NOTICE OF VIOLATION 3

' Kansas Gas'and Electric Company -

Docket: 50-482/85 p _W olf Creek Generating Station ~ License: ' NPF-421

=-

a. ,

"During an NRCfinspection . conducted during -Octpber 1985,- a violatio'niof- NRC ,

e s .

requirements ' was . identified. The violation involved the failure to isolate a

, nonseismic' sight glass ~ level gage. In accordance with the " General Statement.of Policy.and. Procedure for:NRC Enforcement Actions,"

,10 CFRrPart 2, Appendix'C (1985), the. violation is listed below:

J' - Nonseismic Sight Glass Level Gage N'ot Isolated s ,,

r <10 CFR-Part 50, Appendix.B,; Criterion V states','in part, " Activities

. affecting quality.,shall be prescribed by documented ~ instructions,

y. .,

Lprocedures, or. drawings = of a type appropriate to the circumstances. . . ."

The Checklist (CKL) EG-120, Revision 5, " Component Cooling Water System -

Valv'e, Switch, and Breaker Lineup,!' has been established in accordance with 10 CFR Part 50; Appendix B, Criterion V.

~ '

l Contrary to the above, CKL EG-120 was inappropriate to the circumstances in.that Valves EG-V 160, 161, 171, and 172 were opened in accordance twith Checklist A of CKL EG-120 when the valves should have been closed

.due to the'1evel gage between-the valves being nonseismic.

+

This is"a Severity Level-IV violation.(Suppleme.nt I.D).(50-482/8537-01).

.Pursua'n t to the provisions of 10 CFR 2.201,~ Kansas Gas and Electric Company is.hereby required to submit to this'0ffice, within 30 days of the date of

-the >1etter transmitting this Notice, a written statement- or explanation in reply, including: (1) the reason for-the violation'if admitted, (2) the

. corrective steps which have been taken and the results achieved; (3). the corrective. steps which will be taken to avoid further violations; and- '

h. '(4) thefdate when full ~ compliance will be' achieved. ,Where good cause.is ,

shown, consideration will be given to extending the response time.

e Dated at Arlington,: Texas ' .

'k - this Ja/ day of 4 //e m -

1986.

u f, t

=

j82 8601070423'86 -

POR ADOCK O PDR G ,,  ;

7 ' '

- .u. .

s mn -y c. , , , -x n,-- , - --

, -7,,n - en - , + n 4 . p..-. ,, ~w-