40 Nuts, ASTM A194, 1-1"4 N/A NWA N/A SC 0044563-1 NWA Replacement N

UN-2A UTC 437106 11 Studs from Alfthread ASTM NA NWA NA SC 0029507-1 NIA Replacement N

A-193 Gr B7 1-1/4'-8UN-2A UC 442260 11 Nuts ASTM A-194 Gr 7, 1-N/A WA N/A SC 0027861-1 NIA Replacement N

1/4'-SUN-2B UTC 437162

7. Description of Work:

Replaced ICW Pump, Check Valve, Expansion joint and some bolting. Pump documented under WO# 31009255. Expansion Joint documented under WO# 32008465-01. Note: Bolting (Stock Code # 44563-1 Includes one stud (A193 Gr 37) with 2 Nuts (ASTM A-194 Gr7))

  • 8. Tests Conducted:

Hydrostatic:

NIA Other VT-2 Pneumatic N/A Pressure 18 psig Nominal Operating Pressure 20 Test Temperature 84.8 deg F 02-007-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed ISI Date II/ I_

Owner or O4ner's Designee, Title 0

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the perioq 511/2002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Naftonl Board, State. Providence, and Endorsements lStor's Signature 6 /

_/_3 Date 0

02-007-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Olwner Florida Power & Light Date Na__ e 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Sheet 312312003 1

of 12 3

WO#:

32008465 CR#:

N/A

2. Plant Unit
3. Work Performed byI Florida Power & Light Nam 9760 SW 344 Street Florida City, FL 33035 Repair OrganinUon, PO. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A Address

4. Identification of System:

Intake Cooling Water System #:

19 Ouslity Group C

5. (a) Applicable Construction Code 631.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 1989 Edition, N/A
Addenda, N/A Code Case N/A
Addenda, WA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components I.

T-.I.

.Y.

Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No mi r-1 1-Expansion Joint Gartock NIA NIA SC 0014195-1 UTC 443801 NIA Replacement N

i

7. Description of Work:

Replace 3B ICW Pump, Check Valve, Expansion Joint and bolting. Pump documented under WO#31009255, Check Valve and Bolting documented under WO 32008464.

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure 20 Other Vr-2 Pressure 18 psig Test Temperature 84.8 deg F 024008-3

Sheet 2 of 2 FORM NIS-2 (Back) 9-Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed s C),

Owner or Owner's Designee, TWe Date Y/ Io,,

CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described in this Owners Report during the period 5/112002 to 3/2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code. Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or inplied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions 3 Z8 National Board. State, Providence. and Endorsements InVhlor's Signature Date 02-008-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

  • wner 700l
2. Plant 9760
3. Work Performed by -

9760

4. Identification of System:

Florida Power & Light Name Jniverse Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Narne SW 344 Street Florida City, FL 33035 Address Florida Power & Light Date Sheet Unit 7117/2002 1

of 2

3 WO#:

32011929 CR#:

NIA Narm SW 344 Street Florida City, FL 33035 Address Component Cooling Water Repair OrgsnisaUoN, P.O. No, Job No, etc.

Type Code Symbol Stamp NIA Authorization Number NJA Expiration Date NIA System #:

30 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, NIA
Addenda, N/A Code Case 19 89 Edition, N/A
Addenda, NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial National Number Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No 1*

1 1-4 (2) CapScrew, Heavy Hex, Asme SA-193, Gr B7. 3/4"-10 UNC-2A x 3-3/4' NtA NWA N/A SC 0027122-1 UTC 424688 N/A Replacement N

7. Description of Work:

CLEAN DIRTY TUBES

8. Tests Conducted:

Hydrostatic:

N/A O

Other NIA Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-009-3

Sheet 2 of 2 FORM NIS-2 (Bsack)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 I

CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed A-" -

Date C )

Owner Own s Desig e, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Inspected the components described In this Owners Report during the period of 6127/2002 to 7/17/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions A/6 71KCC fZ8

(

Inspector's Signature Date 9-W-paM1 National Board, State, Providence, and Endorsements 0

02-009-3

  • wrier
2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Ught Date 8119/2002 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

of Address Turkey Point Plant Unit 0

2 CR#:

S I by C

Namre 1760 SW 344 Street. Florida City, FL 33035 WO#:

31012691 Address Florida Power & Licht Name 1760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7!

5. (a) Applicable Construction Code 931.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organizaton, P.O. No. Job No. eta.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 5

Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case 19 89 Edition, NIA
Addenda, N416-1 Code Case Name of Component Name of Mfg N/A Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No I.-

1 4*

I Pipe 2" Sch 80 SA-106 Gr B NIA N/A SC 0030668-1 UTC 443303 N/A Replacement N

(3) Elbows, 2' 3000 Ibs SA-1 05, N/A N/A N/A SC 0034040-1 N/A Replacement N

Socketweld UTC 442153

7. Description of Work:

Reroute Piping per CRN M-10330

8. Tests Conducted:

Hydrostatic:

N/A Other VT-2 Pneumatic N/A Pressure 780 psig Nominal Operating Pressure 780 Test Temperature 366 deg F 02-010-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-41,6.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

NIA Signed

\\

(

t MA/

V l

0J (11wn1er)Owner's IgneeT 0

Date T/l

/

0 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 7/16/2001 to 8/19/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

go/ Inspector's Signature Commissions A1 2 Ys14-AZ71' X

National Board, State, Providence, and Endorsements

,-Z-w-,

Date 02-010-3

Owner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power& Light Date 11,
Name, 700 Universe Blvd. Juno Beach, FL 33408 Sheet Addmss Turkev Point Plant Unit 1t5/2002 of 2

0 DI CR#:

N/A I by Na.e

?760 SW 344 Street Florida City, FL 33035 WO#: 320151124

__Address Florida Power & Light I9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repafr Organizsfaon, P.O. No, Job No. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NtA

'5 Quality Group C

19 55 Edition, N)A

Addenda, NA Code Case 1989 Edition, N/A _Addenda, N416-1 Code Case i

I Yt

¶~~~~~~~~~~

Mfg Serial Number National Board Name of Component Name of Mfg Other Identification Year Built

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Pipe. Carbon Steel, SA-106 Gr B. Sch 80, 4' die NtA N/A NtA SC#0030635-1 UTC# 409477 NtA Replacement T

N Pipe, Carbon Steel, SA-106 Gr N/A N/A NIA SC#0030635-1 N/A Replacement N

B, Sch 80, 4" dia UTC# 416324 (1) Elbow, Carbon Steel, 45 NWA N/A N/A SC#0033895-1 N/A Replacement N

deg. ASME SA-234 WPB SchUC#451 80, 4 dia UTC# 445941 (2) Elbow, Carbon Steel, 90 N/A N/A N/A SC#0033902-1 N/A Replacement N

deg. ASME SA-234 WPB, Sch UTC# 440977

60. 4"dia (1) Tee, Carbon Steel, SA-234 N/A NWA N/A SC#0033932 N/A Replacement N

WPB, Sch 80,4" dia UTC# 445940

7. Description of Work:

Replace degraded piping section of Aux. Feed Steam Supply in Aux Feed Cage area. Ref. NIS-2# 02-015-3 for Support Bolting Replacement.

OTests Conducted:

Hydrostatic:

780 Other VT-2 Pneumatic N/A Pressure 780 psig Nominal Operating Pressure 780 Test Temperature 416 deg F 02-011-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

I CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

NIA



a5f:--

5,Ov Date

/

142:

03 Signed L

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Insoected the components described In this Owners Report during the period of e/29/2002 to 11/512002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

- &pectors Signature Date

/- Z3 -23 Commissions j1(37 Y ( f Ft-3'28 National Board, State. Providence, and Endorsements 0

02-011-3

.Obner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power & Light Date 11 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit

/412002 of 2

3 3

CR#:

N/A d by Naie 9760 SW 344 Street Florida City, FL 33035 WO#:

3102440W Address

, Florida Power & Light arne 9760 SW 344 Street Florida City. FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organizationr P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expration Date N/A 7

Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case 1989 Edition.

N/A Addenda.

N/A Code Case ASME

Repaired, Code Name Of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification BuIlt Replacement Yes/No Gland, Stuffing Nut UnIon Pump N/A N/A SC# 0070930-1 N/A Replacement N

UTC# 401315

7. Description of Work:

Repack pump,

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-012-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules df the ASME Code, Section Xl.

Type Code Symbol Stamp yWA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed r

&X) t 4 7 JO ~rO r's Desi e, Title (

Date L/

$s a -

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 1/1112002 to 11/4/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

//Go Commissions 1I&7 4f RC3z 1'

National Board. State, Providence. and Endorsements Inspeclortnature

//_7 00 S

Date 0

02-012-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner 700

2. Plant 9760
3. Work Performed by -

9760

4. Identification of System:

Florida Power & Light Name Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/412002 1

of 2

3 WO#:

32004054 CR#:

NIA Unit Name I SW 344 Street Florida City, FL 33035 Address florida Power & Lliht Nam o SW 344 Street Florida City, FL 33035 Repair Organizatio4, P.O. No, Job No. etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date NIA

_System #:

19 Ouality Group C

Address Intake Cooling Water

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components I

I

  • I*

Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Suil

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No r

(10) Studs, Tap End. Cover 1 -

8 UNC-2A x 5-1/2 Lg, ASTM A-193 87 N/A N/A N/A SC#0014188-2 UTC# 394431 NIA Replacement N

l (4) Studs, Tap End, Cover 1-8 N/A N/A NIA SC#00141882 NIA Replacement N

UNC-2A x 5-1/2 Lg. ASTM A-UTC# 443068 1935B7 (14) Nuts, Heavy Hex, ASME N/A N/A N/A SC#0027840-1 N/A Replacement N

SA-194 Gr 2H, 1"-8 UNC-28 UTC# 442400

7. Description of Work:

Remove one nut at a time and replace IN, Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure NIA Test Temperature NIA deg F 02-013-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPIUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NWA Expiration Date:

NIA LjS e >~AA&gO (Za,M te Ii djo-,

I ia dzn -

v Trid-

. I Signed

<C>

vWn" >Evl 61 C. v"aolw raw I It LI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have inspected the components described in this Owners Report during the period of 711912002 to 11/412002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4217;,,

Commissions 06J7'i4 f ZS3Z8

)

National Board, State, Providence, and Endorsemerns Inspector's Sia le Date 02-013-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

  • Owher Florida Power & Ught Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street, Florida City, FL 33035 Sheet 111412002 1

of 2

3 WO#:

32015737 CR#:

N/A Unit

2. Plant Address Florida Power & Liaht
3. Work Performed by -

9760

4. Identification of System:

Name SW 344 Street Florida City, FL 33035 Repair Organization, PD. No. Job No, ec Type Code Symbol Stamp NIA Authorization Number.

N/A Expiration Date NIA Address Component Cooling Water System #:

30 Ouality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Repaired.

Replaced, or Replacement ASME Code Stamp Yes/No m

I 4-4- -

4--

(1) Nut Heavy Hex. ASTM A-194 Gr 7. 3/4M-l0-UNC-2B N/A N/A N/A SC# 0027837-1 UTC# 437942 N/A Replacement N

7. Description of Work:

Clean Dirty Tubes. Replace missing Channel head nut

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure NIA psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-014-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A-Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date t

e

/,,

OworO er's Desigr, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of 8/30/2002 to 1114/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions t (i 7r. r )

3 z8 a

National Board, State, Providence, and Endorsements Inspector! Sigature Date 02-014-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

.wn&r Florida Power & Light Nare 700 Universe Blvd. Juno Beach, FL 33408 Address Date Sheet 11/5/2002 '

I of 2

0 WOa: 32015112-01 CR#:

N/A Repair Organinzaon, P.O. No. Job Oa, etc.

