| | | Reporting criterion |
|---|
| 05000328/LER-1982-001, Forwards LER 82-001/03L-0 | Forwards LER 82-001/03L-0 | |
| 05000328/LER-1982-001-03, /03L-0:on 820103,ice Condenser Intermediate Deck Door 9.B Discovered Frozen Shut.Caused by Humidity Entering Through Top Deck Blanket Vents,Condensed on I-beams & Dripping Onto Intermediate Deck Door.Ice Removed | /03L-0:on 820103,ice Condenser Intermediate Deck Door 9.B Discovered Frozen Shut.Caused by Humidity Entering Through Top Deck Blanket Vents,Condensed on I-beams & Dripping Onto Intermediate Deck Door.Ice Removed | |
| 05000328/LER-1982-002-03, /03L-0:on 820112,turbine Driven Auxiliary Feedwater Pump Declared Inoperable Due to Failure to Start on Safety Actuation.Caused by Failure to Reset Electronic Overspeed Trip Latch Function.Valve Trip Latch Reset | /03L-0:on 820112,turbine Driven Auxiliary Feedwater Pump Declared Inoperable Due to Failure to Start on Safety Actuation.Caused by Failure to Reset Electronic Overspeed Trip Latch Function.Valve Trip Latch Reset | |
| 05000328/LER-1982-002, Forwards LER 82-002/03L-0 | Forwards LER 82-002/03L-0 | |
| 05000327/LER-1982-003-03, /03L-0:on 820109,pressurizer Level Channel (1-LT-68-320)was Declared Inoperable Due to High Reading. Caused by Loss of Filled Leg Between Condensate Reservoir & Sensor Bellows Due to Evaporation of Fluid.Line Refilled | /03L-0:on 820109,pressurizer Level Channel (1-LT-68-320)was Declared Inoperable Due to High Reading. Caused by Loss of Filled Leg Between Condensate Reservoir & Sensor Bellows Due to Evaporation of Fluid.Line Refilled | |
| 05000327/LER-1982-003, Forwards LER 82-003/03L-0 | Forwards LER 82-003/03L-0 | |
| 05000328/LER-1982-004-03, /03L-0:on 820115,vital Battery Bank II Cell Temp Found to Be Less than 60 F,Rendering Sys Inoperable.Caused by Two Exhaust Fan Dampers Open Simultaneously.One Damper Closed & Room Heat Increased | /03L-0:on 820115,vital Battery Bank II Cell Temp Found to Be Less than 60 F,Rendering Sys Inoperable.Caused by Two Exhaust Fan Dampers Open Simultaneously.One Damper Closed & Room Heat Increased | |
| 05000328/LER-1982-004, Forwards LER 82-004/03L-0 | Forwards LER 82-004/03L-0 | |
| 05000328/LER-1982-005-03, /03L-0:on 820113,remote Shutdown Instrument Channel or Pressurizer Relief Tank Level Declared Inoperable Due to Failure to Meet Surveillance Requirements Caused by Faulty Resistor in Transmitter Circuit Card | /03L-0:on 820113,remote Shutdown Instrument Channel or Pressurizer Relief Tank Level Declared Inoperable Due to Failure to Meet Surveillance Requirements Caused by Faulty Resistor in Transmitter Circuit Card | |
| 05000328/LER-1982-005, Forwards LER 82-005/03L-0 | Forwards LER 82-005/03L-0 | |
| 05000327/LER-1982-006-03, /03L-0:on 820115,turbine Driven Auxiliary Feedwater Pump Declared Inoperable Due to Failure to Meet Surveillance Requirements.Caused by Malfunction in Controller 1-FIC-46-57.Controller Replaced | /03L-0:on 820115,turbine Driven Auxiliary Feedwater Pump Declared Inoperable Due to Failure to Meet Surveillance Requirements.Caused by Malfunction in Controller 1-FIC-46-57.Controller Replaced | |
| 05000327/LER-1982-007, Forwards LER 82-007/03L-0 | Forwards LER 82-007/03L-0 | |
