| | | Reporting criterion |
|---|
| 05000373/LER-1982-001-03, /03L-0:on 820417,while Performing Electrical Maint Test,Diesel Fire Pump Ob Tripped After 3 Minutes Running in Auto Position.Caused by Broken Speed Cable.Broken Cable Replaced | /03L-0:on 820417,while Performing Electrical Maint Test,Diesel Fire Pump Ob Tripped After 3 Minutes Running in Auto Position.Caused by Broken Speed Cable.Broken Cable Replaced | |
| 05000373/LER-1982-001, Forwards LER 82-001/03L-0.Detailed Event Analysis Encl | Forwards LER 82-001/03L-0.Detailed Event Analysis Encl | |
| 05000373/LER-1982-002-03, /03L-0:on 820419,station Vent Stack Flow Recorder DFR-VR019 Read Downscale.Caused by Flow Transmitter Core Hung at Zero Point.Flow Transmitter Repaired | /03L-0:on 820419,station Vent Stack Flow Recorder DFR-VR019 Read Downscale.Caused by Flow Transmitter Core Hung at Zero Point.Flow Transmitter Repaired | |
| 05000373/LER-1982-002, Forwards LER 82-002/03L-0 | Forwards LER 82-002/03L-0 | |
| 05000373/LER-1982-003-03, /03L-0:on 820421,during Grouting of Smoke Detector in Switchgear Battery Room Ceiling,Control Room Alarm Actuated.Caused by Failure to Soak Penetrations for 24-h Prior to Grouting.Penetration Sealed.Detector Replaced | /03L-0:on 820421,during Grouting of Smoke Detector in Switchgear Battery Room Ceiling,Control Room Alarm Actuated.Caused by Failure to Soak Penetrations for 24-h Prior to Grouting.Penetration Sealed.Detector Replaced | |
| 05000373/LER-1982-003, Forwards LER 82-003/03L-0 | Forwards LER 82-003/03L-0 | |
| 05000373/LER-1982-004, Forwards LER 82-004/03L-0 | Forwards LER 82-004/03L-0 | |
| 05000373/LER-1982-004-03, /03L-0:on 820422,sealing Tubing Under Reactor Bldg Trackway Doors Found Partially Pulled Out.Cause Undetermined.Tubing Replaced.Doors Locked Closed W/Shift Engineer Maintaining Control Over Key | /03L-0:on 820422,sealing Tubing Under Reactor Bldg Trackway Doors Found Partially Pulled Out.Cause Undetermined.Tubing Replaced.Doors Locked Closed W/Shift Engineer Maintaining Control Over Key | |
| 05000373/LER-1982-005, Forwards LER 82-005/03L-0 | Forwards LER 82-005/03L-0 | |
| 05000373/LER-1982-005-03, /03L-0:on 820426,OB Control Room HVAC Emergency Makeup Train Found Inoperable.Caused by Binding Limit Switch on Damper OVCO2YB.Limit Switch Adjusted | /03L-0:on 820426,OB Control Room HVAC Emergency Makeup Train Found Inoperable.Caused by Binding Limit Switch on Damper OVCO2YB.Limit Switch Adjusted | |
| 05000373/LER-1982-006, Forwards LER 82-006/03L-0 | Forwards LER 82-006/03L-0 | |
| 05000373/LER-1982-006-03, /03L-0:on 820419,one Shift Channel Was Missed During Reactor Bldg in Fuel Pool Vent Exhaust Radiation Channel Check.Caused by Misinterpretation of Tech Specs. Personnel Reinstructed | /03L-0:on 820419,one Shift Channel Was Missed During Reactor Bldg in Fuel Pool Vent Exhaust Radiation Channel Check.Caused by Misinterpretation of Tech Specs. Personnel Reinstructed | |
| 05000373/LER-1982-007, Forwards LER 82-007/03L-0 | Forwards LER 82-007/03L-0 | |
