. , , Cr;mmonweattle 14 hum Compan)-

- laNalle Generating $t,stion i

' Sol North list Road I

    • Marseilles,11. 613 il 997 Tel 815 .MW61 l

l I

l l

June 10,1996  !

United States Nuclear Regulatory Commission l Attention: Document Control Desk  !

Washington, D.C. 20555

Subject:

LaSalle County Station, Units 1 and 2 Surveillance Requirements for Leak Detection local temperature sensors.

NRC Docket Numbers 50-373 and 50-374.

l

Reference:

Licensee Event Report # 85-021-00, Docket #050-374, dated May 29,1985. "RCIC Leak Detection Mis-wired."

The enclosed letter is to inform you of a change to a corrective action that was transmitted with the Reference letter.

A corrective action listed in LER 85-021, on page 3 stated; "Long term corrective actions include a mechanism to insure that all Leak Detection local temperature sensors are heat checked on a periodic basis to validate proper wiring. Also all modifications to the Leak Detection temperature monitoring sensors and cabling will include a functional test initiated at the sensor." This corrective action to heat check all Leak Detection local temperature sensors on a periodic basis was an over commitment that did not address the root cause of the problem. The root cause

, was an original construction mis-wiring of the detection sensors. This corrective action to perform a periodic check of the sensors will be discontinued. LaSalle has performed these surveillances for the past eleven years and the data shows that no additional mis-wiring problems have been discovered. All modifications to the Leak Detection temperature monitoring sensors and cabling will still include a functional test initiated at the sensor to identify any wiring problems.

1 This action will result in a substantial dose reduction and eliminate unnecessary work.

170039 960618o263 960610 PDR ADOCK 05000374 S PDR L [i D A Unicom Company

4 if there are any questions or comments concerning this letter, please refer

- them to me at (815) 357-6761, extension 2212.

Respectfully,

)

D.J. Ray Station Manager LaSalle County Station Enclosure .

cc: H. J. Miller, NRC Region Ill Administrator P. G. Brochman, NRC Senior Resident inspector - LaSalle C. H. Mathews, IDNS Resident Inspector - LaSalle F. Niziolek, IDNS Senior Reactor Analyst INPO - Records Center D. L. Farrar, Nuclear Regulatory Services Manager I