2. Plant Turkey Point Plant Narne 9760 SW 344 Street Florida City, FL 33035 Address Unit
3. Work Performed by Florida Power & Light Nare Type Code Symbol Stamp Authorization Number Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 Address NfA NIA
4. Identification of System:

Auxiliary Feedwater System :

75 Quality Group C

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda,

_ N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A

Addenda, NWA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mtg Serial Number National Board Other Identification Year Built Repaired.

Replaced, or Replacement

, ASME Code Stamp

'YeslNo t

r-,

I (4) Cap Screws, Hex Head, Steel Grade 5, Zinc Plated 112-13x3 N/A N/A N/A SC#0027296 UTC# 377966 NIA Replacement N

(8) Nut, Heavy Hex, ASTM A NIA N/A N/A SC#0027922 N/A Replacement N

563 Gr B CS UTC#416380

7. Description of Work.

Replace degraded Pipe, Note: This NIS-2 for support 80117-R-332-03 and 80117-R-332-04 Bolting material replacement.

'8.

Tests Conducted:

Hydrostatic:

N/A A

Pneumatic NIA Nominal Operating Pressure N/A Test Temperature N

deg F iuther N~

Pressure N

psig 02-015-3

Sheet 2 of 2 FORM NIS-24Badk)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

Signed 4--

Owne N/A Expiration Doate:

NIA Date IMID7 13I E

er or Owner's Designee>Witle CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 8/27/2002 to 11/512002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

6 X

v Commissions X

3Z ?

ns ctor's Signature National Board, State, Providence, and Endorserments Date 11/n 0

02-015-3

Owner

2. Plant
3. Work Performet FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Sedion XI Florida Power & Light Date 3rd Naime 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit

!3/2003 of 2

3 I

CR#:

NWA I

I by i

Nam 1760 SW 344 Street, Florida City, FL 33035 WO#:

31021701 Adress Florida Power & Light No"e 9760 SW 344 Street Florida City, FL 33035 ddress

4. Identification of System:

Intake Cooling Water

-System I

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. identification of Components Repaired or Replaced and Replacement Components Repair Organizaton, P.O. No. Job No, aetc Type Code Symbol Stamp N/A Authorization Number WA Expiration Date NWA 9

Quality Group C

19 55 Edition, N/A

Addenda, NWA Code Case 1989 Edition, NIA
Addenda, NIA Code Case ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp l Component Number Board Identification Built Replacement Yes/No (1) Valve 1-112' Gate Bronze NIA NIA NWA SC# 0052741 NWA Replacement N

ASTM 661, Class 200. A00ps!

UTC 446134 WOG FNPT ends

7. Description of Work:

Replace Valve

8. Tests Conducted:

Hydrostatic:

NIA Other VT-2 Pneumatic NIA Pressure 5

psig Nominal Operating Pressure Test Temperature 88 5

deg F 02-016-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA N Expiration Date:

N/A Signed Owner or Ownees Desilee, Title Date Ž1 I

.A J 0,3 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have inspected the components described in this Owners Report during the period 511/2002 to 3/2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

liln X/

"'

Commissions _

5 3 R

Natinal Board. State, Providence, and Endorsements s

Inspector Sinature Date 02-016-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

  • owner Florida Power & Light Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Sheet 11112/2002-1 of 2

3 WO#; 32018187-03 CR#:

N/A Repair Organizatio. PO. No, Job No., etc.

2. Plant Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Unit
3. Work Performed by Florida Power & Llght Name Type Code Symbol Stamp Authorization Number Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 NIA N/A Address
4. Identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A
Addenda, 1989 Edition, N/A
Addenda, N/A Code Case NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identfication Year Built
Repaired, Replaced, or Replacement
  • Yes/No 1

I (8) Nuts, Heavy Hex. ASME SA-194 Gr 2H Carbon Steel, 1-13-UNC-2B N/A NIA NIA SC# 0027832-1 UTC# 435416 N/A Replacement N

(2) Rod, Threaded ASME SA-N/A N/A N/A SC# 0029486-1 NA Replacement N

193 Gr B7 1/2-13 UNC-2Ax 6' UTC# 435452 long

7. Description of Work:

Remove Clamp for Inspection, replace damp bolting on support H-334-01

'0 Tests Conducted:

Hydrostatic:

N/A Other NMA Pneumatic NWA Nominal Operating Pressure N/A Test Temperature N/A deg F 02-017-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code.Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed OS

'6 S

N Date l

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston. Rhode Island. have Insoected the components described In this Owners Report during the period of 10123I200, to 11/1212002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Y1 ad A$3 78 Inspector's Signature National BSard. State, Providence. and Endorsements Date

/-3 02-017-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Owner Florida Power & Light Narm 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Nome 9760 SW 344 Street,Florida City, FL 33035 Date Sheet 3/23/2003' I

of 2

3 WO#: 32012859-01 CR#:

NIA Repor OrganIzatlon, P.O. No. Jbb No, etc.

2. Plant Unit Address
3. Work Performed by Florida Power & Light Name Type Code Symbol Stamp Authorization Number Expiration Date NJA

, 9760 SW 344 Street Florida City. FL 33035 Address NIA NtA

4. Identification of System:

Residual Heat Removal

_System #:

50 Ouality Group B

5. (a) Applicable Construction Code B31.1 19 55 Edition, N/AAddenda, 1989 Edition, N/A
Addenda, NIA Code Case N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Narne of Mfg Mfg Serial National Other Year Replaced, or

,Stamp b

Component Number Board Identification Bullt Replacement Yes/No Plate, ASTM A240 type 316 N/A N/A N/A SC# 0030303-1 N/A Replacement N

S.S. # 3/8 UTC# 443118 Rod, Threaded, CS ASME SA-N/A N/A NIA SC# 0029481-1 NIA Replacement I

193 Br B7, 3/8 -24 UNF-2A x 4L UTC# 410463 Nuts (3), 300 Series S.S. Hex, N/A N/A NIA SC# 0029050-2 NIA Replacement N

Machine Screw, Size 318"-24 LITC# 372969 UNF-2B Washer, Flat (2) 316 S.S. 3/8" NtA N/A N/A SC# 0029050-3 N/A Replacement N

ID x 7/8 OD UTC# N/A

7. Description of Work.

Install shim modification-to pump base per CR-02-0845 and MSP#02-058

8. Tests Conducted:

Hydrostatic:

0*

NIA Pneumatic NIA Nominal Operating Pressure NIA Test Temperature N/A deg F 02-018-3 Other VT-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Rernarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp I NIA Certificate of Authorization No.

Signed--

N/A Expiration Date:

N/A '

I ISI Date y I i apJ JWrn`3r or Owner's Desigilee, Title 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period 7/24/2002 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions

/c 3'8

/;n ector's Signature National Board, State. Providence, and Endorsements Date _

02-018-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

  • Owher
2. Plant Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 3/23/2003 1

of 2

0 WO#: 32018187-01 CR#:

N(A Repair Organization, P.O. No, Job No, etr.

Turkey Point Plant Unit Name 9760 SW 344 Street, Florida City, FL 33035 Address

3. Work Performed by Florida Power & Light Wame Type Code Symbol Stamp N/A Authorization Number IWA Expiration Date NIA 9760 SW 344 Street Florida City, FL 33035 Address
4. Identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

a.

5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A
Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition.

N/A

Addenda, N416-1 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Comnonent Name of Mfg Mfg Serial Number National Board Other Identification Year Buit
Repaired, Replaced, or ReDoacement ASME Code Stamp Yes/No

.1.

4

-+

-+

4.

4.

(2) Elbow, Carbon Steel, SA-234 Gr. WPB, 4' dia. 90 deg.

Sch 80 Searmless N/A NWA NMA SCO 0033902-1 UTC# 447005 NIA Replacement N

Pipe, Carbon Steel, SA-106, N/A N/A N/A SC# 0030635-1 N/A Replacement N

Grade B. Seamless Plain Ends.

UTCN 416324 4' Sch 80 (24) Nuts, Heavy Hex SA-194 NWA NA WA SC# 0027832-1 N/A Replacement N

Gr 2h Carbon Steel, 112'-

UTC# 445901 13UNC-2B (6) approx 5S lengths, Threaded N/A WA N/A SC# 0029486-1 N/A Replacement N

Rod, SA-1 93, Gr. B7, Size 1/2'-

UTC# 442843 13 UNC-2A

7. Description of Work:

Replace Degraded Pipe sections and replace bolting on supports H-334-11 and H-334-12, Note: Bolting replaced on H-334-11 (2 studs, and 5 Wuts)

-_33_-__

Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure X

Other VT-2 Pressure 750 psig Test Temperature 385 deg F 02-019-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N416.1 WAS INVOKED FOR THIS REPLACEMENT ACTMTY.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authbrizatidn No.

NIA Expiration Date:

I NIA i

Sig.

IS I

SI I nr-e e; -

Owner or Owner's Desigh'e, Title Date 4/I 1f4l/c I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insnected the components described In this Owners Report during the perici 1011712002 to 3t2312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions X

376' V

Q In_ cte's Signature Date 6 6-14/41 National Board, State, Providence, and Endorsements 7 7-02-019-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi W"

r Florida Power & Light Warne 700 Universe Blvd. Juno Beach, FL 33408 Date Address Turkey Point Plant Sheet Unit 1212/2002 1

of 2

3 WO#: 3201781101 CR#:

02-1639 Repair organization, P.O. No, Job No, tc.

2. Plant Warne 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Forida Power & Light arne Type Code Symbol Stamp Authorization Number Expiration Date N/A NIA 9760 SW 344 Street Florida City, FL 33035 Address NIA
4. Identification of System:

Auxiliary Feedwater System #:

75 Ouality Group C

5. la) Applicable Construction Code B31.1 1955 Edition, NIA
Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, NIA
Addenda, N416-1 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial iNational Number I Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No

-

I I

I I

I l

Pipe, Carbon Steel, ASME A-106 Gr. B Seamless, 4 Sch 80 NIA N/A N/A SC# 0030635 UTC9 416324 N/A Replacement N

(2) Elbows, 90 Deg. Carbon N/A N/A N/A SC# 0033902 N/A Replacement N

Steel, SA-234 Gr WPB 4' Sch UTC# 440977 80

7. Description of Work:

Replace degraded Pipe

8. Tests Conducted:

Hydrostatic:

NIA Other VT-2 Pneumatic N/A Nominal Operating Pressure X

Pressure 750 psig Test Temperature 385 deg F 02-02D-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

CERTIFICATE OF COMPLIANCE We certify thBt the statements made In the report are correct and this replacement conforms to the nries of the ASME Code,Section XV.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

NIA 0,

03 5

l r.L N

-DZ t Date t 2-L

?-

I Signed 690 Owner or Owner's Designee, Title I 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have InsDected the components described In this Owners Report during the period of 10/101200Z to 12/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described I this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Aamo Commissions 146 IP (ft-3748 12 Nabonal Board, State, Providence, end Endorsementa I

Inspector's Signature Date //9/0 3 0

02-020-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power & Light Date Narme 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Sheet 3123/2003 1

of 2

WO#: 32018583-01 CR#:

02-1639

2. Plant Unit 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Light
3. Work Performed by Name 9760 SW 344 Street Florida City, FL 33035 Address Repair Orgalizatlio. P.O. No, Job No.. etc.

Type Code Symbol Stamp NIA Authorization Number NMA Expiration Date NfA

4. Identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

5. (a) Applicable Construction Code 831.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, 1989 Edition, N/A N....
Addenda, Addenda, N/A Code Case N416-1 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired.

Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (30) Pipe, Carbon Steel. ASME NIA WA NIA SC 0030635-1 N/A Replacement N

A-SA-106 Gr B, Seamless, 4" UTC# 447411 Sch 80 (4) Bolts. Stud, All-Thread, N/A NIA N/A SC# 0026265-1 N/A Replacement N

ASME SA-193 GR B7, 314"-10 UTC# 432641 UNC-2A x 4 1/4.

(4) Nuts, Heavy Hex, C.S. SA-N/A NIA NIA SC# 0027084-1.

NIA Replacement N

194 Gr 2H 314'-10 UNC-2B UTC# 433908 Zinc Coated (12) Nuts, Heavy Hex, C.S. SA-NMA N/A NIA SC# 0027084-1 NIA Replacement N

194 Gr 2H 3/4-l0 UNC-2B3 UTC# 444694 Zinc Coated (4) Nuts, Heavy Hex, C.S. SA-NIA WA N/A SC#0027962-1 NIA Replacement N

194 Gr. 2H, Size 5/"-11 UNC-2B UTC0 444374

7. Description of Work:

Replace degraded pipe and degraded bolting on supports

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure X

Other VT-2 Pressure 750 psig Test Temperature 385 deg F 02-021-3

Sheet 2 of 2 FORM NIS-2 (Back)

I

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

I N/A Expiration Date:

N/A Sig I SOI Seihe Ti te O wner or Owner's Desisdhee, Title Date 4lI/ol 0

CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut have inspected the components described in this Owners Report during the perioq 10/2512002 to 3/23/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/A/( 7

Commissions ft National Board. State, Providence. and Endorsements 6 ctor's Signature 6 I/e9 Date 0

02-021-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

@2wnrlr Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 3/23/2003 1

of 2

0 WO#: 32018705-07 CR#:

Ckg by I WA Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035
3. Work Performed by 9760
4. Identification of System:

Addrss Florida Power & Light Name OSWf 344 Street Florida City, FL 33035 Repair Organiztilon, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date N/A Address Auxiliary Feedwater System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, 1989 Edition, NIA
Addenda, W.......

A d.n...

N/A Addenda.

NWA Code Case C.

WJA Code Case

6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp e

Component Number Board Identification Built Replacement Yes/No (1) Pipe Clamp,4' CS ASME NIA N/A N/A SC# 0403668-1 WA Replacement N

SA-36 UTC# 447596

7. Description of Work:

Remove and Replace Supports in Zone 13 (1-334-06)

8. Tests Conducted:

Hydrostatic:

WA Pneumatic WIA Nominal Operating Pressure N/A Other NMA Pressure N/A psig Test Temperature NIA deg F 02-022-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks BOLTED CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NWA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed c45 Is '44-,

Date Owner or Owner's Designee, TIe 6

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the period 112212002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

/_______

Commissions 4

lie or's Signature National Board, State, Providence, and Endorsements Date _

02-022-3

FORM NiS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Ovwner 7001

2. Plant 9760
3. Work Performed by 9760
4. Identification of System:

Florida Power S Light Date NaKe Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant SW 344 Street Florida City, FL 33035 Address Florida Power & Llht Sheet 12/9/2002 1

of 2

0 WO#: 32018`187-02 CR#:

02-1984 Unit Nane SW 344 Street Florida City, FL 33035 Repair Organizatfon, P.O. No, job Noa etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date NIA Address Auxiliary Feedwater

_System #:

75 Quality Group C

5. (a) Applicable Construction Code E31.1 (b plcbeEiino eto iUiie o ear rRpaeet (b) Applicable Editlon of Section XI Utilized for Repsirs or Rep~lacements 19 55 Edition, N/A -Addenda.

N/A Code Case 19 89 EditIon, N/A

Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mg Serial Natonal Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Weld Filler Metal. ER70S-N/A NIA NJA SC# 0011910 N/A Repair N

2,Weld Build-up on Existing UTC# 408016 Piping.UT#481 Weld Filler Metal, ER70S-2, N/A N/A N/A SC# 0011909 NIA Repair N

Weld Build-up on existing UTC 407289 Piping.

=

40.28

7. Description of Work:

Aux. Feedwater 4 Pipe Weld Build Up.

.Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic N/A Pressure NIA psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-023-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Reinarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELDCONTROL MANUAL.

0 CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

I_1

.j NMA Expiration Date:

NIA Date I Z. IZ' OZ.....

t Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described in this Owners Report during the period of 10117/200. to 12/9/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

- /nspector's Signature Date

/Z

/__________

Commissions AAY 7ZWJ a

Xr

,-3ZA National Board, State, Providence, and Endorsements 0

02-023-3

Owner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Fbrida Power & Light Date 1V Nanx 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Addnmss Turkey Point Plant Unit 123/2002 of 2

0 03 CR#:

NIA I by Nane 9760 SW 344 Street, Florida City, FL 33035 WO#: 32018700-Address Florida Power & Light Name 9760 SW 344 Street Florida City, FL 33035 Addrss

4. Identification of System:

Auxiliary Feedwater

5. (a) Applicable Construction Code B31.1 4b) Applicable Edition of Section Xi Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacemer Repair Organizaon P.O. No. Job No, tc.

Type Code Symbol Stamp WA Authorization Number N/A Expiratfon Date N/A

_System #:

75 Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case ients 19 89 Edition, N/A
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National Number Board Other Identification Year Bunt
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Pipe Clamp, 4' Carbon Steel, 3 bolt, BP Part #6150 Bergen Paterson N/A N/A SC#034356-1 UTC# 422539 N/A Replacement N
7. Description of Work:

Remove supports and ihspect pipe, replace clamp on support 4-YPH-39 B. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic NIA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-024-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLiANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

WA Expiration D; In?

O's5LC 5,4W.

ate:

N/A Date 1/ 0/ 03 Signed a

Owner or Owner's Designee, Title 1

0s CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 10/25I200. to 12/2312002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A,,-

C/

Inspector's Signature Date //or Af Commissions a/37Zf

^,5 Zt National Board, State, Providence, and Endorsements I 'I 0

02-024-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

' W ner 700I t

2. Plant 9760
3. Work Performed by 9760
4. IdentifIcation of System:

Florida Power & Light Date nme Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 12/26/2002 1

of 2

0 WO#: 32018700-04 CR#:

NIA Unit Name SW 344 Street Florida City, FL 33035 Address Florida Power & Light Kame SW 344 Street Florida City, FL 33035 Address Auxiliary Feedwater Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A System #:

75 Quality Group C

5. (a) Applicable Construction Code, B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components 1955 Edition, NWA
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No 5

4-I.

4 Paddle end from Strut, Telescoping Rigid. BP Part#

2100-7 Bergen Paterson N/A NA SCt#010&601-1 UTC# 388782 N/A I Replacement N

1 1-1 t-1 1

l~ ~~4 4

5

4.

4.-.4 4

I I

.

.LS 6.h

7. Description of Work:

Replace Paddle on Strut of Support H-336-03, Paddle from New Strut Welded to existing stut.

Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02.025-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

0 CERTIFICATE OF COMPiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

NIUA t 5 '

Date l/

9 lo 3 Signed 6'

Owner or Owners Designee, Title 0

CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston. Rhode Island, have Insoected the components described in this Owners Report during the period of 0I/25&200, to 12/26/2002 and state that to the best of my knowiedge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

' /J)

Commissions

/

ye -rA'8 J-'

National Board, State, Providence, ard Endorsements U

Inspectors Signature Date Z hle2 02.025-4

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Owner Florida Power & Light Nalm 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Date Sheet 1227/2002' 1

of 2

0 WO#: 32018705-09 CR#:

NO Unit

2. Plant Address Florida Power & Licht
3. Work Performed by -

9760

4. Identification of System:

Karne SW 344 Street Florida City. FL 33035 Repair Organizaflon, P.O. No, Job No. etc.

Type Code Symbol Stamp A

Authorization Number NIA Expiration Date NIA System #:

75 Quality Group C

Address Auxiliary Feedwater

5. (a) Applicable Construction Code B31.1 (b

plcal dtono etonX tlie o

episo epae et (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A

Addenda, NIA Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification
Repaired, Replaced, or I Replacement ASME Code Stamp Yes/No Year Built l

Bergon Paterson Pipe Clamp Part No. 2600 N/A N/A Bergen Paterson SC# 0403668-1 UTC# 0000447596 NWA Replacement I

I I

7. Description of Work:

Inspection of piping after damp removal Train #2 Zone 17,Replaced damp for Support H-334-16 ests Conducted:

Hydrostatic:

NWA Other N/A Pneumatic NIA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 02-026-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

slarla N/A Expiration Date:

N/A Date I l

/

3 0

C, (A:f, O0 Owner or Owners Designee, Title I 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described in this Owners Report during the period of 11/22/200. to 12127/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Date

/ /9 lo3 Commissions

&/g 7zfYr1 few ?Z 8 T

National Board, State. Providence, and Endorsements 02-026-3

Owher

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 12/2712002 Narm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

of Address Turkev Point Plant Unit 0

2 CR#:

NIA d by Name 1760 SW 344 Street Florida City, FL 33035 WO#: 32018705-10 Address Florida Power & Light Nane 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7

5. (a) Applicable Construction Code 831.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair rganization. P.O. No, Job No.. eM Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 5

Cuality Group C

1955 Edition, NIA

Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case ASME Name of Mfg Serial National Other

~ ~~~~Repaired, Code Name of Name ol MfG MfG SeNl National Oter Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 4 BP Part #2600-Bergen NIA N/A SC#0403668-1 NIA Replacement N

2.5 Paterson UTC# 447596

7. Description of Work:

Replace Pipe Clamp on Support H-334-20, 8 Tests Conducted:

Hydrostatic:

NWA O

Other NIA Pneumatic N/A Pressure N/A psig Nominal Operating Pressure NIA Test Temperature NIA deg f 02.027-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPUiANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NWA Expiration D; I e Os£ *..A4V ate:

N/A Date I I e/0 3 Signed Coo

  • C)I

-Owner or Owner's Designee, Title 0

CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 11221200Z to 12/27/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concemning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Alwo Commissions MC 71Z Yl-A 3'zg j:

National Board, State, Providence, ard Endorsements (I

Inspectors Signature Date /03 I

0 02-027-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

&Nner 700 1

2. Plant 9760
3. Work Performed by -

9760

4. Identification of System:

Florida Power & Light Date Nane Jniverse Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name SW 344 Street Florida City, FL 33035 Sheet 3/2312003 1

of 2

0 WO#:

32015705-12 CR11:

N/A Unit Address Florida Power & Light Name SW 344 Street Florida City, FL 33035 Kupaer Organizawn, F.C. No, Job No., etc.

Type Code Symbol Stamp NA Authorization Number N/A Expiration Date N/A System #:

75 Quality Group Address Auxiliary Feedwater

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, NIA 1989 Edition, N/A
Addenda, Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replaceinent Yes/No BP Part No.2600-2.5,4" Pipe Bergen N/A WA SC# 0403668-1 WA Replacement N

Clamp Paterson UTC9 0000447596

7. Description of Work-Inspection of piping after pipe damp removal, Replaced Pipe Clamp on R-332-05.
8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure NIA psig Nominal Operating Pressure NIA Test Temperature N/A deg F 02-028-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed IS I

S-T!&

Date

_____S_____

Owner or Owners Designee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the periof 1115/2002 to 312312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

A64e

Commissions fjC-3

.__8 National Board, State, Providence. and Endorsements Insqct/rsSignature W /(/a3 Date 02-028-3

  • Owner
2. Plant
3. Work Performec FORM NIS-2 OWN8RS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 12/

Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 27/2002 of 2

0 02 CR#:

N/A I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 32018705-Address Florida Power & Light Namn 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. IdentIfication of Components Repaired or Replaced and Replacement Components Repair Organization P.O. No, Job No, et.

