==REACTOR SAFETY== | ==REACTOR SAFETY== | ||
===71111.05XT - Fire Protection - NFPA 805 Fire Protection Inspection Requirements (IP Section 02.01a) === | ===71111.05XT - Fire Protection - NFPA 805 Fire Protection Inspection Requirements (IP Section 02.01a) === | ||
{{IP sample|IP=IP 71111.05|count=4}} | {{IP sample|IP=IP 71111.05|count=4}} | ||
The inspectors evaluated fire protection program implementation in the following selected areas and/or fire zones, including analyzed electrical circuits: | The inspectors evaluated fire protection program implementation in the following selected areas and/or fire zones, including analyzed electrical circuits: |
Latest revision as of 05:43, 18 December 2019
ML19301A443 | |
Person / Time | |
---|---|
Site: | Summer ![]() |
Issue date: | 10/25/2019 |
From: | Scott Shaeffer NRC/RGN-II/DRS/EB2 |
To: | Stoddard D Dominion Energy |
References | |
IR 2019012 | |
Download: ML19301A443 (13) | |
Text
ber 25, 2019
SUBJECT:
VIRGIL C. SUMMER NUCLEAR STATION - TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000395/2019012
Dear Mr. Stoddard:
On October 3, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Virgil C. Summer Nuclear Station and discussed the results of this inspection with Mr. George Lippard III and other members of your staff. The results of this inspection are documented in the enclosed report.
The NRC inspectors did not identify any finding or violation of more than minor significance.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely,
/RA/
Scott M. Shaeffer, Chief Engineering Branch 2 Division of Reactor Safety Docket No. 05000395 License No. NPF-12
Enclosure:
Inspection Report 05000395/2019012 w/Attachment: Supplemental Information
Inspection Report
Docket Number: 05000395 License Number: NPF-12 Report Number: 05000395/2019012 Enterprise Identifier: I-2019-012-0013 Licensee: Dominion Energy Facility: Virgil C. Summer Nuclear Station Location: Jenkinsville, SC Inspection Dates: September 16, 2019 to October 03, 2019 Inspectors: P. Braaten, Reactor Inspector E. Coffman, Senior Reactor Inspector (Lead Inspector)
J. Dymek, Reactor Inspector M. Singletary, Reactor Inspector Approved By: Scott M. Shaeffer, Chief Engineering Branch 2 Division of Reactor Safety Enclosure
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a triennial fire protection inspection at Virgil C. Summer Nuclear Station in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors.
Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
List of Findings and Violations No findings or violations of more than minor significance were identified.
Additional Tracking Items Type Issue Number Title Report Section Status NOV 05000395/2017002-01 Closure of Previous NRC- 71111.05XT Closed identified SL-IV Cited Violation NOV 05000395/2016007-01 Closure of Previous NRC- 71111.05XT Closed identified SL-IV Cited Violation
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.
REACTOR SAFETY
71111.05XT - Fire Protection - NFPA 805 Fire Protection Inspection Requirements (IP Section 02.01a)
The inspectors evaluated fire protection program implementation in the following selected areas and/or fire zones, including analyzed electrical circuits:
- (1) Fire Zone CB06 - Control Building Relay Room (CB 436 ft)
Analyzed Circuits:
- Pressurizer Backup Heaters
- (2) Fire Zone AB01.04, Auxiliary Building General Area (AB 388 ft)
Analyzed Circuits:
- Alternate Seal Injection (ASI) Pump XPP0230 Local Disconnect Switch
- ASI Diesel Generator XEG0101 Local Disconnect Switch
- 'A' Component Cooling Water Booster Pump
- LCV-115C-CS and LCV-115E-CS, Volume Control Tank Level Control Valves to Charging Pump Suction
- (3) Fire Zone IB20, Intermediate Building 1DA 7.2kV Switchgear Room (IB 463 ft)
Analyzed Circuits:
- 1DA 7.2kV Switchgear
- Letdown Line Isolation Valves LCV-459-CS and LCV-460-CS
- XPP0043A, 'A' Charging/Safety Injection Pump
- 1DA2 480V Switchgear Bus, Unit 5C
- XVG-8000A-RC, Pressurizer Power Operated Relief Valve Inlet Isolation Valve
- (4) Fire Zone DG01.02, A Emergency Diesel Generator Room (DG 436 ft and 463 ft)
B.5.b Inspection Activities (IP Section 02.03) (1 Sample)
The inspectors evaluated the following B.5.b Mitigating Strategies:
- (1) Refueling Water Storage Tank (RWST) make-up using fire service water
INSPECTION RESULTS
Observation: Closure of Two Previous NRC Identified SL-IV Cited Violations 71111.05XT The inspectors reviewed the licensees response to NOVs05000395/2016007-01 and 05000395/2017002-01 and determined that the reasons, corrective actions taken and plans to address recurrence, and the date when full compliance was achieved for these violations is adequately addressed and captured on the docket.