| 05000327/LER-1982-007-03, /03L-0:on 820108,in Mode 1 at 100% Power,Rod Position Indicator P-4 (Shutdown Bank a) Indicated Greater than 12 Steps Below Step Counter.Defective Indicator Recalibr & Returned to Svc.Connector Pins Cleaned | /03L-0:on 820108,in Mode 1 at 100% Power,Rod Position Indicator P-4 (Shutdown Bank a) Indicated Greater than 12 Steps Below Step Counter.Defective Indicator Recalibr & Returned to Svc.Connector Pins Cleaned | |
| 05000327/LER-1982-008, Forwards LER 82-008/03L-0 | Forwards LER 82-008/03L-0 | |
| 05000327/LER-1982-008-03, /03L-0:on 820114,auxiliary Feedwater Level Control Valve 1-1CV-3-156 Would Not Operate While Attempting to Control Level on Steam Generator.Caused by Failure of Valve Position Controller.Controller Replaced | /03L-0:on 820114,auxiliary Feedwater Level Control Valve 1-1CV-3-156 Would Not Operate While Attempting to Control Level on Steam Generator.Caused by Failure of Valve Position Controller.Controller Replaced | |
| 05000328/LER-1982-009-03, /03L-0:on 820111,in Mode 1 at 8% Rtp,Steam Generator Blowdown Containment Isolation valve,2-FCV-1-7, Operator Diaphragm Ruptured Rendering Valve Inoperable. Caused by Normal Wear.Diaphragm Replaced | /03L-0:on 820111,in Mode 1 at 8% Rtp,Steam Generator Blowdown Containment Isolation valve,2-FCV-1-7, Operator Diaphragm Ruptured Rendering Valve Inoperable. Caused by Normal Wear.Diaphragm Replaced | |
| 05000328/LER-1982-009, Forwards LER 82-009/03L-0 | Forwards LER 82-009/03L-0 | |
| 05000328/LER-1982-010-03, /03L-0:on 820109,loop 3 Steam Generator Pressure Transmitter 2-PT-1-20A Declared Inoperable.Caused by Frozen Sense Line.Lines Thawed.Similar Incidents Occurred on 820110 & 11 | /03L-0:on 820109,loop 3 Steam Generator Pressure Transmitter 2-PT-1-20A Declared Inoperable.Caused by Frozen Sense Line.Lines Thawed.Similar Incidents Occurred on 820110 & 11 | |
| 05000328/LER-1982-010, Forwards LER 82-010/03L-0 | Forwards LER 82-010/03L-0 | |
| 05000328/LER-1982-011, Forwards LER 82-011/03L-0 | Forwards LER 82-011/03L-0 | |
| 05000328/LER-1982-011-03, /03L-0:on 820122,performance of SI-16 Revealed Boron Injection Tank Records Not Kept.Caused by Inadequate Procedures.Revisions to SI-16 Recordkeeping Procedures Include Boron Injection Tank Heat Tracing | /03L-0:on 820122,performance of SI-16 Revealed Boron Injection Tank Records Not Kept.Caused by Inadequate Procedures.Revisions to SI-16 Recordkeeping Procedures Include Boron Injection Tank Heat Tracing | |
| 05000327/LER-1982-012, Forwards LER 82-012/03L-0 | Forwards LER 82-012/03L-0 | |
| 05000327/LER-1982-012-03, /03L-0:on 820122,when Divider Barrier Equipment Hatch 3 Was Opened,Seal Gasket Discovered Missing.Probably Caused by Personnel Failure to Verify Gasket Reinstallation on 811016.Gasket Installed.Engineers Reinstructed | /03L-0:on 820122,when Divider Barrier Equipment Hatch 3 Was Opened,Seal Gasket Discovered Missing.Probably Caused by Personnel Failure to Verify Gasket Reinstallation on 811016.Gasket Installed.Engineers Reinstructed | |
| 05000328/LER-1982-013, Forwards LER 82-013/03L-0 | Forwards LER 82-013/03L-0 | |