| 05000373/LER-1982-007-03, /03L-0:on 820418-24,operating Personnel Used Newly Installed Vent Stack Radiation Microprocessor Rather than Monitor Ref by Surveillance.On 820424-28,no Radiation Readings Taken.Caused by Personnel Unawareness of New Sys | /03L-0:on 820418-24,operating Personnel Used Newly Installed Vent Stack Radiation Microprocessor Rather than Monitor Ref by Surveillance.On 820424-28,no Radiation Readings Taken.Caused by Personnel Unawareness of New Sys | |
| 05000373/LER-1982-008-03, /03L-0:on 820428,vent Stack Recorder Read at Level Higher than Operating Conditions Estimate.Caused by Failure of Flow Transmitter.Transmitter Repaired | /03L-0:on 820428,vent Stack Recorder Read at Level Higher than Operating Conditions Estimate.Caused by Failure of Flow Transmitter.Transmitter Repaired | |
| 05000373/LER-1982-008, Forwards LER 82-008/03L-0 | Forwards LER 82-008/03L-0 | |
| 05000373/LER-1982-009, Forwards LER 82-009/03L-0 | Forwards LER 82-009/03L-0 | |
| 05000373/LER-1982-009-03, /03L-0:on 820505,during Surveillance,Level Scram Switch 1B21-NO24D Had Excessive Hysterisis.Caused by Switch Cam Rubbing Against Switch Plate Spacer.Work Request Initiated 820506 & Level Switch Declared Operable | /03L-0:on 820505,during Surveillance,Level Scram Switch 1B21-NO24D Had Excessive Hysterisis.Caused by Switch Cam Rubbing Against Switch Plate Spacer.Work Request Initiated 820506 & Level Switch Declared Operable | |
| 05000373/LER-1982-010, Forwards LER 82-010/03L-0 | Forwards LER 82-010/03L-0 | |
| 05000373/LER-1982-010-03, /03L-0:on 820428,B Fuel Pool Cooling Ventilation Exhaust Radiation Monitor Read Greater than Tech Spec Allowance.Caused by Failure of Geiger Muller Tube.Tube Replaced & Monitor Returned to Svc | /03L-0:on 820428,B Fuel Pool Cooling Ventilation Exhaust Radiation Monitor Read Greater than Tech Spec Allowance.Caused by Failure of Geiger Muller Tube.Tube Replaced & Monitor Returned to Svc | |
| 05000373/LER-1982-011-03, /03L-0:on 820502,continuous Sampling of Main Stack Gaseous Effluent Not Immediately Established When Bus 141Y Was Taken Down for Cleaning,Causing Monitoring Sys to Be Inoperable.Caused by Temporary Power Outage | /03L-0:on 820502,continuous Sampling of Main Stack Gaseous Effluent Not Immediately Established When Bus 141Y Was Taken Down for Cleaning,Causing Monitoring Sys to Be Inoperable.Caused by Temporary Power Outage | |
| 05000373/LER-1982-011, Forwards LER 82-011/03L-0 | Forwards LER 82-011/03L-0 | |
| 05000373/LER-1982-012-03, /03L-0:on 820505,RHR Shutdown Cooling Suction Line High Flow Differential Pressure Switch Indicated Negative Pressure During Pump Startup in Shutdown Cooling Mode.Caused by Instruments Being Replaced During Preoperational Te | /03L-0:on 820505,RHR Shutdown Cooling Suction Line High Flow Differential Pressure Switch Indicated Negative Pressure During Pump Startup in Shutdown Cooling Mode.Caused by Instruments Being Replaced During Preoperational Testing | |
| 05000373/LER-1982-012, Forwards LER 82-012/03L-0 | Forwards LER 82-012/03L-0 | |
| 05000373/LER-1982-013-03, /03L-0:on 820419,svc Water & Two Loops of RHR Svc Water Effluent Monitor Alarm/Trip Setpoints Not in Compliance W/Tech Specs.Caused by Instrument Surveillance for Effluent Monitors Not Revised to Reflect Current Change | /03L-0:on 820419,svc Water & Two Loops of RHR Svc Water Effluent Monitor Alarm/Trip Setpoints Not in Compliance W/Tech Specs.Caused by Instrument Surveillance for Effluent Monitors Not Revised to Reflect Current Change | |