Type Code Symbol Stamp NIA Authorization Number NJA Expiration Date NtA 5

Quality Group C

1955 Edition, N/A

Addenda, NtA Code Case 1989 EditIon, N/A
Addenda, N1A Code Case Name of Mfg
Repaired, Replaced, or Replacement Name of Component Mfg Serial Number ASME Code Stamp Yes/No Nation Other Identification Year Built Pipe Clamp. 4 BP Part# 2600-2.5 Bergen Paterson N/A NtA SC# 0404668-1 UTC# 447596 N/A Replacerent N

I

7. Description of Work:

Replace Pipe Clamp on Support R-332-03 8 Tests Conducted:

Hydrostatic:

NtA Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature NWA deg F 02429-3

Sheet 2 of 2 FORM NIS-2 tBack)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

S CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA 6*

6 1-== Ce.

64 V, Expiration Date:

N/A Date 1 I 13103 Signed.

6' Owriror Owners Designee, Title I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have Insoected the components described in this Owners Report during the period of I1/25/200, to 12127/2002 snd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

6U / Inspectors Signature Date 11,916 Commissions Sag 72 d rc 5g 7

National Board, State. Providence, and Endorsements 02-029-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Sectio Xl

  • Owner
2. Plant Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant Name 9760 SW 344 Street Florida City. FL 33035 12/27/2002 I

I Of..

2 0

WOU:

32018700-11 CR#:

N/A Unit Address Florida Power & Liht

-3. Work Performed by Narm Repair INganizaae.

P.O. No, Job No, etc.

Type Code Symbol Stamp I

N/A Authorkaion Number N/A Expiration Date NrA 9760 SW 344 Street Florida City. FL 33035 Address Auxiliary Feedwater

4. Identification of System:

System #:

75 Quality Group C

5. (a) Applicable Construction Code i31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired.

Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp I

Component Number Board Identification Built Repbacement Yes/No Pipe Clamp, 4 BP Part # 6150 Bergen N/A N/A SC# 0034356-1 N/A Replacement N