EXIT MEETINGS AND DEBRIEFS
The inspectors verified no proprietary information was retained or documented in this report.
On October 3, 2019, the inspectors presented the triennial fire protection inspection results to Mr. George Lippard III and other members of the licensee staff.
DOCUMENTS REVIEWED
Inspection Type Designation Description or Title Revision or
Procedure Date
71111.05XT Calculations 43035-CALC-08 VC Summer NFPA 805 FRE Report Rev. 3A
DC00070-008 BDBMG CST and RWST Flow Rate Calculations Rev. 1A
DC00340-001 Fire PRA Final Report Rev. 1A
DC00340-001 Fire PRA Fire Risk Quantization Report, Task 5.14 Rev. 0
2
DC00340-003 V.C. Summer NFPA 805 FRE Report Rev. 3A
DC00340-007 Fire Human Reliability Analysis Rev. 1A
DC0780D-001 NFPA Code of Record-Fire Detection Rev. 2A
TR-08620-312 Nuclear Safety Capability Assessment Fire Shutdown Rev. 2
Analysis
TR07800-007 Fire PRA Fire Ignition Frequency Analysis (Task 5.6) Rev. 3
TR07800-008 Non-Power Operational Modes Transition Review Rev. 1
TR07800-009 NFPA 805 and Fire PRA Circuit Analysis, Task 4.4 Rev. 1
TR07800-033 Fire Safety Analysis Report Rev. 0A
TR08620-015 Nuclear Safety Equipment Report Rev. 1
TR08620-034 Fire Response Abnormal Operating Procedures Technical Rev. 1
Basis Document
TR08620-036 NFPA 805 Recovery Actions, Feasibility/Reliability Study Rev. 1
TR08620-036 NFPA 805 Recovery Actions, Feasibility/Reliability Study Rev. 2
Corrective Action CR-16-05919 Corrective actions were not taken to resolve NRC-identified 11/23/2016
Documents severity level IV non-cited violation,05000395/2016001-01,
which resulted in a cited violation
CR-16-06023 Receipt of NRC Problem and Identification Report 11/30/2016
CR-17-00537 Licensing Basis documentation associated with NFPA 805 02/01/2017
CR-17-04331 Receipt of Inspection Report 05000395/2017002 and NOV 08/09/2017
CR-17-04335 Corrective action(s) to restore compliance for the Oil 08/09/2017
Collection Devices for Reactor Coolant Pump Motors
CR-19-00607 Cable that supplies power to MVB03116C-SW has 02/15/2019
KaoWool wrapped around its metal conduit for Fire
Protection.
Inspection Type Designation Description or Title Revision or
Procedure Date
CR-19-02334 Use of data from an unapproved Flowserve Report in the 06/27/2019
station's Fire PRA
Corrective Action CR-19-03076 Discrepancies in the FP1AB-388 and FP1AB-388A fire pre- 08/29/2019
Documents plans
Resulting from CR-19-03342 Discrepancies in the FP1IB-412 fire pre-plan 09/19/2019
Inspection CR-19-03463 Total count for medium voltage HEAFs was incorrect for 09/30/2019
Fire Area IB-20
CR-19-03465 Total count for medium voltage HEAFs was incorrect for 09/30/2019
Fire Area IB-20
CR-19-03491 Fire hydrant FHHH #21 missing label 10/01/2019
Drawings 1MS-55-040 Low Pressure CO2 Fire Extinguishing System Schematic Rev. 4
Arrangement, Sheet 1
1MS-55-040 Low Pressure CO2 Fire Extinguishing System Schematic Rev. 6
Arrangement, Sheet 3
1MS-55-085 Diesel Generator Building/Diesel Fire Pump Room, Sheet Rev. 14
B-023-311 Penetration Seal Typical Design, Wall and Floor Detail, Rev. 0
Sheet 1
B-208-021- Letdown Orifice Isolation XVT 8149A Rev. 9
CS0083A
B-208-021- Letdown Isolation Orifice Isolation XVT-8149A Rev. 7
CS0083B
B-208-021- Letdown Isolation Orifice Isolation XVT-8149A Rev. 11
CS0083C
