ML20058P249

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 900507-11 & 0629-0703. Violation Noted:Inadequately Adjusted Detection Aids Sys
ML20058P249
Person / Time
Site: Wolf Creek 
Issue date: 08/13/1990
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20058P245 List:
References
50-482-90-23, NUDOCS 9008160157
Download: ML20058P249 (1)


Text

.

o APPENDIX A NOTICE OF VIOLATIO_N Wolf Creek liuclear Operating Corporation Docket: STN 50-482 Wolf Creek Generating Station Operating License:

NPF-42 During an NRC inspection conducted May 7-11 and June 29 through July 3,1990, a violation of NRC requirements was identified.

The violation involved an inadequate detection aid.

In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1990)

(Enfore.ement Policy), the violation is listed below:

Inadequate Detection Aids System License Condition 2.E of the Wolf Creek Generating Station Facility Operating License, dated June 4,1985, requires that the licensee fully implement and maintain in effect the Commission approved Physical Security Plan, includin amendments and changes made pursuant to the authority of 10 CFR 50.54(p.

The approved Physical Security Plan requires, in part, that the microwave intrusion detection system (IDS) detect an intruder who is jumping through a detection zone.

6 Contrary to the above, on June 30, 1990, the inspector determined, through test demonstrations that at two zones the IDS could be penetrated by.

i jumping without detecting an intruder.

This is a Severity level IV violation.

(Supplement III) (482/9C'23-01)

The licensee's corrective action for the above violation was reviewed on June 30, 1990, and determined to be adequate to correct the violatior, and prevent a recurrenet. Accordingly, no written response is required for this violation.

Dated at Arlington, Texas, this 13th day of August 1990 ENCLOSURE CONTAINS SAFEGUARD 3 INFORMATION UPON SEPARAil0N THIS PAGE IS DECONTROLLED

82848bil SS$[gg2 h

Q.