| 05000373/LER-1982-013, Forwards LER 82-013/03L-0 | Forwards LER 82-013/03L-0 | |
| 05000373/LER-1982-014, Forwards LER 82-014/03L-0 | Forwards LER 82-014/03L-0 | |
| 05000373/LER-1982-014-03, /03L-0:on 820501,station Stack Flow Recorder Reading Low.Caused by Flow Transmitter Failure.Validyne P232 Flow Transmitter Replaced | /03L-0:on 820501,station Stack Flow Recorder Reading Low.Caused by Flow Transmitter Failure.Validyne P232 Flow Transmitter Replaced | |
| 05000373/LER-1982-015, Forwards LER 82-015/03L-0 | Forwards LER 82-015/03L-0 | |
| 05000373/LER-1982-015-03, /03L-0:on 820417,fire Doors Were Not Inspected Daily or Weekly as Required by Lsf 172 Per Tech Spec.Caused by Security Personnel Inadvertently Deleting Insp.Daily & Weekly Fire Door Insp Immediately Established | /03L-0:on 820417,fire Doors Were Not Inspected Daily or Weekly as Required by Lsf 172 Per Tech Spec.Caused by Security Personnel Inadvertently Deleting Insp.Daily & Weekly Fire Door Insp Immediately Established | |
| 05000373/LER-1982-016, Forwards LER 82-016/03L-0 | Forwards LER 82-016/03L-0 | |
| 05000373/LER-1982-016-03, /03L-0:on 820505,Div II 125-volt Dc Battery Pilot Cells Specific Gravities Found Lower than Tech Specs.Caused by Increase in Dc Loads During Switchgear Cleaning Outage. Battery Charged | /03L-0:on 820505,Div II 125-volt Dc Battery Pilot Cells Specific Gravities Found Lower than Tech Specs.Caused by Increase in Dc Loads During Switchgear Cleaning Outage. Battery Charged | |
| 05000373/LER-1982-017-03, /03L-0:on 820425,during Performance of Instrument Surveillance LIS-PC-05,standby Gas Treatment Suction Valves 1(2)VG001 Did Not Open.Caused by Four Lifted Leads Preventing Opening of Suction Valves.Leads Reterminated | /03L-0:on 820425,during Performance of Instrument Surveillance LIS-PC-05,standby Gas Treatment Suction Valves 1(2)VG001 Did Not Open.Caused by Four Lifted Leads Preventing Opening of Suction Valves.Leads Reterminated | |
| 05000373/LER-1982-017, Forwards LER 82-017/03L-0 | Forwards LER 82-017/03L-0 | |
| 05000373/LER-1982-018-03, /03L-0:on 820504,ultraviolet Fire Detectors to Refuel Floor de-energized to Prevent Damage While Completing Welding on Reactor Side.Welding Completed & Fire Detectors Back in Svc on 820514 | /03L-0:on 820504,ultraviolet Fire Detectors to Refuel Floor de-energized to Prevent Damage While Completing Welding on Reactor Side.Welding Completed & Fire Detectors Back in Svc on 820514 | |
| 05000373/LER-1982-018, Forwards LER 82-018/03L-0 | Forwards LER 82-018/03L-0 | |
| 05000373/LER-1982-019-03, /03L-0:on 820519,LPCS Injection Valve Permissive Switch 1E21-N006 Found Piped Incorrectly.Caused by Line Reversal on Mechanical Drawing.Piping Error Will Be Corrected.Drawing Change Requested | /03L-0:on 820519,LPCS Injection Valve Permissive Switch 1E21-N006 Found Piped Incorrectly.Caused by Line Reversal on Mechanical Drawing.Piping Error Will Be Corrected.Drawing Change Requested | |
| 05000373/LER-1982-019, Forwards LER 82-019/03L-0 | Forwards LER 82-019/03L-0 | |