B-208-032- EF Isolation From Turbine Driven PP to Steam Gen "A" IFV- Rev. 12
EF0037B 3536
B-208-067- Main Steam to EFW Pump Turbine Rev. 11
MS0046
B-208-082- Pressure Power Relief Valve PCV 444B Rev. 16
RC0050
B-208-201- Electrical Elementary Diagram Service Water Pump A Rev. 8
SW0001
D-912-157 Building Service System Flow Diagram Intermediate Rev. 12
Inspection Type Designation Description or Title Revision or
Procedure Date
E-201-240 Electrical, Fire, Pressure and Radiation Barrier Details-Wall Rev. 7
and Floor Openings, Sheet 5
E-206-005 Simplified Plant Electrical Distribution Rev. 32
E-214-073 Arrangement of Cable Trays Auxiliary Building North Above Rev. 5
385-0 and 397-0
E-221-650 Conduit Layout Fire Protection Auxiliary Building above El. Rev. 3
388' & 397'
E-302-671 Chemical and Volume Control Rev. 12
E-302-672 Chemical and Volume Control Rev. 14
E-302-673 Chemical and Volume Control Rev. 21
E-302-674 Chemical and Volume Control Rev. 14
E-302-675 Chemical and Volume Control Rev. 37
E-922-612 Building Service HVAC Control Complex Floor Elevation Rev. 24
436-0
Engineering ECR 50909 RCP Oil Lift Pump Enclosure 01/4/2018
Changes
Engineering 14-03 PRA Evaluation of Fire Procedure Time Estimates Rev. 2
Evaluations TR0780E-001 Safe Shutdown Separation Fire Protection Engineering Rev. 0A
Equivalency Evaluations
TR0780E-005 Fire Protection Engineering Equivalency Evaluations Rev. 0B
TR0780E-006 Fire Protection Equivalency Evaluation, Attachment FEAT- Rev. 0H
Fire Plans FP1AB-388 Auxiliary Building El. 388 Rev. 1
FP1AB-388A Auxiliary Building El. 400 Rev. 1
FP1CB-436 Control Building El. 436 Rev. 1
FP1DG-436 Diesel Generator Building El. 436 Rev. 1
FP1DG-463 Diesel Generator Building El. 463 Rev. 1
FP1IB-412 Intermediate Building El. 412' Rev. 2
FP1IB-463 Intermediate Building El. 463 Rev. 2
FP1IDX-001 Fire Preplan Index Rev. 3
FP1LGD-001 Fire Preplan Legend Rev. 1
Inspection Type Designation Description or Title Revision or
Procedure Date
Miscellaneous Diesel Fire Pump Fuel Oil Storage Tank Sample Analysis 08/20/2019
1MS-54-418 Air Balance Inc. Submittal Data, U.L. Classified Fire 10/28/1977
Seal/Fire Door Model 319W
1MS-54-420 Air Balance Inc. Submittal Data, U.L. Classified Fire 10/09/1978
Seal/Fire Door Model 119L
1MS-54-425 Air Balance Fire/Seal Schedule 09/19/1978
1MS-54-429 S&R Products Electro-Thermal Link 10/25/1978
1MS-55-042 Relay Room CO2 Heat Collector, Cardox Corporation 01/19/1978
Detect-A-Fire 140F, Stock No.150112
1MS-94B-1717 Simplex Incipient Detection Equipment Rev. 0
DBD-FP NFPA 805 Fire Protection Rev. 2
EE-02 Cable and Conduit Routing Rev. 1H
EE-09 NFPA 805 Circuit Selection, Circuit Analysis, and Circuit Rev. 0B
Routing
RC-18-0091 License Amendment Request - LAR-16-01490 NFPA 805 08/28/2018
Program Revisions
RC-18-0091 License Amendment Request to Revise NFPA 805 Program 08/29/2018
RCA 17-00537 Regulatory/Current License Basis Noncompliance 05/02/2019
VCS-TQP-0606 Fire Protection Training Rev. 0C
WCAP-16175-P Model for Failure of RCP Seals Given Loss of Seal Cooling 01/2004
WCAP-16175-P- Model for Failure of RCP Seals Given Loss of Seal Cooling 03/2007
Procedures AOP-900, Operational Impacts of Loss of Electrical Buses Due to Fire Rev. 1
Appendix A
AOP-900, Post Fire Transition to Cold Shutdown - Other Potentially Rev. 0
Appendix B Affected Components