Paterson UTC# 422539

7. Description of Work:

Replace Clamp on support 3-AFH-10

40. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 024030-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Sinned

~~~~~~~~~~~~~~~ °

>~~~~~~~

NIA Expiration Date:

WA os5 '!

Date 'rl 44e3 C'W-l Owner or Owner's Designee, Title '

0 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insmected the components described in this Owners Report during the period of I l21/200 to 12/2712002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

zoa

Commissions A471ZYr AI-1s8 r

National Eoard. State. Providence, and Entdorsernents 1( /

Inspectors Signature Date

. I'f/O g

,--1 0

02-030-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Owner

2. Plant Florida Power & Light Narm 700 Universe Blvd. Juno Beach, FL 33408 Address Date Sheet 12/30/2002 I

Of 2

0 WO#: 32018705-14 CR#:

NIA Repair Organization, PMO.

No, Job No, etc.

Turkey Point Plant Unit Name 9760 SW 344 Street Florida City, FL 33035 Address

3. Work Performed by Florida Power & Light Namn Type Code Symbol Stamp Authorization Number Expiration Date I

N/A N/A 9760 SW 344 Street Florida City, FL 33035 NtA Address

4. Identification of System:

Auxiliary Feedwater

_System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A
Addenda, NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaoed, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 3W CS 3 Bolt A36 Bergen N/A N/A SC# 0034355-1 N/A Replacerpent N

Paterson UTC# 447504 Threaded Rod, ASME SA-193 N/A N/A N/A SC# 0029486-1 NIA Replacement N

Or B7. 1/2-13 UNC 28

_UTC#

442843 (4) Heavy Hex Nuts, ASME SA-N/A NIA N/A SC# 0027832-1 NIA Replacment N

194 i

r 2H. 1/2 13 UNC 2B UTCI 435416

7. Description of Work:

Replace Clamp on Support 3-AFX-7 and replace bolting on Support H-330-01

8. Tests Conducted:

Hydrostatic:

N/A

-\\L KE Pneumatic N/A Nominal Operating Pressure N/A Test Temperature NIA deg F O2031-3 umner NIA Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NMA Certificate of Authorization No.

N/A Expiration Date:

NIA

  • J 4-"_

Date I I 0o3 Signed ao Owner-r Owner's Designee, Title 7 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 1115/2002 to 12/3012002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Ae W".171-Commissions fr'79ZtV-g3Z8 j-6/

Inspector's Signature Date 1 Ah National Board, State. Providence, and Endorsements 7

7 02-031-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Owner Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Nam 9760 SW 344 Street Florida City, FL 33035 Addres Oate Sheet 1213012002 1

of 2

0 WOO: 32018705-08 CR#:

NIA

2. Plant Unit Repair Orguralzation, P.O. No, Job No., etc.

d1 Stamo NIA

3. Work Performed bjI Florida Power & Light TyDe Code Svmk NaWe 9760 SW 344 Street Florida CityFL 33035 Authorization Number Expiration Date N/A N/A Address
4. identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

5. a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, 1989 Edition.

N/A Addenda.

NIA Code Case N/A Code Case

6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No Pipe Clamp, 4 ASME SA-36, Bergen N/A N/A SCtS 0403668-1 N/A Replacenwent N

BP Part # 2600-2.5 Paterson UTC# 447596

7. Description of Work:

Replace Pipe Clamp on support H-334-07

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 02-032-3 Other N/A Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA e

v -S e_7 15 w-4,1 Date I l 3

°03 Signed C ('<

W J

W dI --- Ownei-or Owner's Designee, Title I ---

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a vaid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island. have inspected the components described in this Owners Report during the period of 11111/200. to 1213012002 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

____o___Signature Commissions

'/>'J f~L 328 3

( I Inspectors Signature National Board, State, Providence, and Erndorsements Date

//

, S A+ - _

S 02-032-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner Florida Power & Ught Date Harm 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Nare 9760 SW 344 Street Florida City, FL 33035 Sheet 12130/2002 1

of i 2 0

WON: 32018700-13 CR#:

N/A Unit

2. Plant Address Florida Power & Light
3. Work Performed by -

9760

4. Identification of System:

Nare SW 344 Street Florida City, FL 33035 Repair Organizatimor P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date N/A Address Auxiliary Feedwater System#:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A _Addenda, N/A_

Code Case 1989 Edition.

N/A _Addenda, N/A Code Case

6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired.

Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No N

(2) All Thread, ASME SA-193 NIA N/A NIA SC# 0029486-1 WA Replacement N

Gr B7, 1/2-13 UNC-2A.

UTC# 442843 (8) Heavy Hex Nuts, ASME SA-NIA NIA N/A SC# 0027832-1 NIA Replacement N

194 <r 2H. 112-13 UNC-2B UTCN 445901

7. Description of Work:

Replace Bolting on Support 4-AFX-8

8. Tests Conducted:

Hydrostatic:

N/A I

Other N/A Pneumatic NIA Pressure N/A psig Nominal Operating Pressure NIA Test Temperature NIA deg F 02-033-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

S CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code: Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A 61

_1__N 0e5Fi 5fr Dae 0

Date 610if33 Signed

_s 0

OwnrFor Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described hI this Owners Report during the period of 12118/200, to 1213012002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Qlz

Commissions /I/* 7 Z A' 3-I z ~

National Board, State, Promidence. and Endorsements Inspector's Signature Date 3

02-033-3

  • wner
2. Plant
3. Work Perform&e FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 12130/2002 Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

of Address Turkey Point Plant Unit 0

I 2

CR#:

02-2046 i by Narne 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Liaht WO#: 32018187-07 Rame 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

7

5. (a) Appflcable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organzatm, P.O. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 5

Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case 1989 Edition, NIA
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial Number National Board Year Built Repaired.

Replaced, or Replacement ASME Code Stamp Yes/No Other Identification S

Weld Buildup of Pipe on Train 2 AFSS N/A NWA NIA WPS-89 FPL Weld Control Manual i

N/A Repaired N

7. Description of Work:

Perform Weld buildup in corroded areas, Build up to minimum.300 per MRA 32018187-01

8. Tests Conducted:

Hydrostatic:

NA 0

Other NWA Pneumatic N/A Pressure N/A psig Nominal Operating Pressure NIA Test Temperature NIA deg F 02-034-3

Sheet 2 of 2 FORM NIS-2 1Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

0 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed CK R<

/

DtI IS;ewAqpAe)-,

Date 4.V!za?

z Owner or Owner's Desigtee, Title 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report dwing the period o 10/26/2002 to 12/30/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connted with this inspection.

X0/00_P Commissions fi e z8 In& r's Signature

~, 41 /6 75.

National Board. State, Providence. and Endorsements Date I - I 02-034-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl 2b Owner

2. Plant Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Addrss 12/30/2002 I

I of 2

0 WO#: 32018700-02 CR#:

WNA Repair Organizaton, P.D. No4 Job No., tc Turkey Point Plant Unit Name 9760 SW 344 Street Florida City, FL 33035 Addres

3. Work Performed by Florida Power & Ught Name Type Code Symbol Stamp Authorization Number Expiration Date

.NIA NtA 9760 SW 344 Street Florida City, FL 33035 Address NfA

4. Identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A Addenda.

1989 Edition, N/A Addenda.

N/A Code Case NIA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements

6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg MW9 Serial National Other Year Replaced, or Stamp b

Component Number Board identification Built Replacement Yes/No Pipe Clamp, 4 ASME SA-36.

Bergen N/A N/A SC# 0403668-1 N/A Replacement N

BP Part# 2600-2.5 Paterson UTC# 447596

7. Description of Work:

Replace Pipe Clamp on Support H-330.04

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic NIA Nominal Operating Pressure N/A Omser N/A Pressure N/A psig Test Temperature N/A deg F 02-035-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NMA Certificate of Authorzatioh No.

WIA Expiration Date:

N/A Signed 9K wrer or Owners Designed, Wel Date I I O

103 s

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Insoected the components described In this Owners Report during the period of 10/25/200,c to 12130/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance wlth the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described hI this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable hI any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

ZA

Commissions A1677yr f

C 3-s 2 i

National Board, State, Povidenoe, and Endorsements 61 Inspectoes Signature Date

/ A9 A

T I

S 024035-3

. Owner

2. Plant
3. Work Performed by 700 Ur FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 12

-iverse Blvd. Juno Beach, FL 33408 Sheet 1

Addr Turkev Point Plant Unit 130/2002 I

of..

2 0

406 CR#:

NJA Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Light WOM: 32018706.

9aFe 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacernen Repair Organaticon PM. No. Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A System #:

75 Quality Group C

19 55 Edition, N/A

Addenda, N. A Code Case ierts 19 89 Edition, N/A Addenda N/A Code Case it Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Bunt Replacement Yes/No (2) Pipe Clamps, 4' ASME SA-Bergen N/A NIA SCU 0403688-1 N/A Replacement N

36, BP Part# 2600-2.5 Paterson UTC# 447596

7. Description of Work:

Replace Pipe Clamps on H-334-01 and H334-21

8. Tests Conducted:

Hydrostatic:

N/A 0

Other NIA Pneumatic NIA Pressure NJA psig Nominal Operating Pressure NJA Test Temperature N/A deg F 02436-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION. NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NfA Certificate of Authorization No.

N/A Expiration Date:

N/A t<

Dat I

Date 1 /61o-7 1

Signed cf<

I0 Owner or Owner's Designee. Tkle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of 12/181200 to 12130/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

A-J

Commissions A/67ZYV PIZY J-National Board. State, Providence, and Endorsements (I

Inspector's Signature Date

// t /O3 0

02.036-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Owner Florida Power & Ught Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Addresa 12/30/2002 I

I of 2

0 WO#: 32018187-08 CR#:

NIA Repair Organizatlon, P.O. No, Job No., et.

2. Plant Turkey Point Plant Unit Wame 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Perlormned by Florida Power & Ught Nare Type Code Symbol Stamp Authorization Number Expiration Date I

NIA N/A 9760 SW 344 Street Florida City, FL 33035 N/A Address

4. Identification of System:

Auxiliary Feedwater

_System #:

75 Quality Group C

5. (a) Applicable Construction Code

% 831.1 19 55 Edition, NtA

Addenda, 1989 Edition1 N/A
Addenda, N/A Code Case N416-1 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (30) Pipe, 4-Carbon Steel, N/A N/A N/A SC# 0030635-1 N/A Replacement N

ASME SA-106 Gr B. Sch 80 UTC# 416324 (1) Elbow, 4" 90 deg, Carbon N/A N/A N/A SC# 0033902-1 N/A Replacement N

Steel, ASME SA-234 Gr WPB UTC# 447005 Sch 80 (8) Nut, Heavy Hex, ASME SA-N/A N/A N/A SC# 0027832-1 N/A Replacement N

194 Gr 2H, 1/27-13 UNC 2B UTC# 445901 (2) lengths, Threaded Rod, N/A N/A N/A SC# 0029486-1 NIA Replacement N

ASME SA-193 Gr B7, 112"-13 UTC# 442843 UNC 2A

7. Description of Work:

Replace corroded Aux Feed Steam Supply (Train 2) pipe and also replace bolting on support R-334.02 O

Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Other VT-2 Nominal Operating Pressure 760 Test Temperature 495 deg F 02-037-3 Pressure 760 psig

Sheet 2 of 2 FORM NIS-2 (Back)

ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE NA416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

9. Rehiarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed Date e

werorOne'sit Title 0

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insnected the components described In this Owners Report during the period a 10129/2002 to 12/30/2002 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A/L Commissions

/,-

Z National Board, State, Providence, and Endorsements I)tpores Signature Date 02-037-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

  • 3wner Florida Power & Light Date 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address 1/7/203 I

I of 2

3 WO#: 32018705-13 CR#:

NIA fRpaiJ Organizalon, P.O. No, Job No., etc.

2. Plant Turkey Point Plant Unit Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power S Light NHae Type Code Symbol Stamp Authorization Number Expiration Date NIA 9760 SW 344 Street Florida City, FL 33035 Address WA NJA I
4. Identification of System:

Auxiliary Feedwater

.System 75 Quality Group C

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda, N/A
Addenda, NWA Code Case N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition,
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No t

t I

I I

(2) Threaded Stud, 5/8-11UNC-2A ASME SA-193 Gr 87 N/A NIA NIA SC# 0029490-1 UTC# 443307 NJA Replacement N

(3) Threaded Stud, 1/2-13UNC-NIA N/A N/A SC# 0029486-1 NJA Replacement N

2A, ASME SA-193 Gr B7 UTC# 442843 (12) Nuts. Heavy Hex, ASME N/A N/A N/A SC# 0027832-1 NWA Replacement N

SA-194 GR 2H, 12r-13UNC-UTC# 445901 2B.

(8) Nuts, Heavy Hex, ASME SA-N/A N/A N/A SC# 0027962-1 N/A Replacement N

194 Gr-2H, 5&81 1UNC-2B UTC# 444374

7. Description of Work:

Replace bolting on pipe clamps for supports 4-AFX-1, 4-AFX-6 and 4-AFX-7

8. Tests Conducted:

Hydrostatic:

NIA 0

Pneumatic NIA Nominal Operating Pressure N/A Test Temperature NWA deg F 03-001-3 Other N/A Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

WA Expiration Date:

NWA 05-e6 5

4ph Date 1

86 /0°3 Signed

'Cot, A-C)

Owner or Owners Designe'e. The CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors end the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have Inspected the components described In this Owners Report during the period of 117/2003 to 1/7/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

0

-t Inspector's Signature Date //9/0 Commissions //t72nI tZz JE National Board, State, Providence, and Endorsements I

03-001-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner

2. Plant Florida Power 8 Light Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Date Sheet 1/7/2003 '

I of 2

Unit Name 9760 SW 344 Street Florida City, FL 33035 3

WOO: 32018700-08 CR#:

NWA Addres Florida Power & Light

3. Work Performed by -

9760

4. Identification of System:

Name i SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No. Job No, etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A System #:

75 Quality Group C

Address Auxiliary Feedwater

5. ia) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Repaired,.

Replaced, or Replacement ASME Code Stamp Yes/No 4

t-

1 Paddle End from Strut, BP Part# 2100-7 Bergen Paterson N/A N/A SC# 0100601-1 UTC# 388782 N/A Replacemnent N

Load Pin manufactured from N/A N/A N/A SC# 0029992-1 N/A Replacment N

Round Stock, 1 ASTM A-193 UTC# 443308 GrB (2) Studs from Alhthread, 3/4 -

N/A NIA N/A SC# 0029493-1 N/A Replacement N

10 UNC-2A, ASME SA-193 Gr UTC# 437941 87 (8) Heavy Hex Nuts, ASTM A-N/A N/A NIA SC# 0027837-1 N/A Replacement N

194 Gr 7, 3I4'-10 UNC-2B UTC# 437942

7. Description of Work:

On support R-337-02 replace paddle on strut, from new strut UTC#388782, replace bolting on pipe clamp, and replaced Load Pin

.Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure NIA psig Nominal Operating Pressure NIA Test Temperature N/A deg F 03-002-3

Sheet 2 of 2 FORM NIS-2 (Back)

I

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Sinnpd aJg1 NIA Expiration Date:

105e v0

_AG-_

Date N/A 03 1 I'S /

4IIR

!I I

e}

CIK Owner or Owners Designee, Title' CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described in this Owners Report during the period of 11712003 to 117/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

A40*

Commissions( FEZ4 6> 5238 Yf National Board, State, Providence. and Endorsements (jppectors Signature Date

/ /4 M?

0 03-002-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Nare 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Date Sheet 1/8/2003 I

1 of 2

3 WO#: 32018700-14 CR#:

N/A Unit

2. Plant iame 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Light Name
3. Work Performed by 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Authorization Numt Expiration Date System #:

75 Quality Group NIA Repalr Orgadsiaon P.O. No. Job No, eta.

S rStamp N/A NIA Address Auxiliary Feedwater

4. Identification of System:

C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A Code Case 19 89 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components T

F I

Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No w

Pipe Clamp. 3' CS. BP Part#

6150, 3 Bolt N/A Bergen Paterson N/A SC# 0034355-1 U'TC# 447504 NA Replacerrent N

t 1*

1--I t

4 4

+

  • 9*
7. Description of Work:

Replace Clamp on support 3-AFX-8 Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F

.03-003-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

i CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Sinnd E

a N/A Expiration Date:

N/A z>r 5

t: _ -

v/v Date I

E3 /°0

-. S, -

Lov<

A Ownri or Owner's Designee, Title-CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described in this Owners Report during the period of 111412002 to 1/812003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code. Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A2'~

Commissions &/6 7,YrAc 37z&

National Board, State, Providence, and Endorsements 6J Inspector's Signature Date

/-

I - O 3 03-003-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 119/2003 1

of 2

3 WO#: 32018700-12 CR#:

N/A

2. Plant Unit Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Light
3. Work Performed by 9760
4. Identification of System:

Naffe SW 344 Street Florida City, FL 33035 Address Auwdilary Feedwater Repair Organnfdon, P.O. No, Job No. etc.

Type Code Symbol Stamp I

N/A Authorization Number-NIA Expiration Date N/A System #:

75 Quality Group C

  • 5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components 1010 ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (2) Pipe Clamps, 4-BP Part#

Bergen N/A N/A SC# 0403668-1 N/A Replacement N

2600-2.5. ASME SA-36 Paterson UTC# 447596

7. Description of Work:

Replace damps on supports H-337-02 and R-337-05 Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic NIA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 03-004-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

Sined NIA Expiration Date:

N/A iDate

'l9

/03 al,..