| 05000373/LER-1982-020-03, /03L-0:on 820512,while Performing LOS-FP-W2,OA Diesel Tripped After Running 2 Mins.Caused by Operator Shorting Out Starter W/Engine Oil Dipstick During Test. Control Circuit Repaired | /03L-0:on 820512,while Performing LOS-FP-W2,OA Diesel Tripped After Running 2 Mins.Caused by Operator Shorting Out Starter W/Engine Oil Dipstick During Test. Control Circuit Repaired | |
| 05000373/LER-1982-020, Forwards LER 82-020/03L-0.Detailed Event Analysis Encl | Forwards LER 82-020/03L-0.Detailed Event Analysis Encl | |
| 05000374/LER-1982-021, Informs of Change in C/A in LER 82-021-00 Re RCIC Leak Detection Miswired | Informs of Change in C/A in LER 82-021-00 Re RCIC Leak Detection Miswired | |
| 05000373/LER-1982-021-03, /03L-0:on 820515,outside Air Radiation Monitor 2D18-K751A Failed High.Caused by Rain Water Seeping Into Circuitry Around Conduit,Junction Boxes or Metal to Metal Interfaces.Detectors Will Be Sealed | /03L-0:on 820515,outside Air Radiation Monitor 2D18-K751A Failed High.Caused by Rain Water Seeping Into Circuitry Around Conduit,Junction Boxes or Metal to Metal Interfaces.Detectors Will Be Sealed | |
| 05000373/LER-1982-021, Forwards LER 82-021/03L-0 | Forwards LER 82-021/03L-0 | |
| 05000373/LER-1982-022-03, /03L-0:on 820523,emergency Makeup Train Heater Temp Switch for Control Room HVAC Tripped.Caused by Inadvertent Closure of Tornado Damper Which Blocked All Suction to Train Thus Raising Temp & Tripping Switch | /03L-0:on 820523,emergency Makeup Train Heater Temp Switch for Control Room HVAC Tripped.Caused by Inadvertent Closure of Tornado Damper Which Blocked All Suction to Train Thus Raising Temp & Tripping Switch | |
| 05000373/LER-1982-022, Forwards LER 82-022/03L-0.Detailed Event Analysis Encl | Forwards LER 82-022/03L-0.Detailed Event Analysis Encl | |
| 05000373/LER-1982-023, Forwards LER 82-023/03L-0 | Forwards LER 82-023/03L-0 | |
| 05000373/LER-1982-023-03, /03L-0:on 820524,piston Seal on Damper Actuator Failed to Operate in Control Room Emergency HVAC Sys.Caused by Personnel Failure to Adequately Review Degraded Equipment Log.Other HVAC Train Repaired & Parts Ordered for Dampe | /03L-0:on 820524,piston Seal on Damper Actuator Failed to Operate in Control Room Emergency HVAC Sys.Caused by Personnel Failure to Adequately Review Degraded Equipment Log.Other HVAC Train Repaired & Parts Ordered for Damper | |
| 05000373/LER-1982-024-03, /03L-0:on 820526,fuel Oil Found Leaking from Flange on Flexible Fuel Line Connecting Day Tank to Diesel Fire Pump 0A.Caused by Broken Flexible Fuel Line.Temporary Copper Tube Fuel Line Installed & Pump Tested | /03L-0:on 820526,fuel Oil Found Leaking from Flange on Flexible Fuel Line Connecting Day Tank to Diesel Fire Pump 0A.Caused by Broken Flexible Fuel Line.Temporary Copper Tube Fuel Line Installed & Pump Tested | |
| 05000373/LER-1982-024, Forwards LER 82-024/03L-0 | Forwards LER 82-024/03L-0 | |
| 05000373/LER-1982-025, Updated LER 82-025/03X-1:on 820516 & 17,during Leak Rate Testing,Drywell Equipment Sump Pump Started & Pumped Down Sump.Caused by Control Switches for Valves 1RE024 & 25 Left in Auto Position Instead of Closed Position | Updated LER 82-025/03X-1:on 820516 & 17,during Leak Rate Testing,Drywell Equipment Sump Pump Started & Pumped Down Sump.Caused by Control Switches for Valves 1RE024 & 25 Left in Auto Position Instead of Closed Position | |