Notice of Violation from Insp on 851005-1130
ML20136F538
Person / Time
Site: Wolf Creek 
Issue date: 01/02/1986
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20136F533 List:
References
50-482-85-37, NUDOCS 8601070423
Download: ML20136F538 (1)


Text

-- '

~

i.

~

W

. N m. g T~,

y w

g 9,

L

,. 7,. i x ; a.

+

~

u

$. j 7'.

[

g

/

?? Y' APPENDIX A-r 7

NOTICE OF VIOLATION 3

' Kansas Gas'and Electric Company Docket: 50-482/85 '

_ olf Creek Generating Station ~

License: ' NPF-421 W

p

=-

a.

"During an NRCfinspection. conducted during -Octpber 1985,- a violatio'niof-NRC requirements ' was. identified. The violation involved the failure to isolate a e

s nonseismic' sight glass ~ level gage.

In accordance with the " General Statement.of Policy.and. Procedure for:NRC Enforcement Actions,"

,10 CFRrPart 2, Appendix'C (1985), the. violation is listed below:

J'

- Nonseismic Sight Glass Level Gage N'ot Isolated

<10 CFR-Part 50, Appendix.B,; Criterion V states','in part, " Activities r

s

. affecting quality.,shall be prescribed by documented ~ instructions, Lprocedures, or. drawings = of a type appropriate to the circumstances...."

y.

The Checklist (CKL) EG-120, Revision 5, " Component Cooling Water System -

Valv'e, Switch, and Breaker Lineup,!' has been established in accordance with 10 CFR Part 50; Appendix B, Criterion V.

~

l Contrary to the above, CKL EG-120 was inappropriate to the circumstances in.that Valves EG-V 160, 161, 171, and 172 were opened in accordance twith Checklist A of CKL EG-120 when the valves should have been closed

.due to the'1evel gage between-the valves being nonseismic.

This is"a Severity Level-IV violation.(Suppleme.nt I.D).(50-482/8537-01).

+

.Pursua' t to the provisions of 10 CFR 2.201,~ Kansas Gas and Electric Company n

is.hereby required to submit to this'0ffice, within 30 days of the date of

-the >1etter transmitting this Notice, a written statement-or explanation in reply, including:

(1) the reason for-the violation'if admitted, (2) the

. corrective steps which have been taken and the results achieved; (3). the corrective. steps which will be taken to avoid further violations; and-h.

'(4) thefdate when full ~ compliance will be' achieved.,Where good cause.is shown, consideration will be given to extending the response time.

e Dated at Arlington,: Texas '

'k -

this Ja/ day of 4 //em 1986.

u f,

t

=

8601070423'86 j82 POR ADOCK O PDR G