A Owner or Ownees Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by Factory Mutual Insurance Company of Johnston, Rhode Island, have insoected the components described In this Owners Report during the period of I191200, to 119/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I r6 os Signature Date Z

I Commissions J6772-Y-)3?76 7 National Board. State. Providence, and Endorsements I

f S

03-004-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 311 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Addreas Turkey Point Plant Unit 1612003 I

of 2

3 02 CR1:

02-1640

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 WO#: 32003971-Address Florida Power & Light
3. Work Performed by Name 9760 SW 344 Street Florida City, FL 33035 Address
4. Identification of System:

Containment Emergency Filters System #:

5

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components RepaIrOpaniznfon, P.O. No, Job No. etc.

Type Code Symbol Stamp NIA Authorization Number NIA Expiration Date N/A 6

Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case 1989 Edition, N/A
Addenda, NIA Code Case ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No SV-3-2905, Reweld Canopy NIA N/A N/A Existing N/A Replacement N

seal weld Existing

7. Description of Work:

Cut Seal Weld, Rework valve and reweld seal weld

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic NWA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 03-05-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

I CERTIFICATE OF COMPLIANCE We certify that the statements made I the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Signed NfA Expiration D.ate:

N/A Date X/de 3 ZS/

X r44~

r"" - 't

>A Owner or Owners Desigheevritie CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a vasld commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the period 111412003 to 3/1612003 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions A*.35Z8

( J iectors Signature Date 4-/G-v ?

National Board, State, Providence, and Endorsements 03-005-3

700 Ur FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 311 Name ilverse Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 17/2003 of 2

3 01 CR#:

NrA

2. Plant
3. Work Performe Nam.

9760 SW 344 Street Florida City, FL 33035 WO:

32009982.~

d by Ajddrns Florida Power & Lbiht Hame 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Spent Fuel Pit Cooling System #:

3

5. ta) Applicable Construction Code 931.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair O"ganizaUon, P.O. No. Job No. etc Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NIA 3

Quality Group C

19 55 Edition, N/A

Addenda, N.A Code Case 1989 Edition.

N/A

Addenda, N/A Code Case Name of Mfg

-r I

Name of Component Mfg Serial National Number Board Year BuIlt Other Identification

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Bonnet from Valve, 27 Diaphram SA-351 Gr CF8, Class 150 NIA NJA NJA SC0237682-1 UTC# 434928 N/A Replacement N
7. Description of Work:

Replace bonnet and diaphram

'6 Tests Conducted:

Hydrostatic:

N/A Other Vr-2 Pneumatic NJA Pressure 120 psig Nominal Operating Pressure X

Test Temperature 81 deg F 03.006-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I e

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

WA Expiration Date:

NWA SignesZI is/ S_

A perJjc Date __

__I Owner or Owner% Designee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have Inspected the components described In this Owners Report during the periq 6/5/2002 to 3/17)2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, conceming the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions

/

5?&

lIsr~ed&-r Signature National Board, State, Providence, and Endorsements Date 034006-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date Name 700 Universe Blvd. Juno Beach, FL 33408 Addes Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Sheet 3117/2003 I

of.

2 3

WO#: 30005430-01 CR#:

NIA Unit

2. Plant Addmss Florida Power & Light
3. Work Performed by -

9760

4. Identification of System:

NWo SW 344 Street Florida City, FL 33035 Addres Auxiliary Feedwater Repair OrgarlztiloN P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NIA System 9:

75 Quality Group B

5. (a) Applicable Construction Code 631.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components National Board Name of Component Name of Mfg Mfg Serial Number Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No I.

4

.1

4.

4-.4.

.4.

(4) Bonnet Studs, ASTM-A-193 GR B7 N/A N/A N/A SC# 0062455-1 UTC# 402077 NIA Replacement N

(8) Nuts, Carbon Steel, SA-194 N/A NA NIA SC# 0027957-1 N/A Replacement N

Gr 2H Ull 443838

7. Description of Work:

Disassemble, clean, Inspect, repair, replace bonnet nuts and studs and reassemble

8. Tests Conducted:

Hydrostatic:

NIA 0

Other N/A Pneumatic WA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 03-007-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

0 I

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

NWA Signed ~

Date

/17/0 3

_v z

Owner or Owners Designd'e, Title 0

CERTiFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the periaq 912512002 to 3/1712003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/J0f Commissions

/

r 3X National Board. State, Providence, and Endorsements

-I orie Signature C6/l/o3 Date 03-0074

  • wner
2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Secton Xl Florida Power& Light Date 3/17/2003 Name 7f00 Universe Blvd. Juno Beach, FL 33408 Sheet

.1 of Address Turkey Point Plant Unit 3

2 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WOM: 33004384-01

3. Work Performed by Address Florida Power & Light Name 9760 SW 344 Street Florida City, FL 33035 Address
4. Identification of System:

Main Feedwater System #:

7

5. (a) Applicable Construction Code 931.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components RepSor Organization, P.O. No, Job No., eft.

Type Code Symbol Stamp.

NA Authorization Number N/A Expiration Date NIA 47 Quality Group B

1955 Edition, N/A

Addenda, N/A Codi 1989 Edition, NIA
Addenda, NIA Codi l Case l Case Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No (1) Bonnet Stud, CS ASTM A-193 B16 1 3/44-8 UN2A x 8 3/4" N/A N/A N/A SC# 0028046-1 UTC# 393975 NIA Replacement N

(5) Bonnet Stud, CS ASTM A-NWA NA N/A SC# 0028046-1 N/A Replacement N

193 B16 1 3/4"-8 UN2A x 8 3/4" UTC# 448140 (5) Nut, Heavy Hex, 1-3/4"-8 N/A N/A NA SC# 0027992-1 NIA Replacement N

UN-2B, ASTM A-194 Gr 7 LTC# 449340

.I

7. Description of Work:

Disassemble, inspect and reassemble. Replace 6 bonnet studs and 5 nuts

8. Tests Conducted:

Hydrostatic:

N/A W

Other N/A Pneumatic NIA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature NIA deg F 03-008-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NrA Certificate of Authorization No.

NIA

-Expiration Date:

NIA Signed

/5/

Moore c D

Date Y/71P;!

Owner or Owners Designed Tite CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period 3/712003 to 3/1712003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I 451 Commissions 3

National Board, State, Providence, and Endorsements lnsp6fi-sSignature "Al la Date 03-008-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light 7ar.

700 Universe Blvd. JIuno Beach. FL 33408 Date Sheet Addrss Turkey Point Plant Sf28/2003 I

of 2

3 WO#: 3300458101 CR#:

03-0522 Unit

2. Plant Narm 9760 SW 344 Street Florida City, FL 33035 Addres Florida Power & Light
3. Work Performed by Type Code Symbol Authorization Nurnt Expiration Date

_System #:

78 Quality Group kepair Organlzation. P.O. No, Job No_, etc.

Staffn WJA NtA 9760 SW 344 Street Florida City, FL 33035 NIA Address Steam Generator Wet Layup

4. Identification of System:

i

5. (a) Applicable Construction Code 631.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1955 Edition, _NA
Addenda, NIA Code Case 1989 Edition, NIA
Addenda, NA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced.-or Stamp Component Number Board Identification Built Replacement Yes/No flat Bar, CS, ASTM A-36 3/8' WA NWA NIA SC# 0029702-1 NIlA Replacement N

UTC# 433598

7. Description of Work:

Replace Supports H-5 and H-6 on SGWL system, supports removed for inspection.

8. Tests Conducted:

Hydrostatic:

N/A 0

Other VT-3 Pneumatic NIA Noninal Operating Pressure N/A Test Temperature NtA deg F 03-009-3 Pressure NWA psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

I 0

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

NWA -

Signed

_X/

-5)'Ac/O 6i\\ner or Owneres Designed' Ttie Date

/

0, 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period a 3/9/2003 to 5128/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any marnner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A_

Commissions Af 3Zfi National Board, State, Proidence, and Endorsements 03-009-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

  • Jner
2. Plant Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 3/21/2003 1

of 2

3 WO#: 32003812-01 CR#:

NIA Repair Organization. P.O. No. Job No.. etc.

Turkey Point Plant Unit 9760 SW 344 Street Florida City, FL 33035 Address

3. Work Performed by Florida Power & Light Name Type Code Symbol Stamp Authorization Number Expiration Date N/A NWA 9760 SW 344 Street Florida City, FL 33035 Addzs N/A
4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 19 55 Edition, NIA
Addenda, 19 89 Edition, NIA
Addenda, NIA Code Case NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No 1

9 A

(14) Cover Studs, Tap End, 1--

8 UNC-2A x 5-1/2" ASTM A-193 Gr B7 N/A NfA NIA SC# 0014188-2 UTC# 443068 NIA Replacement N

7. Description of Work:

Open and dean basket strainer, replace the cover studs

' Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 03-010-3 Other N/A Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Cerfcate of Authorization No.

NWA Expiration Date:

N/A Signed

/ /5/

s i-Date tlt/1/3 Owner or Owner's Designee, 'title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described In this Owners Report during the perio4 2/2712002 to 3121/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising froAr connected with this Inspection.

Commissions jn-c536' L/Inspector's Signature National Board. State, Providence, and Endorsements Date 03-010-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

  • owner Florida Power & Light Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Sheet 3/24/2003 1

of 2

3 WO#: 31005379-01 CR#:

NJA Repair Organization, P.O. No, Job No, etc.

2. Piant Turkey Point Plant Hare 9760 SW 344 Street Florida City, FL 33035 Address Unit
3. Work Performed by Florida Power & Lbaht anae Type Code Symbol Stamp Authorization Number Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 Address N/A NIA
4. Identification of System:

Safety Injection

-System #:

62 Quality Group A

5. (a) Applicable Construction Code 831.1 19 55 Edition, N/A
Addenda, N/A Code Case 1989 Edition, N/A
Addenda, N416-1 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial INational Number Board Other Identification Year Built
Repaired, Replaced, or Replacement ASME Code Stamp Yes/No I

t t

t 1-~~~~~~~~~~~~~~~~~~~~~~~~~~

Valve, 2-Piston Check SS Edwards N/A N/A SC# 0052484-i UTC# 436261 NIA Replacement N

Coupling, 2 6000#, SA-182 Gr N/A N/A N/A SC# 0047748-1 N/A Replacement N

316 Socketweld ends IJTC# 433574 Pipe, 2" Sch 160, SA-3121376 NWA N/A NA SC# 0030938-1 NIA Replacement N

F316 SS UTC# 427841

7. Description of Woric Replace Valve 3-873C
8. Tests Conducted:

Hydrostatic N/A Other VT-2 Pneumatic N/A Nominal Operating Pressure N/A Pressure 1470 psig Test Temperature 91 deg F 03-011-3

Sheet 2 of 2 FORM NIS-2 (Back) 9-Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL. CODE CASE N-416.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code.Section X(.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insaected the components described in this Owners Report during the period or 3/24/2003 to 3124/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal irjury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Y zs _

Inspector nature National Board, State, Providence, and Endorsements Date 14 -5 a o 03-o 1-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner Florida Power & Light Date 700 Universe Blvd. Juno Beach, FL 33408 Address Sheet 312412003 1

of 2

3 WO#: 32003412-01 CR#:

NWA Repair OrganiLzton, P.O. No, Job No. etc.

2. Plant Turkey Point Plant Nane 9760 SW 344 Street Florida City, FL 33035 Address Unit
3. Work Performed by Florida Power & Llht Name Type Code Symbol Stamp Authorization Number Expiration Date NIA NIA N/A 9760 SW 344 Street Florida City, FL 33035 Address
4. Identification of System:

Reactor Coolant

_System #:

41 Quality Group A

5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A
Addenda, WA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements

\\ 1989 Edition, NJA

Addenda, NWA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Comronent Mfg Serial National Number I Board Other Identification Year Built
Repaired, Replaced, or Reolacement ASME Code Stamp Yes/No T

Crosby Pressurizer Safety Valve, 1500# class, 4 NIA N/A SC# 0053561-1 NJA N/A Replaced N

Pressurizer Safety Valve, Crosby NWA NIA SC# 0053561-1 NA Replacement 1500# class, 4' UTC# 389248 Studs. Threaded Rod, ASME NtA N/A N/A SC# 0029566-1 N/A Replacement N

SA-453. Gr 660 Class B 1-114'-

UTC# 447963 8 UN-2A Nuts, Heavy Hex, 1-114'-8 UN-NWA NWA NWA SC# 0027843-1 NWA Replacement N

25, ASME SA-194 Gr 2H UTC# 448737

7. Description of Work.

Replace relief valve (SN# H51249-1361) with spare relief valve (SN# H51249-1581)

Tests Conducted:

Hydrostatic:

N/A Other Vr-2 Pneumatic NWA Nominal Operating Pressure X

Pressure 2280 psig Test Temperature 547 deg F 03-012-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A I

I Signed I S I Z %J P-¶iP hAS &,-

Owner or Owneres Designre, Tide Date

%t I I it;

,t I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described hI this Owners Report during the period 9/2412002 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners! Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A0/40 Commissions National Board, State, Providence, aid Endorsements I ~~or's Signature 6 z Date 0

03-12-3

)wner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 3

Nare 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Addres Turkey Point Plant Unit M/2003' of 2

3 01 CR#:

N/A dby Kanae 9760 SW 344 Street Florida City, FL 33035 WON: 3200341 1-Addrns Florida Power & Licht anme 9760 SW 344 Street Florida City, FL 33035 Addrs

4. Identification of System:

Reactor Coolant

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacemen Repair OrgAnzafloh, PFO.

No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number NIA Expiration Date NIA

_System #:

41 Quality Group A

1955 Edition, N/A Addenda.

N/A Code Case ients 19 89 Edition, N/A Addenda.

NIA Code Case I.

Other Identification

Repaired, Replaced, or Replacement

, Stamp Yes/No Name of Comoonent Name of Mfg Mfg Serial Number National Board Year Built

4.

4 -v _

Pressurizer Safety Valve Crosby NIA NIA N/A NWA WA Replaced I

N I

Pressurizer Safety Valve Crosby N/A N/A SC# 0053561-1 NIA Replacement v

UTC# 389249 (8) Studs. Threaded Rod, WA WA NWA SC# 0029566-1 N/A Replacement N

ASME SA-453, Gr 660, 1-114--

UTOC 447963

8. UN-2A (16) Nuts, Heavy Hex, SA-194, NIA NIA NIA SC# 0027843-1 NIA Replacement N

Gr 2H, 1-1/4-8 UN-28 UTC# 448737

7. Description of Work, Replace Relief Valve (SN# N69877-00-0005) with spare Relief Valve (SN# N6987700-0004)

' Tests Conducted:

Hydrostatic:

N/A Other VT-2 Pneumatic NIA Pressure 2280 psig Nominal Operating Pressure X

Test Temperature 547 deg F 03.013-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp INIA Certificate of Authorization No.

NIA Expiration Date:

II NfA I

Signed PO

.A03,W Date t/ I p/a,

Owner or Owneres Desidee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 9/24/2002 to 312412003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions AR g

_4 National Board, State, Providence, and Endorsernents Inspe s Signature C /6 Date 03.0134

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi wner Florida Power & Light warml 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 312412003

.. I I

'of 2

3 WO#: 32003410-01 CR#:

NJA

___epalianlzjjlon,?~Q. No, Job No. eO.

2. Plant Turkey Point Plant Unit Name 9760 SW 344 Street Florida City, FL 33035

Address

3. Work Performed by Florida Power & Ltght NKma Type Code Symbol Stamp Authorization Number Expiration Date INJA N/A I I 9760 SW 344 Street Florida City, FL 33035 Address NIA
4. Identification of System:

Reactor Coolant

_System #:

41 Quality Group A

I, I I

5. (a) Applicable Construction Code B31.1 1955 Edition, NIA
Addenda, (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements

, 19 89 Edition, NIA

Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mig n
Repaired, Reptaced, or Replacement Name of Component Mfg Serial National Number I Board ASME Code Stamp Yes/No Other Identification Year Built Replaced Pressurizer Safety Valve Crosby N/A NWA N/A N/A N/A N

Pressurizer Safety Valve Crosby N/A N/A SC# 0053561-1 N/A Replacement N

UTC:# 389085 AStudslbrieaded Rox

_N/A NIA N/A SC# 0029566-1 N/A Replacement N

ASME SA-453, Gr 660, 1-1/4"-

UTC# 447963.

8. UN-2A (16) Nuts. Heavy Hex, 1-1/4"-

N/A N/A N/A SC# 0027843-1 N/A Replacement N

8UN-2E, ASME SA-194 Gr 2H UTC# 448737

7. Description of Work:

-Replace-Relief-Valvel4N#454-24913 362 ith spare-relief valve4SN 1H51249-1579)

' Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure X

Test Temperature 547 deg F 03.0144 Other VT-2 Pressure 2280 psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I1, CERTIFICATE OF COMPLIANCE

  • --Wicartifyltha'the stiterfris -made-in-t-report dre crrectundhis-replacement-cnforms-to the rules of the ASME Code, Section Xi.

. I Type Code Symbol Stamp N/A Certificate of Authorization No.

INIA Expiration Date:

NWA I

Signed 15* / SvDate Date 441 # J1631 Owner or Owner's Desigrbe, Title I,

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Inspected the components described In this Owners Report during the period 9124/2002 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners. Report In accordance with the recquirements of ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions A

J

-I or's Signature Natioall Board, State, Providence, and Endorsements Date 6 /&/I3 s

03-014-3

Sp wriwner

2. Plant
3. Work Performed by 700 Ur FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Oate 3124/2003 niverse Blvd. Juno Beach, FL 33408 Sheet 1

of Address Turkey Point Plant Unit 3

2 CR#:

NIA Narrie 9760 SW 344 Street Florida City, FL 33035 Address Florida Power & Light WO#: 29016850-01 Naie 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Reactor Coolant System #: 4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization. P.O. No, Job No., etc Type Code Symbol Stamp NWA Authorization Number N/A Expiration Date N/A 41 Ouaflty Group A

1955 Edition, N/A

Addenda, N/A Code Case 19 89 Edition, NIA
Addenda, NIA Code Case Name of Component l Name of Mfg i Mfg Serial I~am of Mfg INumber
National, Boardi Other Identification Year

_BuiK Repaired.

Replaced, or Reolacement ASME Code Stamp Yes/No I

~

~

~

