IR 05000321/1980018

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-321/80-18 & 50-366/80-18 on 800331-0402. Noncompliance Noted:Failure to Perform post-mod Testing
ML19318A505
Person / Time
Site: Hatch  
Issue date: 04/30/1980
From: Burnett P, Dance H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19318A484 List:
References
50-321-80-18, 50-366-80-18, NUDOCS 8006230237
Download: ML19318A505 (4)


Text

,.,,.

8[

%,,

UNITED STATES NUCLEAR REGULATORY COMMISSION o

.

$

I REGION 11

.

o 101 MARIETTA ST N.W., SUITE 3100 ATLANTA, GEORGIA 30303

.....

.

,

Report Nos. 50-321/80-18 and 50-366/80-18 Licensee: Georgia Power Company 270 Peachtree Street Atlanta, GA 30303 Facility Name: Hatch Docket Nos. 50-321 and 50-366 License Nos. DPR-57 and NPF-5 Inspection at Plant Match, near Baxley, GA Inspectors:

@'

-

- 3d - 60 H. C. DariceN Date Signed

}/AnuW

'YdfY

- \\

M. Burnetr ~ '

Date Signed Approved by:

R. C. Lewis, Acting Chief, RONS Branch Date Signed SUMMARY Inspection on March 31 to April 2, 1980

!

Areas Inspected This special, announced inspection involved 32 inspector-hours on site in the areas of followup of resident-inspector identified items of noncompliance, unit startup operations and post-modification testing.

Results of the three areas inspected, no items of noncompliance or deviations were p

identified in two areas; one apparent item of noncompliance was found in one area (Infraction - failure to perform post-modification testing paragraph 7).

-

e.

'

t 8 0062 80 2.$ 9 h

.-..

.

.

,

.

DETAILS 1.

Persons Contacted Licensee Personnel

  • W. A. Widner, Vice President Nuclear Generation
  • M. Manry, Plant Manager T. V. Green, Assistant Plant Manager S. K. Baxley, Superintendent of Operations
  • C. L. Coggins, Superintendent of Engineering Services H. W. Dyer, Operations Suprevisor
  • G. B. Ellis, I&C Supervisor F. Gorley, Shift Supervisor
  • S. F. Curtis, Reactor Engineer
  • C. E. Belflower QA Site Supervisor
  • G. E. Spell, Jr., Senior QAFR Other licensee personnel contacted included two shift foremen and six control room operators.

Other Organizations Southern Company Services

.

L. K. Mathews, Manager Core Analysis and Licensing NRC Resident Inspector R. F. Rogers, Senior Resident Inspector

  • Attended exit interview 2.

Exit Interview A meeting was held with those persons indicated in paragraph 1 on April 2, 1980. The scope and findings of the inspection were presented. The items of noncompliance related to the startup of unit 2 on January 28-29, 1980, which had been identified by the Senior Resident Inspector and reviewed

,

during this inspection, were discussed. Also discussed, was another item of noncompliance involving failure to adequately test the rod sequence control system (RSCS) for unit 2 following modifications. The licensee acknowledged the comments. The inspectors stated that they accepted the arguments and analysis put forth by the licensee that the out-of prescribed-order control rod withdrawal that occurred during the January 28-29 event

,

l did not appear to constitute an unreviewed safety question. ~

The inspectors stated that the number of errors associated with this startup

-

,

i is indicative that management controls have not been effective. The inspec-

,

tors stated that a meeting between Georgia Power Company management and the

_ _ -

_

-

.

,

-2-

.

Director of Region II would be recommended. A meeting with GPC in Region II to dsicuss the items of noncompliance was subsequently held on April 16, 1980 (IE Report Nos. 50-321/80-20 and 50-366/80-20).

<

3.

Licensee Action of Previous Inspection Findings The special inspection took place in response to the items of noncompliance identified by the resident inspector (Inspection Report No. 50-366/80-11),

4.

Unresolved Items No new unresolved items were identified during this inspection.

5.

Review of Unit 2 Startup Activities In the course of the startup of unit 2 on January 28-29, 1980, two control rods were not withdrawn in the prescribed order.