| 05000328/LER-1982-013-03, /03L-0:on 820118,steam Generator 3 Feedwater Flow Transmitter Loop 2-FT-3-90A Declared Inoperable.Caused by Frozen Sense Lines.Lines Thawed & Insulation Added.Design Change Request Initiated | /03L-0:on 820118,steam Generator 3 Feedwater Flow Transmitter Loop 2-FT-3-90A Declared Inoperable.Caused by Frozen Sense Lines.Lines Thawed & Insulation Added.Design Change Request Initiated | |
| 05000328/LER-1982-014, Forwards LER 82-014/03L-0 | Forwards LER 82-014/03L-0 | |
| 05000328/LER-1982-014-03, /03L-0:on 820125,vital Battery Bank II Declared Inoperable When Terminal to Cell 1 Connection Resistance Exceeded Tech Spec.Caused by Corrosion.Connection Cleaned | /03L-0:on 820125,vital Battery Bank II Declared Inoperable When Terminal to Cell 1 Connection Resistance Exceeded Tech Spec.Caused by Corrosion.Connection Cleaned | |
| 05000328/LER-1982-015-03, /03L-0:on 820121,safety Injection Pump 2B-B Tripped Immediately After Starting on 1X Start Relay. Caused by Intermittent Contact Closing Due to Bent Contact Finger.Contact Finger Replaced.Pump Retested | /03L-0:on 820121,safety Injection Pump 2B-B Tripped Immediately After Starting on 1X Start Relay. Caused by Intermittent Contact Closing Due to Bent Contact Finger.Contact Finger Replaced.Pump Retested | |
| 05000328/LER-1982-015, Forwards LER 82-015/03L-0 | Forwards LER 82-015/03L-0 | |
| 05000328/LER-1982-016, Forwards LER 82-016/03L-0 | Forwards LER 82-016/03L-0 | |
| 05000328/LER-1982-016-03, /03L-0:on 820127,steam Generator Pressure Channels for Loops 3 & 4 to Remote Shutdown Instrumentation Declared Inoperable Due to Failure to Meet Channel Check Requirements.Caused by Open Circuit on Loop 2-PI-1-19C | /03L-0:on 820127,steam Generator Pressure Channels for Loops 3 & 4 to Remote Shutdown Instrumentation Declared Inoperable Due to Failure to Meet Channel Check Requirements.Caused by Open Circuit on Loop 2-PI-1-19C | |
| 05000327/LER-1982-017, Forwards LER 82-017/03L-0 | Forwards LER 82-017/03L-0 | |
| 05000327/LER-1982-017-03, /03L-0:on 820128,during Insp & testing,safety- Related Mechanical Snubbers 47A053-272,47A053-300 & 1-CVCH-914 Discovered Inoperable.Caused by Corrosion of First & Bent Retaining Nut Guide Rods on Latter Two | /03L-0:on 820128,during Insp & testing,safety- Related Mechanical Snubbers 47A053-272,47A053-300 & 1-CVCH-914 Discovered Inoperable.Caused by Corrosion of First & Bent Retaining Nut Guide Rods on Latter Two | |
| 05000327/LER-1982-018, Forwards LER 82-018/03L-0 | Forwards LER 82-018/03L-0 | |
| 05000327/LER-1982-018-03, /03L-0:on 820207,during Startup,Containment Lower Compartment Average Air Temp Discovered at 124.19 F.Two Lower Compartment Train a Coolers Temp Control Valves Had Wrong Settings.Cause Unknown | /03L-0:on 820207,during Startup,Containment Lower Compartment Average Air Temp Discovered at 124.19 F.Two Lower Compartment Train a Coolers Temp Control Valves Had Wrong Settings.Cause Unknown | |
| 05000328/LER-1982-019, Forwards LER 82-019/03L-0 | Forwards LER 82-019/03L-0 | |
| 05000328/LER-1982-019-03, /03L-0:on 820211 During startup,turbine-driven Auxiliary Feedwater Pump Declared Inoperable When Outboard Seal Packing Blew Out.Caused by Normal Deterioration of Packing & Wear of Shaft Sleeve.Packing Replaced | /03L-0:on 820211 During startup,turbine-driven Auxiliary Feedwater Pump Declared Inoperable When Outboard Seal Packing Blew Out.Caused by Normal Deterioration of Packing & Wear of Shaft Sleeve.Packing Replaced | |