~~~~

l i

4 Bonnet Assembly N/A N/A 1

I

-I N/A SC# 0223705-1 UTC# 442732 NIA Replacement N

(8) Nuts, Heavy Hex, 1-1/4'-8 NIA I

N/A N/A SC# 0056776-1 NtA Replacement N

UN-2B,_ASME SA-194 GrB6 lUTC# 400719 (8) Studs, ASME SA-453, Gr B

NIA N/A N/A SC# 0056927-1 l N/A Replacement N

660,1-1/4 UTC# 400731 I~~~~~~~~~~~~~~~~~~~~~~~~

7. Description of Work:

Delete Bonnet extension and replace bonnet per PCM-98-008

8. Tests Conducted:

Hydrostatic:

N/A Other VT-2 Pneumatic N/A Pressure 2280 psig Nominal Operating Pressure X

Test Temperature 547 deg F 03-015-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REOUIRED.

i Bi CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Signed C=

N/A Expiration Diate:

N/A Date Y/7/v73-Ag 5e~v./D Owner or Owner's DesigneE Title 0*

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the slate of Florida and employed bv HSBCT of Hartford. Connecticut, have inspected the components described in tlis Owners Report during the pericd

¶ 1/3/1999 to 3/24/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concemning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions A4 3 8

National Board, State, Providence, and Endorsements 0

03-015-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

  • wner Florida Power & Light "are 700 Universe Blvd. Juno Beach. FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street, Florida City, FL 33035 Date Sheet 312412003 1

of 2

3 WO#: 33004373-01 CR1:

03-0446 Unit

2. Plant Address Florida Power 8 Light
3. Work Performed by Nan*

Repair "

Type Code Symbol Stamp Authorization Number Expiration Date enizatO.

P.O. No. Job No, at.

N/A N/A 9760 SW 344 Street Florida City, FL 33035 N/A Address Safety Injection

4. Identification of System:

System #:

62 Ouatity Group A

5. (a) Applicable Construction Code B31.1 pplcabeEdtioofSecion tiizdfrepi (ib) Applicable Edition of Section XIM Utilized for Repairs or Replacements 1955 Edition.

NIA

Addenda, 19 89 Edition, N/A
Addenda, N/A Code Case NtA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg l Mfg Serial INa I Number I E tional'

~oard i Name of Component Other Identification Year I Built

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Shim, Flat Bar, A-36 Carbon Steel N/A N/A N/A SC# 0206836-3 N/A N/A Replacement N

I

.t I

I I

_~

~

~ II r~~

I

7. Description of Work:

Add shims to support per CR 03-0446,

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure N/A Other VT-3 Pressure N/A psig Test Temperature N/A deg F 03-016-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

I I,.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed S55Ew.

Date Owner or Owneres Designee, Title I-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

.00 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors end the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period 319/2003 to 3124/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Sig nature Commissions 3Z5 I,/nspetor's Signature National Board, State, Providence, and Endorsements Date 4/

/4 03 0

03-016-3

Oer

- 2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REP LACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 31; Nama 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit 2512003 of 2

3 Name 9760 SW 344 Street Florida City, FL 33035 WOM: 32011891-01 CR#:

NIA Address Repair Organization, P.O. No, Job No., etc.