One of the rods was later withdrawn by improperly bypassing control-rod position reed switches. This event and the related items of noncompliance are described in detail in the resident inspector's report (50-366/80-11). A late licensee event report, LER 50-366/1980-023, was issued by the licensee to describe the occurrence.

The inspectors discussed the event with reactor operators, the reactor engineer and other members of the plant staff, and reviewed control room log books for the period in question. The inspectors concluded that the sequence of events was most likely different from that described in LER-023.

Specifically it appeared unlikely that the out-limit reed switch on rod 46-23 had been bypassed to permit movement of that rod in sequence and the required motion overlooked.

It appeared that rod 46-43 (a group 2 rod) had been inadvertently skipped over', assumed to be withdrawn without independent verification of position, and then by passed to improperly clear a proper RSCS rod withdrawal block when a group 3 rod was selected. The licensee concurred with this interpretation of events and agreed to submit a revised LER.

An item of concern raised when this event was first reported was whether or not an unreviewed safety question existed with respect to an increased probability or consequence of the rod drop accident. Prior to the inspec-tion this issue was discussed extensively in telephone conversations with members of the IE Headquarters technical staff and NRR project management.

During this inspection the licensee and his technical consultant addressed this issue in a line-by-line comparison with the requirements of 10 CFR 50.59.

Their conclusion was that no unreviewed safety question existed. When asked if the issue of an unreviewed safety question had been considered prior to withdrawing rod 46-43, a licensee representative stated no.

He then went on to say that the control rod configuration and power level were identical with conditions that exist during control rod scram time testing, when use of by pass switches to facilitate control rod withdrawal is auth-orized under special test exception 3.10.2 of Technical Specifications.

.

eq%QwH%% w HWh '

_W'

__

vW~'

- ~'

  1. ' ' " ~
  • '**~~***"YT*"

-~*

~ **

.

_

-

--.

_-

-

. -.

---. - - -.

.

.

,-

.

'e-3-Based upon all of the foregoing the inspectors concluded that there was no issue of an unreviewed safety question.

6.

Procedure Review Applicable plant procedures were reviewed for their relationship with the management control of the control rod error events for the January 28-29, 1980 startup. The following procedures were reviewed.

HNP 2-9207 Rev 1 Rod Movement Sequences HNP 2-9402 Rev 1 Control Rod Scram Testing HNP 2-1001 Rev 7 Normal Startup HNP 2-2900 Rev 1 All A/B Sequence Rods not Full Out HNP 2-2901 Rev 2 Rod bypassed HNP 2-1924 Rev 1 RPIS Failure HNP 2-2902 Rev 1 Rod Sequence Control System Malfunction The review determined that instructions were not provided or were inadequate-to control the bypassing of the control rod limit switches, to define the operability of the Rod Sequence Control System, and how to cope with an out of sequence control rod. These omissions contributed to the errors associ-ated with these events during the startup. The licensee stated that instruc-tions addressing RSCS operability would be provided to cover these cases (366/80-18-02). This is related to and will be reviewed along with the corrective actions taken for the items of noncompliance in the resident laspectors report dealing with procedural matters.

7.

Design Control The inspector reviewed Design Change Request (DCR) No.79-342 associated with the Licensee Event Report 50-366/1980-008 Rev. I dated March 19, 1980, in which the rod sequence control system (RSCS) was found inoperable in notch control. The design change was confirmed to have had a preliminary review by the plant review board. The inspector judged the DCR to be erroneously checked as not involving a safety system; however, the main issue dealt with the inadequate checkout following the modification completion on December 2-3, 1979, with the unit at power. According to the associated Maintenance Request, the functional test was completed on or about January 16, 1980, during a control rod sequence exchange. In addition to not being timely, this specific test was performed at a power level in which the RSCS

'

is automatically bypassed and therefore the test was inadequate. No other checkout was indicated to have been performed following the modification.

Thus the inoperability of the RSCS in notch control was not noted until the reactor startup on January 29, 1980. This failure to perform a timely and appropriate test following a modification is an apparent item of noncompli-ance (366/80-18-01) with Technical Specification 6.8.1.

HNP-809, Plant Modifications, which implements these requirements states tha't functional tests that are more than simple tests that can be described on the

-

Maintenance Request must be provided written and approved functional test procedures..The test specified for this modification did not recognize that something more than a simple observation was warranted.

.

- -,