AOP-900, Local Operator Actions Rev. 1
Appendix C
AOP-900.01 Fire Response Initial Actions Rev. 3
AOP-900.02 Control Room Evacuation Due to Fire Rev. 2
AOP-900.04 Control Building Fire Zone Response Actions Rev. 4
AOP-900.05 Intermediate Building Fire Zone Response Actions Rev. 1
Inspection Type Designation Description or Title Revision or
Procedure Date
AOP-900.06 Auxiliary Building and Fuel Handling Building Fire Zone Rev. 1
Response Actions
AOP-900.10 Diesel Generator Fire Zone Response Actions Rev. 0
BDMG-2.0 Beyond Design Basis Mitigating Guideline Rev. 2
EC-03 Processing Engineering Change Packages Rev. 6I
ES-0427 Program / Issue Screening Rev. 3F
ES-0911 NFPA 805 - Fire Protection Monitoring Program Rev. 0
FPP-020 Program Administration Rev. 6E
FPP-022 Fire Prevention Rev. 5A
FPP-024 Fire Suppression Rev. 5
FSP-2.0 Flex Support Procedure - Alternate EFW Suction Source Rev. 1
ICP-230.006 Incipient Detection Functional Check Rev. 1
ICP-500.030 Incipient Detection Maintenance Procedure Rev. 1A
OAP-100.6 Control Room Conduct and Control of Shift Activities Rev. 4N
SAP-0131 Fire Protection Program Rev. 10B
SAP-0142 Station Housekeeping Program Rev. 17E
SAP-131A Fire Protection Surveillances and Compensatory Measures Rev. 4A
STP-128.012 NFPA 805 Required Fire Hydrant Inspection Rev. 8
STP-128.021 Fire Service Water Flow Test Rev. 11B
STP-128.024 CO2 System Functional Refuel Test Rev. 10
STP-606.002 Fire Pump Diesel Engine Fuel Oil Storage Tank Oil Analysis Rev. 9D
STP-728.402 Fire Yard Hydrant Annual Inspection and Hydrostatic Rev. 6
Testing
TR07870-019 Penetration Seal Design Guide Rev. 0
VCS-ERP-0050 ERU Equipment Inventory Rev. 4
VCS-ERP-0130 BDB Emergency Equipment Management Rev. 0A
Self-Assessment CR-19-00506 71111.05XT Triennial Fire Protection Self Assessment 04/12/2019
QA-AUD-2017-03 Fire Protection Audit Notification 01/31/2017
QA-AUD-201804 Fire Protection Annual 03/26/2018
QA-AUD-201903 Fire Protection Bi/Triennial 03/27/2019
Work Orders 1610548 CO2 System Functional Test 01/19/2017
1610897 Fire Hose Hydro Test 06/26/2017
Inspection Type Designation Description or Title Revision or
Procedure Date
1615983 DG Building Pre-Action Sprinkler Operability Test 07/25/2017
1615983 Diesel Generator Pre-action Sprinkler System OPS Testing 07/25/2017
1706346 ESF SWGR RM. 1DA Air Handling Unit XFD-0178 01/02/2018
Inspection
1714790 CO2 Valve Line-up Verification 01/31/2018
1800412 CO2 System Functional Test 05/24/2018
1801620 Intermediate Building El. 436-0 Simplex 4100 UT1B2 05/29/2018
1801620 Smoke Detector Functional Test 05/09/2019
1801625 Smoke Detection Functional Test 05/29/2018
1801625 Intermediate Building El. 436-0 Simplex 4100 UT1B2 05/29/2018
1801690 Fire Hose Visual Inspection 04/23/2018
1802465 Incipient Detection Surveillance 01/02/2019
1810811 CO2 Valve Line-up Verification 08/02/2018
1811319-001 DG Building Preaction Sprinkler Operability Test 01/15/2019
1812537-001 Control Room Evacuation Panel Emergency Tool Locker 06/29/2019
Inventory List
1816495 Relay Room Cooling, XFD-0016 Inspection 01/30/2019
1817412-001 IB Preaction Sprinkler System Operability Testing 02/14/2019
1904113-001 Smoke Detector Functional Test Zone N Control Building 04/03/2019
448'
1904467-001 Smoke Detector Functional Test Zone XX Control Building 04/10/2019
448'
10