3. Work Performed by Florida Power & Licht Type Code Symbol Stamp NWA Nam

~~~~~~~Authorization Number NWA 9760 SW 344 Street Florida City. FL 33035 Extiration Date WA Address Expiration Date N/A

4. Identification of System:

Supports and Hangers System #:

105 Ouality Group B

5. (a) Applicable Construction Code 1_3311 1955 Edition, N/A
Addenda, NIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, NIA
Addenda, NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of i

Component Mfg Serial Number National Board

Repaired, Replaced, or Replacement ASME Code Stamp Yes/No Other Identification Year Built SF Snubber 3-1038 PSA-35 NA Rpae PSA 11934 NWA NWA N/A NIA Replaced N

Snubber 3-1038 PSA-35 PSA 42410 N/A

[0015324-1 2003 1Replacemnent N

10000448596 Snubber 3-1039 PSA-10 PSA 16241 N/A NIA NIA Replaced N

IN /A Snubber 3-1039 PSA-10 PSA 7782 NIA N/A N/A 1 Replacement N

NIA i

l t

i 1~~~~~~~~NI N/A

7. Description of Work:

Inspect/Functionally Test/Rebuild snubbers as required.

(This NIS-2 is I of 3).

S. Tests Conducted:

Hydrostatic:

N/A 0

Other VT-3 Pneumatic NIA Pressure N/A psig Nominal Operating Pressure N/A Test Temperature NIA deg F 03-017-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed IS/ IS

)1Sk -

Date 6/p/D s Owner or Owner's'Designee, Title 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the perio 6)26/2002 to 3/25/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions My Z

J&nsaectnr's Sianature National Board, State, Providence, and Endorsements I----------

Date 03-017-3

  • ne;
2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Date 3/26/1 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit

?003 of 2

3 CR#:

N/A 0a4re 9760 SW 344 Street Florida Ciy, FL 33035 WOMl 32011891-01 Address Repair Organization. PO. No, Job No., etc.

3. Work Performed by Fldrida Power & Light Type Code Symbol Stamp N/A Narne Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 E

t e

Address ~~~~

~Expiration Date N/A Address

4. Identification of System:

Supports and Hangers System #:

105 Quality Group A

5. (a) Applicable Construction Code,

__B31.1 19 55 Edition, N/A

Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utiized for Repairs or Replacements 19 89 Edition, N/A
Addenda, N/A Code Case,
6. Identification of Components Repaired or Replaced and Replacement Components w
Repaire,

,ASME 1

Repaired, Code Name of i Name of Mfg I Mfg Serial National, Other Year j Replaced, or Stamp Component

! Number Board Identification Built I Replacement Yes/No Snubber 3-1048 PSA-10 PSA 15718 N/A lN/A N/A Replaced N

N/A Snubber 3-1048 PSA-10 PSA 16238 N/AtI NIA N/

I elcmn I N/A Snubber 3-1049 PSA-10 PSA 7782 NIA IN/A N/A Replaced N

_ _ _ ___ INIA Snubber 3-1049 PSA-10 PSA 11461 NIA IN/A N/A I Replacement N

NIA NIA I

7. Description of Work:

Inspect/Functionally Test/Reuild snubbers as required.

(This NIS-2 is 2 of 3)

8. Tests Conducted:

Hydrostatic:

N/A 0

Other VT-3 Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 03-018-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed 5=

-Z,6Z Date 6e7/

r Owner or Owner's Ded!gnee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the perio 612612002 to 3/26/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4 cto'sgignture Commissions /:e:

' [i National Board, State, Providence. and Endorsements 1 6**, 4-9`3 Date 0

03.018-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

  • wrier Florida Power & Light Date 34 Warm 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address

2. Plant Turkey Point Plant Unit Norne WO#: 32011891-9760 SW 344 Street Florida City, FL 33035 Address Repair Orgs
3. Work Performed by Florida Power S Light Type Code Symbol Stamp _

Narre 9760 SW 344 Street Florida City, FL 33035 Authorization Number Address Expiration Date

4. Identification of System:

Supports and Hangers System I:

105 Ouality Group

?6/2003 o -

_ of.2 3

01 CR#:

N/A nihzaon, P.O. No. Job No, etc.

NIA NIA NtA A

5. (a) Applicable Construction Code B31.1 19 55 Edition, NIA
Addenda, (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Edition, N/A
Addenda,
6. Identification of Components Repaired or Replaced and Replacement Components N/A Code Case NIA Code Case I

e I Name of Mfg I

Name of Component I

u Snubber 3-1075 PSA -1/2 PSA Snubber 3-1094 PSA-3PSAI Snubber 3-1075 PSA-1t2 PSA I

Snubber 3-1094 PSA-3 1

PSA Mfg Serial 'National Number i Board 18074 N/A 18072 N/A 1 i

Repaired, i Year Replaced, or I Built I Replacement Other Identification ASME Code Stamp Yes/No N/A N/A NIA N/A I

I N/A !

Replaced N

I I N/A i

' NtA I Replacement N

I i

Ii 17424 N/A I N/A I N/A I N/Ai Replaced N

Snubber 3-1094 PSA-3 PSA 27092 N/A I N/A I N/A l Replacement N

j..

l..

N/A A

I i

I

7. Description of Work:

Inspect/Functionally Test /Rebuild snubbers as required.

This NIS-2 is 3 of 3.

8. Tests Conducted:

Hydrostatic:

N/A Other VT-3 Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 03-019-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks MECHANICAL CONNECTION. NO WELDING REOUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed

==

/9

_...-io Date 4/i/"iY Owner or Owner's Designee, Title I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut. have inspected the components described in this Owners Report during the perio 6/26/2002 to 3/26/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ ~

~

inn~ture______________

_Commissions

/

3 eS Ino~oestor'rs Ainnahirr, National Board, State, Providence, and Endorsements Date C__ _ a-_

03-019-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl iwner Florida Power & Light Date Kam 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address 41112003 1

of 2

3 WOK: 33005095-02 CR#:

N/A iepair Organizatior PDO. No, job No., tc.

2. Plant Turkey Point Plant Unit arne 9760 SW 344 Street Florida City, FL 33035 Address FIirda Power & Light Name
3. Work Performed by Type Code Sy nbol Stamp Authorization Number Expiration Date NIA N/A 9760 SW 344 Street Florida City, FL 33035 N/A Address
4. Identification of System:

Containment Spray System #:

68 Quality Group B

5. (a) Applicable Construction Code.

B31.1 19 55 Edition.

N/A

Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A
Addenda, N/A Code Case
6. Identificatiorl of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National I Board Oter identification Year Built Repaired.

Replaced, or Replacement ASME Code Stamp Yes/No Pump, Pullout assembly, Size 4 x6 Goulds NIA N/A SC# 0069617-1 UTCA 358104 N/A Replacement N

7. Description of Work:

This NIS-2 to document the replacement of pump casing and to perform weld build up and machining of casing.

8. Tests Conducted:

Hydrostatic:

N/A

  • s

^h0-

%r 7 Pneumatic N/A Nominal Operating Pressure NIA Test Temperature 95 deg F 03-020-3

-l M~l we'd Pressure 295 psig

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed Date Owner or Owner's Designee, Title 0

CERTIFICATE OF INSERViCE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have hIsoected the components described I this Owners Report during the period c 3112003 to 4/i12003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

xa4JO59 Commissions 5 ?g Insff Signature National Board, State, Providence, and Endorsements Date 0

03-020-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power & Light Date 4/112003 Name 700 Universe Blvd. Juno Beach. FL 33408 Sheet 1

of 2

Address

2. Plant Turkey Point Plant Unit Narme 9760 SW 344 Street Florida City, FL 33035 3

WO#: 33004558-01 CR1#:

03-0452 Repair Organization, P.O. No, Job No.. atc.

Address Firda Power & Light Name

3. Work Perforrned by Type Code Symbol Stamp Authorization Number Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 N/A N/A Address
4. Identification of System:

CVCS Charging and Letdown System #:

47 Quality Group A

5. (a) Appflcable Construction Code B31.1 19 55 Edition, NWA
Addenda, 1989 Edition, NIA
Addenda, N/A Code Case WIA Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components I

Name of Component Name of Mfg Mfg Serial National Number I Board Other Identification Year Built

Repaired, Replaced, or Rerdaacemevt ASME Code Stamp VacftJ 4

I I



A (1) pc 6" x 10 plate carbon steel. A-36, 1/2-thick N/A N/A N/A SC# 0030265-1 UTC# 443829 N/A Replacement N

(4) pc's 2' x 2 x 1/4" cut to N/A N/A WA SC# 0029598-1 N/A Replacement N

length, Angle A-36 carbon steel, UTC# 428831

7. Description of Work:

Repair broken support H-4 per CR 03-0452

8. Tests Conducted:

Hydrostatic:

N/A 0

Other VT-3 Pneumatic NWA Nominal Operating Pressure N/A Test Temperature NWA deg F 03-021-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 JBack)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WITH THE FPL WELD CONTROL MANUAL.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A

/S/

-S Dt 6

Signed Date tZ441-a-T Owner or Owner's Designee640ite CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have insoected the components described In this Owners Report during the period o 319/2003 to 4/1/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions i

3 lop ctoes Signature National Board, State, Providence, and Endorsements Date 03-021-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS I

As Required by the Provisions of the ASME Code Section Xl Florida Power & Light arme 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 4/3/2003 1

of 2

3 WO#: 31016675-01 CR#:

01-1481 Repair Organinzaton, PO. No, Job No0, et.

2. Plant Turkey Point Plant Unit Nare 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Flbdda Power & Light Name Type Code Symbol Stamp Authorization Number Expiration Date NIA N/A 9760 SW 344 Street Florida City, FL 33035 Address NIA
4. Identification of System:

Intake Cooling Water System #:

1i Quality Group C

5. (a) Applicable Construction Code B31.1 I

I 1955 Edition, N/A

Addenda, WA_ Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Edition, NIA Addenda.

N/A Code Case

6. Identification of Components Repaired or Replaced and Replacement Components 9

r 9

1 Name of Component Name of Mfg Mfg Serial Number Nabonal Board I Other Identification Repaired.

Replaced, or Replacement Year Built ASME Code Stamp Yes/No Angle Steel, ASTM A-36, 4" x 3' x 3/8' N/A N/A N/A SC# 0043839-1 LUTC# 441680 N/A Replacement N

I

7. Description of Work:

Rework support to MRA-CR-01-1481-01

8. Tests Conducted:

Hydrostatic:

N/A 0

Other VT-3 Pneumatic N/A Nominal Operating Pressure NWA Pressure NIA psig Test Temperature N/A deg F 03-022-3

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks ALL WELDING PERFORMED IN ACCORDANCE WiTH THE FPL WELD CONTROL MANUAL.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

MA Signed

/ S/

Owner or Owneres Designa, Title Date 6^/R/c > P CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described In this Owners Report during the period o 9/1712001 to 41312003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions

/C Z

I pectores Signature National Board, State, Providence, and Endorsements Date

-4

° 3 0

'03-022-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Oner Florida Power & Light Name 700 Universe Blvd. Juno Beach. FL 33408 Address Date 5/211/2003 Sheet 1

of 2

. 2. Plant Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Unit 3

WO#: 32022760-01 CR1:

N/A rtepair Oranizaltion, P.O. No, Job Now, etc.

3. Work Performed by Forida Power & Light Name' Type Code Symbol Stamp Authorization Number Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 Address N/A N/A
4. Identification of System:

Component Cooling Water System #:

30 Ouality Group C

5. (a) Applicable Construction Code -

531.1 19 55 Edition, N/A

Addenda, N/A Code Case (b) Appflcable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition, N/A
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (6) Nuts, Heavy Hex, 3/4 NIA N/A N/A SC #0045910-1 N/A Replacement N

UNC-2B, ASME SA-194 Gr 7 UTC# 419593 (4) Studs from All thread, 314 -

N/A NIA NA SC # 0029493-2 N/A Replacement N

10UNC-2A, ASTMA-193GrB7 irUTC# 449812

7. Description of Worki Replace channel head nuts (6) and studs (4)
8. Tests Conducted:

Hydrostatic:

N/A 0

Other NIA Pneumatic NIA Nominal Operating Pressure N/A Pressure N/A psig Test Temperature N/A deg F 03-023-3

Sheet 2 of 2 FORM NIS-2 (Back) 9-Remarks MECHANICAL CONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

MA Signed

/S-'

S A,

£C>L-Date 64,>-

r r

Owner or Owners Desiyhee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report during the period c 1213112002 to 512112003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, conceming the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

o e

Commiss'ions f'

3ZE Insp 9w's Signature

/dA/l3 National Board, State, Proidence, and Endorsements Date

1 03-023-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS I

As Required by the Provisions of the ASME Code Section Xl Florida Power & Light Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 5U2912003 1

of 2

3 WO: 32015300-01 CR#:

NWA Repair Orftn-1 P. No. Job No. ec

2. Plant Turkey Point Plant Uhit Klem 9760 SW 344 Street Florida Cfty, FL 33035 Address
3. Work Performed by Flkibia Power& Light Type Code Symbol Stamp Authorization Number Expiration Date NIA NIA 9760 SW 344 Street Florida City, FL 33035 W/A Address
4. Identification of System:

Containment Airlocks I Hatches

_System #:

51 Quality Group B

  • 5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 Edition, N/A
Addenda, N/A Code Case.
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired.

Code Name of Name of Mi Serial Niational Other Year Replaced, or Stamp Camponent Number Board Identification Built Replacement Yes/No Vaive, 2 Gate, 800 Class, SW N/A NWA NWA SC# 0052777-1.

NIA Replacement N

ends. SA351-CF8M. Pressure UTC# 448720 Seal Pipe. 2 ASME SA,3121376 N/A N/A NfA SC# 0030803-1 N/A Replacement N

Type 304, Seamless Sch 10 UTC# 391850 Pipe Cap, 2. 3000 lbs, ASME NIA N/A N/A SC# 0046389-1 N/A Replacement N

SA-182 F304 UTC# 447986

7. Description of Work.

Perform P-34 Mod with valve 3-40-205 change

  • sts Conducted:

Hydrostatic:

NIA Other VT-2 Pneumatic N/A Noninal Operating Pressure X

Test Temperature htsf deg F 03.024-3 Pressure 100 psig

Sheet 2 of 2 FORM NIS-2 (Back) 9-Remarks ALL WELDING PERFORMED IN ACCORDANCE WiTH THE FPL WELD CONTROL MANUAL CODE CASE N-4$6.1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

WA Signed Date _________

Owner or Owners Designee, Title e

CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florkda and employed bv HSBCT of Hartford. Connecticut, have Insoected the components described in this Owners Report during the period a 911612002 to 5r9/2003 and state that to the best of my knowledge and beflef, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described i this Owners' Report. Furthermore, neither the Inspector nor his employer shal be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions

_3 I

ctors Signature Nallonal Board. State. Providence. and Endorsements Date_________

03-024-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power & Ught Mane 700 Universe Blvd. Juno Beach, FL 33408 Addness Turkey Point Plant Raun 9760 SW 344 Street Florida City. FL 33035 Address Date Sheet 6/152003 I

of 2

3 WO#: 32000625-01 CR#:

N/A Unit

2. Plant
3. Work Performed by Florida Power & Ught Nme Repair Orgaramon, P.O.
o. Jeob No. etc.

Type Code Symbol Stamp NJA Authorization Number N/A Expiration Date NtA 9760 SW 344 Street Florida City, FL 33035 Address Main Feedwater

4. Identification of System:

_System #:

74 duality Group B

5. (a) Applicable Construction Code 931.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, NIA
Addenda, 1989 Edition, NIA
Addenda, NWA Code Case NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME
Repaired, Code Name of Name of Mfg Mfg Serial National Other Year Replaced, or Stamp Component Number Board Identification Built Replacement Yes/No (4) Pipe,2 ASME SA-106 Gr 6 NWA WNA NWA SC# 0030663-1.

N/A Replacement N

Sch 80 Carbon Steeel UTC# 428095 (2) Elbows. 1-12? 90 deg.

N/A WIA NWA SC# 0034037-1 NWA Relacement

(1) Valve, 1-11r Gate Carbon N/A NtA NtA SC# 0052751-1 NIA Replaoement N

Steel ASTM A-105 Class 1500 UTC# 379986 Sch 80

7. Description of Work NIS-2 Is to doccument replacement of valves 3-20-710 and associated piping.

sts Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure N/A Other VT-2 Pressure 1543 psig Test Temperature 101 deg F 03.025-3

Sheet 2 of 2 FORM NIS-2 (Back)

I 9-Remarks ALL WELDING PERFORMED IN ACCORDANCE WiTH THE FPL WELD CONTROL MANUAL.

CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section )X.

Type Code Symbol Stamp N/A Certificate of Authorkiztion No.

N/A

-Expiration Date:

NMA Signed Date 4C/4Z Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed bv HSBCT of Hartford. Connecticut. have Insoected the components described In this Owners Report during the period o 3/412002 to 615/2003 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

commissions 3Z e I spectors Signature National Board, State, Providence, and Endorsements Date 03-025-3