| 05000327/LER-1982-020, Forwards LER 82-020/03L-0 | Forwards LER 82-020/03L-0 | |
| 05000327/LER-1982-020-03, /03L-0:on 820203,emergency Gas Treatment Sys Room Cooler Declared Inoperable Due to Fuses Blowing in Coolers Control Circuitry.Caused by Shorted Solenoid Coil of 2-FSV-67-338.Coil Replaced | /03L-0:on 820203,emergency Gas Treatment Sys Room Cooler Declared Inoperable Due to Fuses Blowing in Coolers Control Circuitry.Caused by Shorted Solenoid Coil of 2-FSV-67-338.Coil Replaced | |
| 05000328/LER-1982-021-01, /01T-0:on 820217,during Startup,Shutdown Rods in Shutdown Bank a Exceeded Plus/Minus 12 Steps of Actual Position on Indicators.Caused by Misinterpretation of Limiting Condition for Operation 3.1.3.3.Rods Recalibr | /01T-0:on 820217,during Startup,Shutdown Rods in Shutdown Bank a Exceeded Plus/Minus 12 Steps of Actual Position on Indicators.Caused by Misinterpretation of Limiting Condition for Operation 3.1.3.3.Rods Recalibr | |
| 05000328/LER-1982-021, Forwards LER 82-021/01T-0 | Forwards LER 82-021/01T-0 | |
| 05000328/LER-1982-022-03, /03L-0:on 820213,during Surveillance Testing, Lower Containment Airlock Inner Door Was Declared Inoperable.Caused by Braces Being Torqued Too Tight.Seals Reset & Surveillance Procedure Revised | /03L-0:on 820213,during Surveillance Testing, Lower Containment Airlock Inner Door Was Declared Inoperable.Caused by Braces Being Torqued Too Tight.Seals Reset & Surveillance Procedure Revised | |
| 05000328/LER-1982-022, Forwards LER 82-022/03L-0 | Forwards LER 82-022/03L-0 | |
| 05000328/LER-1982-023, Forwards LER 82-023/03L-0 | Forwards LER 82-023/03L-0 | |
| 05000328/LER-1982-023-03, /03L-0:on 820209,in Mode 1,loop 4 Main Steam Header Remote Shutdown Pressure Channel 2-PT-1-26C Declared Inoperable.Caused by Failure of Amplifier Card in GE Transmitter Due to Excessive Heat from Steam Leaks | /03L-0:on 820209,in Mode 1,loop 4 Main Steam Header Remote Shutdown Pressure Channel 2-PT-1-26C Declared Inoperable.Caused by Failure of Amplifier Card in GE Transmitter Due to Excessive Heat from Steam Leaks | |
| 05000327/LER-1982-024-03, /03L-0:on 820218,turbine Bldg Sump & Condensate Demineralizer Radioactive Effluent Line Monitors Declared Inoperable.Caused by Crud & Debris Buildup on Flow Switch. Switches Cleaned | /03L-0:on 820218,turbine Bldg Sump & Condensate Demineralizer Radioactive Effluent Line Monitors Declared Inoperable.Caused by Crud & Debris Buildup on Flow Switch. Switches Cleaned | |
| 05000327/LER-1982-024, Forwards LER 82-024/03L-0 | Forwards LER 82-024/03L-0 | |
| 05000327/LER-1982-025-03, /03L-0:on 820212,pressurizer Level Channel 1-LT-68-335 Declared Inoperable.Caused by Transmitter Out of Calibr Due to Instrument Drift.Barton Model 764 Transmitter Recalibr | /03L-0:on 820212,pressurizer Level Channel 1-LT-68-335 Declared Inoperable.Caused by Transmitter Out of Calibr Due to Instrument Drift.Barton Model 764 Transmitter Recalibr | |
| 05000327/LER-1982-025, Forwards LER 82-025/03L-0 | Forwards LER 82-025/03L-0 | |
| 05000328/LER-1982-026, Forwards LER 82-026/03L-0 | Forwards LER 82-026/03L-0 | |